GENERAL MODBUS TABLE ORGANIZATION Starting of the Starting of the Group s Group s System Version (Release) System Version (Build) Group Name (Text) Group Code Group Complexity Group Version 36096 8D00 Table Option F040 D 0, C 3676 8D50 Alarms F040 D 0, C 5052 C550 Measures - Metrology Affected by current and voltage transformers F040 D2 0, C 50768 C650 Measures - Energies F040 D2 0, C 5024 C750 Measures - Statistique Affected by current and voltage transformers F040 D2 0, C 5280 C850 Measures - Metrology No Affected by current and voltage transformers F040 D2 0, C 5536 C950 Measure - Harmonic THD F040 D2 0, C 024 400 Reset F040 D2 0, C 36352 8E00 Table setup F040 D2 0, C 57344 E000 Network Settings F040 D2 0, C 57856 E200 Action System F040 D2 0, C MODBUS PROTOCOL DETAILS Code Exception 3 0, 02, 03, 04, 05, 06, 07, 08 6 0, 02, 03, 04, 05, 06, 07, 08 6 0, 02, 03, 04, 05, 06, 07, 08 Encoding "Big Endian" (most significant byte first) MODBUS OVER SERIAL DETAILS Physical Layer Trasmission Modes Device ing Baud Rates (bit/s) Bits bits trasmission sequence Parity Stop Bits standard EIA/TIA 485 (RS-485) two-wire configuration RTU 247 programmable (2400, 4800, 9600, 9200, 38400) 8 Least significant bit first no, odd, even, 2 MASTER/SLAVE COMMUNICATION TIMING Timer Descrtiption Timer Value (msec) Inter-character time-out <,5 character times Response delay (from master request) 250 Delay Time (between two master trasmissions) - REFER ALSO TO: www.modbus.org - MODBUS over serial line specification and implementation guide V.02 - MODBUS APPLICATION PROTOCOL SPECIFICATION V.b NOTE: File and printed copies of this document are not subject to document change control. File and printed copies of this document are not subject to document change control. Page /0
DISCRETE INPUT Bits (R) [bit] Description Note Read (no DISCRETE INPUTS availables) File and printed copies of this document are not subject to document change control. Page 2/0
COILS Bits (R&W) [bit] Description Note Read (no COILS availables) Write File and printed copies of this document are not subject to document change control. Page 3/0
INPUT REGISTERS Words (R) Bit Position Description Type Scale Unit Range Note Read Code 36097 36096 8D00 4 Table Option 36097 36096 8D00 Product option code (bit field) : bit : Metering Option 3 bit 2: Communication option 36098 36097 8D0 (reserved) 3 36099 36098 8D02 Option Slot 0xFF : None 0x0 : Metering option 3 0x : Communication option 3600 36099 8D03 Option Slot 2 0xFF : None 0x0 : Metering option 3 0x : Communication option 3677 3676 8D50 Table Option 3677 3676 8D50 Current alarm on lower threshold cause: 0 : No Alarm / : I / 2 : I2 / 3 : I3 / 4 : IN / 5 : U2 / 6 : U23 / 7 : U3 / 8 : P+ / 9 : Q+ / 0 : S / : F / 2 : PFL / 5: thdi / 6: thdi2 / 7 : thdi3 / 8 : thdu2 / 9 : thdu23 / 20 : thdu3 / 2 : Hour / 22: V / 23 : V2 / 24 : V3 / 26: thdv / 27 : thdv2 / 28 : thd V3 / 3 : PFC / 32 : T C 0 : / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 0 : mva : Hz/000 2 : 5 / 6 / 7 : /000 8 / 9 / 20 : /000 2 : Hour/00 22 / 23 / 24 : mv 3: 32 : C/0 3678 3677 8D5 2 Current alarm on lower threshold : min value 3 3679 3678 8D52 Current alarm on upper threshold cause: 0 : No Alarm / : I / 2 : I2 / 3 : I3 / 4 : IN / 5 : U2 / 6 : U23 / 7 : U3 / 8 : P+ / 9 : Q+ / 0 : S / : F / 2 : PFL / 5: thdi / 6: thdi2 / 7 : thdi3 / 8 : thdu2 / 9 : thdu23 / 20 : thdu3 / 2 : Hour / 22: V / 23 : V2 / 24 : V3 / 26: thdv / 27 : thdv2 / 28 : thd V3 / 3 : PFC / 32 : T C 0 : / 2 / 3 / 4 : ma 5 / 6 / 7 : mv 8 : mw 9 : mvar 0 : mva : Hz/000 2 : 5 / 6 / 7 : /000 8 / 9 / 20 : /000 2 : Hour/00 22 / 23 / 24 : mv 3: 32 : C/0 3680 3679 8D53 2 Current alarm on upper threshold : max value 3 368 3680 8D54 Current alarm duration s 3 3 3 File and printed copies of this document are not subject to document change control. Page 4/0
INPUT REGISTERS Words (R) Bit Position Description Type Scale Unit Range Note Read Code 5053 5052 C550 54 Measure - Metrology Affected by current and voltage transformers 5053 5052 C550 2 Hour Meter unsigned long 0,0 h NOTE 3 5055 5054 C552 2 Phase to Phase Voltage: U2 unsigned long 0,0 V NOTE 3 5057 5056 C554 2 Phase to Phase Voltage: U23 unsigned long 0,0 V NOTE 3 5059 5058 C556 2 Phase to Phase Voltage: U3 unsigned long 0,0 V NOTE 3 5052 50520 C558 2 Simple voltage : V unsigned long 0,0 V NOTE 3 50523 50522 C55A 2 Simple voltage : V2 unsigned long 0,0 V NOTE 3 50525 50524 C55C 2 Simple voltage : V3 unsigned long 0,0 V NOTE 3 50527 50526 C55E 2 Frequency : F unsigned long 0,0 Hz NOTE 3 50529 50528 C560 2 Current : I unsigned long ma NOTE 3 5053 50530 C562 2 Current : I2 unsigned long ma NOTE 3 50533 50532 C564 2 Current : I3 unsigned long ma NOTE 3 50535 50534 C566 2 Neutral Current : In unsigned long 0,0 ma NOTE 3 50537 50536 C568 \ active Power +/- : P signed long 0,0 kw NOTE2 3 50539 50538 C56A 2 reactive Power +/- : Q signed long 0,0 kvar NOTE2 3 5054 50540 C56C 2 apparent power : S signed long 0,0 kva NOTE2 3 50543 50542 C56E 2 power factor : -: leading et + : lagging : PF signed long 0,00 NOTE2 3 50545 50544 C570 2 Active Power phase +/- : P signed long 0,0 kw NOTE2 3 50547 50546 C572 2 Active Power phase 2 +/- : P2 signed long 0,0 kw NOTE2 3 50549 50548 C574 2 Active Power phase 3 +/- : P3 signed long 0,0 kw NOTE2 3 5055 50550 C576 2 Reactive Power phase +/- : Q signed long 0,0 kvar NOTE2 3 50553 50552 C578 2 Reactive Power phase 2 +/- : Q2 signed long 0,0 kvar NOTE2 3 50555 50554 C57A 2 Reactive Power phase 3 +/- : Q3 signed long 0,0 kvar NOTE2 3 50557 50556 C57C 2 Apparent power phase : S unsigned long 0,0 kva NOTE 3 50559 50558 C57E 2 Apparent power phase 2 : S2 unsigned long 0,0 kva NOTE 3 5056 50560 C580 2 Apparent power phase 3 : S3 unsigned long 0,0 kva NOTE 3 50563 50562 C582 2 Power Factor phase -: leading and + : lagging : PF signed long 0,00 NOTE2 3 50565 50564 C584 2 Power Factor phase 2 -: leading and + : lagging : PF2 signed long 0,00 NOTE2 3 50567 50566 C586 2 Power Factor phase 3 -: leading and + : lagging : PF3 signed long 0,00 NOTE2 3 50769 50768 C650 6 Measure - Energies 50769 50768 C650 2 Hour meter unsigned long 0,0 h NOTE 3 5078 50780 C65C 2 Partial Positive Active Energy: Ea+ unsigned long kwh NOTE 3 50783 50782 C65E 2 Partial Positive Reactive Energy: Er + unsigned long kvarh NOTE 3 5025 5024 C750 8 Measure - Statistique Affected by current and voltage transformers 507 5070 C77E 2 Max/avg I unsigned long ma NOTE 3 5073 5072 C780 2 Max/avg I2 unsigned long ma NOTE 3 5075 5074 C782 2 Max/avg I3 unsigned long ma NOTE 3 5077 5076 C784 2 Max/avg In unsigned long ma NOTE 3 5079 5078 C786 2 Max/avg P+ unsigned long 0,0 kw NOTE 3 508 5080 C788 2 Max/avg P- unsigned long 0,0 kw NOTE 3 5083 5082 C78A 2 Max/avg Q+ unsigned long 0,0 kvar NOTE 3 5085 5084 C78C 2 Max/avg Q- unsigned long 0,0 kvar NOTE 3 5087 5086 C78E 2 Max/avg S unsigned long 0,0 kva NOTE 3 528 5280 C850 30 Measure - Metrology No Affected by current and voltage transformers 528 5280 C850 Hour Meter unsigned word h NOTE 3 5282 528 C85 Phase to Phase Voltage: U2 unsigned word 0,0 V NOTE 3 5283 5282 C852 Phase to Phase Voltage: U23 unsigned word 0,0 V NOTE 3 5284 5283 C853 Phase to Phase Voltage: U3 unsigned word 0,0 V NOTE 3 5285 5284 C854 Simple voltage : V unsigned word 0,0 V NOTE 3 5286 5285 C855 Simple voltage : V2 unsigned word 0,0 V NOTE 3 File and printed copies of this document are not subject to document change control. Page 5/0
INPUT REGISTERS Words (R) Bit Position Description Type Scale Unit Range Note Read Code 5287 5286 C856 Simple voltage : V3 unsigned word 0,0 V NOTE 3 5288 5287 C857 Frequency : F unsigned word 0,0 Hz NOTE 3 5289 5288 C858 Current : I unsigned word ma NOTE 3 5290 5289 C859 Current : I2 unsigned word ma NOTE 3 529 5290 C85A Current : I3 unsigned word ma NOTE 3 5292 529 C85B Neutral Current : In unsigned word ma NOTE 3 5293 5292 C85C active Power +/- : P signed word 0,0 kw NOTE2 3 5294 5293 C85D reactive Power +/- : Q signed word 0,0 kvar NOTE2 3 5295 5294 C85E apparent power : S unsigned word 0,0 kva NOTE 3 5296 5295 C85F power factor : -: leading and + : lagging : PF signed word 0,00 NOTE2 3 5297 5296 C860 Active Power phase +/- : P signed word 0,0 kw NOTE2 3 5298 5297 C86 Active Power phase 2 +/- : P2 signed word 0,0 kw NOTE2 3 5299 5298 C862 Active Power phase 3 +/- : P3 signed word 0,0 kw NOTE2 3 5300 5299 C863 Reactive Power phase +/- : Q signed word 0,0 kvar NOTE2 3 530 5300 C864 Reactive Power phase 2 +/- : Q2 signed word 0,0 kvar NOTE2 3 5302 530 C865 Reactive Power phase 3 +/- : Q3 signed word 0,0 kvar NOTE2 3 5303 5302 C866 Apparent power phase : S unsigned word 0,0 kva NOTE 3 5304 5303 C867 Apparent power phase 2 : S2 unsigned word 0,0 kva NOTE 3 5305 5304 C868 Apparent power phase 3 : S3 unsigned word 0,0 kva NOTE 3 5306 5305 C869 Power Factor phase -: leading and + : lagging : PF signed word 0,00 NOTE2 3 5307 5306 C86A Power Factor phase 2 -: leading and + : lagging : PF2 signed word 0,00 NOTE2 3 5308 5307 C86B Power Factor phase 3 -: leading and + : lagging : PF3 signed word 0,00 NOTE2 3 532 53 C86F Total Positive Active Energy (no resetable) : Ea+ unsigned word MWh NOTE 3 534 533 C87 Total Negative Active Energy (no resetable) : Ea- unsigned word MWh NOTE 3 5537 5536 C950 0 Measure - Harmonic THD 5537 5536 C950 thd U2 unsigned word 0, % NOTE 3 5538 5537 C95 thd U23 unsigned word 0, % NOTE 3 5539 5538 C952 thd U3 unsigned word 0, % NOTE 3 5540 5539 C953 thd V unsigned word 0, % NOTE 3 554 5540 C954 thd V2 unsigned word 0, % NOTE 3 5542 554 C955 thd V3 unsigned word 0, % NOTE 3 5543 5542 C956 thd I unsigned word 0, % NOTE 3 5544 5543 C957 thd I2 unsigned word 0, % NOTE 3 5545 5544 C958 thd I3 unsigned word 0, % NOTE 3 5546 5545 C959 thd In unsigned word 0, % NOTE 3 NOTE value if not available (0xFFFFFFFF for long, 0xFFFF for word) NOTE 2 value if not available (0x7FFFFFFF for long, 0x7FFF for word) File and printed copies of this document are not subject to document change control. Page 6/0
INPUT REGISTERS Words (R) Bit Position Description Type Scale Unit Range Note Read Code EXAMPLE: Read the "Simple voltage: V" value from device having Modbus address 5 Modbus Request: 05 03 C558 0002 CRC Bit Position Description Type Scale Unit Range Note Read Code 5052 50520 C558 2 Simple voltage : V unsigned long 0,0 V NOTE 3 Modbus Reponse: "Simple voltage" value: ) 2) 3) 4) 5) 05 03 02 08FC CRC Value 08FC is in Hexadecimal Value 08FC correspond to 2300 in Decimal "Simple voltage: V" register has Scale=0,0 Real value= Value * Scale "Simple voltage: V" value is 2300*0,0=230 V File and printed copies of this document are not subject to document change control. Page 7/0
HOLDING REGISTERS Words (R&W) 025 024 400 Reset 025 024 400 Reset : Max 4I : 0x Max P+,Q+,S : 0x2 kwh+ : 0x80 kvarh+ : 0x00 All parameters : 0x000 Bit Position Description Scale Unit Range Note Read These values could be combine all 36353 36352 8E00 7 Table setup Network : 0 : BL : 2BL 36353 36352 8E00 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL 36354 36353 8E0 Current Transformer secondary : : A 5: 5 A A 36355 36354 8E02 Current Transformer primary A 36356 36355 8E03 Reserved 36357 36356 8E04 Synchronisation of I AVG/MAX: 2 : 2 seconds 0 : 0 seconds 300 : 5 minutes 480 : 8 minutes 600 : 0 Minutes 900 : 5 minutes 200 : 20 minutes 800 : 30 minutes 3600 : 60 minutes 36358 36357 8E05 Synchronisation of P/Q/S AVG/MAX 0 : 0 seconds 300 : 5 minutes 480 : 8 minutes 600 : 0 Minutes 900 : 5 minutes 200 : 20 minutes 800 : 30 minutes 3600 : 60 minutes 36359 36358 8E06 OUT : pulse output allocation : 0 : kwh+ : kvarh + 2 :Alarm 3 : Command 36360 36359 8E07 OUT : pulse output value : 0 : 0, kwh/kvarh : kwh/kvarh 2 : 0 kwh/kvarh 3 : 00 kwh/kvarh 4 : 000 kwh/kvarh 5 : 0000 kwh/kvarh 3636 36360 8E08 OUT : pulse output duration : : 00ms - 2 : 200ms 3 : 300ms - 4 : 400ms 5 : 500ms - 6 : 600ms 7 : 700ms - 8 : 800ms 9 : 900ms Write 6 File and printed copies of this document are not subject to document change control. Page 8/0
HOLDING REGISTERS Words (R&W) 36362 3636 8E09 Bit Position Description Scale Unit Range Note Read Hour meter allocation : Auxiliary power supply 2 : Currents 3 : phase to phase voltage Write 36363 36362 8E0A Hour meter trigger threshold Alarm Type : A/V : I 2 : In 3 : U 4 : V 5 : P+ 6 : Q+ 7 : S+ 8 : PFC 9 : PFL 36364 36363 8E0B 5 : P 6 : Q 7 : S 8 : CPF 9 : LPF 0 : THDU : THDV 2 : THDI 3 : HOUR 4 : F 5 : Internal temperature 36365 36364 8E0C Alarm Specified time (0-999) 36366 36365 8E0D Alarm upper Threshold 36367 36366 8E0E Alarm Lower Threshold 36368 36367 8E0F Alarm Hysteresis(0-99) Relay State : 36369 36368 8E0 0 : Open : Closed 57345 57344 E000 3 Network Settings 57345 57344 E000 Network Type : 0 : BL : 2BL 2 : 3BL 3 : 3NBL 4 : 4BL 5 : 4NBL 57346 57345 E00 Current Transformer secondary : : A 5: 5 A A 57347 57346 E002 Current Transformer primary A 57857 57856 E200 Action System 57857 57856 E200 Action : 0xA : Product Configuration storage 0xB2 : Produit reboot value if not available = 0xFFFF value if not available = 0xFFFF value if not available = 0xFFFF NOTE4 6 File and printed copies of this document are not subject to document change control. Page 9/0
HOLDING REGISTERS Words (R&W) Bit Position Description Scale Unit Range Note Read Write NOTE 4 - Configuration Procedure ) Write the new Configuration (one or more registers...) 2) Save/Confirm the new Configuration (writing the value 0xA in the register 0xE200) 3) Reset the device (writing the 0xB2 in the register 0xE200). The new Configuration is now available 4) The new Configuration is now available File and printed copies of this document are not subject to document change control. Page 0/0