S Reclosers. Contents. Form 4C Recloser Control Protocol Conversion Kits KME , -7002, and Installation Instructions

Similar documents
S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

COOPER POWER SERIES. Fiber-optic/RS-232 communications module installation and operation instructions. Voltage Regulators MN225020EN

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

COOPER POWER SERIES. Ethernet communications module installation and operation instructions. Voltage Regulators MN225033EN

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Single Phase Vacuum Capacitor Switch. UltraVacLT 15kV 95kV or 125kV BIL

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

PIX 520. PIX 520 Product Overview CHAPTER

Vapor Monitor Interface Module

INSTALLATION INSTRUCTIONS

4 Channel 4~20mA/0~10VDC Analog Data Fiber Link System

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

PIX 515/515E. PIX 515/515E Product Overview CHAPTER

Serial Data DIN Fiber Link System

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

5504 Thermocouple Analog Input Module

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

PS/IO Circuit Board Retrofit

Installation NOTICE. S&C IntelliCap Automatic Capacitor Control. Table of Contents. Instruction Sheet

4100/ VDC Converter Installation Instructions

PowerLogic High Density Metering System 1-Meter Enclosure

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Model 2380 Rack-Mount Kit

CMU 100 Multimode Fiber Optic to Singlemode Fiber Optic Converter User Manual

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches. Installation Guide. P/N (Rev G)

INSTALLATION INSTRUCTIONS FOR THE BV10-100/1000

EOS-6000 Series Optical A/B Switch User Manual DC Version

COM32. Installation & Operation Manual

Installation and Operation

CMU 100 RS232 to Singlemode Fiber Optic Converter User Manual

Pretium Rack-mountable 1U Housing Hardware

Series Amp Pad Mount Quick Connect Input and Output Power Panels

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

Vista SD Portable Remote Control Pendant

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

Expansion module EM-BAC-MOD-01. Installation manual

Source-Transfer Application Guide

Industrial Serial RS-232 to Fiber Converter. KSC-200 Series. Installation Guide

Installing the Cisco MDS 9020 Fabric Switch

S Reclosers Kyle Form 5 Microprocessor-Based Recloser Control Installation and Operation Instructions. Contents

RS-232 Industrial Media Converter

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

MC 11 EB-2 Power supply cabinet with external bus, AC version

Installation Instructions

Model 2380 Rack-Mount Kit

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

and Network Interface Modules Installation Instructions

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS

INSTRUCTION MANUAL RA 59 RACK ADAPTER. 1) This manual is valid for the following Model and associated serial numbers: MODEL SERIAL NO. REV. NO.

USER MANUAL MODEL 2017P MODEL 2017P60. RS-232 to 20mA and. RS-232 to 60mA Current Loop Converters

Square D Clipsal Pascal Automation Controller

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Replacing the Power Supply

Reclosers Service Information Form 5 Microprocessor-Based Recloser Control Programming Guide

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1

S Reclosers Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Microprocessor-Based Recloser Controls Installation and Operation Instructions.

TECHKNOW, INC. Kiosk Order Confirmation System INSTALLATION MANUAL. Revision Date: July 11, 2012 Part # Version 3.2

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

INCOM communications adapter module

Tile Plow Installation O Connell

Installing the Fiber Optics Card

E1135C PDU and Pod Upgrade Procedure

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1

2 Wire Digital Phone Fiber Link Card System

M215 (M215-60) Safety

Installation Instructions

ELECTRO-MECH SCOREBOARD CO.

An ISO-9001 Certified Company

YASKAWA AC Drive-1000 Series Option Operator Mounting Kit NEMA Type 4X, IP66 Installation Manual Model No.: UUX or UUX000527

Electrical network protection Sepam series 20 Sepam series 40 Quick start

PIX 535. PIX 535 Product Overview CHAPTER

GWI Rev. 5 September, 2014 Supersedes Rev.4 June, 2013

TippingPoint Zero Power High Availability Installation Guide

Installing the Cisco 2524 and Cisco 2525 Routers

Primary Injection Test Procedure

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

KSD-800 Series. Installation Guide. Industrial 8-Port Fast Ethernet Switches with Fiber Connectivity DOC A -1-

KFC-200. Installation Guide

INSTALLATION INSTRUCTIONS

AutoScan to MultiScan Replacement Kit

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

Application Note (Revision NEW) Original Instructions EGCP-3 LS Using an EGCP-3 in a Single-Phase Zig Zag Generator Application

BRB Systems USA Co. Instruction Manual. USA Trap Solo Voice Release System. 12V & 120V Versions.

V910 Kit. Hardware Installation Guide. P/N Revision: A

Manual No: Revision: F. Relay Output Modules. Installation Guide

COOPER POWER Effective August 2015 Supersedes S July 2014

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Transcription:

Reclosers Form 4C Recloser Control Protocol Conversion Kits KME4-589-7001, -7002, and -7003 Installation Instructions Service Information S280-77-11 DB-9 Connector for MODBUS/FSK option RS-232 DB-9 Connector TX RX Fiber- Optic 010029KM Figure 1. Form 4C Recloser Control Protocol Conversion Kit circuit board for 2179 Protocol Conversion to DNP, MOD- BUS protocol. Contents Safety Information......................... 2 Hazard Statement Definitions............... 2 Safety Instructions....................... 2 Product Information....................... 3 Introduction............................ 3 Read This Manual First.................... 3 Additional Information..................... 3 Quality Standards........................ 3 Acceptance and Initial Inspection............ 3 Handling and Storage..................... 3 Description............................. 3 Installation............................... 4 To Remove Control From Service............ 4 Protocol Conversion Kit................... 4 Testing.................................. 6 Fiber-Optic Cable Specifications............. 8 Kit Parts................................. 9 December 2003 Supersedes 3/02 Printed in USA 1

Form 4C Recloser Control Protocol Conversion Kit Installation Instructions Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our Safety For Life mission. The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions INFORMATION Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER: Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high and low voltage lines and equipment. G103.3 WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment damage. G102.1 WARNING: Power distribution equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain power distribution equipment can result in death, severe personal injury, and equipment damage. G122.2 2

S280-77-11 PRODUCT INFORMATION Introduction Service Information S280-77-11 provides installation instructions for the Form 4C Protocol Converter Accessory kit. This accessory kit enables the use of additional communication protocols to meet application needs. This kit contains a protocol board with required hardware and wiring sub-assemblies. For additional information related to the installation and operation of the Form 4C control, refer to S280-77-1 Form 4C Microprocessor-Based Recloser Control Installation and Operation Instructions. For programming instructions, refer to S280-77-4 Form 4C Microprocessor-Based Recloser Control Programming Guide. Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing and operating this equipment. Additional Information These instructions do not claim to cover all details or variations in the equipment, procedures, or process described, nor to provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, contact your Cooper Power Systems representative. Quality Standards The Quality System at the Cooper Power Systems, Kyle Distribution Switchgear plant is certified to the ISO 9001 standard. Acceptance and Initial Inspection Each accessory is tested and inspected at the factory. It is in good condition when accepted by the freight carrier for shipment. Upon receipt, thoroughly inspect the accessory for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately. Handling and Storage CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in circuit board damage. T253.1 This kit includes a grounding wrist strap designed to control static electricity (Figure 2). Be certain to wear the wrist strap before unpacking and during the installation of the protocol board accessory. Failure to use a grounding wrist strap may result in damage to the protocol board(s). Following are instructions specific to using the grounding wrist strap: 1. Unwrap the first two folds of the strap and place the exposed adhesive side firmly around your wrist. 2. Unroll the rest of the strap and peel the liner from the copper foil at the opposite end. 3. Attach the copper foil end to a clean area on the grounded back-panel inside the control cabinet. Attach end of strap to Form 4C cabinet ground. Figure 2. Correct use of grounding strap. If this accessory will be stored for any appreciable time, place circuit board assembly in static-proof bag and store it and all other items in a clean, dry storage area. Description The function of the protocol converter is to interface between the Form 4C Control (native 2179 protocol) and a host system of DNP or MODBUS protocol. The protocol converter is a DTE device and is connected to a radio or modem (DCE device) with a straight DB-9 connector (RS-232). The DNP version is equipped with a terminal program which allows access to DNP and advanced communications parameters as defined in the R280-90-16 DNP3 Device Profile, Release 2.0. Connection from the PC to protocol converter is made through a null modem. 3

Form 4C Recloser Control Protocol Conversion Kit Installation Instructions INSTALLATION IMPORTANT: The Form 4C control must be removed from service and transported to a clean and suitably equipped service center prior to the kit installation process. To Remove Control From Service The following steps must be taken to remove the control from service and prevent possible recloser misoperation. 1. Switch Ground Trip Block switch to BLOCK. 2. Disconnect control cable from the control. 3. De-energize ac power from the control. 4. Unplug the control battery. Protocol Conversion Kit Circuit Board Installation The protocol communications accessory circuit board mounts to the bracket, which is part of the Form 4C battery-supply shelf. The following procedure should be used to install the Form 4C accessory circuit board. For additional information, refer to Service Information S280-77-1 Form 4C Microprocessor-Based Recloser Control Installation and Operation Instructions. A linear (standard) power supply can be used if the application will not be equipped with a radio. Note: Note: When using the linear (standard) power supply, discard the red/black twisted-pair wire (Item 6) included with the kit. This is not used with linear (standard) power supplies. When using the automation power supply, discard the orange/brown wire (Item 9) included with the kit. This is not used with automation power supplies. CAUTION: Recloser misoperation. The control must be removed from service prior to performing any maintenance, testing, or programming changes. Failure to comply can result in misoperation (unintentional operation) of the recloser. T216.2 1. Remove the Form 4C Recloser Control from service. Refer to S280-77-1 Form 4C Microprocessor-Based Recloser Control Installation and Operation Instructions for additional information. 3. Carefully transport the control to a suitable service facility. Note: The entire kit assembly/installation process should be conducted in a clean environment, such as a repair shop. 4. Open the control front panel by turning two springloaded wing studs. 5. Locate the four wing nuts that fasten the battery holddown brackets to control box. Note: On later models, there are two additional empty studs to be used for board installation. On earlier models, remove the second and fourth wing nuts and lockwashers. This hardware will not be reused for board installation. CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in circuit board damage. T253.1 6. Refer to the Handling and Storage section of this manual before continuing with board installation. Carefully remove the protocol communications board accessory from the static-proof bag. 7. With circuit board components facing out, install the board to the mounting studs (Figure 3). Secure board with the supplied wingnuts and washers. Tighten hardware securely. Board Mounting Bracket (Flange on shelf of battery storage compartment.) Washers and Wingnuts Component Side of Kit Circuit Board Figure 3. Accessory circuit board mounting. Install this section of circuit board over first stud on right of bracket. CAUTION: Control damage. De-energize both ac and dc power prior to removing or installing any internal connections or circuit boards in the control. Failure to comply can result in damage to the control. T241.1 2. Completely de-energize the control by disconnecting all ac and dc voltages to the control box. 4

S280-77-11 8. Connect wires (either red/black or orange/brown) between power supply and protocol board. Wire color is dependent upon the type of power supply in the Form 4C control. Follow the applicable instructions: Form 4C Control with the Automation Power Supply: Use red/black twisted pair wire (Item 6). Orange Wire (+) P11 + Brown Wire ( ) Orange to P11 + Brown to P11 A. Strip leads at one end of supplied twisted-pair wire (red/black) to expose 6 mm (1/4 inch) of bare wire. B. Fasten stripped wires to terminal P3 on power supply. C. Route red/black wire to Pll on new communication board and strip wire ends as stated in first step. D. Insert wire into P11 with the red wire to the + side. Refer to Figure 4 for polarity orientation. Interface Cable P2 P11 + Linear Power Supply Configuration Dependant P11 Connector (Screws face away from board.) Circuit Board Red Wire P11 + Black Wire Red Wire (Terminal 1) P3 24 Vdc 1 2 3 4 Black Wire (Terminal 3) Figure 4. Terminal connections of red/black twisted pair wire. (Applicable to the automation power supply only.) Form 4C Control with the Linear (Standard) Power Supply: Use orange/brown wire (Item 9). A. Disconnect the orange/brown wire from the power supply to the optional I/O board. Discard wire. See Figure 5. B. Replace discarded wiring with kit-supplied yellow/brown wiring. Connect end plug to power supply and second plug to optional input/output board. C. Route the remaining brown and orange leads to P11 on communications protocol board. Note: If required, strip both wires to expose 6.4 mm (1/4 inch) of bare wire. D. Connect stripped areas of wires to P11 with orange wire to + side of connector. Refer to Figure 5. 9. Connect the interface cable as follows: Note: The interface cable has a connector at each end. One end also has a protruding ground wire. A. Insert the cable end without the ground wire into P2 on the protocol conversion circuit board. B. Connect the cable end with ground wire to P20, located on the lowest board attached to the swing panel (Figure 6). Figure 5. Connection of orange/brown wire. (Applicable to the linear (standard) power supply only.) C. Route the cable as shown in Figure 6 with the provided wire ties (Item 7) to secure it to existing cabling. D. Connect the ground wire to swing panel (Figure 6). Ground Interface Cable here Wire Ties P20 P20 (below P4 near interior side of swing panel) Swing Panel Figure 6. Placement of interface cable. Cabinet 10. Attach the communications protocol identification label to the inside of swing panel door. 11. Review to make sure all components are installed correctly. Ensure all wires are fastened securely. Proceed to Set Point Configuration section of this manual. P2 Route cable (Item 5) from P2 on protocol conversion board to P20 on swing panel as shown. Secure with wire ties (Item 7). 5

Form 4C Recloser Control Protocol Conversion Kit Installation Instructions Set Point Configuration IMPORTANT: All installation procedures must be completed prior to beginning Set Point Configuration. Refer to the Installation section of this manual. MODBUS/FSK Option Protocol boards with MODBUS/FSK option require no additional configuration. Fiber-Optic/RS-232 Option Refer to Figure 7 for location of set point switches on protocol board with Fiber-Optic/RS-232 options. Set Communications Mode A bank of four dipswitches (SW1) configures the control external communication mode. Set Dipswitch 1 to appropriate settings for hardware to be used (RS-232/Fiber- Optic). Then, select the appropriate baud rate to communicate with the RTU by adjusting SW3. Refer to Table 3 for proper settings. Table 1 depicts mode settings. TABLE 1 Dipswitch SW1 Communication Modes Dipswitch 4 3 2 1 RS-232 Off Off * * Fiber-Optic Non-Echo Off On * * Fiber-Optic Echo On Off * * * Not used for these settings. Switch SW2 Control Selection TABLE 2 Rotary Switch SW2 Control Selection Setting Control Type 0 Voltage Regulators 1 Voltage Regulator/MJX Mode 2 Form 4C Control Rotary Switch SW3 Baud Rate Settings When SW1 dipswitch 1 is set to ON, set baud rates through local or remote computers or other devices. When SW1 dipswitch 1 is set to OFF, manually set baud rates using rotary switch SW3. Table 3 depicts baud rates for switch SW3 settings. TABLE 3 Rotary Switch SW3 Baud Rate Settings Settings Baud Rate 0 300 1 1200 2 2400 3 4800 4 9600 5 19200 Run LED Indicator Run LED indicator (Figure 7) blinks when communications are operating normally. Reset Button When activated, this momentary push-button initiates a reset of the microprocessor on the communications board. TESTING CAUTION: Equipment misoperation. Do not connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury. G110.3 Refer to S280-77-1 Form 4C Microprocessor-Based Recloser Control Installation and Operation Instructions and S280-77-4 Form 4C Microprocessor-Based Recloser Control Programming Guide for testing procedures prior to returning the control to service. 6

S280-77-11 Rotary Switch SW3 Rotary Switch SW2 LED Indicator Dipswitch SW1 RS-232 ON 4 3 2 1 TX RX Fiber- Optic Reset Button Figure 7. Communications protocol board configured for RS-232 and fiber-optic communications. 010070KM LEGEND Protocol Board Switches and Indicators Description Dipswitch SW1 Rotary Switches SW2 SW3 LED indicator Reset button Function Select communications parameters. Select type of control. Set baud rate. Indicate RUN status. Initiate reset of microprocessor on communications board. 7

Form 4C Recloser Control Protocol Conversion Kit Installation Instructions FIBER-OPTIC CABLE SPECIFICATIONS Construction Multi-mode glass fiber-optic cable suitable for direct burial and/or outdoor use. Specifications 1. Operating Temp. Range: -40 C to +65 C 2. Strength Member: KEVLAR NOTE: The strength member cannot be steel or any other conductive material as electrical isolation will be lost. 3. Inner Jacket: PVC 4. Outer Jacket: Polyethylene 5. Optical window: 850 nanometers (nm). 6. Core size: 62.5 microns (µm). Other core sizes are allowable; however, they will affect the output power of the optical transmitter. See Maximum Cable Lengths section. 7. Attenuation at 850 nm: 3.5 db/km Cables with different attenuations are acceptable; however, maximum allowable cable length will be affected. See Maximum Cable Lengths section for an example of how to calculate maximum permissible cable length. Cable Terminations ST style connectors must be used to mate with the KME4-142 fiber-optic circuit board and the KME4-163 fiber-optic to EIA-232D converter. Maximum Cable Lengths 1. The maximum cable length depends on the output power of the transmitter, the input power level that the receiver can detect as well as the attenuation of the fiber-optic cable. 2. The Form 4C control has used two different style transmitters, the HFBR-1412 and the high efficiency HFBR-1414. The HFBR-1414 transmitter went into production on 3-19-91, serial number 200925. The output power of the transmitter is dependent on the fiber-optic core size. Output Power P(dBm)* Fiber Core Size HFBR-1414 HFBR-1412 50.0 µm -20.5-23.5 62.5 µm -16.0-20.0 100.0 µm -10.5-16.0 200.0 µm - 5.5-11.0 *P (dbm) = 10 log (PµW/1000) 3. Cable length calculation example: Typical 62.5 µm fiber cable attenuation:... 3.5 db/km HFBR-1412 Transmitter, Output Power:... -20.0 dbm HFBR-2412 Receiver, Input Level:... -24.0 dbm Safety Margin:... -1.5 dbm Budget for Cable: -24.0 dbm - (-20 dbm) - (-1.5 dbm) = -2.5 dbm -2.5 dbm Max. Cable Length = -3.5 db/km = 0.71 km 8

S280-77-11 KIT PARTS Swing Panel Control Cabinet Hinge Cabinet Body 2 3, 4 Terminal 1 Red Wire Terminal 3 Black Wire 5 P3 24 VDC P20 (below P4, near interior side of swing panel) Component Side Protocol Conversion Kit Circuit Board (Board layout is configuration dependent.) P4 6 P2 P20 P3 P11 + - RED BLACK 12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 2 3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 N H 7 Optional Input/Output Board Standard Input/Output Board Figure 8. Illustration of an installed Form 4C control protocol conversion circuit board. Refer to Table 4 for parts identification. 1 TABLE 4 Kit Parts Identification Quantity in Kit Item Part Identification Description KME4-587-7001 KME4-587-7002 KME4-587-7003 1 S280-77-11 Protocol Kit Installation Manual 1 1 1 2 KME4-589-7001 DNP 3.0 Fiber-Optic/RS-232 Board 1 0 0 KME4-589-7002 MODBUS FSK/RS-232 Board 0 1 0 KME4-589-7003 MODBUS Fiber-Optic/RS-232 Board 0 0 1 3 N/A Zinc Plated Steel Spring Lockwasher 2 2 2 4 4-2UNC 18-8 Stainless Steel Wingnut 2 2 2 5 #24AWG Shielded Interface Cable 1 1 1 6 #18AWG Twisted Pair Wire, Red/Black 610mm (2ft) 610mm (2ft) 610mm (2ft) 7 N/A Wire Tie 12 12 12 8 N/A Decal, Comm. Kit Accessory (not shown) 1 1 1 9 Wiring Assembly Orange/Brown wire for standard 1 1 1 transformer (not shown) 9

Form 4C Recloser Control Protocol Conversion Kit Installation Instructions 2003 Cooper Power Systems, Inc. Kyle is a registered trademark of Cooper Industries, Inc. P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com KA2048-550 Rev: 02 KYLE 12/03