EY-RU : Room operating unit, ecounit

Similar documents
EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RU 355: Room operating unit, ecounit355

EY-SU 358: Push-button unit for room operating unit, ecounit358

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

EY-EM : Remote I/O module, ecolink

ecounit : Room operating unit with EnOcean wireless technology

EY-IO 534: I/O module, analogue inputs with galvanic isolation, modu534

I/O module, digital and universal inputs, modu530

EYE 200: DDC single-room controller, ecos200

I/O module, universal, digital, S0 inputs, modu533

I/O module, digital outputs (relays), modu550

I/O module, digital outputs (open collector), modu551

I/O module, analogue outputs and universal inputs

modunet292: novanet-ethernet interface

modu : Local override and indicating units

EY-RC 208, 209: Room automation stations, ecos208, 209

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

EY-RC 500: Room automation station, ecos500

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

EY-RC 311: Programmable controller, ecos311

Sauter Systems

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

Content. Product Description

Room unit with PPS2 interface

Room unit with PPS2 interface

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

AVF 125S: SUT valve actuator with spring return

AVM 321, 322: Valve actuator

EY-WS 500: Web server for moduweb Vision and moduweb500 BACnet networks

EY-AS 521: Compact automation station, modu521

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Room unit with PPS2 interface

Room unit with PPS2 interface

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Manual operation and local visualisation. with SAUTER EY-modulo.

Digital input modules

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

TXM1.8RB. TX-I/O Blinds module

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

KM692K KELOX BUS room thermostat - Digital

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

UCU Room Display. Operation Modes. Features. Applications DATASHEET

1 IF-812 or IF-815 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-812/IF-815

Product and Function Description

AVM 105S, 115S: Valve actuator with SAUTER Universal Technology (SUT)

Room Temperature Controller

Super universal modules

Pre-programmed room controller with display and communication

Room Temperature Controller

Non-communicating room controllers

TM-2100 Series Room Command Module

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

ASV215BF152*: VAV compact controller for laboratory and pharmaceutical applications

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Products no longer available

Room Temperature Controllers

Eco Climate Control. Intelligent comfort for radio control of surface heating and cooling systems.

Rotary version, three-position control

TC-8900 Controller Units with PM-8900 Power Modules

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

IRMA MATRIX Release 2

Semi flush-mounted room temperature controllers with LCD

1 IF-810 or IF-811 Terminal (Slave) 2 Intended Use. 3 Assembly and Installation _V IF-810/IF-811

SAUTER EY-modulo. Compatibility for a secure investment.

RDF301 RDF CE1N3171en 02 Jun 2010 Building Technologies

Resistance measuring module

Technical data. Safety notes. Product features

Product and functional description

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

TM-2100 Series Room Command Module

Immersion Temperature Sensors

Product and functional description

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

7-day room temperature controller

Allure EC-Smart-Comfort Series

Semi flush-mounted room temperature controllers with LCD

Precision thermometer Model CTR5000

AVM321S, 322S: Actuator SAUTER vialoq AVM 1000 with SAUTER Universal Technology (SUT )

Allure EC-Smart-Comfort Series

Heating Circuit Controller

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Non-communicating room controllers

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4.

Product and functional description

Semi Flush-mount Room Temperature Controllers with LCD

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Push Button Interface UP 220D31

Master room unit for RRV controllers

Data sheet GCM MOD GMM EC.1 Communications module Modbus for GMM EC

Transcription:

Product data sheet 94.051 EY-RU 310...316: Room operating unit, ecounit310...316 How energy efficiency is improved Individual setting of occupancy and absence as well as a room setpoint correction, control of lights and window blinds for optimum energy usage in the room. Visualisation of the local energy consumption by means of multicolour LED indicator Features Part of the SAUTER EY-modulo 5 system family Room operating unit for eco500, 502, 504, 505 and modu521 Can be extended with EY-SU 306 push-button unit Operating unit to control and guarantee the highest possible room comfort Temperature measurement and setpoint adjustment Device insert with transparent front, fits into frame with 55 x 55 mm aperture Frame can be ordered as an accessory Indoor climate can be adapted individually The operating mode can be set for the room occupancy and the actuation of a 3-speed fan Control of window blinds, windows and lighting (ON/OFF/dim) Multicolour LED indicators for visualisation of local energy consumption Room operating unit with a wide range of different functions, designs and colours EY-RU316F001 Technical data EY-RU310F001 Power supply Power supply From automation station Current consumption 25 ma 38 ma with 2 EY-SU306 Operating temperature 0...45 C Ambient conditions Parameters Sensors Functionality Interfaces and communication Connection to automation station Storage and transport temperature 25...70 C Admissible ambient humidity 10...85% rh, no condensation Measuring range 0...40 C Resolution 0.1 K Time constant Approx. 7 min Setpoint correction Variable Room occupancy (presence) 3 modes, LED indicator Fan speeds 5 functions, LED indicator Position LED Switchable: green/red/off Activation ecos 5, modu521 Interface RS485 Protocol SLC Line 4-wire, twisted, shielded Cable length1) 100 m (30 m) with bus termination Connection terminals Pluggable; for wire of 0.12...0.5 mm² (Ø 0.4...0.8 mm) Fitting Recessed/surface-mounted (see accessories) Dimensions W x H x D 59.5 59.5 25 mm Weight 0.1 kg Housing Pure white (similar to RAL 9010) Plastic insert Silver (similar to Pantone 877 C) of protection IP30 (EN 60529) Construction Standards and directives 1) max. 30 m for industrial applications as per EN 61000-6-2 Right of amendment reserved 2016 Fr. Sauter AG 6.1 1/6

Protection class III (EN 60730-1) Environment class 3K3 (IEC 60721) CE conformity according to EMC Directive 2004/108/EC EN 61000-6-1, EN 61000-6-3 Overview of types Properties Buttons EY-RU310F001 NTC sensor EY-RU311F001 EY-RU314F001 EY-RU316F001 Accessories Operating unit EY-SU306F001 Fitting Operating unit, NTC sensor, dxs setpoint correction (rotary knob) Operating unit, NTC sensor, dxs setpoint correction (rotary knob), fan, occupancy Operating unit, NTC sensor, dxs setpoint correction (rotary knob), fan, occupancy, window blinds / light Description Push-button unit, without frame Description 0940240*** For frames, mounting plates and adaptors for third-party frames: see product data sheet PDS 94.055 0949360004 Plug-in connectors ecounit, 2-pin, "01/02", "03/04" (2 x 10 pcs.) 0949241301 Transparent cover for EY-RU 310 (10 pcs.) 0949241302 RAL 9010 white cover for EY-RU 310 (10 pcs.) Description of operation The ecounit 3 room operating units EY-RU 310...316 measure the room temperature and have a rotary knob for setpoint correction, buttons to select the presence mode and the fan speed and up to two freely allocatable buttons. The room operating units belong to the ecos 5 product family and can be connected to a (room) automation station (RC/AS) of the EY-modulo 5 system family using the digital RS485 connection. The LED indicators can be controlled using the room controller. Intended use This product is only suitable for the purpose intended by the manufacturer, as described in the Description of operation section. All related product regulations must also be adhered to. Changing or converting the product is not admissible. Front view and labelling inserts Depending on the type of device, different labelling inserts are included. The operating unit can be adapted to the spatial conditions. 2 4 EY-RU 310 Labelling inserts included in the scope of delivery EY-RU 311 2/6 6.1 Right of amendment reserved 2016 Fr. Sauter AG

EY-RU 314 Labelling inserts included in the scope of delivery EY-RU 316 A 0 1 2 3 Engineering notes Fitting The EY-RU 310...316 room operating units are suitable for various fitting methods. Product data sheet PDS 94.055 shows the mounting options and the accessory material required. The EY-SU 306 switching unit can be used to enhance the EY-RU 310...316 room operating devices with 6 additional button functions. EY-SU 306 is connected to EY-RU 310 316 with a 2-core connection and can only be used in conjunction with a basic unit (EY-RU). Two EY-SU 306 with the same button assignment/function can be connected in parallel. Switching unit EY-SU 306 can be installed up to 30 m (total line length) away from the EY-RU. Connection to automation station The room operating units are connected to the AS with a 4-wire shielded cable with twisted wire pairs. The max. admissible bus length depends on the cable type used and the correct termination with terminating resistors. Observe the correct polarity of all signals. The wire shield of the entire bus line must be connected continuously, and connected to the protective earth as directly as possible (max. 8 cm) at one location, for optimum resistance to interference. For Ethernet CAT-5 cables, as well as IYST-Y cables, a bus length of up to 100 m is possible, for applications in residential, business and commercial areas (interference resistance requirements as per EN61000-6-1). Applications in industrial areas (interference resistance requirements as per EN61000-6-2) allow a max. total bus cable length of 30 m. In the case of RS485 interfaces, the bus wiring must follow line topology. Star, tree or branch topologies are not recommended. The devices do not have internal terminating resistors. Therefore, a terminating resistor of 120 Ω (0.25 W) must be connected at the start and end of the bus line, parallel to the D+/D- data lines. Addressing the operating units A device address must be set on the communicative room operating units to ensure that they can be contacted by the automation station. The housing cover of the ecounit is located under the transparent cover or the labelling insert. All operation and indication functions are clearly labelled on this surface. Sw: Connection name in firmware module. At least 2 buttons are available on all variants: Top left button (A), top right button (B). On devices EY- RU 310 and EY-RU 311, these two buttons or LEDs can only be used for addressing. There are also 5 LEDs on the right-hand side (1, 2, 4, 8, 16) and 3 LEDs on the left-hand side (G, H, J). Right of amendment reserved 2016 Fr. Sauter AG 6.1 3/6

Addressing mode The device address can be set without a time restriction after switching on if: a) no address has previously been assigned (ex works condition) or b) there is no communication with the AS, for example because addressing has been carried out incorrectly. The addressing mode is signalised using the bi-colour position LED which is located under the potentiometer. The LED state during addressing mode overwrites the LED state requested by the user program of the AS. The following applies: Position LED Status Meaning Red Flashing Device is not addressed Red Continuously ON Device is in addressing mode (temporary) Green Flashing Valid address is displayed (temporary, approx. 10 s) Green, red Continuously ON or OFF Device in operation, see position LED Non-addressed device, set address In ex works condition, the devices are not addressed. After powering up, the position LED flashes red. If button (B) is pressed for over 5 seconds, the device switches to addressing mode, the position LED is lit continuously red and the LED (G) is lit green. Address 0 is displayed. Pressing the button (B) again activates input mode. The device address (1 to 4) can now be set. The addresses 0 and 5...15 are currently not supported by the automation stations. Using button (B), the LEDs (1, 2, 4) are scanned upwards as per binary code, using button (A) they are scanned downwards again. The following table shows the coding to set the device address: Address LED (1) LED (2) LED (4) 0 --- --- --- 1 X 2 X 3 X X 4 X Pressing and holding button (A) stores the setting and returns to the operating mode. However, if no change is made for 5 seconds, the device returns to the operating mode without saving the settings that have been carried out. Changing addressed devices The position LED is lit continuously green, red or OFF according to the AS user program. If button (B) is pressed for over 5 seconds within the first minute after voltage is restored, the device switches to addressing mode and the set address is displayed. If button (B) is pressed again, the device switches to input mode. Pressing and holding button (A) stores a new address and returns to operating mode. However, if no change is made for 5 seconds, the device returns to the operating mode without saving the settings that have been carried out. Position LED Starting with the index D devices, the state of the position LED for the types EY-RU 311 316 can be set using the user program of the AS: continuously green, red or off. For example, this function can be used to indicate optimal energy consumption in the room by the colour green. The colour red can be used in the same way in order to indicate energy consumption that is too high. This function is not available for devices up to and including index C. Connecting EY-RU 3 ** to the user program of the AS How the automation station or the operating unit respond to the press of a button is programmed in the user program. The room unit module is available in the firmware for this purpose. This module is described in the Firmware modules documentation. 4/6 6.1 Right of amendment reserved 2016 Fr. Sauter AG

Additional information Fitting instructions P100001965 Declaration on materials and the environment MD 94.051 Dimension drawing EY-RU310 EY-RU311...316 Connection diagram Disposal M10487 M10488 A10523 When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product. Connection diagram for EY-RC 500 (RS485A), 502, 504, 505, EY-AS 521 EY-SU306 EY-RU3.. EY-RC5../EY-AS521 RS-485 bus wiring ecos 5 modu521 ecounit 3 ecounit 3 ecounit 3 V V V V 0,25 W 0,25 W EN 61000-6-1: EN 61000-6-2: 3 (Ø 0.5 mm²) For industrial applications, the entire bus length may be max. 30 m to fulfil the criteria for interference resistance as per EN-61000-6-2. For residential, business and commercial applications with requirements as per EN61000-6-1, the entire bus length may be up to 100 m. Right of amendment reserved 2016 Fr. Sauter AG 6.1 5/6

Dimension drawing EY-RU 310 EY-RU 311...316 25 59,5 15,5 M10487 59,5 Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61-695 55 55 www.sauter-controls.com 6/6 6.1 Right of amendment reserved 2016 Fr. Sauter AG