TOUCH SCREEN CONTROLLER for Air Conditioning Control System

Similar documents
DIGITAL INPUT/OUTPUT RELAY INTERFACE BMS-IFDD01E

INTELLIGENT SERVER. Model: BMS-LSV6E

Installation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL

Installation Manual. BN interface. Model name: BMS-IFBN640TLUL. English

TCS-NET AIR CONDITIONING CONTROL SYSTEM (TOUCH SCREEN CONTROLLER)

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

SERVICE MANUAL WEB BASED CONTROLLER

TOUCH SCREEN CONTROLLER for Air Conditioning Control System

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

1:1 Model Connection Interface

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

1. Safety Precautions (Read these precautions before use.)

F1000 User's Manual. (Version: V1.01)

Table of Contents. Automatic Transfer Switch. User Manual ATS-16A/20A/30A/32A

BACnet System SERVICE MANUAL. Intelligent Server. BACnet Server Software BMS-LSV6UL BMS-STBN09UL. FILE No. A Revised Nov (2) Model name:

INSTALLATION INSTRUCTIONS

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

XTM1250SA DIN rail three phase four wire LCD display energy meter

PRO-1250D CT MID DIN rail three phase four wire energy meter.

Mitsubishi Electric Air-conditioner Network System

Touch-controller_IM_03943A_1_Co_EN.indd 오후 3:06:00

PRO-75 SERIES. User manual

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

Package Contents. GP Options (Made by Digital)

The following symbols are used to show dangerous operation or handling. Make sure you understand them before reading the guide.

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5

User Manual. Solar Inverter for Water Pump

RS232C/RS485 Data can be easily monitored by LAN

Appearance Size (mm) Power supply voltage Model (W H D) 100 to 240 VAC K3SC to 240 VAC

TCS-NET GSM PHONE CONTROL INTERFACE

FEATURES FEATURES. Macro Function Usage Supports strong Visual Basic script language which includes more than 500 built-in functions.

Power supply unit Model: PAC-SC51KUA

User Guide Automatic Transfer Switch (ATS)

BASIC PA AMPLIFIER A-1031 A-1061 A-1121 OPERATING INSTRUCTIONS TABLE OF CONTENTS

INSTALLATION MANUAL. Gateway option box EKLONPG EKBNPG

Suitable for detecting transparent films or transparent bottles

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

MT-8000 series. MT-8056T/ MT-6056T Installation Instruction. 1.0 Installation and Startup Guide. 2.0 Installation Instructions

NPN output PNP output Cord connection Cord length: 2 m Through-beam 7 m Light-ON. 2 m. (selectable by wiring) Diffuse reflective 0.

EC07 EC63. Compatible actuators: ERL2 ESD2. How to order EC 07 B. Series. B Installation. method

Nokeval. FD100 series. User Manual

Easy use Easy read. Warning

1. Safety Precautions (Read these precautions before use.)

DIO-1616LN-FIT. Features. Specifications. Ethernet Remote I/O F&eIT N Series Isolated Digital Input/Output Unit DIO-1616LN-FIT 1. Ver.1.

Thread length (overall length) material

PRO1 V21.xxx series MID DIN rail single phase two wire energy meter

Network Instrumentation Module Communications box NX-CB1 Communications adapter NX-CL1/NX-CR1 Terminal adapter NX-TL1/NX-TR1

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21-

Part No. Z , IA Mar OPERATION MANUAL. High Voltage Digitalmeter A

LED W RGBA User Manual

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

LED PANEL. User Manual Please read the instructions carefully before use LED-212RGB TABLE OF CONTENTS. 1. Safety Instructions

E2Q4 Square Proximity Sensor

TABLE OF CONTENTS 1. Safety Instructions 2. Technical Specifications 3. Installation 4. How to Connect the Fixture 5. DMX512 Connections 6.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

SIM-9106/9303 High Current Switching Mode Power Supply with C.C., C.V., Remote Control & Sensing User Manual

CONTENTS PRODUCT FEATURES... EG-2 SAFETY PRECAUTIONS... EG-2 PARTS DESCRIPTION... EG-3 INSTALLATION AND ADJUSTMENT... EG-4 SPECIFICATIONS...

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19-

USER MANUAL. RC-43SL 6-Button Room Controller MODEL: P/N: Rev 1.

MIC-2 MKII, Multi-instrument DATA SHEET

Model Number Structure

PanelView Plus/VersaView CE Terminals and Display Modules

Model Number Structure

Installation manual for for Schleifenbauer DPM3

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

Installation Manual RB-RWS20-E. Lite-Vision plus Remote Controller. Model name: English

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

R1M-GH BEFORE USE... POINTS OF CAUTION INSTRUCTION MANUAL PC RECORDER MODEL. (thermocouple or DC input, 16 points)

USER MANUAL. RC-43SL 6-Button Room Controller MODEL: P/N: Rev 3.

Network Camera. Installation Manual Before operating the unit, please read this manual thoroughly and retain it for future reference.

MODEL: R1M-P4. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

USER MANUAL. RC-54DL KNET Auxiliary Control Panel MODEL: P/N: Rev 2

User's Guide. Model W 3-in-1 Switching DC Power Supply

Standalone Keypad Access Control. User Manual. Please read the manual carefully before use this unit

INFORMATION AMPLIFIER TA-102 OPERATING INSTRUCTIONS TABLE OF CONTENTS

User Manual. 2.2KW/7.5KW/11KW Solar Inverter for Water Pump. Version: 1.8

Standalone Keypad Access Control. User Manual. SS-TS2000 Size:120*80*25 mm

General-Purpose Photoelectric Sensor

Please read the instructions carefully before use LED PYRAMID LED-904D. Innovation, Quality, Performance 15-

LED BEAM 300 LED-MB50. User. Guide. Professional Entertainment Technology

Professional Entertainment Technology LED BEAM 300 LED-MB50. Innovation, Quality, Performance 23-

Part No. Z , IA Nov OPERATION MANUAL. High Voltage Digitalmeter A

FX1N-4EX-BD Input Expansion Board

USER'S GUIDE FX-485ADP COMMUNICATION ADAPTER FX0N-485ADP COMMUNICATION ADAPTER

Professional Entertainment Technology LED BEAM 300 LED-MB50. User. Guide

BGS (at min. setting) BGS (at max. setting)

The following symbols are used to show dangerous operation or handling. Make sure you understand them before reading the guide.

COGNEX. Checker SensorView. Quick Reference Guide

Blue Weapon Laser. User manual UK. Version 1.0

EE-SPX74/84. Ordering Information. Compact Sensor for High-Density Mounting with Easy Snap-In Connector. H Connector features a built-in safety

ERV Control Interface Installation / Operation manual. TCB-IFVN1UL ERV Control Interface ENGLISH

User Manual. 2.2KW LS (Low PV Input Range) Solar Inverter for Water Pump. Version: 1.1

Transcription:

INSTALLATION MANUAL TOUCH SCREEN CONTROLLER for Air Conditioning Control System Model: BMS-TP064ACE BMS-TP064PWE BMS-TP52ACE BMS-TP52PWE Thank you very much for purchasing the TOSHIBA Touch Screen Controller. Please read this manual carefully beforehand for proper installation of the. CONTENTS Precautions for Safety... Introduction... 2 Before Installation... 3 Installation... 3 2 Connection of Power cables/earth wires/signal wires... 5 3 Trial Operation... 8

Precautions for Safety Read these "Precautions for Safety" carefully before installation. The precautions described below include important items regarding safety. Observe them without fail. After the installation work, perform a trial operation to check for any problem. Follow the Owner's Manual to explain how to use and maintain the unit to the customer. Ask the customer to keep this Installation Manual together with the Owner's Manual. WARNING Ask an authorized dealer or qualified installation professional to install or reinstall the Touch Screen Controller. Improper installation may result in electric shock or fire. Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off. Failure to do so may cause electric shock. Perform installation work properly according to this Installation Manual. Improper installation may result in electric shock or fire. Do not modify the unit. Any modification may cause a malfunction, resulting in overheating or fire. CAUTION Upon customer s approval, install the Touch Screen Controller at a place which satisfies the following conditions. Place where the Touch Screen Controller can be installed securely. Place which can reserve a sufficient service space for safe maintenance or check. Place where CF (Compact Flash) card can be removed easily. Place which provides sufficient space for connecting/checking the terminals of interface, Input- Output ports, etc. Avoid the following places. Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is installed. (A bad influence may generated by malfunction of the, control error, or noise may affect such equipment.) Perform wiring correctly in accordance with specified the current capacity. Failure to do so may result in short-circuiting, overheating, or fire. Connect the specified cables for the terminals securely to prevent external forces from affecting them. Failure to do so may result in disconnection, overheating, or fire.

Introduction Applications/Functions/Specifications Applications/Functions The Touch Screen Controller is equipped with the LCD display and the touch panel and has various functions such as operation control, operation status monitoring, scheduled operation, and error code display of up to 64 or 52 indoor units. Specifications Power consumption Operating temperature/humidity Storage temperature Dimensions Mass 00-240 VAC, 50/60Hz 50VA 0 C to 50 C, 20% to 85% RH (no condensation) -0 C to +60 C 256 (H) 36 (W) 54 (D) mm 3.5kg Air conditioning control Power distribution s connected External View BMS-TP064ACE BMS-TP064PWE BMS-TP52ACE BMS-TP52PWE Max. 64 units Max. 64 units Max. 52 units Max. 52 units CF (Compact Flash) card slot (CF card for data files) Input/Output port USB Ethernet COM(RS-232C) COM2(RS-485) : available : Not available Power input terminal block PCI expansion unit connector cover POWER LED Function switch (F, F2, F3) 54 5 49 75 36 249 99.3 70 75 9.75 242 95.75 256 M4 Tap ( 4 pcs.) (depth: 0 mm max.) 48 82.5 6 9 30 302 55.5 unit: mm 2

Before Installation Check the following package contents. No. Item Touch Screen Controller 2 Fixture 3 CF(compact flash) for data file 4 CF adapter 5 Simple stand 6 Triangle thread screw (M4 8, Ni) 7 Card cover 8 Triangle thread screw (M3 6, Ni) 9 RS-485 cable 0 Installation Manual Quantity 6 Remarks For fixing the unit at pannel mount It is inserted in the CF card slot of at shipment. (For data file) It is inserted in the CF card slot of at shipment. For simple stand For preventing CF(compact flash) from coming out For card cover For connecting and TCS-NET Relay Interface This manual Use the following materials to connect the signal lines and power lines. (procured on site) No. Line Description 2 3 For RS-485 For digital Input/Output connection For Power Type Wire size Length Type Wire size Length Type Wire size 2-core shield wire.25mm 2, 500m max. (total length) 2-core wire, 0.3mm 2, 00m max H07 RN-F or 245IEC66 0.75mm 2, 50 m max. Installation Installation Space and Maintenance Space Space 30mm or more in between the and surrounding objects. Make space for service. Panel 30 mm or more (top) 30 mm or more (side) Interface side Panel Bottom view 30 mm or more (bottom) 30 mm or more (rear) Side view 3

Installation Method Two installation methods are provided. One is the panel mount with the fixture. The other is the desk top installation using the CONTEC stand (procured on site). () Panel Mount How to install the fixture. Insert the from outside of the panel. Panel cut size 303 + -0 R or less 243 + -0 Panel thickness:.6-7 mm [mm] 2. Insert the fixtures from inside of the panel. Touch Screen Controller Panel Fixture REQUIREMENT Use a panel (procured on site) of thickness.6-7 mm. Tightening screws excessively may cause the screws to break. Optimum tightening torque for good waterproofing effect is 0.6N/m. (2) Desk Top Installation using the CONTEC stand (procured on site) 75 mm 75 mm The angle adjustment lock screw. (Loosen the screw and adjust angle.) For reference Display stand (not supplied with the ) Use the CONTEC stand (model: IPC-SND-03). For details of the stand, visit the CONTEC web site. Europe: http://www.contec-europe.com/ China: http://www.contec.sh.cn/ REQUIREMENT Do not install the unit in any of the following places. Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain (outdoors, under eaves, etc.) 4

Connection of Power cables/earth wires/ 2 Signal wires Connect cables to the connectors and terminals specified. REQUIREMENT Power cable is not supplied for the Touch Screen Controller. Prepare a 3-pin power cable conforming to applicable safety standards. Be sure to connect the earth line earth of the power cable securely. Digital Input Power input terminal COM2 Ethernet I/O port Digital Output For details of the connection, refer to I/O port connection on next page. Ethernet (To customer's PC) N L Connect firmly the power cable to the power input terminal. COM2 (RS-485) (TCS-NET relay interface) Connect the attached RS-485 cable to COM2. Length of stripped power cable 35 0 Length of stripped digital Input/Output connector wire 35 0 45 0 CAUTION Ensure to connect the breaker to the primary side of power. 5

Connection of Power cables/earth wires/ 2 Signal wires (continued) I/O Port Connection The I/O Port is used to control air conditioners by interlocking them with electric lock signals and fire alarm signals, and to transmit air conditioner failures to other devices. I/O Port 0 Front (LCD side) Pin No. Signal name Remarks PI_PCOM Input plus common 2 PI(0) Input 0 3 PI() Input 4 PI(2) Input 2 5 P_PO(0) Output 0+ 6 N_PO(0) Output 0-7 P_PO() Output + 8 N_PO() Output - 9 P_PO(2) Output 2+ 0 N_PO(2) Output 2- Input/Output specifications Input Output Input type Number of input Input resistance Output type Number of output Output current Output voltage Photo-coupler insulation 3 3k ohm Open collector 3 Max. 00mA (per output) Less than 30V DC () The example of input circuit is shown below. It is electrically insulated by the photo-coupler. (2) The example of output circuit is shown below. It is electrically insulated by the photo-coupler. PI_PCOM (External circuit) 0 k ohm 3 k ohm /2 W External power supply (2 V - 24 V DC) 330 ohm PC357 load P_PO(0) - P_PO(2) 2SD780A External power supply (Max. 30 V DC) PI(0) - PI(2) Input/Output connector Input c ontact 4.7 k ohm N_PO(0) - N_PO(2) Input/Output connector 6

Connection of Power cables/earth wires/ 2 Signal wires (continued) The example of the system wiring connection is shown below. Terminator Resistor Setting RS-485 terminator resistor The terminator resistors of RS-485 are set at both ends of communication cable. The RS-485 terminator resistor (at one end) of the Touch Screen Controller is set at shipment. No setting is needed. TOUCH SCREEN CONTROLLER Caution: RS-485 cable has polarity. If incorrectly connected, it does not work. Switching HUB Customer's PC Yellow Brown B A Red Orange Crimp 3 wires with a closed end wire joint. A Red/Orange B Brown/Yellow TCC-LINK TCC-LINK N N L B A U2 U FG N L B A U2 U FG N L L RS-485 RS-485 SW 4 ADDRESS DIGITAL I/O INTERFACE SW ADDRESS SW6 ON 2 SW5 ON 2 SW6 ON 2 SW5 ON ENERGY MONITORING INTERFACE 2 TCC-LINK TERMINATOR RS-485 TERMINATOR ADDRESS ADDRESS DI DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 DO DO2 DO3 DO4 GND +2V DI DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 8 TCS-NET RELAY INTERFACE TCS-NET RELAY INTERFACE A B A B SW TCC-LINK TERMINATOR RS-485 TERMINATOR SW RS-485 RS-485 Outdoor unit Remote Outdoor unit Remote U2 U U2 U U2 U U2 U U2 U U2 U U2 U U2 U U2 U U2 U Input contact Input contact 2 Input contact 3 Input contact 4 Input contact 5 Input contact 6 Input contact 7 Input contact 8 Load Load 2 Load 3 Load 4 Power meter Power meter 2 Power meter 3 Power meter 4 Power meter 5 Power meter 6 Power meter 7 Power meter 8 Outdoor unit Remote Outdoor unit Remote Central remote Central remote The setting of the Touch Screen Controller is done at shipment. No setting is required. 7

3 Trial Operation Before Trial operation Setting File Creation The setting file is necessary to use the Touch Screen Controller. Please inquire of your local sales office about it. The setting file will be copied to the Compact Flash card inserted in the CF slot of the Touch Screen Controller. Trial Operations of Air Conditioner and Each Interface Confirm the trial operations of the air conditioner and the each interface. And turn on the power of each device. Trial operation Start-up of the Touch Screen Controller Connect the power cable, earth wire and signal wire of the Touch Screen Controller. Insert the compact flash containing the setting file in the CF slot and turn on the power. The initial screen appears. Initialization It is necessary to initialize the system to make the setting file effective. Operational Procedure () Press the [MENU] button. The menu screen appears. (2) Press the [SYSTEM RESET] button on the menu screen. The message to confirm the operation appears. Press [Yes] to execute. Then, the system re-starts up. Confirmation of Communication with Each Interface When the communication with the interface listed on the setting file is disconnected, the communication error is displayed on the Touch Screen Controller. Press the [Alarm List] button to confirm whether the communication error occurs or not. (Communication error judging time: Approx. 5 minutes) The suspected causes of the communication error will be as follows. The interface is not powered. The address setting of the interface is incorrect. The communication between the Touch Screen Controller and the interface is disconnected. The setting file is incorrect. Confirmation of Communication with Air Conditioner When the communication with the air conditioner is disconnected, the communication error is displayed on the Touch Screen Controller. The frame of air conditioner button on the screen is displayed orange. The suspected causes of the communication error will be as follows. The air conditioner is not powered. The address setting of the air conditioner is incorrect. The communication between the TCS-NET relay interface and the air conditioner is disconnected. The communication between the Touch Screen Controller and the TCS-NET relay interface is disconnected. The setting file is incorrect. 8

EH9985250