selectivity module Selective monitoring of 24 V DC load circuits

Similar documents
Miniature circuit-breaker versus electronic selectivity module Selective monitoring of 24 V DC load circuits

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

Miniature Circuit Breakers for Railway Applications

Siemens AG Industrial Communication. SINEMA Server. Making your network transparent. Edition 06/2018. Brochure. siemens.

ST (6ES7132-6FD00-0BB1)

Block for SIMOTION SCOUT for Monitoring 24V-Branches

SITOP modular 1ph/2ph. SITOP power supply. SITOP modular 1ph/2ph. Overview. Safety instructions. Description, device design, dimension drawing 2

SENTRON 3VL Molded Case Circuit Breakers

Siemens AG Industrial Communication. SINEMA Server. Making your network transparent. Edition 09/2017. Brochure. siemens.

Protect Against Power-Related DUT Damage During Test

Automation meets IT. SCALANCE X-500 central interface between Industrial Ethernet and IT networks SIMATIC NET. siemens.

SITOP UPS1600 under STEP 7 V13. SITOP UPS1600 under STEP 7 V13. Introduction. Safety notes. Description. Assigning the IP address

New Functions and Integrated Communication Capability. The new SENTRON 3VL ETUs SENTRON 3VL. Answers for industry.

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Power Supplies & Logic Modules

What supplies 24 V DC even with voltage fluctuations, power failures, or overload reliably?

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM

ESS20 Electronic Circuit Breaker

EPSITRON Advanced Power Supplies. High-Performance and Efficient

SITOP modular 1ph/2ph. SITOP power supply. SITOP modular 1ph/2ph. Overview. Safety instructions. Description, device design, dimension drawing 2

5SL Miniature Circuit Breakers

SINAMICS DCM Cabinet. DC drive converter cabinets for fast and simple system integration. siemens.com/sinamics. Answers for industry.

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

SIRIUS Overload Relays. SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

SITOP PSU8200 1ph. SITOP power supply. SITOP PSU8200 1ph. Overview. Safety instructions 1. Description, device design, dimension drawing 2

Flexibility for your network

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Industrial Controls. Motor management and control devices SIMOCODE pro. Introduction 1. Configuring a reversing starter. List of abbreviations

Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties.

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD

SIRIUS 3RB24 Solid-State Overload Relays with Complete Starter Functionality via IO-Link

UMG 20CM. UMG 20CM 20 Channel Branch Circuit Monitoring Device with RCM. Harmonics via analysis channel RCM. Alarm management.

Applications & Tools. Block for STEP 7 V5.5 for monitoring 24 V DC load circuits using SITOP PSE200U Single Channel Message and S7-300/400 CPUs

SIMATIC system power supply SIMATIC ET200SP PS. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/removal 3

SIMATIC ET 200SP and ET 200MP

IELR Rail-Mount Series Magnetic Circuit Protectors

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions

Power module PM-E DC24V HF SIMATIC. ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface. Properties.

SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

Circuit Breaker Operation & its load calculations

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 3

SITOP PSU8600 power supply system

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V (6ES7138-4CA50-0AB0) Preface. Properties 1. Parameters 2. Diagnostics 3.


Miniature circuit breakers for all applications

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Siemens Industrial s

4. CIRCUIT BREAKERS. Functional Emergency Switching

Infrastructure for the Architecture

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

LED LIGHTING INRUSH CURRENT AND OVERCURRENT PROTECTION DEVICES

Flexible insurance against downtimes. SIMATIC S7-400H: high availability and safety in one system based on PROFIBUS and PROFINET

Solid State Remote Power Controller E /627

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V/AC V (6ES7138-4CB11-0AB0) Preface. Properties 1. Parameters 2.

SIGUARD Safety Combinations and Safe Load Feeders. safety INTEGRATED

SITOP Power Supply usa.siemens.com/sitop

Top integration. Top efficiency. Top reliability. SITOP

TR150 DRIVE STANDARD FEATURES

Siemens AG Introduction

Converter SINAMICS G150. Type 6SL37102G

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Siemens. SITOP power supply SITOP PSU300S. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/removal 3

Siprotec 7ST61 / 7ST63

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

WHITE PAPER. Overload or Short Circuit Protection? How to protect your design against both dangers. E-T-A Circuit Breakers USA. E-T-A Circuit Breakers

Combinable for All Applications

Manual. Industrial Controls. Motor Management and Control Devices. SIMOCODE pro Fail-Safe Digital Modules. Edition 11/2017. siemens.

QUINT-BUFFER/24DC/24DC/40

IELR Series

KNX DALI Gateway Plus - User Manual

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0)

SITOP power supply 24 V nonstop. The standard for reliability, compactness and functionality. siemens.com/sitop

The innovative interface for the last few meters to the process

SIMATIC. S7-1500/ET 200MP Power supply module PS 60W 24/48/60VDC HF (6ES7505-0RB00-0AB0) Preface. Documentation guide. Product overview.

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Readme

Wireless connected with SCALANCE W! Industrial Wireless LAN. Industrial Wireless Communication. Edition 09/2017. Brochure. siemens.

ifeatures special industrial functions for wireless applications Industrial Wireless LAN Industrial Wireless Communication Edition 09/2017 Brochure

Considerations for Use. of the SITOP DC UPS Module

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview.

Product and functional description

SIMATIC S plus TIA Portal

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

Safety is a SIRIUS business

Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) SIMATIC. ET 200SP Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) Preface

SITOP power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/removal 3

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

Unmanaged Industrial Ethernet Switches

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

Monitoring of 24 V load circuits

Siemens Drives & PLCs

Transcription:

Siemens AG 07 Miniature circuitbreaker versus electronic selectivity module Selective monitoring of 4 V DC load circuits In modern plant and machine construction all 4 V DC loads whether rugged electro-mechanical loads or highly sensitive electronics are supplied by a single, common, stabilized switch mode power supply. To ensure that a fault in one load does not bring the complete plant to a halt, the 4 V DC power supply circuit is divided into separate branches and selectively protected. Miniature circuit-breakers (s) are often used for this purpose. In many cases, however, they do not offer reliable protection. Conversely, the electronic selectivity module monitors the 4 V DC branches safely and ensures. Switched-mode power supplies protect themselves with electronic output current limiting To provide power to the 4 V DC level of automated plants, primary switchedmode power supplies have long ago gained widespread acceptance and replaced the unregulated transformer power supply. In most cases, however, the distribution of the 4 V feed among multiple load groups and their protection are still handled by conventional miniature circuit-breakers. The internals of switching power supplies are dimensioned for a specific nominal power output. To protect the devices against damage from overloading, the output current is electronically limited. The current limiting normally starts at. to.5 times the nominal value. This limited maximum current also has an effect on the tripping response of miniature circuit-breakers. The typical behavior of miniature circuit-breakers The function of miniature circuit-breakers is the protection of wires against thermal damage to the insulation from too high a current. The tripping characteristics are thus matched to the current voltage characteristics of the wires. Looking at the various current-time characteristics of s, two general tripping ranges can be distinguished resulting from two different disconnection mechanisms. In the range of small overcurrents, a timedelayed thermal tripping occurs through a bimetal. The duration until the tripping depends on the level of the overcurrent and can range from minutes to hours in the case of small overcurrent. The disconnection in the case of larger overcurrents (electrical shorts), on the other hand, is tripped electromagnetically without a delay. Here, the immediate tripping takes place within milliseconds by means of an electromagnet. So that the electromagnetic tripping of the does not already respond at the normal operational starting current surges caused by the connected loads, different sensitivities exist, which are reflected in the tripping characteristics A to D. In all cases, however, a multiple of the nominal current is required for the to trip rapidly.

Siemens AG 07 If, for instance, a miniature circuit-breaker of the common type C is considered, the electromagnetic instant tripping occurs at 5 to 0 times the nominal current; if operated with DC voltage, the limit current values increase by a factor of.4. For a safe configuration, 4 times the nominal current thus has to be taken into account to achieve the instant tripping required for the selectivity.. The problem with modern power supplies and conventional miniature circuit-breakers The electronic current limiting of a power supply limits the output current during overloads to, for example,.5 times the nominal current. In the case of a 0 A device, this corresponds, for example, to a maximum current of 30 A. With this device, at best type C miniature circuit-breakers with a rated current up to A can be safely and instantly tripped. Tripping time in s B Fast tripping is important, because when the 4 V DC supply fails the intact branches are also undersupplied. Voltage interruptions of 0ms are already critical for the PLC and will cause the process to be interrupted or even to crash. AC 0 4 0 3 0 0 0 0 0-0 - 0-3 0 0 Dip of 4 V DC Overload C Thermal trip 0 D x * Rated current Magnetic trip 0 Ethernet Oversizing is an inadequate solution approach In the simplest case, a tripping of higher current-rated miniature circuit-breakers can be achieved by using a power supply with a higher power output. This, however, also requires more space and increases the costs. In some power supplies, a so-called power boost is integrated. Here, the device is capable of supplying at least temporary up to 6 times the nominal current. But even this theoretically possible high output current is not the perfect solution for the problem since in practice, ohmic resistances of the feed and return wires to and from the fault location often prevent this maximum current from flowing. Already at a loop impedance of only 0.4 Ohm (for a wire with a cross section of mm, this corresponds to a distance of only m between power supply and load), a 0 A power supply capable of briefly supplying 6 times the current (0 A) can only drive 3 times the current (60 A) through the short-circuit path. With this current, a type C miniature circuit-breaker with a nominal current of up to 4 A can then be safely tripped instantly. If, in addition to the pure lead resistance, the internal resistances of the power supply and miniature circuit-breaker are taken into account as well as the transfer resistances of the terminals and the actual short circuit, even this 60 A will not be achieved and C4 will not trip immediately (see the application example on the next page). Although a higher current is flowing in the case of lower-ohmic faults, with which larger miniature circuit-breakers can be tripped as well, the parallel load branches see a voltage drop at least until the disconnection of the faulty path. This can disturb other electronic loads, if the disconnection does not take place within a few milliseconds. In the end, one has to realize that in the combination of switching power supply and miniature circuit-breaker, a selective disconnection of faulty load branches can only be achieved in special cases and with a lot of configuration effort. Application example with selective protection via miniature circuit-breaker: In the event of an overload the switched-mode power supply limits the current and the miniature circuit-breaker does not trip sufficiently quickly. The 4 V DC supplies dip, all loads are undersupplied, and the PLC switches to the Stop state.

Siemens AG 07 = Miniature circuit breaker R SITOP modular 4 V/ 0 A C4 C4 60 A DC DC 0..56 A Leads: m; mm R R T SC R i R i PS = R = R + R i PS + R i + R + R R SC I SC = U / R SC Application example with limited short circuit current The short circuit current is reduced by various ohmic impedances which means that the current required for fast tripping of the miniature circuit-breaker cannot be achieved regardless of the output performance of the power supply. Extensive functionality assures a targeted fault localization The selectivity module is specifically matched to the output response of switched-mode power supplies and the 4 V DC branches to be supplied. With its special shutdown characteristic (see right) it responds to overcurrent in a faulty branch even if it only minimally exceeds the rated current. Long thin leads for which the short circuit current is limited by the high ohmic impedance can also be reliably protected in this way. This means that smaller conductor cross-sections are possible which result in savings especially over long distances. Apart from current monitoring in the individual branches, the selectivity module also measures the output voltage from the power supply. However, should the power supply output voltage simultaneously drop below 0 V DC due to the total power being exceeded, all outputs carrying more than 00% of the individually set tripping current at that moment will immediately be disconnected. For all branches not overloaded, the 4 V DC supply is maintained without a disturbing drop the operation of large plant sections can be continued. Shutdown characteristic Tripping time 00.0 sec 0.0 sec.0 sec 0. sec 0.0 sec 0 % 5.0 sec 0. sec 50 % 00 % 50 % ) Load current I/I threshold Selectivity module SITOP PSE00U: Response with current requirements per output circuit... from 0 A to set value (I/I threshold = 00 %) no shutdown from set value up to 50 % ) shutdown after approx. 5 s above 50 % ) of set value current limiting to approx. 50 % ) for typ. 00 ms, then shutdown above set value with simultaneous collapse of supply voltage below 0 V DC immediate shutdown ) Versions with NEC Class : 0%

Siemens AG 07 Extensive functionality assures a targeted fault localization The tripping current of each output can be individually set with a potentiometer accessible from the front. This reduces the device variety and allows changes to be easily made even during commissioning. Two device versions with adjustment ranges from 0.5 to 3 A and 3 to 0 A are available, including versions with power limitation of the output to 00 W according to NEC Class. The status of the separate load circuits is indicated by one multi-colored LED per channel. In the event of a disconnection, the indicator changes from green to red. Depending on the device version, the fault is output by means of a common signaling contact or single-channel signaling. For single-channel signaling, the signaling output is to be connected to the PLC by only one standard digital input. The deactivated channel is signaled by a pulse pause protocol which is evaluated by a function block in the PLC (see below). Faults can be localized very quickly this way in a higherlevel control system or operator control and monitoring system which reduce downtimes even further. Additional benefits during operation and commissioning If a fault only occurred temporarily during operation, the affected output can be reactivated via remote reset. The function can reduce travel times and possibly downtimes especially for remote parts of the plant. Individual branches can be activated and deactivated manually by means of pushbuttons for support during commissioning and maintenance. A manually deactivated channel is indicated by a yellow LED. For safety reasons, the manual reset is not reversible via remote reset. Another important function is the sequential switching on of the individual output channels. A delay time of 5 ms, 00 ms or load-optimized - i.e. as soon as the previous output is less than the set value. That prevents a temporary overloading of the upstream power supply and thus a disruption of the 4 V DC voltage by not simultaneously switching on several connected loads. The reduced total inrush current may allow for the use of a smaller power supply. SITOP PSE00U with single-channel signaling: Cyclic signaling of channel states Failure indication Reset 0 Signal output OUT OUT OUT 3 OUT 4 digital input The SITOP PSE00U module with single-channel signaling outputs the status of the 4 channels cyclically by means of a serial code which can be read in by a digital input, e.g. of a PLC. Function blocks for SIMATIC S7-500/00/300/400, ET00 SP/ET00 S for STEP 7 Classic and TIA Portal as well as for SIMOTION SCOUT and SIMOTION CPUs are available free-ofcharge for the evaluation. As an application example you will also find the integration in LOGO! logic modules. Further information and downloads: SIMATIC S7: http://support.industry.siemens.com/cs/ww/en/ view/645084 AC 4 V DC Deactivation Ethernet Application example with a standard power supply (for example, from the SITOP smart product line) and selectivity module SITOP PSE00U: The selectivity module deactivates faulty channels at once in the event of imminent danger of a 4 V DC voltage drop. Critical loads like a PLC are supplied without interruption. SIMOTION: http://support.industry.siemens.com/cs/ww/en/ view/855546 LOGO!: http://www.siemens.com/logo-application-examples

Siemens AG 07 Application range of miniature circuit breakers and selectivity module: Conclusion Safety / Functionality Selectivity module and standard power supply + Safe shutdown, even for low short-circuit current, e. g. due to long cables, small core cross-sections, creepage short-circuits + Uninterruptible operation of electronic loads such as PLCs, due to immediate disconnection of faulty branches when there is a risk of a voltage dip + Fault diagnosis via LEDs, common signaling contact or single channel signaling and power supply with power boost + Rapid shutdown of faulty branches. Requires appropriate dimensioning of power supply,, core cross-sections and wire lenght Miniature circuit-breaker () and standard power supply + Shutdown of faulty branches, longer tripping time and voltage dips possible; insensitive loads only, such as electro-mechanical systems, continue to operate With the selectivity module SITOP PSE00U, selectivity is reliably achieved in 4 V DC power supply circuits, it eliminates undesired reactions affecting the power supply resulting from short-circuits or overloads since it monitors the current of each load circuit and reliably prevents a dropping of the supply voltage. The single-channel signaling already offers fault localization and a response from a central location. The channel-specific LED indicators in the control cabinet help you locate faults quickly, to prevent complete plant failures and to minimize partial failures to a very short period of time. Remote reset, manual activation and deactivation as well as sequential switching on of individual 4 V DC branches are additional benefits. Switched mode power supplies with miniature circuitbreakers offer a cost-efficient solution for loads that are not affected by voltage drops. With a high overload capability of the power supply (Power Boost, for example, up to 6 x I rated), tripping of the miniature circuit breaker can be accelerated. However, this combination does not guarantee adequate protection for critical loads in case of low short-circuit current. The selectivity module offers higher configuration reliability under all conditions. Plus a standard switched-mode power supply is sufficient. Siemens AG Process Industries and Drives Process Automation Postfach 48 48 9006 Nürnberg Germany Siemens AG 07 The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners. www.siemens.com/sitop