FR-PU07 QUICK START MANUAL

Similar documents
FR-PU04 TRANSISTORIZED INVERTER INSTRUCTION MANUAL PARAMETER UNIT PRE-OPERATION INFORMATION. Chapter 1. FUNCTIONS Chapter 2. HELP Chapter 3 FR-PU04

Parameter Unit FR-PU04

FR-PU04 FR-PU04V INSTRUCTION MANUAL

FR-PU07 FR-PU07BB INSTRUCTION MANUAL

TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- RELAY OUTPUT FR-A5AR

VECTOR INVERTER -INSTRUCTION MANUAL- HIGH RESOLUTION ANALOG INPUT / EXTRA CONTACT INPUT / THERMISTOR INTERFACE FR-V5AX

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01

INVERTER INSTRUCTION MANUAL. Relay output function. Plug-in option FR-A7AR PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING RELAY OUTPUT

INVERTER Option unit FR-LU08 FR-LU08-01 INSTRUCTION MANUAL

FR-A8AR INSTRUCTION MANUAL

INVERTER INSTRUCTION MANUAL. Analog output function Digital output function. Plug-in option FR-A7AY PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING

D700 QUICK START MANUAL

Manual FC 3500 DC Fan Control

INSTRUCTION MANUAL. communication function. Plug-in option FR-A8ND PRE-OPERATION INSTRUCTIONS INSTALLATION WIRING INVERTER SETTING FUNCTIONS

TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- COMMUNICATION OPTION FR-A5NC

FR-A7NCN INSTRUCTION MANUAL. communication function. Plug-in option PRE-OPERATION INSTRUCTIONS INSTALLATION WIRING INVERTER SETTING FUNCTIONS

FR-A7ND INSTRUCTION MANUAL

OPC-VG1-PG / PGo. PG Interface Card for FRENIC-VG. Instruction Manual

INVERTER SCHOOL TEXT INVERTER PRACTICAL COURSE (DEMONSTRATION MACHINE OPERATING INSTRUCTION)

INVERTER INSTALLATION GUIDELINE. FR-F to NA FR-F to NA

ICON SERIES ipool. Swimming Pool Pump Controller. User Manual

MITSUBISHI TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- Option. DeviceNet TM FR-E5ND MITSUBISHI ELECTRIC

Optional add-on cassette Attachment Instruction manual

INVERTER CC2 FR-CC2-P (CONVERTER UNIT FOR PARALLEL OPERATION) INSTRUCTION MANUAL

TRANSISTORIZED INVERTER

TOS-SN-1 Extended Panel Operation Manual

TRANSISTORIZED INVERTER -INSTRUCTION MANUAL- COMMUNICATION OPTION FR-A5ND

MRZJW3- SETUP154E. General-Purpose AC Servo Servo Configuration Software MODEL INSTALLATION GUIDE

INVERTER FR-D700 INSTALLATION GUIDELINE FR-D to 318-NA FR-D to 160-NA FR-D720S-008 to 100-NA FR-D710W-008 to 042-NA

INVERTER FR-A800 INSTALLATION GUIDELINE FR-A (0.4K)

Please read here first

INVERTER FR-A802 (SEPARATED CONVERTER TYPE) INSTRUCTION MANUAL (HARDWARE) FR-A (315K) to 12120(500K) INTRODUCTION INSTALLATION AND WIRING

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

FR-A7NC E kit cover SC

Zenith DS9000 Dispensing System

POCKET MULTIMETER Model No: MM18

PAR-WT50R-E PAR-WR51R-E

User Manual. Solar Inverter for Water Pump

TRANSISTORIZED INVERTER

Remote Keypad "TP-E1"

PIEZO FEEDER CONTROLLER

INVERTER INSTRUCTION MANUAL. Converter Unit. FR-CC2-H315K to H630K CC2 INTRODUCTION INSTALLATION AND WIRING

User Guide True RMS Multimeter Extech EX205T

CoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide

ALPHA Automated Transfer Switch Operating Manual. Rev 1.21 The original of this document is drawn up in English language

Cable specifications PVC

INSPECTION CAMERA MODEL NO: CIC2410 OPERATION & SAFETY INSTRUCTIONS PART NO: GC0116

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Motorized Curtain Tracks Progress 50 Motor Set

Inverter (VFD) Manual

AutoRanging Digital MultiMeter

INVERTER A800 FR-A802 (SEPARATED CONVERTER TYPE) INSTRUCTION MANUAL (HARDWARE)

FR-A7NCA INSTRUCTION MANUAL. communication function. Plug-in option PRE-OPERATION INSTRUCTIONS INSTALLATION WIRING INVERTER SETTING FUNCTIONS

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004

CoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide

Table of Contents Product Overview Before using the product Installation Procedure... 5

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

Evolution 650/650 Rack 1U 850/850 Rack 1U 1150/1150 Rack 1U 1550/1550 Rack 1U Installation and user manual Pulsar Series

User Manual. 2.2KW/7.5KW/11KW Solar Inverter for Water Pump. Version: 1.8

ELV12 Series. Instruction Manual

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

NIR Moisture Analyzer KB-30

EQUIPMENT OPERATION MANUAL

Data editing software EZED3

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

ICON SERIES IDRIVE. Intelligent Constant Pressure. Water Supply Controller User Manual. idrive

Multi-Loader Parameter writer Instruction Manual PWU003Z

Series IZH10. Handheld Electrostatic Meter. How to Order. Accessories and Option / Part Number for Individual Parts.

Installation and safety instructions for devices for conveying air/gas mixtures

Owner's Manual. True RMS Multimeter. Model No Safety Operation Maintenance Español

PowerMust Office Uninterruptible Power System

Hardware Manual. intelligent Touch Controller

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

INVERTER FR-F800 INSTALLATION GUIDELINE FR-F (0.75K) to 04750(110K) FR-F (0.75K) to 06830(315K)

DC I/O Conversion Module FA-TB32XY

Instruction Manual LAN CABLE HiTESTER. March 2013 Revised edition A H

Table of Contents. Automatic Transfer Switch. User Manual ATS-16A/20A/30A/32A

Fire Fogger 1500 fog machine. user manual

EC Series. Safety Guide

English Version ENGLISH

VC200 Mobile Phone Tester Please Read before Use

HV-CS kv Edge Mount Triaxial Jack

[ ACD-NA ] User s Manual. O-Sung Electric Machinery Co., Ltd. 136, Hataemal-gil, Wollong-Myeon Paju-si, Gyeonggi-do, Korea

This manual classifies the safety precautions into two categories: and.

Model 2657A-LIM-3 LO Interconnect Module

DC I/O Conversion Module

GENERAL PRECAUTIONS GENERAL DESCRIPTION... 6

MDM 011-Z1 Regen Resistor

Model 7705 Control Module

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

FengMi Wemax One Laser Projection TV

LED Commander 16/2 DMX controller. user manual

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

1395 Node Adapter Board Troubleshooting

High Power Electronic Gear Installation and operation Guide

Remote Keypad Instruction Manual RKP002Z

Transcription:

VARIABLE FREQUENCY DRIVE MODEL FR-PU07 QUICK START MANUAL

1. INTRODUCTION...3 1.1 SAFETY...3 2. APPEARANCE AND PARTS IDENTIFICATION...4 3. PARAMETERS TO BE CHECKED FIRST...4 4. FUNCTIONS...4 5. OVERVIEW OF FUNCTION MENU...5 6. OPERATION...6 2

1. INTRODUCTION Thank you for choosing the Mitsubishi inverter option unit. This Quick Start Manual gives handling information and precautions for use of this equipment. Incorrect handling might cause an unexpected fault. Before using the equipment, please read this manual carefully to use the equipment to its optimum. Please forward this manual to the end user. All illustrations given in this manual may have been drawn with covers or safety guards removed to provide in-depth description. Before starting operation of the product, always return the covers and guards into original positions as specified and operate the equipment in accordance with the manual. 1.1 SAFETY Do not attempt to install, operate, maintain or inspect the inverter until you have read through the Quick Start Manual carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. In this Installation Guideline, the safety instruction levels are classified into DANGER and CAUTION. DANGER Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury. CAUTION Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage. Depending on the circumstances, procedures indicated by CAUTION may also cause severe injury. It is important to follow all precautions for personal safety. DANGER ELECTRIC SHOCK PREVENTION Do not run the inverter with the front cover removed. You may access exposed high voltage terminals or charging devices and get an electric shock. Before starting wiring or inspection, check that the operation panel indicator is off, wait for at least 10 minutes after the power supply has been switched off, and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power off and it is dangerous. Any person who is involved in the wiring or inspection of this equipment should be fully competent to do the work. Always install the inverter before wiring. Otherwise, you may get an electric shock or be injured. Operate the keys with dry hands to prevent an electric shock. CAUTION TRANSPORTATION AND MOUNTING Do not install and operate the parameter unit if it is damaged or has parts missing. Do not stand or rest heavy objects on this equipment. Check the inverter mounting orientation is correct. The parameter unit is a precision device, do not drop it or subject it to impact. Use the inverter under the following environmental conditions: Surrounding Air -10 C to +50 C (14 F to 122 F) (non-freezing) Temperature Ambient Humidity 90%RH maximum (non-condensing) Storage -20 C to +65 C *1 (-4 F to 149 F) Temperature Indoors (free from corrosive gas, flammable gas, oil mist, dust Atmosphere and dirt) Altitude/Vibration Maximum 1000m (3280.80 feet) above sea level, 5.9m/s² or less *1 Temperature applicable for a short time, e.g. in transit. CAUTION TEST OPERATION AND ADJUSTMENT Before starting operation, confirm and adjust the parameters. A failure to do so may cause some machines to make unexpected motions. DANGER USAGE Since pressing STOP/RESET key may not stop output depending on the function setting status, provide a circuit and switch separately to make an emergency stop (power off, mechanical brake operation for emergency stop, etc). Make sure that the start signal is off before resetting the inverter alarm. A failure to do so may restart the motor suddenly. Do not modify the equipment. Do not perform parts removal which is not instructed in this manual. Doing so may lead to fault or damage of the inverter. CAUTION USAGE When parameter clear or all parameter clear is performed, each parameter returns to the factory setting. Reset the required parameters before starting operation. CAUTION CORRECTIVE ACTIONS FOR ALARM Provide safety backup devices, such as an emergency brake, to protect machines and equipment from hazard if the parameter unit becomes faulty. CAUTION MAINTENANCE, INSPECTION AND PARTS REPLACEMENT Do not carry out a megger (insulation resistance) test on the control circuit of the inverter. It will cause a failure. CAUTION DISPOSAL Treat as industrial waste. DANGER SAFETY PRECAUTIONS FOR ALKALINE BATTERY Do not throw an alkaline battery in the fire. Do not shortcircuit, break down or heat an alkaline battery. Do not charge an alkaline battery. Use the battery of the specified type. CAUTION SAFETY PRECAUTIONS FOR ALKALINE BATTERY Check the following to prevent liquid leakage, heating, ignition, burst, etc. When the battery liquid leaked, wipe the liquid of the battery box well and then put in a new battery. If the liquid attaches to the body, rinse it off well with running water. Insert an alkaline battery with the correct polarity. When a battery is run down or not used for an extended period of time, take the battery out. Do not use a new battery with a used battery or a battery of different type. CAUTION SAFETY PRECAUTIONS FOR NICKEL METAL HYDRIDE BATTERY When using a nickel metal hydride battery and charger, read the instruction manuals carefully before using them. 3

2. APPEARANCE AND PARTS IDENTIFICATION Unpack the parameter unit, check the name plate on the back, and make sure that the product has not been damaged before using the equipment. Front POWER lamp Lit when the power turns on. READ:List 6 STF FWD PU Rear Monitor Liquid crystal display (16 characters 4 lines with backlight) Interactive parameter setting Help function Trouble shooting guidance Monitor (frequency, current, power, etc.) ALARM lamp Lit to indicate an inverter alarm occurrence. Operation keys Connection connector Connector to be connected to the inverter. Connected directly to PU connector of the inverter 3. PARAMETERS TO BE CHECKED FIRST Change the following parameter settings as required. n PU DISPLAY LANGUAGE SELECTION (PR. 145) By setting the Pr. 145 PU display language selection value, you can select the language displayed on the parameter unit. Pr. 145 Setting Display Language 0 (initial value) Japanese 1* English 2 German 3 French 4 Spanish 5 Italian 6 Swedish 7 Finnish * When the inverter is NA or EC model, the initial value is 1 (English). n PU BUZZER CONTROL (PR. 990) By setting the Pr. 990 PU buzzer control value, you can select to either generate or mute the beep which sounds when you press any of the parameter unit keys. Pr. 990 Setting Description 0 No buzzer sound 1 (initial value) Buzzer sound generated 4. FUNCTIONS Change the following parameter settings as required. n MONITORING FUNCTION (1) Main monitor READ:List 120.00 OL Hz STF FWD PU 4 Rating plate Cable connection connector Connect using the connection cable (FR-CB2 ). (2) Rotation direction indication (3) Operating status indication 1. Main monitor Shows the output frequency, output current, output voltage, alarm history and other monitor data. Using to change to the next screen Using to change to the next screen Using the parameter PU main display data selection 2. Rotation direction indication Display the direction (forward rotation/reverse rotation) of the start command. STF: Forward rotation STR: Reverse rotation --- No command or both STF and STR on 3. Operating status indication Display the running status of the inverter. STOP: During stop FWD: During forward rotation REV: During reverse rotation JOGf: During jog forward rotation

JOGr: During jog reverse rotation ARAR: At alarm occurrence n FREQUENCY SETTING The frequency in PU operation mode and external/pu combined operation mode (Pr. 79 = 3 ) can be set. When changing the operation mode from external operation mode to PU operation mode, operation mode can not be changed if the external starting signal (STF or STR) is on. Direct setting Directly enter a frequency setting using 0 to 9. Operation procedure (Changing from 0Hz setting to 60Hz setting) 5 (1) Direct setting Press. * Enter the desired value. Or (2) Step setting Press. Display "180" using. 6 Press. The set value is changed. 8 Dec.T1 5.0S 180S 0~3600 8 Dec.T1 180.0S Completed 1 Press. The frequency setting screen appears. 7 Press to display the next parameter. 9 Set THM 2.55A 0~500 2 Press and. Enter 60Hz. * 60.00Hz * If you entered an incorrect value, press to return to the pre-entry state. 6. OVERVIEW OF FUNCTION MENU 3 Press. The 60Hz setting is complete. SET 60.00Hz Completed If you entered an incorrect value, press ESC to return to the pre-entry state. n SETTING AND CHANGING THE PARAMETER VALUES Using the FR-PU07/FR-PU07BB allows you to read the parameter of inverter or change the set value easily. Refer to the inverter instruction manual for details of the parameters. Specifying the parameter number to change the set value Example: When changing 5s to 180s as the Pr. 8 Deceleration time setting. 1 Press. The frequency setting screen appears to switch to PU operation mode. (You need not press when the parameter unit is already in the PU operation mode.) 2 Press. The parameter unit enters the parameter setting mode. 3 Press. Enter the desired parameter number. 4 Press. The current setting appears. 5 SETTING MODE 0~9:Ser Pr.NO. Select Oper SETTING MODE Pr.NO. 8 <READ> 8 Dec.T1 5.0S 0~3600 Menu screen page 1 1 MONITOR 2 PU Oper 3 Pr.list 4 Pr.Clear Hold down and press to shift one screen. Menu screen page 2 + 5 Alarm Hist 6 AlarmClear + 7 INV.Reset 8 T/Shooting Menu screen page 3 9 S/W 10 Selectop 11 Option 12 FRCpy set Press any of the,, and keys to switch to the corresponding mode. The functions vary with the inverter model and may be invalid for some inverters. Function Menu Description 1. MONITOR The monitor list appears, and you can change from one monitor to another and set the first priority screen. You can select the PU operation mode via direct input (direct 2. PU Oper setting with the number keys) or select the jog operation mode from the PU, and displays how to operate the keys. The parameter menu appears, and you can perform 3. Pr.List parameter setting, list display, parameter change list display and initial value list display. 4. Pr.Clear The parameter clear menu appears, and you can perform parameter clear and all clear. 5. Alarm Hist This function displays history of past eight faults (alarms). 6. AlarmClear This function clears all the fault (alarm) history. 7. Inv.Reset This function resets the inverter. The inverter displays the cause of mismatch between 8. T/Shooting inverter operation and control/setting or the cause of an inverter fault. 9. S/W This function displays the software control number of the inverter. This function displays the signals assigned to the I/O 10. Selectop terminals of the control circuit and the ON-OFF states of the signals. 11. Option This function displays the option fitting states of the option connectors 1 to 3. 12. FRCpy set The function can perform the parameter copy (read, write verification). 5

6. OPERATION Switching from external operation mode [EXT] to PU operation mode [PU]. Confirmation Make sure that the external input signal (STF, STR) is OFF. --- STOP EXT --- STOP PU Pressing switches to the PU operation mode and changes the operation mode indication to [PU]. Switching from PU operation mode [PU] to external operation mode [EXT]. Confirmation Make sure that the external input signal (STF, STR) is OFF and that the operation command indication is "- - -". --- STOP PU --- STOP EXT The relationship between the running frequency and the start signal is as indicated in the following table. Pr. 79 Setting 3 Pr. 79 Setting 4 Description Running frequency setting Parameter unit Direct setting and / key setting External signal input Multi-speed selection (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27) 4 to 20mADC across terminals 4-5 Description Running frequency setting External signal input 0 to 5/10VDC across terminals 2-5 4 to 20mADC across terminals 4-5 Multi-speed selection (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27) JOG frequency (Pr. 15 ) Start signal External signal input Terminal STF Terminal STR Parameter unit If the operation mode cannot be switched properly, check the following: Make sure that the external input signal is off. If it is on, the operation mode (STF or STR signal) cannot be switched properly. Confirm the Pr. 79 Operation mode selection setting. n HOW TO OPERATE PU OPERATION Ordinary operation During motor operation, the speed can be changed by merely executing Step 2. Start signal Step Operation Procedure Image 1 Switch power on. Make sure that the monitor appears. ON 1. Power on Operation mode check 6 Pressing switches to the external operation mode and changes the operation mode indication to [EXT]. n SWITCHING TO THE EXTERNAL / PU COMBINED OPERATION MODE Changing the Pr. 79 Operation mode selection setting to 3 or 4 switches to the external / PU combined operation mode. PU+E is displayed in the operation mode indication position. READ:List --- STOP PU+E 2 Set the running frequency. Set the running frequency using direct setting or step setting. (Refer to page 26) 3 Press or. 3. Start The motor starts running. (or) The parameter unit automatically enters the monitoring mode and shows the output frequency. Step Operation Procedure Image 4 4. Stop Press. The motor is decelerated to a stop. --- STOP PU 2. Running frequency setting <Direct setting> 6 STF STOP PU Stop

When performing PU operation to run the motor, pressing the start key (FWD or REV) after setting the running frequency switches to monitor mode automatically. When FR-PU07BB is used in the battery mode (the inverter power is OFF), the operation is not available. n PU JOG OPERATION Hold down FWD or REV to perform operation, and release it to stop. Jog operation cannot be performed in the following cases: During motor operation The Pr. 15 Jog frequency is less than the Pr. 13 Starting frequency. Example: To operate at the PU jog running frequency of 8Hz Step Operation Procedure Image 1 Switch to the PU operation mode. If the operation mode indication is not [PU], switch to the PU operation mode. 1. Power on Operation mode check ON --- STOP PU 2 The frequency for jog operation can be set with Pr. 15 Jog frequency and the acceleration/deceleration time with Pr. 16 Jog acceleration/deceleration time both in the parameter unit. 2. Parameter setting 3 <Initial value> Pr. 15 5Hz Pr. 16 0.5s Press, then. The PU jog operation mode is selected, and the PU jog frequency setting screen appears on the display. To change the frequency, enter the value and press. 3. Jog operation mode selection PU/JOG SET 8.00Hz 4 Press or. The display changes to the monitor screen. Hold down the key to perform operation and release it to stop. 5 Press. The inverter exits from the jog operation mode and returns to the ordinary PU operation mode. 4. Operation (or) 5. Exit from jog operation mode The jog operation mode may also be selected from FUNC. When FR-PU07BB is used in the battery mode (the inverter power is OFF), the operation is not available. 7

MITSUBISHI ELECTRIC AUTOMATION, INC. 500 Corporate Woods Parkway, Vernon Hills, IL 60061 Ph 847.478.2100 Fx 847.478.2253 us.mitsubishielectric.com/fa/en/support January, 2016 2016, Specifications subject to change without notice. All rights reserved AZ-IB(NA)-0600240ENG-C