CONTROLLER INFORMATION SHEET

Similar documents
Summary. Compatible PLCs. Communications Cable. PLC Settings. Gemini GV6 Series

MODBUS RTU. HMI Setting: PLC Setting: Supported Series : MODBUS RTU CONTROLLER Website :

CONTROLLER INFORMATION SHEET

C O N T R O L L E R I N F O R M A T I O N S H E E T. Allen-Bradley SLC500 & MicroLogix Series (DF1 BCC Checksum)

CONTROLLER INFORMATION SHEET

19.Configure HMI as a MODBUS Server

Allen-Bradley ONTROLLER NFORMATION HEET. MicroLogix 1000, 1100, 1200, Overview. Communications Cable. PLC Settings

Set HMI as a MODBUS Server

CONTROLLER INFORMATION SHEET

C O N T R O L L E R I N F O R M A T I O N S H E E T. Siemens S7-300 Series (Ethernet)

MODBUS RTU (0x/1x Range Adjustable)

MODBUS RTU (Adjustable)

using the Data-Linc SRM6000 Spread Spectrum Radio Modem (version 5.39) and Wonderware InTouch 95 (version 7.0.1)

Title: Using the AUX Port.

ABB Modbus RTU Driver for JMobile

Keyence KV Series ONTROLLER NFORMATION HEET. Overview. Communications Cable. PLC Settings

Title: Using the AUX Port.

Idec ONTROLLER NFORMATION HEET. Micro 3 & OpenNet Series. Overview. Communications Cable

Please refer to application note AN00129 for further details on HCP2 configuration in ABB motion control products.

IntelliSense Application Note 1

Title: HMI500 Series Frequently Asked Questions

Mitsubishi FX Series ONTROLLER NFORMATION HEET. Overview. Communications Cable. PLC Settings

Modbus TCP Client Ethernet Modbus TCP Client Modbus TCP Server Ethernet Modbus TCP Server 5

Modbus TCP Driver for JMobile

Motion Control Products Application note Connecting CP600 to motion products via Modbus RTU

Title: Can I use Ethernet to read and write values to my HMI?

Motion Control Products Application note Connecting CP600 to motion products via Modbus RTU

Golander Peristaltic Pump MODBUS Communication Instruction

GE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C

Modbus on K45 asense. Table of contents:

ICC. Modbus RTU Slave Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

Pass-Through Function

Lufkin Modbus Serial Driver Help Kepware Technologies

ICC. Modbus RTU Sniffer Driver Manual INDUSTRIAL CONTROL COMMUNICATIONS, INC Industrial Control Communications, Inc.

Animatics SmartMotor Series, RTC Series ONTROLLER NFORMATION HEET. Overview. Communications Cable

Getting Started with your D3000M Series Module

Modbus Protocol For TGP03 / THP03

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

GTWIN 1.1 CONTROL TECHNOLOGY CORPORATION. GTWIN 2.8 Quick Start. MGT Panel & GTWIN Quick Start Guide

Modbus on SenseAir S8

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2

4511 MODBUS RTU. Configuration Manual. Solenoid / alarm driver. No. 9203MCM100(1328)

SIXNET EtherTRAK Driver PTC Inc. All Rights Reserved.

ICP PANEL-TEC PEX3000 II

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM102(1739) For 4511 devices from ser. no:

DeviceMaster UP Modbus Controller to Controller Communication

Magelis XBT-G Modbus (RTU) driver. eng

EGW1-IA3-MB User s Manual

Serial Connection of HC900 Hybrid Controller to 900CS Control Station

Chapter. Modbus. In This Chapter...

This document assumes the user has a reasonable understanding Modbus, RS485 communications, and Rockwell Software s RSLogix product line.

ABB LVP&S Training AC500 to EMAX Modbus RTU ABB Automation Technologies

Connecting UniOP Using Generic Modbus RTU

INTELLIS. Modbus Direct Network Monitor

Instructions. Modbus RTU Card (WSIQ-COM-MB)

4511 MODBUS RTU. Configuration Manual. Pulse isolator. No. 9202MCM101(1707) For 4511 devices from ser. no:

Yaskawa Electric MP900 Series Driver

QS460MMDS1000 ModBus/DeviceNet Communication Module

ProtoConvert Modbus RTU / Modbus TCP/IP / BACnet MSTP / BACnet IP / SNMP - Telnet (Lighting Controller) PG

Interface design document MODBUS Protocol. Ab s t r a c t Description of the MODBUS implementation for the Modbus I/O board

TECH TIP. Tritex Modbus Protocol Specification

Modbus Hans-Petter Halvorsen

P2 Configuration Guide

Chapter 1. Introduction. Additional Documentation

D0 DCM Module Setup Direct

Modbus ASCII Serial Device Driver Help 2009 Kepware Technologies

T1K MODBUS Base Controller Specifications

Conto D1 MODBUS COMMUNICATION PROTOCOL

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Connecting UniOP to Modbus/TCP

Modbus RTU Serial / Modicon Serial Device Driver Guide

Cutler-Hammer ELC Serial Driver Help Kepware Technologies

KTA-250 Anemometer Alarm Card

Communications guide. Line Distance Protection System * F1* GE Digital Energy. Title page

LoRaWAN Wzzard Utility Quick Guide. v /11/1

Modbus Protocol For FTS/FTM 3x&8x

Modbus on S8. Modbus is a simple, open protocol for both PLC and sensors. Details on Modbus can be found on

Module with RS485 communication option for

Modbus on tsense. Table of contents:

Modbus on S8. Modbus is a simple, open protocol for both PLC and sensors. Details on Modbus can be found on

Modbus on CO 2 Engine and esense

This command can be used for reading the current state of one or several digital inputs, according to the table below.

[ 公司地址 ] Modbus Protocol. For THS/THM 30X&80X_Temp.&Humididy & THS8X/THM8X_Dew Point Series V7.0

WRC Modbus to DeviceNet Gateway for GPD 506/P5

Contrex M-Series Driver Help Kepware Technologies

CO General Specifications GS48D62Z00-00E-N GENERAL. ProSafe-COM extended communication system

MPU-32 AND FPU-32 TIA-485 NETWORK

OPERATOR INTERFACE PRODUCTS APPLICATION NOTE

Compumotor. 6000, 6K & Germini Series (OITware)

Modbus Protocol For PMX / PXM3X

Protocollo Modbus sui controlli pco Modbus protocol for pco controllers

VersaMax* Serial Communications Module

Mitsubishi FX3 Driver Configuration Manual

Application Note CTAN #165

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Connecting UniOP as a Modbus Slave

Revision 1.2. July 24, COM Protocol Manual. for MDC and ADC N 11th St - San Jose CA

WebAccess Driver Configuration Manual

Application Note. Application Note. IntelliSense Application Note 3. Messaging between Bimba IntelliSense SIM Module and Siemens S PLC

Transcription:

CONTROLLER INFORMATION SHEET Maple Model(s) Graphic HMIs PLC or Controller Modbus RTU P/N: 1036-0045 Rev. 06 Date: 09/17/2015 Summary Maple Systems Graphic HMIs communicate with any device that uses the Modbus RTU protocol. The HMIs use the Modbus RTU Master protocol driver to allow the Graphic HMI to act as the master in a single master, (single slave or multiple slave) format. RS-485 networking is supported to connect multiple Modbus slave devices to a single Graphic HMI. The Modbus RTU Master protocol driver in EZware also has the following features: Network support using RS-485 4-wire or RS-485 2-wire connection. Ability to swap bytes within words (16-bit) or swap words (32-bit) for both read and write operations. Ability to define the minimum and maximum addresses for 0x and 1x device types. Ability to read/write to individual bits in 4x memory. Ability to set a turnaround delay that can be used to slow the rate at which the HMI expects a reply from the PLC/controller for data. Ability to force a Modbus function code 06 (6x) for controllers that do not support function code 16. Ability to address 32-bit registers.. Communications Cable The Graphic HMI should be connected to the controller s serial port that supports Modbus. A list of communications cables offered by Maple Systems as well as cable assembly instructions to assist you in assembling your own communications cable are available on our website at www.maplesystems.com. WARNING If your communications cable is not wired exactly as shown in our cable assembly instructions, damage to the HMI or loss of communications can result. PLC Controller Settings The Modbus port on the controller must be set to RTU slave mode in order to properly communicate with the HMI (master). 1036-0045 Page 1 of 8 Rev. 06, 09/17/2015

Accessible PLC Memory Register Memory The following table lists the PLC s register memory ranges that the Maple HMIs are able to access. Please note that your PLC s memory range may be smaller or larger than that supported by these HMIs. The following register memory can be displayed in 16 or 32-bit format on the Maple HMI. Controller Register Type Address Controller Register Description 300001-365535 3x 1-65535 Input Registers, Read Only 400001-465535 4x 1-65535 500001-565535 5x* 1-65535 600001-665535 6x** 1-65535 Holding / Output Registers (high-word, low-word order) Same as 4x but does a word swap (for 32-bit word swapping - low word first) Force HMI to use function code 06 to write to this register. 300001 365535 3x_Double 1-65535 Defaults to 32-bit Unsigned numeric format 400001 465535 4x_Double 1-65535 Defaults to 32-bit Unsigned numeric format 40001 465535 4x_32bit 1-65535 Same as 4x but used for 32-bit registers. 00001 09999 0x_single_coil 1-65535 Discrete Coils/Outputs (0 = coil off; 1 = coil on) NOTES: * The 5x register type is exactly the same as the 4x memory area. Use the 5x memory area when reading/writing to a 32-bit register using the Low Word First format. ** The 6x register type forces the HMI to execute a function code 06 to write a single register. (The HMI default is to use a function code 16 to write multiple registers, even if it is only writing to one register) Discrete Memory The following table lists the PLC s discrete memory ranges that the Graphic HMIs are able to access. Please note that your PLC s memory range may be smaller or larger than that supported by these HMIs. The following discrete memory is displayable in single-bit format on the Graphic HMI. Controller Bit Type Address Controller Bit Description 00001-09999 0x 2,3 1-65535 Discrete Coils / Outputs 00001-09999 0x_multi_coil 1-65535 Discrete Coils / Outputs 00001-09999 0x_single_bit 4 1-65535 10001-19999 1x 2,3 1-65535 Discrete Inputs, Read Only 10001-19999 1x_single_bit 4 1-65535 3x_Bit 3x_Bit 1,2,3 100-6553515 Input Registers, (bit level access) 1036-0045 Page 2 of 8 Rev. 06, 09/17/2015

4x_Bit 4x_Bit 1,2,3 100-6553515 Holding/Output Registers, (bit level access) 6x_bit 6x_Bit 1,2,3 100-6553515 Holding/Output Registers, (bit level access) NOTE: 1 The 4x_Bit memory area is used to read/write to individual bits in the 4x memory area. To use this feature, select the 4x_Bit as Device Type for bit-type objects such as Bit Lamps. Under Device Address, use the format nnnnbb to enter the word memory area, followed by the two-digit bit reference. For example, to target the 3rd bit of 40015, enter "1502" into the Device Address, (nn=15, bb=02). 3x_Bit device type works the same as for the 4x_Bit, except that it is for accessing bits in a 3x input register. 2 The EasyBuilder Modbus driver reads a group of 16 bits at a time. Bit groups are 1-16, 17-32, 33-48, 49-64, etc. All bits in the group must be available in the controller for the HMI to read or errors will result. Examples: A) If a Bit Lamp is programmed in the HMI that is addressed for bit 00038, then bits 00032 through 00048 must be available and programmed in the controller. B) If a Bit Lamp in the HMI is addressed as bit 1068, then bits 10065 through 10080 must be available and programmed in the controller. If required, the address range of the 0x, 1x, and 0x_multi_coil device types can be defined, which overrides the 16-bit group requirement. Click the Address Range Limit button in the Device Properties window to define the minimum and maximum address range for each device type (see Address Range Limit on page 6). 3 Unlike the read statements for bits, the EasyBuilder Modbus driver will write to just one bit at a time; however, whenever a bit write occurs, the HMI will automatically execute a read. Therefore, even if the intention is to only write to one bit, all sixteen bits must be available and programmed into the PLC that includes the bit being written to (unless the Address Range Limit is enabled). 4 The 0x_single_bit and 1x_single_bit, unlike the 0x and 1x addresses, allow the HMI to read a single bit one bit at a time instead of a group of 16 consecutive bits. Address Format when Networking NOTE: There are two methods of addressing devices on a multi-drop network: Method 1: If you are connecting multiple PLCs/Controllers on a network to an HMI, you can specify the network node address for each object placed onto the HMI screen. To target a specific slave address, you must use the following format when entering the address in the Device Address box: aaa#nnnn where aaa=network address (1-255) and nnnn=memory address. The pound sign (#) is used as a placeholder. For example, to configure the Numeric Data object to read memory address 40015 of a PLC that has been assigned a network address of 2: Device Type=4x, Device Address=2#15. Method 2: LW10000 through 10015 are used to change the node address for a multi-node RS- 485 network. i.e. to specify the station number. This feature is enabled in the Device properties window for a Modbus device, by clicking on the Default station no. use station no. variable option: 1036-0045 Page 3 of 8 Rev. 06, 09/17/2015

You then get a dropdown list where the variable to use (LW-10000 through 10015) is selected: A Numeric Input can be configured in the project to write to the selected register and choose the node to use. This allows you to select which device the HMI is communicating with on the network during runtime. 1036-0045 Page 4 of 8 Rev. 06, 09/17/2015

Network Settings When connecting multiple PLCs/controllers to a single Graphic HMI, you must also set the following in the Edit-System Parameters menu: In the Device Properties, select RS-485 4w for a 4-wire cabling scheme. Select RS-485 2w for a 2-wire cabling scheme (TXD+ and RXD+ connected together, TXD- and RXD- connected together). The HMI uses the following Modbus codes: Data Type 0x and 0x_multi_coil; 0x_single_bit Read/ Write Description R Read output bit [read coil] 01 Uses Modbus Code 0x; 0x_single_bit; 1x_single_bit W Write output bit [write coil] 05 0x_multi_coil W Write output bit 15 1x; 1x_single_bit R Read input bit [read discrete input] 02 3x R Read input register [read input register] 04 3x_Bit R Read input register - bit level [read input register s bit] 04 4x R Read holding register (normal word order) 03 4x W Write holding register (normal word order) 16 4x_Bit R Read holding register bit level 03 4x_Bit W Write holding register bit level 16 5x R Read holding register (double word, swap word order) 5x W Write holding register (double word, swap word order) 03 16 6x R Read holding register 03 6x W Write holding register (force a function code 06 when writing) 06 4x_32Bit R Read holding register (32-bit) 03 4x_32Bit W Write holding register (32-bit) 16 1036-0045 Page 5 of 8 Rev. 06, 09/17/2015

EZware Settings The following table lists the communications settings that must be configured in EZware. These settings can be found in the Edit-System Parameters menu under the PLC Settings > Device Properties. Please note: The Recommended Settings column provides the recommended setting based upon the default settings most commonly used in Modbus Devices. The Options column lists EZware s options; your PLC may not support every option Name Recommended Settings Options Important Notes Name: Modbus RTU Master Description label HMI or PLC PLC Location Local Local, Remote PLC type: Modbus RTU Master Select Local if PLC directly connected to HMI, Remote if PLC connected thru another HMI. PLC I/F: RS-232 RS-232, RS-485 2W, RS-485 4W Must match the controller port setting. Setting: COM: COM1 COM1-COM3 Settings: Baud rate 19200 Settings: Data Bits 8 7 or 8 Settings: Stop Bits 2 1 or 2 Settings: Parity: Settings: Timeout (sec) Settings: Turn around delay (ms): None 9600, 19200, 38400, 57600, 115200 Even, Odd, None 1.0 0.1 to 25.5 0 0-1000 Serial port of the HMI connected to the controller. Must match the Modbus port setting. Use the fastest baud rate supported by the controller. Must match the Modbus port setting. Must match the Modbus port setting. Must match the Modbus port setting. Adjust if longer timeout is required. Timeout period between HMI polls. 1036-0045 Page 6 of 8 Rev. 06, 09/17/2015

Name Recommended Settings Options Important Notes Settings: Reserved 1 : 0 Not Applicable Settings: Reserved 2: 0 Not Applicable Settings: Reserved 3: 0 Not Applicable Settings: Reserved 4: 0 Not Applicable PLC default station no.: 1 0-255 Default station no. use station no. variable Unchecked Use broadcast command Unchecked Must match the node address assigned to the PLC. Optional Not Applicable* Interval of block pack (words): 5 0-512 See Help Optimizing the Update Rate with PLC Block Pack Max. read-command size (words): Max. write-command size (words): 120 1-512 Max number of words for a read command 120 1-512 Max number of words for a write command Note: (*) The HMI does not support broadcast messages. The HMI always expects a reply message after it sends a request. Some Modbus controllers use address 0 as a broadcast message so that all node addresses will listen and process the command, but they will not reply back to the master (such as a broadcast RESET command). If, however, the controller has a valid address of 0 and it is not used as a broadcast address, then address 0 can be used. Address Range Limit The Address Range Limit button allows you to define an address range for the 0x, 1x, and 0x_multi_coil device types. Normally, the Modbus RTU driver reads a group of 16 bits at a time. If your Modbus device does not allow defining bits in groups of 16 bit increments, an address range can be defined in the 0x/1x Address Range window. 1036-0045 Page 7 of 8 Rev. 06, 09/17/2015

Conversion Some Modbus devices may have the word order or byte order reversed from the way it is read by the EZware Modbus RTU driver. Click the Conversion button to select the correct setting for your device. AB -> BA does a byte swap. ABCD -> CDAB does a word swap. 4x_Double ABCD -> CDAB is the same as selecting 5x. Note that you can do a byte swap and word swap with 3x_Double and 4x_Double. 1036-0045 Page 8 of 8 Rev. 06, 09/17/2015