COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

Similar documents
COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

COOPER POWER SERIES. Fiber-optic/RS-232 communications module installation and operation instructions. Voltage Regulators MN225020EN

COOPER POWER SERIES. Ethernet communications module installation and operation instructions. Voltage Regulators MN225033EN

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

Single Phase Vacuum Capacitor Switch. UltraVacLT 15kV 95kV or 125kV BIL

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

Series NRX drawout circuit breaker and cassette rejection interlocks

INCOM communications adapter module

Time delay undervoltage module

S Reclosers. Contents. Form 4C Recloser Control Protocol Conversion Kits KME , -7002, and Installation Instructions

Instructions for Testing Magnum DS Trip Units Using PACB Test Kit Styles 87C0270G01-G03

Digitrip 520MC with Maintenance Mode

Vista SD Portable Remote Control Pendant

Power Xpert Meter 350 (PXM350) three-phased DIN-rail multifunction meter

GridAdvisor Series II smart sensor installation instructions

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

Instructions for installation, operation and maintenance of the Arc Quenching Device (AQD)

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

Multi Unit Enclosed Meter

COOPER POWER SERIES. Type GN3E and GN3VE sectionalizers installation and operation instructions

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

PS/IO Circuit Board Retrofit

PWRguard PLUS Spring City Drive Waukesha, WI

Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Install Motor Controller User Manual

Eaton Innovative TechnologyT XT50/100 surge protective device

Power Xpert Meter 2000 Series

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

Model 7705 Control Module

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

COOPER POWER Effective August 2015 Supersedes S July 2014

User's Guide. Model High Precision Quad Output DC Power Supply

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

Shutter Assembly Guide Frame Accessory

User's Guide. MiniTec TM Series Model MN25 MultiMeter

User's Guide. Extech AM A AC Analog Clamp Meter

Configuration. S&C Scada-Mate Switching System Outdoor Distribution (14.4 kv through 34.5 kv)

E-Series Troubleshooting Guide

Type VR Electrically Operated Ground and Test Device

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Quick Start Guide TS A

Effective May 2018 Supersedes October 2017

Installation and Operation

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Electrical network protection Sepam series 20 Sepam series 40 Quick start

1-36V, 0-3A DC Power Supply

COOPER POWER SERIES. Form 6 triple-single microprocessor-based pole-mount recloser control Installation and operation instructions

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

VisoVac padmount fault interrupter

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

Installation Manual Updated May 2017

Abstract. GLV User Manual 1

Primary Injection Test Procedure

RVDT Setup and Polarity Checking Tool for EG Governors. Product Manual (Revision B) Original Instructions T87444

Service Instructions. Conductor 420

Automated Tuner System Power Distribution Hub

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

MFP5G, MFP8G, & MFP12G D-M-E Smart Series Mainframes

4300 WINDFERN RD #100 - HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Instructions for Operation of S&C Test Accessory Catalog Number TA-2669

SIRIUS CAPACITOR MODULE User Manual. Model number: A-1.7C-M-SD-G Version 1.0; Release Date: April 2018

for the SPV Installation and Operation Manual Instruction Manual IM E Contents

4300 WINDFERN RD #100 HOUSTON TX VOICE (713) FAX (713) web: IMPORTANT!!!

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

S82S (3/7.5-W Models)

iconverter 2-Module Power Chassis

Broadband Automatic Disconnect Switch. User Manual

VIP-812A DUAL NETWORKED STATION PORT

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

INSTRUCTIONS FOR THE IQ DC POWER SUPPLY INSTRUCTION LEAFLET IL E

DIGITAL VOLTAGE INDICATOR

Source-Transfer Application Guide

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

High Pressure E/P Regulator. ITVH Series

EnCell Battery Cell Monitor

INSTRUCTION MANUAL. Model Dual Input RTD Thermometer. Measures two temperatures simultaneously. Dual RTD probe inputs

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

Installation Instructions

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

OPERATING PROCEDURES for the UPS-S2 Universal Power Supply Series 2

Installation Instructions

UPS READY POWER DISTRIBUTION ASSEMBLY

Series IZH10. Handheld Electrostatic Meter. How to Order. Accessories and Option / Part Number for Individual Parts.

Model VT120 Fast Timing Preamplifier Operating and Service Manual

700 Series 200 Amp Clamp Meters

MAXIMA+ Series Rotary Level Indicator

Application Guide. M 2174B Moloney Replacement Adapter Panel

Rotork Fairchild PAX1 Linear Actuator User s Manual

850A/B Contact Chatter Detector User Manual

Transcription:

Padmounted Switchgear MN285018EN Effective May 2017 Supersedes October 1994 (S285-80-1) COOPER POWER SERIES DC motor operator control installation and operation instructions

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. OPERATION INSTRUCTIONS MN285018EN May 2017 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... I SAFETY FOR LIFE... III SAFETY INFORMATION... III Hazard statements... iii Safety instructions... iii PRODUCT INFORMATION.... 1 Introduction...1 Additional information............................................................................1 Acceptance and initial inspection...1 Handling and storage...1 ISO Standards...1 Control battery storage and charging...1 Control power....2 DESCRIPTION OF CONTROL.... 2 Control operation...2 Auxiliary contacts...2 Simultaneous indication for SCADA....2 Electrical interlocks....2 Control operation-local Mode.... 3 LOCAL Mode operation... 3 LOCAL Mode features... 3 Battery charger board.... 3 Wiring schematic... 4 Instructions for LOCAL Mode operation... 6 SCADA Operation.... 6 REMOTE Mode features... 6 Extended control accessory.... 7 Extended control accessory operation.... 7 Outline diagram... 8 SCADA Terminal block connection procedures........................................................ 9 DC Motor actuator... 9 TESTING PROCEDURES... 9 Battery test.... 9 Lamp test... 9 MAINTENANCE INFORMATION.... 10 Maintenance program... 10 Replacement parts... 10 ii OPERATION INSTRUCTIONS MN285018EN May 2017

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 OPERATION INSTRUCTIONS MN285018EN May 2017 iii

Product information Introduction Service Information MN285018EN provides installation and operating instructions for Eaton s Cooper Power series DC Motor Operator control. Before installing and operating this control, carefully read and understand the contents of this manual. Additional information These instructions do not claim to cover all details or variations in the equipment, procedures, or process described, nor to provide directions for meeting every possible contin gency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user s purpose, contact your Eaton representative. Acceptance and initial inspection Each Motor Operator control is completely assembled, tested, and inspected at the factory. It is carefully calibrated, adjusted and in good condition when accepted by the carrier for shipment. Upon receipt, inspect the equipment for signs of damage. Inspect the control thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and storage Be careful during handling and storage of the control to minimize the possibility of damage. If the control is to be stored for any length of time prior to installation, provide a clean, dry storage area. If storage is in a humid atmosphere, make provisions to keep the control circuitry energized. Ensure that the battery is disconnected during storage. Quality standards ISO 9001 Certified Quality Management System. Control battery storage and charging The 24 Vdc control battery is fully charged prior to shipment and is ready for use. The 2.5 amp-hour sealed lead acid jell-cell battery supplies the energy to activate the motors and the control functions. The battery is capable of running a motor for up to 25 open and 25 close operations before recharge. The 24 Vdc battery is charged by the temperature/voltage regulated battery charger. The charger will provide an ideal charge voltage based on the ambient temperature. The battery charger will charge at a rate of 0 to 0.3 amps, depending on battery voltage, and will return the battery from low charge to full charge in 24 hours. Nominal battery life is approximately six years. If the battery is removed from the control for long term storage, or if spare batteries require charging prior to being put into service, a plug-in, bench-type, 2.5 amp-hour battery charger is available, identified by the following catalog number: KME4-85-3 (120 Vac) When shipped from the factory, the battery is disconnected. Connect the battery plug into the mating connector to complete the battery circuit. DC Battery Disconnect AC Indicator light Battery Test THI R8 D3 R9 V1 V2 RY1 P1 F1 F2 B- B+ 1 P2 Battery TEST BATTERY Source #1 Fuse Source #2 Fuse Ground Source #2 Neutral #1 Source #1 Neutral #2 Figure 1. Outline diagram of AC supply and battery charger board OPERATION INSTRUCTIONS MN285018EN May 2017 1

Control power The control requires a 120 Vac (104-127 Vac) to operate the battery charger. An additional 120 Vac input with a flip-flop relay will be provided for preferred/alternate voltage sources (See Figures 2 and 3). The basic DC control can be operated in either the LOCAL or REMOTE modes by making the appropriate selection with the SCADA toggle switch. With the SCADA switch on LOCAL, STATUS and control functions are accessed via the control panel. With the SCADA switch on REMOTE, STATUS and control functions are accessed via the SCADA interface (See Figures 4 and 6). Figure 2. AC supply and battery charger board 941195KM Auxiliary contacts One a and one b auxiliary switch contact from the B phase of each actuated mechanism are utilized for status indication. To read status in either LOCAL or REMOTE modes, a motor must first be selected. Description of control Control operation The DC motor operator control is designed for use with Eaton s Cooper Power series Type RVAC and VFI pad-mounted switchgear. The motor operator control is applicable with both 600 amp vacuum loadbreak switch mechanisms and vacuum fault interrupter mechanisms. The motor operator control is designed to monitor and direct the operation of DC motors when supplied with Type RVAC and VFI pad-mounted switchgear. The control will operate up to six motor actuators-one at a time-in a user-selected random order for 25 OPEN and 25 CLOSE operations without line voltage. Simultaneous indication for SCADA For some SCADA applications, it may be necessary to monitor the status of each stage simultaneously. To provide this capability, an additional stage for each actuated mechanism is required. For these applications, an optional interface, separate from the control, can be additionally provided (consult factory for details). Electrical interlocks The DC motor operator control may be supplied with the capability for user-specified electrical interlocking. For these applications, an additional stage may be required (consult factory for details). CLOSED indicator light CLOSING indicator light OPEN indicator light LAMP TEST push button SCADA Toggle Switch Power Switch OPENING indicator light STOP push button Motor Select Knob CLOSE push button OPEN push button 941194KM Figure 3. Operator panel of DC motor operator control 2 OPERATION INSTRUCTIONS MN285018EN May 2017

Control operation-local mode The operator panel is located inside, and at the top, of the control cabinet. The operator panel contains the power toggle switch, the SCADA toggle switch, the motor select knob, the operation switches, and the status indicators. (See Figure 4). Local mode operation Status and control operation are provided via the operator panel. The control is activated in the LOCAL mode when the SCADA toggle switch is set to LOCAL. Operations capabilities from the control panel: Select local or remote operation. Select one of several motors. Read status of selected motor. Operate the selected motor. Monitor opening or closing action. Test indicating lights. Read status of 120 Vac. Disconnect 120 Vac. Test battery (with user-supplied volt meter). Disconnect 24 Vdc. Local mode features Features and capabilities of the DC motor operator control, which can be accessed from the control panel, are described as follows: POWER SWITCH (ON/OFF TOGGLE)e: Disconnects the DC voltage to the control and motors. When the Power switch is in the OFF position, all control features are inactive with the exception of the battery test feature. The AC supply will be unaffected. SCADA SWITCH (TOGGLE)e: In the Local position, prevents the operation of Open, Close, and Motor selection from the SCADA terminals. Operation of the motor operator is only possible from the control panel. Conversely, placing the SCADA toggle switch in the REMOTE position prevents the operation of Open, Close, and Motor selection from the control panel. Operation of the motor operator is only possible via the SCADA terminal points. (Also see Control Operation-Extended Control). MOTOR SELECT SWITCH (ROTARY)e: Selects which motor is active for status indication and operation. This switch should be returned to the OFF position after operation is completed to disable the panel indicating lights so as to avoid battery drain. CLOSE (RED PUSH BUTTON)e: Closed the selected switch or interrupter mechanism via the motor operator. OPEN (GREEN PUSH BUTTON)e: Opens the selected switch or interrupter mechanism, via the motor operator. STOP (YELLOW PUSH BUTTON)e: Stops the motoroperated opening or closing action of the selected switch or interrupter mechanism. Mechanisms should not be left between an open and closed position. A mis-operation could occur. Restart the motor and actuate to a fully OPEN or fully CLOSED position. LAMP TEST (WHITE PUSH BUTTON)e: Checks status indicator lights by energizing all lights. CLOSED INDICATION (RED LIGHT)e: Indicates that the selected switch or interrupter mechanism is in the CLOSED position. OPEN INDICATION (GREEN LIGHT)e: Indicates that the selected switch mechanism is in the OPEN position. It also indicates that the fault interrupter mechanism is in either the OPEN or TRIPPED position. CLOSING INDICATION (YELLOW LIGHT)e: Indicates that the motor actuator is closing the selected switch or interrupter mechanism. OPENING INDICATION (YELLOW LIGHT)e: Indicates that the motor actuator is opening the selected switch or interrupter mechanism. Do not move MOTOR SELECT switch during motor operation as motor will halt partially operated and actuation may transfer to new motor selection. Do not leave motor partially operated. The interrupter may be on the verge of operating. Complete actuation to either the fully open or fully closed position. IMPORTANT The VFI mechanism is a trip-free mechanism. If the VFI is closed by a motor operator and a fault occurs, the handle will be held in the CLOSED position, but the VFI mechanism will trip and the control panel will indicate OPEN. To reset the VFI, select the correct motor and push the OPEN pushbutton. The motor operator will open and reset the VFI. The VFI can then be closed by pushing the CLOSE push button. Battery charger board The battery charger, battery test pushbutton, AC indicator light, fuses, and 120 Vac terminals are located inside, and at the bottom of, the control housing. See Figures 2 and 3. The charger board can receive 120 Vac from either of the two 120 Vac sources which can be connected simultaneously through the supply terminals (See Figures 2 and 3). Each 120 Vac supply is fused on the board with a 1A fuse. OPERATION INSTRUCTIONS MN285018EN May 2017 3

Figure 4. Wiring schematic of DC motor operator control 4 OPERATION INSTRUCTIONS MN285018EN May 2017

This is a typical schematic diagram for standard Motor Operator Control. Refer to the schematic diagrams supplied with your control for specific information on accessories or special modifications that were supplied at the time of manufacture. Dashed wires indicate customer-made connections. OPERATION INSTRUCTIONS MN285018EN May 2017 5

Instructions for LOCAL mode operation For DC Motor Operator Control wiring and outline information, refer to Figure 5 and 8. 1. POWER switch must remain ON for normal operation. Power OFF disables both control and motors. The power switch is a 5-amp, DC breaker which will operate in 1 to 3 seconds for 20 amps. Placing the switch in the OFF position disables the DC, which powers both the control and the motors. 2. SCADA switch must be set to LOCAL. To operate the motors from the control panel, the SCADA switch must be set to LOCAL. 3. Set MOTOR SELECT switch to desired motor. To read contact status or to select a motor to operate, set the MOTOR SELECT switch to the desired position. 4. Confirm correct status indicators are lit. After selecting a motor, confirm that the status lights indicate the actual position of the mechanism. 5. Push OPEN or CLOSE pushbuttons to operate motor. Yellow light indicates motor operation in progress. Push STOP to halt motor operation immediately; then push OPEN or CLOSE to complete a full open or full close operation. (See Note below). Push the appropriate pushbutton to perform the OPEN or CLOSE operation. If necessary, push the STOP pushbutton to halt the motor immediately. Do not leave the motor in this condition. Complete a full OPEN or CLOSE operation to prevent an inadvertent mechanism operation. 6. When complete, return MOTOR SELECT switch to OFF. Set SCADA switch as desired. Leave POWER switch ON to permit SCADA operation. The status lights will remain lit as long as a motor is selected. If AC power is lost, the batteries will eventually be drained. Be sure to return the MOTOR SELECT switch to the OFF position. Leave the POWER switch on if SCADA operation is desired. The POWER SWITCH does not disable 120 AC or the battery charger. To disconnect 120 Vac, remove the fuses or disconnect 120 Vac from Terminal P2. SCADA Operation Remote monitoring and control operation are provided through the SCADA terminals. The control is activated in the REMOTE mode when the SCADA toggle switch is set to REMOTE. Features available through SCADA terminals: Select one of several motors. Read status of selected motor. Operate the selected motor. Monitor opening or closing action. REMOTE Mode Features All remote features are accessed through a terminal strip mounted on the relay circuit board. (See Figures 6 and 8). Remote operation is permitted only when the SCADA switch is in the REMOTE position. The operation of each feature is described as follows: MOTOR SELECT CONTACTSe: Dry contacts for SCADA selection of a switch or interrupter mechanism for status indication or operation. These contacts require a maintained contact closure for as long as the status is being read or the motor actuator is active. If this contact is opened during an operation, the motor actuator will stop immediately. If more than one motor is selected simultaneously, the lowest numbered motor will be selected by default. STATUS CONTACTSe: Dry contacts which indicate open or closed status of the switch or interrupter mechanism selected via the SCADA Motor Select Contacts. CLOSE CONTACTe: Dry contact which initiates closing the switch or interrupter mechanism selected via the Motor Select contacts. A momentary contact closure between terminal 21 and terminal 22 on the SCADA terminal strip is required. OPEN CONTACTe: Initiates opening the switch or interrupter mechanism, selected via the Motor Select contact. A momentary contact closure between terminal 19 and terminal 20 on the SCADA terminal strip is required. CLOSING CONTACTe: Dry contact which indicates that the motor actuator is closing the switch or interrupter mechanism selected via the Motor Select contacts. The motor is closing when the contact is closed (terminals 1 and 2). OPENING CONTACTe: Dry contact which indicates that the motor actuator is opening the switch or interrupter mechanism selected via the Motor Select contacts. The motor is opening when the contact is closed (terminals 3 and 4). SCADA SWITCH POSITION CONTACTe: A dry contact which indicates the position of the SCADA switch. When the SCADA switch is in the REMOTE position, this contact will be closed. When the SCADA switch is in the LOCAL position, this contact will be open (terminals 5 and 6). 6 OPERATION INSTRUCTIONS MN285018EN May 2017

Control operation extended control With the DC Motor Operator Control SCADA toggle switch set to LOCAL and the rotary MOTOR SELECT switch set to the OFF position, the operation capabilities from the extended control accessory are: Select one of several motors. Read status of selected motor. Operate the selected motor. Monitor opening or closing action. Test indicating lights. The operation of each feature is described as follows: MOTOR SELECT SWITCH (ROTARY)e: Selects which motor is active for status indication and operation by the extended local control. The SCADA switch must be set to the LOCAL position for extended local control operation. Figure 5. SCADA Terminal block Extended control accessory The DC Motor Operator control can be operated via a separate portable control when equipped with the appropriate accessory components. The Extended Control Accessory components include the portable control, the control cable, and modifications to the DC Control (ie: an additional connector and associated wiring). The cable is supplied with a separable connector at both ends and can be supplied in user-specified lengths up to 200 feet. Modifications to the DC Control should be made at time of manufacture, but can be purchased optionally as a field retrofit kit. Figure 6. Extended control accessory Extended control accessory operation 941194KM The DC Control can be optionally equipped with an accessory which allows the control to be operated (in the LOCAL mode) from an additional portable control panel. Monitoring and operation are provided through the extended control accessory. CLOSE (RED PUSH BUTTON)e: Closes the selected switch or interrupter mechanism, via the motor operator. OPEN (GREEN PUSH BUTTON)e: Opens the selected switch or interrupter mechanism, via the motor operator. STOP (YELLOW PUSH BUTTON)e: Stops the motoroperated opening or closing action of the selected switch or interrupter mechanism. Mechanisms should not be left between an open or closed position. A mis-operation could occur. Restart the motor and actuate to a fully OPEN or fully CLOSED position. LAMP TEST (WHITE PUSH BUTTON)e: Checks status indicator lights by energizing all lights. CLOSED INDICATION (RED LIGHT)e: Indicates that the selected switch or interrupter mechanism is in the closed position. OPEN INDICATION (GREEN LIGHT)e: Indicates that the selected switch mechanism is in the open position. It also indicates that the fault interrupter mechanism is in either the open or tripped position. CLOSING INDICATION (YELLOW LIGHT)e: Indicates that the motor actuator is closing the selected switch or interrupter mechanism. OPENING INDICATION (YELLOW LIGHT)e: Indicates that the motor actuator is opening the selected switch or interrupter mechanism. Important Notee: The VFI mechanism is a trip-free mechanism. If the VFI is closed by a motor operator and a fault occurs, the handle will be held in the CLOSED position, but the VFI mechanism will trip and the control panel will indicate OPEN. To reset the VFI, select the correct motor and push the OPEN pushbutton. The motor operator will open and reset the VFI. The VFI can then be closed by pushing the CLOSE pushbutton. OPERATION INSTRUCTIONS MN285018EN May 2017 7

Figure 7. Outline diagram of DC motor operator control 8 OPERATION INSTRUCTIONS MN285018EN May 2017

SCADA Terminal block connection procedures SCADA terminal block connection can be completed via side-entry or front-entry connection. The maximum wire size to be used is #14. The minimum wire size to be used is #26. To connect the SCADA terminal block, use the screwdriver provided in the DC Motor Operator Control cabinet in conjunction with the following instructions (See Figure 9): 1. Insert the screwdriver into the operating slot. 2. Insert stripped wire. Hold the clamping spring open with the screwdriver so that the conductor can be inserted into the clamping unit. 3. Withdraw the screwdriver. The conductor will automatically be clamped. The DC motor actuator can be manually disconnected by removing the cotter pin which connects the motor to the yellow handle (See Figure 11). Translator Tube 941197KM Figure 10. DC Motor actuator - disconnected The actuator and limit switches are adjusted for proper operation prior to shipment. Moving the translator tube manually or electrically while disconnected from the switchgear will necessitate re-adjustment of the assembly. Testing procedures Figure 8. SCADA terminal block connection procedures DC Motor actuator The DC Motor Operator Control is designed for operation with the DC Motor Operator. The DC Motor actuates to open or close when supplied with 24 Vdc via the control (See Figure 10). WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Battery test 1. Remove AC Input for two minutes. 2. Measure Vdc of battery with no load present - positive probe to P1-2 (B+), negative probe to P1-5 (B-, ground) (See Figure 2). If less than 23.3 volts, charge battery for 24 hours. 3. Push white Battery Test push button. Voltage drop should not exceed two volts. Figure 9. DC Motor actuator - connected 941196KM Lamp test Push the LAMP TEST (white) pushbutton to check indicator operating lights. This energizes all lights simultaneously. The remote status and operating contacts are not tested. OPERATION INSTRUCTIONS MN285018EN May 2017 9

Maintenance information WARNING This equipment requires routine inspection and maintenance to ensure proper operation. If it is not maintained it may fail to operate properly. Improper operation can cause equipment damage and possible personal injury. G105.1 Maintenance program A routine maintenance inspection program is required to ensure proper operation of the equipment. Detailed service records should be recorded in the unit s inspection and maintenance record log. Refer to Tables 1 and 2 for typical operating characteristics of the DC Motor Operator Control. Table 2. DC motor operator-operating characteristics Close (secs.) Open (secs.) Min. Avg. Max. Min. Avg. Max. Motor run time 4 12 4 7 Device time (RVAC) 5 5 Device time (VFI) 5 5 Replacement parts Replacement parts for the DC Motor Operator Control are available through the factory Service Department. To order parts, contact your Eaton representative for additional information and ordering procedures. Table 1. DC motor operator ratings Close max. (amps) Running load amperage (RLA) 12 12 Lock rotor amperage (LRA) 24 23 In rush 20 19 Open max. (amps) 10 OPERATION INSTRUCTIONS MN285018EN May 2017

This page intentionally left blank. OPERATION INSTRUCTIONS MN285018EN May 2017 11

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN285018EN May 2017 KA2048-0406 REV01 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.