SE-701 MANUAL GROUND-FAULT MONITOR

Similar documents
PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

PGR-2601 MANUAL DC GROUND-FAULT RELAY

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-3200 MANUAL INSULATION MONITOR

SE-703 MANUAL EARTH-LEAKAGE MONITOR

PGM-8134 MANUAL GROUND CONTINUITY MONITOR

SE-601 MANUAL DC GROUND-FAULT MONITOR

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR

SE-134C MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-330 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR

SE-330HV MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR

ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

EL731 MANUAL AC/DC SENSITIVE EARTH-LEAKAGE RELAY

SE-330AU MANUAL NEUTRAL-EARTHING-RESISTOR MONITOR

SB6100 MANUAL INDUSTRIAL SHOCK-BLOCK

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

SE-330HV MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR

Measuring and Monitoring Relays

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

Section 4 Ground-Fault Protection Devices

EL731 PROFIBUS INTERFACE

INSTRUCTION MANUAL FOR BREAKER FAILURE RELAY BE1-50BF. BE1-50BF BREAKER FAILURE RELAY Style No. XXX XXX XXXXX Serial No. HXXXXXXX

E1 Plus Electronic Overload Relay

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

EL731 DEVICENET INTERFACE

RM4TR31 three-phase network control relay RM4-T - range V

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

ASCO 920 Remote Control (RC) Switches

RT4B-110V/12A RECTIFIER

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

920 Remote Control (RC) Switches

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

Model Number Structure

Model Number Structure

RM4JA01F current measurement relay RM4-J - range ma V AC

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

RT4F-120V/20A-WAC RECTIFIER

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

RT4F-110V/25A RECTIFIER

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Zelio Control-modular measurement and control relays 1

sigma the power to protect Instruction Manual C-453EM

Bus Bar Protection Relay B-PRO 4000

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.

SE-330/SE-330AU/SE-330HV DEVICENET INTERFACE

RE7YA12BU. Main. Contacts type and composition Component name Time delay type. 24 V AC/DC at 50/60 Hz V AC/DCat 50/60 Hz

Voltage Sag Simulator

RM4TA32 three-phase network control relay RM4-T - range V

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

TM221CE40R controller M IO relay Ethernet

SLI 15 Inverter Series Data Sheet 1500 Watt, 1U Compact Inverters

Applying branch circuit breakers and supplementary protectors in North America

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

RM4JA32MW current measurement relay RM4-J - range A V AC DC

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

Contact protection relay

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

RM4JA31M current measurement relay RM4-J - range ma V AC

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

TM221CE24R controller M IO relay Ethernet

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

TM221M16R controller M IO relay

02/11/2015

ACCESS 9340/9360 Meter Input/Output Module

RE8YG31BUTQ industrial timing relay s - type Qc - 24 V AC/DC, V AC - 1C/O

02/11/2015

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

FM2. Economical and compact feeder protection for low voltage feeders. Digital Energy Multilin. Monitoring & Metering. Protection and Control

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

ABL8WPS24400 regulated SMPS - 3-phase V - 24 V - 40 A

Rugged MediaConverter

ACOPOSinverter P74. User's Manual. Version: 2.20 (August 2016) Model no.: Original instruction

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models

PROTECT Electronics Co. Ltd

Application Techniques CENTERLINE 2100 Motor Control Centers

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

60103 Circuit Breaker

ATV1200A kv kva. Phase-shifting transformer Medium voltage arrestors Cooling fans Human machine interface Plinth (2) Power cells (9)

ATV1200A kv kva

Transcription:

SE-701 MANUAL GROUND-FAULT MONITOR DECEMBER 19, 2000 REVISION 4 Copyright 2000 by Startco Engineering Ltd. All rights reserved. Publication: SE-701-M Document: S95-C701-00000 Printed in Canada.

Blank Page

Startco Engineering Ltd. Page i TABLE OF CONTENTS PAGE Table of Contents...i List of Figures...i 1. General...1 2. Operation...1 2.1 Configuration-Switch Settings...1 2.1.1 Relay Operating Mode...1 2.1.2 Inhibit...1 2.1.3 CT Verification...1 2.1.4 Filter Selection...1 2.1.5 Autoreset...1 2.2 Front-Panel Controls...1 2.2.1 Ground-Fault Trip Level...1 2.2.2 Ground-Fault Trip Time...1 2.2.3 Reset...1 2.2.4 Test...3 2.3 Front-Panel Indication...3 2.3.1 Power...3 2.3.2 Ground-Fault Trip...3 2.3.3 Inhibit...3 2.4 Analog Output...3 FIGURE LIST OF FIGURES PAGE 1 SE-701 Outline and Mounting Details... 2 2 Typical Connection Diagram... 4 3 EFCT-1 Outline and Mounting Details... 6 4 EFCT-2 Outline and Mounting Details... 7 5 PMA-55 Panel-Mount Adapter... 8 DISCLAIMER Specifications are subject to change without notice. Startco Engineering Ltd. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction. 3. Installation...3 4. Technical Specifications...3 5. Ordering Information...5

Blank Page

Startco Engineering Ltd. Page 1 1. GENERAL The SE-701 is a microprocessor-based ground-fault monitor for resistance-grounded and solidly grounded systems. Its output relay can operate in the fail-safe or nonfail-safe mode for undervoltage or shunt-trip applications, and the output contacts are isolated for use in independent control circuits. Additional features include LED and fluorescent-flag trip indication, autoreset or latching trips with front-panel and remote reset, self test, 0 to 5-V analog output, inputs for standard and sensitive ground-fault current transformers, CT verification for sensitive current transformers, digital selector switches, switch-selectable algorithms for fixed-frequency or variable-frequency applications, and an inhibit that can be enabled to prevent the output relay from operating during a high-current ground fault. Ground-fault current is sensed by a standard CT with a 1-A or 5-A secondary, or by a sensitive CT with a 5-Aprimary rating (EFCT-1 or EFCT-2). The trip level of the ground-fault circuit is digital-switch selectable in 1% increments from 1% to 99% of the CT-primary rating. Trip time is digital-switch selectable with 10 settings from 0.05 to 2.5 s. 2. OPERATION 2.1 CONFIGURATION-SWITCH SETTINGS (See Fig. 1) 2.1.1 RELAY OPERATING MODE The SE-701 has one output relay with isolated normally open and normally closed contacts. Switch 1 is used to set the operating mode of the output relay. In the fail-safe mode, the output relay energizes when the ground-fault circuit is not tripped. In the non-fail-safe mode, the output relay energizes when a ground-fault trip occurs. 2.1.2 INHIBIT Switch 2 is used to select Class I or Class II operation. In the INHIBIT OFF position, high-current inhibit is off for Class I operation. In the INHIBIT ON position, highcurrent inhibit is on for Class II operation. If high-current inhibit is on and ground-fault current escalates above eleven times the CT-primary rating before the ground-fault circuit trips, the output relay will not operate until ground-fault current falls below eight times the CT-primary rating. This feature allows the overcurrent protection to operate in applications where the ground-fault current can be larger than the interrupting capacity of the device tripped by the SE-701. 2.1.3 CT VERIFICATION Switch 3 is used to enable CT verification with the EFCT-1 or EFCT-2. In the CT VERIFY ON position, a trip will occur if the CT is disconnected. The red LED will flash to indicate a trip initiated by a CT fault. Switch 3 must be in the CT VERIFY OFF position when a 5-A- or 1-Asecondary CT is used. 2.1.4 FILTER SELECTION Switch 4 is used to select the filtering algorithm for a fixed-frequency (50/60 Hz) or variable-frequency application. The fixed-frequency algorithm allows lower trip levels to be used by rejecting harmonics that can cause nuisance tripping. The variable-frequency setting should be used if the CT is located on the load side of a variablefrequency drive. 2.1.5 AUTORESET Switch 5 is used to select autoreset or latching trips. See 2.2.3. 2.2 FRONT-PANEL CONTROLS 2.2.1 GROUND-FAULT TRIP LEVEL The % CT PRIMARY selector switches are used to set the ground-fault trip level as a percentage of the CT-primary rating. Protection against arcing ground faults in a solidly grounded system requires a ground-fault CT that will not saturate below the operating value of the overcurrent protection. For reliable ground-fault detection, the groundfault trip level must be substantially below the prospective ground-fault current. To avoid sympathetic tripping, the trip level must be above the charging current of the largest feeder; and to eliminate nuisance tripping, surge current must not saturate the CT. See Startco Technical Information 11.1 available at www.startco.ca. 2.2.2 GROUND-FAULT TRIP TIME The TIME (s) selector switch is used to set the groundfault trip time for coordination with upstream and downstream ground-fault devices. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault. 2.2.3 RESET The reset circuit responds only to a momentary closure so that a jammed or shorted switch will not prevent a trip. The front-panel RESET switch is inoperative when the remotereset terminals (6 and 7) are shorted.

Startco Engineering Ltd. Page 2 FIGURE 1. SE-701 Outline and Mounting Details.

Startco Engineering Ltd. Page 3 If Switch 5 is in the LATCHING position, a trip remains latched until the RESET switch is pressed, the remote-reset terminals are momentarily shorted, or the supply voltage is cycled. Cycling the supply voltage will not reset (black) the fluorescent flag. If Switch 5 is in the AUTORESET position, a trip will reset when the fault is removed. The fluorescent flag will not reset until the RESET switch is pressed or the remotereset terminals are momentarily shorted. Cycling the supply voltage will not reset the fluorescent flag unless the remotereset terminals are shorted. If Switch 5 is in the AUTORESET position and the remote-reset terminals are shorted, operation is the same as for older SE-701 s with the A1 or A2 option. 2.2.4 TEST The TEST switch is used to test the ground-fault circuit, the indication, and the output relay. When the TEST switch is pressed for one second; the circuit will trip, trip indication will come on, and the output relay will operate. If highcurrent inhibit has been selected, the inhibit indicator will come on. 2.3 FRONT-PANEL INDICATION 2.3.1 POWER The green LED labeled PWR indicates presence of the supply voltage. 2.3.2 GROUND-FAULT TRIP The red LED and the fluorescent flag, labeled TRIP, indicate a trip. A solid red LED indicates a ground-fault trip and a flashing LED indicates a trip initiated by a CT fault. 2.3.3 INHIBIT The yellow LED labeled INHB indicates that outputrelay operation was inhibited during a high-current ground fault. Inhibit indication is reset when the ground-fault trip is reset. Inhibit operation and indication will not respond if Switch 2 is in the INHIBIT OFF position. 2.4 ANALOG OUTPUT The non-isolated, 0 to 5-V analog output indicates ground-fault current sensed by the ground-fault CT. The output is 5 V at 100% of the CT-primary rating. 3. INSTALLATION Pass the phase conductors through the CT window as shown in Fig. 2 (for 4-wire and single-phase systems, also pass the neutral conductor through the CT window). Do not pass ground conductors through the CT window. In applications that require shields or drain wires to pass through the CT window, return them through the CT window before connecting them to ground. If a groundfault CT with a 5-A secondary is used, connect it to terminals 2 and 3 (terminals 1 and 3 with a 1-A secondary) and ground terminal 3. If the EFCT-1 or EFCT-2 is used, connect it to terminals 4 and 5, connect the shield to terminal 5, and ground terminal 5. Remove the connection to terminal 9 for dielectric-strength testing all inputs and outputs have ANSI/IEEE C37.90 surge-protection circuits that conduct above 300 Vac. 4. TECHNICAL SPECIFICATIONS Supply: 01 Option...120 Vac (+15%, -40%), 50/60 Hz, 2.5 VA 02 Option...240 Vac (+15%, -40%), 50/60 Hz, 2.5 VA 03 Option...24 Vac (+15%, -40%), 50/60 Hz, 2.5 VA 0S Option...120 or 240 Vac (+15%, -40%), 50/60 Hz, 2.5 VA 0U Option...55 to 275 Vac, 50/60 Hz, 3.5 VA 75 to 275 Vdc, 2.0 W (1) 0D Option...9 to 36 Vdc, 3.0 W (1) 0T Option...30 to 70 Vdc, 3.0 W (1) (1) CSA Certification pending. Dimensions: Height...75 mm (3.0") Width...55 mm (2.2") Depth...115 mm (4.5") Shipping Weight...0.45 kg (1 lb.) Trip-Level Range...1% to 99% CT-Primary Rating in 1% increments (50 ma to 4.95 A with EFCT-1 or EFCT-2) Trip-Time Settings...0.05, 0.10, 0.20, 0.30, 0.40, 0.50, 1.0, 1.5, 2.0, and 2.5 s Accuracies: Trip Level...+1%, -5% of trip level for settings 10%. +0.1%, -0.5% of full scale for settings 9%. Trip Time...+15 ms, -25 ms

Startco Engineering Ltd. Page 4 FIGURE 2. Typical Connection Diagram.

Startco Engineering Ltd. Page 5 Inhibit: Off... Class I On... Class II Level... 11 x CT-Primary Rating Input: Algorithms... DFT Digital or Peak Digital Filter... 50 to 60 Hz, Bandpass CT... 1-A or 5-A Secondary Rating, EFCT-1, or EFCT-2 Thermal Withstand: Continuous... 5 x CT-Secondary Rating 1-Second... 80 x CT-Secondary Rating Burden... < 0.01 Ω for 5-A input < 0.05 Ω for 1-A input Operating Mode... Latching or Autoreset Analog Output: Range... 0 to 5 V, 5 V = 100% Output Impedance... 220 Ω Reset... Front-Panel Switch and Remote, N.O. Contact Functional Test... Front-Panel Switch Output Relay: Contact Rating... 8 A Resistive, 250 Vac/30 Vdc Contact Configuration... Isolated N.O. and N.C. Operating Mode... Fail-Safe or Non-Fail-Safe Supplemental Contact Ratings: Make/Carry 0.2 s...20 A Carry Continuous...8 A Break: dc...30 W Resistive, 15 W Inductive (L/R = 0.4 s) ac... 2000 VA Resistive 1400 VA Inductive (PF = 0.4) Subject to maximums of 8 A and 250 V (ac or dc). Environment: Operating Temperature...-40 C to 60 C Storage Temperature...-55 C to 80 C Humidity...85% Non-Condensing Surge Withstand...ANSI/IEEE 37.90.1-1989 (Oscillatory and Fast Transient) Certification...CSA NRTL/C (Canada & USA) 5. ORDERING INFORMATION SE-701-0 1 120-Vac Supply 2 240-Vac Supply 3 24-Vac Supply S 120- or 240-Vac Supply U Universal ac/dc Supply D 9- to 36-Vdc Supply T 30- to 70-Vdc Supply EFCT-1...Sensitive Ground-Fault CT, 5-A Primary Rating, 82-mm (3.2") Window EFCT-2...Sensitive Ground-Fault CT, 5-A Primary Rating, 155-mm (6.1 ) Window EFCT-1FC...Flux Conditioner, 70 mm (2.7 ) Window EFCT-2FC...Flux Conditioner, 139 mm (5.5 ) Window PMA-55...Panel-Mount Adapter SE-EFVC...Voltage Clamp NRTL /C LR 53428 Consult factory for custom mounting adapters.

Startco Engineering Ltd. Page 6 FIGURE 3. EFCT-1 Outline and Mounting Details.

Startco Engineering Ltd. Page 7 FIGURE 4. EFCT-2 Outline and Mounting Details.

Startco Engineering Ltd. Page 8 SE-701 Ground-Fault Monitor Rev. 2 FIGURE 5. PMA-55 Panel-Mount Adapter.