SmartRail I/O Ethernet Base HE599ETX300

Similar documents
SmartBlock I/O Module HE579MIX577/977 Isolated 4/8 Analog Inputs 2/4 Analog Outputs

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

4-20 ma Analog Input Module HE800ADC020 / HE800ADC120 HE-ADC020* / HE-ADC120* 12-Bit Resolution * HE-denotes plastic case.

RTD Input Module HE800RTD000 / HE800RTD100 HE-RTD000 / HE-RTD100* * HE- denotes plastic case.

Temperature I/O Module HE800MIX963 / HE-MIX963* * HE- denotes plastic case.

Thermistor / Current / Voltage Analog Input Module HE800ADC920 / HE-ADC920* 12-Bit Resolution * HE- denotes plastic case.

Thermocouple / Millivolt Input Module HE800THM000 / HE800THM100 HE-THM000 / HE-THM100* * HE- denotes plastic case.

24VDC Bipolar Digital In 10-28VDC, 0.5A Sourcing Digital Out 4-20mA Analog In/Out HE800MIX902 / HE-MIX902* * HE- denotes plastic case.

DeviceNet Master (Scanner) HE800DNT450 / HE-DNT450* DeviceNet Communications * HE- denotes plastic case.

XL7 OCS Datasheet for HE-XW1E0, HE-XW1E2, HE-XW1E3, HE-XW1E4, HE-XW1E5 HEXT391C100, HEXT391C112, HEXT391C113, HEXT391C114, HEXT391C115

MAN October 2010 PAGE 1 HE-579ACM300 SmartBlock Power and Energy Monitor HE-579ACM300

Specifications / Installation. QX Series Models:

QX751 CANOpen HEQX751C203/HEQX751C205 HE-BP41/HE-BP43 Back Pack Module

SAVE THESE INSTRUCTIONS

CompactBlock Guard I/O EtherNet/IP Safety Modules

Specifications / Installation. Specifications Digital DC Inputs XL103 XL104 Digital DC Outputs XL103 XL104

PanelView Plus/VersaView CE Terminals and Display Modules

XL4 OCS DATASHEET MODEL DC In, 12 DC Out, 2 12-bit Analog In. Serial Ports. USB mini-b USB A. CAN Port Isolated 1 kv.

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

P3-SCM. General Specifications

POINT I/O Family. Chapter. Overview

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

4-20mA Analog Output Module HE800DAC002 / HE800DAC102 HE-DAC002* / HE-DAC102* 14-Bit Resolution * HE- denotes plastic case.

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter

24VDC Bipolar Digital In 10-28VDC, 0.5A Sourcing Digital Out 0-20mA Sourcing Analog In/ Out HE800MIX906 / HE-MIX906* * HE- denotes plastic case.

Environmental Specifications CompactLogix Controllers and Compact GuardLogix 5370 Controllers

IES User Manual. 8 FE + 1 MM SC Unmanaged Switch -40 to 75, DIN-rail. v

Thermocouple Input Module Product Specifications and Installation Data

Perle IDS-108F(XT) Unmanaged 10/100 Ethernet Switches. Installation Guide. P/N (Rev G)

IES User Manual. 6 GE + 2 SFP Unmanaged Switch -20 to 60C, DIN-rail. v

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

IMC-101 Series Quick Installation Guide

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT

8-Port IP40 IEEE802.3af PoE Unmanaged Industrial Switch User s Manual

About the FLEX I/O and FLEX Ex I/O Systems

EXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

Industrial Ethernet Switch

EnerSure Installation Guide

Ethernet/IP Module. User Manual. Contents

LNP series. 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input.

SK CU4-EIP-C Part number:

RSTI-EP Slice I/O. PROFINET Scanner EPXPNS001. GFK-2965C November 2017

PHOENIX CONTACT - 10/2009

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide

XL4 OCS Datasheet for HE-XC1E0, HE-XC1E2, HE-XC1E3, HE-XC1E4, HE-XC1E5 HEXT251C100, HEXT251C112, HEXT251C113, HEXT251C114, HEXT251C115

General Specifications. P2-8AD4DA-2 Analog Input/Output

POINT I/O Family. Chapter. Overview

8 10/100/1000T Industrial Switch. User Manual MS655208(X)

P2-04DAL-2 Analog Output. Removable Terminal Block Specifications

Tempco Instruction Manual

RSTI-EP Slice I/O. EtherCAT Network Adapter Module EPXETC001. GFK-2967B Septembery 2016

Advanced Ladder Logic Required Power 24VDC. Full IEC Languages (Steady state) (heater duty cycle) 24VDC

Model 7705 Control Module

iologik E4200 Modular Active Ethernet I/O adaptor IT and Instrumentation for industry Introduction Specifications LAN Regulatory Approvals Warranty

iothinx 4500 Series (45MR) Modules

Hardened Media Converter

Select a Micro800 Controller

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

ETD-BL-1T-OFF-CC- 10S

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

General Specifications. P2-SCM Serial Communications

Analog Voltage Combination Module

iologik E1200 Series Ethernet remote I/O with 2-port Ethernet switch Introduction Remote I/O Daisy-Chained Ethernet I/O Connection

TN-5308 Quick Installation Guide

EtherNet/IP Communications Module

iologik E1200 Series Ethernet remote I/O with 2-port Ethernet switch Introduction Remote I/O

Installation Instructions

P2-04AD Analog Input. Removable Terminal Block Specifications

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

PHOENIX CONTACT - 05/2007

4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual

Quick Start Guide Elinx ESW100 Series. 5 and 8 port Unmanaged Ethernet Switch

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

Twido Programmable Controllers Discrete I/O Modules

iologik 4000 Series Modular remote I/O Introduction iologik E4200 Specifications Remote I/O Slice Form Factor and Flexible I/O Variety

Quick Start Guide Elinx ESW200 Series. 5 and 8 port Unmanaged Ethernet Switch

FL MC 2000E (SM40) LC

FL SWITCH SFNB. Five- and Eight-Port Standard Function Ethernet Switch with Narrow Housing. AUTOMATION Data Sheet 2642_en_H.

Installation and commissioning guide SmartLink PSD Power Supply Module (DC)

PTC-101-M12 Hardware Installation Guide

Signamax Connectivity Systems

Hardened PoE Ethernet Switch

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Installation Guide EtherNet/IP Module

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

CompactBlock Guard I/O Modules ArmorBlock Guard I/O Modules POINT Guard I/O Modules

General Specifications. P2-08THM Analog Input

KSD-800 Series. Installation Guide. Industrial 8-Port Fast Ethernet Switches with Fiber Connectivity DOC A -1-

External level devices for conductive point level switch

PTC-101 Quick Installation Guide

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

EL1142 Series. IEC / IEEE 1613 Hardened 2-Port 10/100BASE-TX to 2-Port 100BASE-FX Media Converter. User s Guide

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

User Manual Entry Line Industrial Fast Ethernet Switch 5x 10/100Base-TX

LNP-0602 series. 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx. User Manual

Transcription:

MAN--EN Specifications / Installation SmartRail I/O Ethernet Base HE599ETX INTRODUCTION SmartRail I/O is a real-time, modular I/O system that supports a variety of Ethernet and Fieldbus Communication architectures. The SmartRail I/O Ethernet/IP Base (ETX) utilizes Ethernet/IP communications, the popular Industrial Etherned protocol based on Common Industrial Protocol (CIP) distributed by the Open DeviceNet Vendor Association (ODVA). Unlike other SmartRail I/O Bases (such as the HE599CNX) which utilize Horner Controllers, the ETX supports third party PLCs and Ethernet IP Scanners, such as those from Rockwell Automation. Each SmartRail I/O base can support up to 8 SmartRail I/O Modules, addressed with up to 56 digital and 64 analog I/O per base. The number of ETX bases allowed on a single network is defined by Controller memory limitations. INSTALLATION. Physical Installation The ETX is compact (45mm W x 9mm H x 6mm D), and mounts on DINrail. Each I/O module installed adds width in increments of mm (for DC & analog I/O) or 7mm (for relay I/O). Modules can be added either before or after the ETX base has been installed on the DIN-rail.! The ETX features a built-in unmanaged Ethernet switch for the convenience of wiring and system expansion. SmartRail I/O is not complex to configure the ETX Ethernet/IP can be configured with a variety of manufacturer s software suites that Support Ethernet/IP communications. SPECIFICATIONS General Specifications Required Power (Steady State) 55mA @ 4 VDC CLASS POWER SUPPLY ONLY Primary Power Range 9. 8.8 VDC Output Power 5mA @ 5 VDC Terminal Type M Screw Type, Fixed Terminal Torque Rating.6 N-m (5. in-lb) Recommended Wire Size 4-8AWG (copper) Wire Stripping Length 7mm Relative Humidity 5 to 95% Non-condensing Operating Temp. -5 C to +5 C Storage Temp. -4 C to +75 C Dimensions (H x W x D) 9 x 45 x 6 mm [.54 x.77 x.6 in] Weight 4oz. (4g) Vibration & Shock Per IEC- Noise Immunity Per IEC-, IEC6-4-, IEC6-4-, IEC6-4-4 CE Yes UL & C-UL Class I, Div Groups A, B, C & D Communications Specifications Data Transmission / Mbps Flow Control Full/Half-duplex Connectors RJ-45 (8P8C), ports (AutoMDIX) Built-in Switch Unmanaged type I/O Protocol EthernetI/P Inactivity Timeout sec IP configuration Boot/p I/O Specifications Compatible I/O SmartRail I/O Modules Supported (per base) 8 Digital I/O, max (per base) 56 (Inputs + Outputs) Analog I/O, max (per base) 64 (Inputs + Outputs) I/O Limitations (per system) 48 Digital In, 48 Digital Out, 5 Analog In, 5 Analog Out Power Supplied for I/O 5mA @ 5V DC maximum modules I/O Module 5V Power Usage (5mA total available) 8 DC In 6 DC In DC In 8 DC Out DIM5 ma DIM6 4mA DIM7 5mA DQM56 4mA 6 DC Out DC Out 8 Relay Out 6 Relay Out DQM66 6mA DQM76 DQM5 ma DQM6 4mA ma 8DC + 8 Relay 4 Analog In 4 RTD In 4 T-couple In DIQ5 5mA ADC7 5mA RTD ma THM ma 4 Anlg. Out (ma) 4 Analog Out Analog In + Analog Out (V) DAC6 ma DAC 7mA MIX6 ma ETX Front View ETX Bottom View I/O modules are physically added with the following procedure:. Remove the cover (if present) for the expansion connector from the ETX base, and for all but the rightmost I/O module.. Make sure that the locks on the top and bottom of the ETX base are slid all the way to the front in the Open position.. Align the first I/O module to the right of the ETX base using the alignment features in the plastic case. 4. After affixing the module securely, slide the locks on the top and bottom of the base all the way to back in the Close position. 5. Repeat steps -4 above until all modules are affixed. 6. Hang the ETX base and all the affixed I/O modules to the top of the DIN-rail, and secure them by sliding the DIN-rail latches to the up position.. Wiring! Each SmartRail ETX Base requires 4VDC power, and an appropriate Earth Ground connection for normal operation. Port & Port are AutoMDIX RJ45 ports (8P8C), compatible with both straight through and crossover cables. Horner APG offers high-quality cables in a variety of convenient lengths. +4V Earth V Ground 4VDC Power Supply & Earth Ground Terminals June 6, 4 Page of 8

4 Software Each SmartRail ETX can be configured using a variety of Ethernet/IP ready devices. Setup has two top-level steps: use Boot/P service to assign I/P address to the ETX module, then use UCMM (unconnected message manager) through the desired software package to configure parameters of the I/O modules attached to the ETX SmartRail Base. 4. Startup Sequence Overview The software that is configured to control the SmartRail I/O will use the I/O configuration data (programmed via UCMM in the following section) to configure each ETX base. The following sequence is followed:. Upon power-up, the ETX will broadcast the MAC address to be assigned I/P data. This follows the Boot/P protocol convention.. Once in RUN mode, the Boot/P protocol will check its I/O configuration database, looking for a matching MAC ID entry.. If a match is found, the Boot/P protocol to assigns the appropriate IP address, Net Mask, and Default Gateway to the ETX Base. 4. Once all bases are assigned IP addresses, setup I/O configuration in Logic software by entering IP address of the base module. a. The PLC will place the ETX base in RUN mode b. Then, send a UCMM message to the base unit to configure the I/O modules attached to it. c. UCMM message will contain configuration parameters for the I/O attached to the base module for Ethernet I/P communication, assigning the arrays in the following order: 4. in RSLogix 5 4.. Setting up communication with the ETX Module in RSLogix: ) In project, right-click I/O Configurtion folder and select New Module. ) Select the scanner being used, in this case: 769-LE Ethernet port on Compact Logix 5E (see image below), and press OK: ) Enter revision number of the scanner and press OK.

MAN--EN Specifications / Installation 4) Enter name and IP address for the scanner. Click Finish. 5) This will p lace the scanner module below the I/O folder in the folder explorer tab. 6) Right-click on the added scanner and select New Module 7) The same dialogue box from adding the scanner will appear. This time, select Generic Ethernet Module and press OK. Configure the Module Properties: - Enter a name that will be tagged later on (here Rail) - Enter IP address on the ETX Module - Choose Assembly Instance Input, Output, and sizes - should always be set to Instance and Size Vendor ID 59 Device Type Product Code Input Size (words) * Output Size (words) * RPI (ms) Assembly instance (input) 6 Assembly instance (output) 7 Instance *Note: Choose an assembly instance for the input and output not in use. The size refers to words ( 6-bit word above) and is determined by the number of modules attached to the ETX 8) The next window will ask for RPI Settings. Start with ms and adjust if needed. 9) Click Next> then Finish>> ) Check the tags under Controller Tags in the folder navigation menu to make sure they are desired for the installed ethernet module. You can also add or edit tags from this pane, as you will do in the next section. 4.. Explicit Messaging Tags The first step of creating the Explicit message for parameter settings of the ETX modules is generating Tags that will be used to move information: - Create a tag with MESSAGE type The explicit message block will use this tag. - Create a tag with INT type This tag holds the parameter data that the explicit message uses. - Assign the generated MESSAGE tag to the Message block - Add required parameters (shown in section 4.) to the explicit message - Create a path to the module; here Rail ) Create MESSAGE Tag. Open Controller Tags and click Edit Tags. ) Click in the space next to blank line to add tag. Use desired name, here: MESSAGE June 6, 4 Page of 8

) Click the [... ] button under Data Type and change to MESSAGE. Press OK. (see above). 4) Create INT tag. Create another tag with desired name. Here: Test 5) Click the [... ] under Data Type and change to INT. Change DIM_ to 4 array dimensions (byte address - will be accessed in parameter data). Press OK. Note: Each module requires words of configuration data (which are configured via the Array Dimensions) Ex) modules = 4 words of data. Use Dim_ through Dim_. See section 4. for module configuration mapping. 6) Create BOOL tag. Create the last tag with the desired name. Here: Test 7) Click the [... ] Data Type and change to INT. Change DIM_ to. (Each module uses bits of configuration data. 4 bytes from the INT tag above) The second step is to create and configure the MESSAGE block in the Main Program : ) Add a rung with a normally open contact and a Message block. ) Double-click on the contact and assign the BOOL tag from step 6 above. ) Assign the message block the MESSAGE tag. 4) Double-Click the [... ] button on the message block to get to the following Message screen:

MAN--EN Specifications / Installation 5) Enter the values above. Source Element is the first array of the Test INT [4] previously made. Source Length depends on how many modules attached. bytes per array, arrays per module = bits per module. Destination is the INT[4] tag from before. Here: Test and open the Communication Tab: 6) From the Path section, click Browse and set the path to the Generic Ethernet Module set up in 4... Above: Rail. Press OK 7) Click Tag tab and ensure Message is tagged: 8) To Change Parameters, Move parameter data into the added/established memory in the processor (INT[4] tagged above). Example UCMM message Service Code : 6 (x: Set) Instance : 4 (x4: Assembly Class) Class : 8 (xb4 : parameter setting Assembly Object) Attribute : (x: Data) Data: :XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX (Parameter Setting Value) 9) Power Cycle the ETX Base once configuration is completed to finalize the boot/p process June 6, 4 Page 5 of 8

4. Parameter Settings for SmartRail devices. Note: addresses are formatted as such:. The first 8 bits, byte address, use bits -7. The second 8 bits, byte address use bits 8-5. The Second word is addressed in the same fashion. ADC7 Analog Input Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled Input Voltage / Current Range Output Data Range Ch Ch Ch Ch : ~V : ~ma : 4~mA 7 6 5 4 : ~4 : -~ Ch Ch Ch Ch :~(4~/~) : ~ - - - - - - - - DAC Analog Output Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled Output type configuration Ch Ch Ch Ch : -V Input Data Range Designation Output Status 7 6 5 4 : ~4 : -~ Ch Ch Ch Ch :~(4~/~) : ~ : former value : min. value Ch Ch Ch Ch : medium. value : max. value DAC6 Analog Output Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled Input Voltage / Current Range Ch Ch Ch Ch : ~V Output Data Range 7 6 5 4 : ~4 : -~ Ch Ch Ch Ch :~(4~/~) : ~ : former value : min. value Ch Ch Ch Ch : medium. value : max. value

MAN--EN Specifications / Installation All Digital I/O SmartRail Modules Address 7 6 5 4 Input Filter Maintaining output is allowed - - - - Input filter of maintaining output :ms : ms :5ms : ms :ms : 7ms :ms : Allow Others: Prohibit of maintaining output by channels 7 6 5 4 56~ 6 48~ 55 4~ 47 ~ 9 4~ 6~ 8~ 5 - - - - - - - - ~ 7 MIX6 Mixed Analog I/O Module Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled of Output Type Output Data Range of Output Status by Channels : 4~mA : ~ma Output Output Input Input : ~5V Ch Ch Ch Ch : ~V 7 6 5 4 :~4 Output Ch Output Ch Input Ch Input Ch :-~ :~(4~/~) :~ : former value : min. value Channel Channel : medium. value : max. value RTD Resistance Temperature Detector Input Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled of output Type Input Data Type Ch Ch Ch Ch 7 6 5 4 Ch Ch Ch Ch - - - - - - - - : PT : JPT off (): Centigrade on (): Fahrenheit June 6, 4 Page 7 of 8

THM Thermocouple Input Address 7 6 5 4 - - - - Ch Ch Ch Ch off (): Disabled on (): Enabled of output Type Input Data Type : K : J Ch Ch Ch Ch : T : R 7 6 5 4 off (): Centigrade Ch Ch Ch Ch on (): Fahrenheit - - - - - - - - ADC7 Analog Mixed Module 5 SAFETY Memory Address Operating Channel I/O Range (Ch-Ch) I/O Range (Ch4-Ch7) Output Data Type This equipment is suitable for use in Class I, Division, Groups A, B, C and D or Non-hazardous locations only Setting off (): stop on (): run : 4~mA : ~ma : ~5V : ~5V : ~V : ~ 4 : - ~ : precise value : ~ Wear proper personal protective equipment including safety glasses and insulated gloves when making connections to power circuits. WARNING - EXPLOSION HAZARD - Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous WARNING - EXPLOSION HAZARD - Substitution of any component may impair suitability for Class I, Division WARNING POSSIBLE EQUIPMENT DAMAGE Remove power from the I/O Base and any peripheral equipment connected to this local system before adding or replacing this or any module. When found on the product, the following symbols specify: Ensure hands, shoes, and floor are dry before making any connection to a power line. Make sure the unit is turned OFF before making connection to terminals. Make sure all circuits are de-energized before making connections. WARNING: To Before avoid each the risk use, of inspect electric shock all cables or burns, for breaks always or connect cracks the in the safety (or earth) ground insulation. before making Replace any immediately other connections. if defective. WARNING: To reduce the risk of fire, electrical shock, or physical injury it is strongly recommended to fuse the voltage measurement inputs. Be sure to locate fuses as close to the source as possible. WARNING: Replace fuse with the same type and rating to provide protection against risk of fire and shock hazards. Warning: Consult user documentation. Warning: Electrical Shock Hazard. WARNING: In the event of repeated failure, do not replace the fuse again as a repeated failure indicates a defective condition that will not clear by replacing the fuse. All applicable codes and standards need to be followed in the installation of this product. Adhere to the following safety precautions whenever any type of connection is made to the module. Connect the green safety (earth) ground first before making any other connections. When connecting to electric circuits or pulse-initiating equipment, open their related breakers. Do not make connections to live power lines. Make connections to the module first; then connect to the circuit to be monitored. Route power wires in a safe manner in accordance with good practice and local codes. WARNING: Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. 6 TECHNICAL SUPPORT For assistance and manual updates, contact Technical Support at the following locations: North America: Tel: -877-665-5666 Fax: 7 69-479 Web: http://www.heapg.com Email: techsppt@heapg.com Europe: Tel: +5--466 Fax: +5--486 Web: http://www.horner-apg.com Email: tech.support@horner-apg.com