S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Similar documents
S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

S Reclosers. Contents. Form 4C Recloser Control Protocol Conversion Kits KME , -7002, and Installation Instructions

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

UPS READY POWER DISTRIBUTION ASSEMBLY

Single Phase Vacuum Capacitor Switch. UltraVacLT 15kV 95kV or 125kV BIL

SED2 Variable Frequency Drives

PANEL MOUNT INTERCOMS

HID. GE Consumer & Industrial Multilin. High Impedance Differential Module Instruction manual GEK Copyright 2005 GE Multilin

INSTRUCTION MANUAL FOR VAR/POWER FACTOR CONTROLLER SCP

COOPER POWER SERIES. Fiber-optic/RS-232 communications module installation and operation instructions. Voltage Regulators MN225020EN

S Reclosers Kyle Form 5 Microprocessor-Based Recloser Control Installation and Operation Instructions. Contents

S Reclosers Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Microprocessor-Based Recloser Controls Installation and Operation Instructions.

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

LCI AUXILIARY I/O TERMINAL BOARD DS200DDTBG_A

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

5B Series 16 Channel Backplane 5B01 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Multi Unit Enclosed Meter

COOPER POWER SERIES. Ethernet communications module installation and operation instructions. Voltage Regulators MN225033EN

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Installation & Operation Guide

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions.

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

PowerFlex 400 AC Drive Guide Specification

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

Series 8000 RF Signal Switch Solution

Table of Contents. Safety. Attention. Warnings

Service Instructions. Conductor 420

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1

SE-701 MANUAL GROUND-FAULT MONITOR

OPERATING INSTRUCTIONS AND SERVICE MANUAL BASEBALL SCOREBOARD MODEL MP-3350 WITH MP-2002 CONTROL

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers

Installation Instructions

Operating Instructions & Service Manual FOULS

Analog Output Module Installation Instructions

NightStar. Installation, Operation, & Maintenance Instructions M /04/2016

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Installation, Operation and Maintenance Manual

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

24/48/120 VAC Interface Card Instruction Manual

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

INSTRUCTION MANUAL FOR

USER MANUAL. WBV412U01 AC voltage transducer

Series 8000 RF Signal Switch Solution

Model 7705 Control Module

EM-F-7G Safety Extension Module

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

ASCO 920 Remote Control (RC) Switches

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

OPERATING INSTRUCTIONS AND SERVICE MANUAL BASKETBALL SHOTCLOCK MODEL MP-5299

USER MANUAL. WBI414F21 AC current transducer

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

Mini Digital Multimeter

DC Power Considerations for Intrinsically Safe Applications

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

OPERATING PROCEDURES for the UPS-S2 Universal Power Supply Series 2

USER MANUAL. WBI412F41 AC current transducer

COOPER POWER SERIES. Type GN3E and GN3VE sectionalizers installation and operation instructions

ZC Series Zone Monitoring Controllers

OPERATING INSTRUCTIONS AND SERVICE MANUAL. MODEL MP-3804 BLACK FLAG DISPLAY WITH MP-2002 Control

PGR-2601 MANUAL DC GROUND-FAULT RELAY

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

PS/IO Circuit Board Retrofit

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

S Sectionalizers

ATE QUICK START GUIDE. KEPCO An ISO 9001 Company. VOLTAGE/CURRENT STABILIZED POWER SUPPLY I INTRODUCTION

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY WARNINGS I INTRODUCTION II SAFETY.

VLT 2800 DRIVE SPECIFICATIONS

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

S Reclosers. Contents. Form 6 Microprocessor-Based Rack Mount Recloser Control Installation and Operation Instructions

SECTION SWITCHBOARDS

PumpDrive. Self -cooling, motor-independent frequency inverter. Brief Instructions

Installing the Tracer MP503 Input/Output Module Ordering number: ,

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

Masibus Automation And Instrumentation Pvt. Ltd.

RVDT Setup and Polarity Checking Tool for EG Governors. Product Manual (Revision B) Original Instructions T87444

Siemens TEC Extended I/O Controller

IDEAL INDUSTRIES INC. TECHNICAL MANUAL MODEL:

Installation Instructions

OPERATING INSTRUCTION

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Transcription:

Reclosers Form 4C Microprocessor-Based Recloser Control KME4-88-1 (120V) and KME4-88-2 (240V) Analog Current Metering Accessory Design II Service Information S280-77-6 961015, 961016 Figure 1. Kyle KME4-88 Analog Current Metering Accessory Design II, consisting of the main circuit board (left) and power supply board (right). Contents Safety Information... 2 Hazard Statement... 2 Safety Instructions... 2 Product Information... 3 Introduction... 3 Acceptance and Initial Inspection... 3 Application... 3 General Description... 4 Features... 4 Description of Operation... 4 Input Power Requirements... 4 Customer Connections... 4 Operation... 5 Verification of Operation... 6 Test Procedure... 7 December 1996 New Issue 1 Printed in USA

KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II Description and Operation Instructions SAFETY FOR LIFE Kyle Distribution Switchgear products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Kyle employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our Safety For Life mission. SAFETY INFORMATION Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual contains two types of hazard statements: WARNING: Refers to hazards or unsafe practices which can result in death, severe personal injury, and equipment damage. CAUTION: Refers to hazards or unsafe practices which can result in damage to equipment or in personal injury. Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high voltage lines and equipment. G103.2 2

S280-77-6 PRODUCT INFORMATION Introduction Service Information S280-77-6 provides operating instructions for, and information about, the Kyle KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II option. KME4-88-1 is wired for 120V applications (jumpers J1 and J2, Figure 6, are present; jumper J3 will NOT be present), and KME4-88-2 is wired for 240V use (jumper J3, Figure 6, is present; jumpers J1 and J2 will NOT be present). The accessory is shipped factory-installed in a double-size cabinet housing the Form 4C microprocessorbased recloser control (see Figure 2). The information contained in this manual is organized into the following major categories: Safety Information, Product Information, General Description, and Operation. Refer to the table of contents for page numbers. Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described, or provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Cooper Power Systems representative. Maintenance Information This accessory is designed to be maintenance-free. If the accessory fails to perform satisfactorily, consult your Cooper Power Systems representative. Acceptance and Initial Inspection Each accessory is completely assembled, inspected, tested and adjusted at the factory when installed in the Form 4C control. It is installed, ready to use, and in good condition when accepted by the carrier for shipment. Upon receipt of the control, follow these steps: 1. Inspect the Form 4C control thoroughly for damage or loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. 2. Check for hardware and tighten all fasteners that may have loosened during shipment. ANSI Standards Kyle Distribution Switchgear products are designed and tested in accordance with ANSI standards C37.60 and C37.85, and meet the requirements of C37.61 Application, Operation, and Maintenance of Automatic Circuit Reclosers Guide. ISO Standards The Quality System at the Cooper Power Systems Kyle Distribution Switchgear plant is ISO 9001 certified. Application The accessory is pre-configured at the factory within the Form 4C control for external power of 120Vac or 240Vac, as required. KME4-88-1 is wired for 120V applications (jumpers J1 and J2, Figure 6, are present; jumper J3 will NOT be present), and KME4-88-2 is wired for 240V use (jumper J3, Figure 6, is present; jumpers J1 and J2 will NOT be present). The accessory has the ability to derive a signal representative of recloser (line) current by interfacing with the existing control circuitry, thereby eliminating the need for bushing-mounted current-sensing transformers (CT s). The circuitry involved has negligible effect on the minimum pick-up circuits of the controls. The key features of this derived signal are accuracy, isolation and minimal effect on minimum trip level. The accessory provides a universal dc output of either 0-1mA (current) or 0-10Vdc (voltage) for customer monitoring purposes. The output is an analog signal of 0 10Vdc or 0 1mA for primary currents of 0 1000 amperes using 1000:1 current-sensing transformers. Other CT ratios are compatible, but the output will be scaled appropriately. TABLE 1 CT Ratio Primary Amps Output 500:1 0 500A 0 1mA / 0 10Vdc 1000:1 0 1000A 0 1mA / 0 10Vdc 2000:1 0 2000A 0 1mA / 0 10Vdc 3

KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II Description and Operation Instructions GENERAL DESCRIPTION The Analog Current Metering Accessory consists of two circuit boards: the current resolution amplifier board (see Figure 3) and a regulated power supply board. The current resolution amplifier circuitry is comprised of recloser CT interface and buffering amplifiers, full-wave amplifiers, and a final filtering amplifier. There are three such sections, one for each phase. The power supply board has a fused, surge-protected input to a transformer primary. The isolated secondary of the transformer is rectified, filtered, and regulated to provide power to the current resolution amplifier board. Features Key features of the Analog Current Metering Accessory Design II include: Continuous Overload Without Damage: Inputs of 1.5A continuous, 20A for 1.0 seconds, 40A for 0.25 seconds. Accuracy: ± 5% of reading or ± 5 amps primary line current, whichever is greater. Power Factor Range: All. Temperature Range: -40 0 C to +60 0 C. Frequency Range: 50/60Hz. Effect on Minimum Trip and TCC s: Less than 1%. Analog Outputs of 0 1mAdc or 0 10Vdc at 1000A primary current Monitoring of phase A, B, and C line currents No extra CT s or cables for transducers required. Description of Operation The established normal operating range on the input is zero-to-one amps ac RMS, based on a 1000:1 CT ratio. The Analog Current Metering Accessory is capable of a continuous overload of 50% and is capable of sustaining the expected overloads during momentary fault conditions. Input Power Requirements The Analog Current Metering Accessory requires four watts of ac power and ships from the factory with either of the following options: 120Vac ± 10% @ 50/60Hz 240Vac ± 10% @ 50/60Hz Figure 2. A double-size Form 4C Recloser Control cabinet is required for the KME4-88-1 or KME4-88-2 Analog Current Metering Accessory Design II. Customer Connections CAUTION: Equipment damage; misoperation. External leads must be shielded and the shield must be grounded at both ends. Terminate the shield and each lead with a GE V150LA20A metal oxide varistor (MOV), or equivalent, at the remote end. Attach MOV s between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or unintentional operation. G117.1 The customer connections (Figure 4) are located on the accessory amplifier circuit board and are identified as the P3-1 through P3-4 terminals. Always use shielded cable for wires entering or exiting from the control cabinet. 4

S280-77-6 OPERATION The Analog Current Metering Accessory monitors instantaneous load current with 0 1mAdc current output or 0 10Vdc voltage output at 1000A primary current, 1000:1 sensing CT s. The Analog Current Metering Accessory consists of three isolated phase circuits. Each circuit places only a small burden (0.2VA) on the recloser current transformer secondary, and has negligible effect on the control currentsensing and fault-timing functions. The input current is fed through another current transformer with its secondary connected across a resistance to establish an ac voltage proportional to line current. This voltage is then full-wave rectified, filtered and scaled. The signal is then fed into a buffering amplifier which delivers a current or voltage output through surge-protected contacts. Figure 3. KME4-88-1 or KME4-88-2 Analog Current Metering Accessory Design II amplifier circuit board layout. Figure 4. KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II customer connections are made at terminal strip P3, with common located at P3-4. 5

KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II Description and Operation Instructions Verification of Operation CAUTION: Recloser misoperation. The control must be removed from service prior to performing any maintenance, testing, or programming changes. Failure to comply can result in mis-operation (unintentional operation) of the recloser. T216.2 If the unit is in service, by-pass and trip the recloser. For bypass procedure, refer to Service Information S280-77-1 Form 4C Microprocessor-Based Recloser Control Installation and Operation Instructions. Use the following procedures to confirm the operation of the accessory. Refer to Figures 4, 5 and 6. Equipment required: A recloser tester, or a control tester (such as the Kyle Type MET Tester or equivalent) and a multimeter. Figure 5. The KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II amplifier circuit board schematic. 6

S280-77-6 Test Procedure The accessory can be tested to verify proper operation. Testing will require either a high-current test source, or a control tester (such as the Kyle KMET tester). The full scale test with 1000A primary gives 10Vdc or 1mA; this test may be proportionally scaled for any other desired input test point so that other values may be chosen. 1. Verify that power is present at the power supply board (see Figures 4 and 6). Check voltage across terminals P1-2 and P1-3. Voltage should be either 120Vac or 240Vac, depending on configuration of accessory. 2. Verify that the output of the power supply board is ± 15Vdc ± 0.3Vdc on both supplies (P1-5 is +15; P1-7 is -15 with respect to common P1-6). 3. Apply test current and measure output at terminals P3 1, 2, 3, and 4 (see Figure 4). For example: A. Apply a simulated load current of 100A to the A phase of the control. B. Verify that the output of the accessory on terminal P3-1 is 1.0Vdc, or 0.1mA. C. Repeat the procedure for both the B and C phases of the control. D. Repeat test steps A, B, and C for other current values as desired. This concludes verification of operation for the accessory. In the event the above test indicates the accessory is malfunctioning, contact your Cooper Power Systems representative. Figure 6. The KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II power supply board schematic. KME4-88-1 is wired for 120V applications (jumpers J1 and J2 will be present, jumper J3 will NOT be present), and KME4-88-2 is wired for 240V applications (jumper J3 will be present, jumpers J1 and J2 will NOT be present). 7

KME4-88-1 and KME4-88-2 Analog Current Metering Accessory Design II Description and Operation Instructions 1996 Cooper Power Systems, Inc. Kyle is a registered trademark of Cooper Industries, Inc. P.O. Box 1640, Waukesha, WI 53187 http://www.cooperpower.com/ KA2048-418 Printed on Recycled Paper KBP 2/97