ETV Control ETV Valve

Similar documents
ETV. Electronic Tempering Valve. Installation and Operation Manual. Operates a Modulating Motorized Valve to Regulate Domestic Hot Water Temperature

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Sidewinder Pumps Inc. AC Timer/Controller

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

ASI Systems ML5740A Series

ASI Systems ML5720A Series

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

AirPro Surveyor 2 Manual

Linear Actuators (235N)

SP6R Level Controller Operation Manual

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

Tempco Instruction Manual

Multi-Unit Controller Installation Manual

MAXIMA + Series ROTARY LEVEL CONTROL

Electrical Actuators

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

The customer will see the blue-green florescent display of the TIMEMASTER, which will be showing the minimum amount needed to start the car wash.

Emech Troubleshoot Guide

VA-7700 Series. Electric Valve Actuators. Product Bulletin

IRB-MON UNIVERSAL SAFETY PHOTOEYE OPERATING UL MONITORED DEVICE

24/7 Sprinkler Monitor. The Ultimate Rain/Freeze Sensor

Electrical Actuators

Modulating controlled actuators AME 10, AME 20, AME 30 AME 13, AME 23, AME 33 - with DIN EN certified safety function (spring down)

OPERATING MANUAL TCAT-2DF CONTROLLER PHYSITEMP INSTRUMENTS INC. 154 Huron Avenue Clifton NJ USA Tel: Fax:

CO2 Controller Operating Instructions Models: RAD-0501, RAD-0501A, RAD-0501E 1. Product Description

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

CR87B TEMPERATURE RECORDER

MAXIMA + Series ROTARY LEVEL CONTROL

icp installation guide

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

Actuators for modulating control AME 13SU, AME 23SU - safety function (spring up)

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

PDS100 Programmable Dispensing System SAFETY INSTRUCTIONS

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

POWER SERIES Plus Watt-VAR / Watt-Power Factor Digital Switchboard Meter User s Manual IM2492WVPF-1

Elapsed Timer Control Panel

Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions

MAXIMA+ Series Rotary Level Indicator

RTD SAMPLER OPERATOR S MANUAL

Electrical Actuators

MICRO GROW GREENHOUSE SYSTEMS, INC ZEVO DR., SUITE B-1, TEMECULA, CA PHONE (951) FAX

OV1000 Part No OV1000 HEIGHT ADJUSTABLE TABLE USER GUIDE

ETV Platinum Plus Remote Communications

Cantata m100 Amplifier

Series RMA Hot Runner Controller Setup and Operation Manual

DEVAR Inc. Model d-rtti User Manual

OV1001 Part No OV1001 HEIGHT ADJUSTABLE TABLE USER GUIDE

Wireless Temperature Module

POWER SERIES Plus Watt / VAR / Power Factor Digital Switchboard Meter User s Manual IM2493WVP-3

Electrical actuator AME 855

Omni. User Manual. Economic Self-Tune PID Temperature Controller. Omni 96. Omni 72 72X72. Omni ~ 265 V AC SUPPLY

Three-Phase Solar Pump Controller 1.5 kw 380V User Manual

MICRO GROW GREENHOUSE SYSTEMS, INC

Limit Switch Box YT-870/875 SERIES

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

User's Guide. MiniTec TM Series Model MN25 MultiMeter

PREFACE. Thank you for choosing Zen Space Desks. We hope your desk helps you find your zen when being used. Zen Space Desks Team

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

Modulating controlled actuator AME 11

FIT. Fuel Island Terminal Installation and Operation Manual. The material in this manual is subject to engineering changes and editorial revisions

Plus-X 300. Installation and Operation Manual

Basketball Shot Clock Set LX2180 Manual

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

PT35. Dual Pulse Timer Instructions. Precision Flow Measurement An ONICON Brand PROUDLY MADE IN THE USA

PRO I Series CAPACITANCE PROBE

Service Instructions. Conductor 420

Electromotive actuators for combi valves

Differential Liquid/Gas Pressure Transmitter

Series RMT Hot Runner Controller Setup and Operation Manual

Mechanically Activated Device for Dry Run Protection in Applications with LORENTZ Solar Pump Systems

TSD-DA28 2x8 Balanced Line Distribution Amplifier

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

USER S MANUAL ENTITY. Energy Meter TRINITY. Entity Operational Manual

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

zpen-1080p Features zpen-1080p Layout

YT-870 / 875 Series. Rotork YTC Limited VERSION 1.06

ONE SERIES Electronic Pressure and Temperature Switches. with "I AM WORKING" Signal

impact INSTRUCTIONS LiteTrek 4.0 Monolight lighting equipment and accessories

PWRguard PLUS Spring City Drive Waukesha, WI

REMOTE THROTTLE. FOR CUMMINS CELECT and CELECT+ ENGINES SERIES M11, N14, L10 MODEL : RTU 1 OPERATING INSTRUCTIONS IDLE SETTING RTU

Electrical actuators

TS InteliSwitch Digital Time Switch 24VDC/VAC

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Series 803 LED Product Price Display

24V, Motorized Actuators

INSTALLATION INSTRUCTIONS

PRO REMOTE 25 CAPACITANCE PROBE OPERATING INSTRUCTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT Jamieson Equipmen toll free 800

User Manual. 1U LCD Keyboard Drawer. KwikDraw - A Series. Manual. IT and Instrumentation for industry. - With KVM options - 15", 17, 19 screen size

CC186 AND CC186/2 STAND-ALONE OR SYSTEM CLOCK

ILEA_IOM. Installation Instructions for ILEA electric actuators ILEA-Ax ILEA-Bx ILEA-Px ILEA-Qx TABLE OF CONTENTS

User's Guide. Model High Precision Quad Output DC Power Supply

Grundfos MAGNA, GENI Module

OPERATION MANUAL MODEL TT-LP

Carefree-Security. Installation and programming instructions 1050A. Owner s Manual

Thermometer / Barometer System

4-20mA Display. Installation and Operation Manual. Rev 4/3/2019 Part #

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

RESIDENTIAL OPERATOR MOTOR CONTROL BOARD REPLACEMENT INSTRUCTIONS

Transcription:

R ISTALLATIO/OPERATI ISTRUCTIOS ELECTROIC TEMPERI VALVE () Actuator Display current temp and control settings LED indicates actuator operation 3 buttons to view and change settings L 1 2 3 4 5 6 7 8 9101112 Control Valve WARI The Heat-Timer tempering valve is a primary tempering valve and is OT designed or recommended to be used as a Failsafe or Anti-Scald valve. For safety, it may be required to install separate anti-scald and safety devices.

2 Electronic Tempering Valve () Manual Installation Mounting The Control The Electronic Tempering Valve () control can be located up to 500' from the Heat-timer valve actuator. Locate the control in a convenient indoor location near the valve actuator. Use the three mounting brackets on the outside of the enclosure to secure the controller to the selected surface. Mounting Brackets Installing the Valve and Actuator The valve and actuator can be mounted upright vertical or sideways or any angle in between. They must not be mounted upside down. Make sure the valve ports and piping are correct. (See Diagram.) Calculate a clearance of a minimum of 15" for mounting and servicing the actuator. Mount actuator to valve body using U bolt and nuts provided. Use manual override (Red Tab) to adjust actuator shaft open or closed in order to align square nut to actuator shaft bracket. Tighten jam nut. Install supplied conduit adaptor to actuator housing knockout. L 1 2 3 4 5 6 7 8 9101112 Minimum Clearance 15 Conduit Adaptor Square ut Alert When the manual operation handle is lowered, the actuator does not respond to control signals. COLD Tempered Jam ut U Bolt Actuator Manual / Override Operation Lower the manual Red Tab handle. The actuator stops. Operate the actuator manually by turning the Red Tab clockwise or counter clockwise. When the actuator has been manually operated, the handle must be raised completely in order for the actuator to work. Flip Red Tab downward for manual operation HOT VALVE PORT IDICATOR Turn Red Tab clockwise or counter clockwise to make adjustment to valve opening Flip Red Tab upward for normal operation

O 1 2 3 4 5 6 7 8 9 Setting Actuator Dip Switches Before changing any dip switch positions, either the power must be off to the actuator or flip the Red Tab to the Manual position (Down). For the Actuator to move the valve in the correct direction, Set Dip Switch 7 to O (on 9 Dip Switch Actuators) or Set Dip Switch 6 to OFF (on 8 Dip Switch Actuators). All other dip switches must be OFF. Calibrating Actuator End Positions The Actuator must be calibrated to the valve size it is mounted on. This allows the actuator to find the valve end positions. Start by moving the blue and red tabs on actuator path closer to each other. Flip the Red Tab down and switch Dip Switch 9 to O then OFF (on 9 Dip Switch Actuators) or switch Dip Switch 8 to O then OFF (on 8 Dip Switch Actuators). Then, flip the Red Tab up for the calibration to start. The Actuator will move up and down. Then, it will resume normal operation. 1 2 9 Dip Switch Motors 8 Dip Switch Motors 2-10V Open @10V ormal O 1 2 3 4 5 6 7 8 0-10V Heat-Timer Corp. 3 2-10V 2 Close @10V Open @ 10V 3 0-10V Close @ 10V Calibrate ormal O 1 2 3 4 5 6 7 8 9 Calibrate Y X1 MX VH VC 1 0 WARI To Avoid scalding, prior to powering the or prior to calibrating the Motor, make sure that the valve hot input port is closed using an additional ball or shutoff valve or by installing the Heat-Timer TMC (Temperature Monitoring Control). The Motor will fully open to calibrate its highest and lowest points prior to following the control signal and resuming normal operation. If the supply to the building is excessively hot, scalding or serious injury might occur. Power Wiring The Control Bring the 120VAC 60Hz power wires through the Power Knockout (KO) on bottom of enclosure (Do not use REAR knockouts). The left KO is preferred. Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring. Connect the hot line to terminal market L. Connect the neutral line to the terminal marked. Alert When powering controls, Heat-Timer recommends installing a surge suppressor before connecting the power line to the control. Valve Actuator Wiring The control is designed to connect directly to the actuator. Terminal 1 of the control connects to actuator terminal (24VAC power). Terminal 2 of the control connects to valve terminal 0 (24VAC neutral). Terminal 3 of the control connects to valve terminal X1 (0-10VDC Signal) Terminal 4 of the control connects to valve terminal MX (0-10VDC round) Class 2 voltages must enter the enclosure through different opening from any Class 1 voltage wiring. L 120VAC eutral

4 Electronic Tempering Valve () Manual Sensor Wiring The temperature sensor wires can be extended up to 500' by splicing with 18 gauge shielded wire. Do not run sensor wires in conduit with line voltage. The sensor should be inserted into a 3/8" ID well (HT#904011 or equivalent). The will control the water temperature based on the temperature it reads at the sensor location. Therefore, select a sensor location which is representative of the entire system. (Min. 3-5 ft. from outlet) The sensor wires must be connected to terminals 6 and 7. Polarity is not important. Either wire from the sensor can be connected to either input terminal. Class 2 voltages must enter the enclosure through a different opening from any Class 1 voltage wiring. Setback Wiring The Setback feature can be used to provide a lower domestic hot water (DHW) setting during the night or when hot water use is minimal. The Setback signal must be a dry contact only. o voltage can be placed across terminals 7 and 8. When terminals 7 and 8 are shorted, the Setback is enabled and the will hold the lower Set Point. The right decimal point of the right digit will blink indicating this condition. Setting the Temperature Display Mode ( F or C) The temperature display mode is set when the control is powered up. Once set, it won t need to be set again. Power outages will not cause the display mode to be reset. ote: If you change the temperature display mode, you will need to reset the Set Point and Setback. To set the temperature display mode, use the following steps: 1. Remove power to the controller (if it was powered) and reapply power. (Valve will self adjust through its full stroke, open/close) 2. The display will show the software version number. 3. Wait approximately 5 seconds and the display will change to read either F or C. If the display shows F then the controller will operate in Fahrenheit degrees. If the display shows C then it will operate in Celsius degrees. 4. Hold down the center button while pushing either the UP or DOW button to toggle between the displays of F and C. 5. When the correct temperature mode is selected, release the buttons and wait approximately 5 seconds. 6. If the temperature display mode was changed, the display will flash. Then the will display the sensor temperature. Operation Digital Display During normal operation, the three digit display will show the temperature of the DHW (at the sensor location). If the right decimal of the right hand display digit flashes, this indicates the is holding the lower Setback water temperature. Viewing and Adjusting the Control Settings The Select, UP, and down buttons are used to view and adjust the Set Point, Setback, and ain. Repeatedly press the center Select button to advance through the control settings A setting can only be adjusted when it is being displayed. Use the Up and Down buttons to adjust the setting. The display will always revert back to the actual DHW temperature measured by the sensor after 30 seconds. Settings will not be lost if power is interrupted. The Control Settings chart describes each setting and how to adjust it. SELECT Control Settings Displays Settings and their Values In Setback when Dot is blinking LED to indicate Valve Movement UP and DOW Press and hold to Adjust Settings

Press SELECT Button Once Twice Display SP Set Point St b Setback 3 Times gan ain Control Settings Heat-Timer Corp. 5 Press and hold either the UP or DOW button to adjust the value The Set Point is the temperature that the will hold during normal operation. The temperature may fluctuate slightly around the Set Point value. The amount of fluctuation is controlled by the ain setting. ( 60 F to 180 F) Default 120 F. The setback is the number of degrees the DHW temperature will be lowered when the Setback input is shorted. The Setback provides a lower DHW temperature when demand is low. ( 0 F to 50 F) Default 20 F. The ain setting provides PID type control of the valve. The higher the ain setting, the more aggressively the control adjusts the valve based on a change in water temperature. If the water temperature tends to fluctuate quickly above and below the Set Point, reduce the ain. If the water temperature tends to stay below the Set Point, increase the ain. Start with a ain setting of 0.0, and always wait at the least ten minutes after adjusting the gain to determine its affect on the system. (-10 to +10) Default 3. 4 Times Default The returns to the default display of sensor temperature. Troubleshooting o Display Check the power to the controller. Turn the power off and back on. OFF or OP Display The does not see a sensor connected. Check the sensor wires are continuous from the sensor to the controller s terminals 6 and 7. Then, follow the procedure for Incorrect Temperature Display. SHT Display The sees a short across the input terminals 6 and 7. If you remove the sensor wires from the terminals, the display should change to read OP. If the display does not change to OP, the may be damaged. Incorrect Temperature Display Remove the wires from the sensor input terminals 6 and 7. The display should change to read OP. If it doesn t, the may be damaged. Take an ohm reading across the detached sensor wires. The ohm reading should correspond to the temperature chart. If the ohm reading is significantly different, the sensor may be damaged. does not provide Setback Check input terminals 7 and 8 are shorted together. When shorted, the right decimal point on the right digit of the display should flash. If it does, check the Setback setting is not zero. If the Setback setting is greater than zero, then the displayed Set Point temperature should be lowered by the amount of the Setback when terminals 7 and 8 are shorted. If the control was just switched into Setback, it may take a few minutes for the system water temperature to lower to the new Setback value. controller does not control the valve First remove all the wires attached to terminals 1 through 4. Check for 12 to 15VAC across terminals 1 and 2 on newer controllers. Older controllers should read 24 to 30VAC across terminals 1 and 2. If no voltage is present, the may be damaged. Then measure for between 0 to 10VDC across terminals 3 and 4. If there is no voltage across these terminals, adjust the Set Point. If the Set Point was previously above the displayed water temperature, adjust the Set Point until it is now below the displayed water temperature, and vice versa. Wait a couple of minutes, and then check terminals 3 and 4 again for voltage between 0 and 10VDC. If voltage is present, the controller is providing a signal to adjust the valve. Check the valve. WARI If Sensor is open or shorted, the valve will fully close. If you lose signal voltage, the valve will also close.

6 Electronic Tempering Valve () Manual Piping Diagrams Plumbing One Motorized Valve Control Module Cold Water Tempered Water Circ. Pump (Contiuous Running) Hot Water Sensor Tempered Water Circulating Return 32 Minimum Vertical Drop HOT WATER Plumbing Two Motorized Valves Control Module Tempered Water Cold Water Sensor Circ. Pump (Contiuous Running) Tempered Water Circulating Return Hot Water 32 Minimum Vertical Drop HOT WATER

O 1 2 3 4 5 6 7 8 9 O 1 2 3 4 5 6 7 8 9 O 1 2 3 4 5 6 7 8 9 Wiring Diagrams Heat-Timer Corp. 7 WIRI COTROL TO ACTUATOR MOTOR Control Actuator Motor 24VAC eutral 10V Signal Signal round } Temp Sensor } Setback Dry Contact Sensor Y X1 MX VH VC 1 0 L 1 2 3 4 5 6 7 8 9101112 Setback A0 AI C D1 D2 H Y X1 MX VH VC 1 0 0-10VDC Signal 120VAC eutral 24VAC Actuaor Motor Power WIRI OE COTROL TO TWO ACTUATOR MOTORS Control Actuator Motor1 Actuator Motor2 24VAC eutral 10V Signal Signal round } Temp Sensor } Setback Dry Contact Sensor Y X1 MX VH VC 1 0 Y X1 MX VH VC 1 0 L 1 2 3 4 5 6 7 8 9101112 Setback A0 AI C D1 D2 H A0 AI C D1 D2 H Y X1 MX VH VC 1 0 Y X1 MX VH VC 1 0 0-10VDC Signal 120VAC eutral 24VAC Actuaor Motor Power

COTROL SPECIFICATIO Heat-Timer Corp. 8 Voltage Input:.................................................. 120 VAC 60 Hz Power Consumption:................................................ 16 VA Max Output Power to Actuator:..................................Power to Actuator 24VAC Output Signal to Actuator:.............................................0-10VDC Temperature Display:..................................... (ºF) Fahrenheit or (ºC) Celsius. Display:........................................................3 7-Segment Set Point Range:.................................................. 60 F to 180 F Setback Range:.................................................... 0 F to 50 F Sensor Ranges:.................................... temperature sensor - minus 35 F to 250 F ain:.......................................................... - 10 to + 10 Enclosure:.........................................................EMA 1 Enclosure Dimensions:........................................7 ⅛ W x 9 ⅝ H x 3½ D ACTUATOR SPECIFICATIO Power Input:....................................................24 VAC 60 Hz Voltage Signal Input:.................................................. 0-10V Valve Stroke Calibration:............................(9 Dip switch motors) Flip Dip Switch 9 O (8 Dip switch motors) Flip Dip Switch 8 O Manual Operation:..........Flip Red Tab Down to activate manual Operation. Turn red tab to open or close valve MIXI VALVE SPECIFICATIO Maximum Pressure:.................................................. 225 PSI Maximum Temperature:................................................ 300 F Connections:......................................................... PT Body and Trim:......................................................Bronze Stem:......................................................... Stainless Steel Stem Packing:........................................... EPDM Spring Loaded V-Cup Size (in) Cv Max Pressure Drop PSI ½" 4.7 70 ¾" 7.3 65 1" 11.6 65 Size (in) Cv Max Pressure Drop PSI 1-¼" 18.5 55 1-½" 29 55 2" 46.3 40 LIMITED OE YEAR WARRATY This Heat-Timer device was thoroughly tested for defects and workmanship before leaving our factory. We do warrant the equipment to be free of defects under normal use for a period of one year from the date of installation. Transportation charges for factory repairs must be prepaid. Damage to the Heat-Timer device or any of its components due to misuse, abuse, improper installation, or caused by power failures, fire, flood, or lightning are not covered by this warranty. The company assumes no liability for indirect or consequential damages of any nature. This Heat-Timer warranty applies only to the original purchaser/user, is not assignable or transferable, and does not cover damage to the device occurring in shipment. Any service, repairs, modifications or alterations to the unit not expressly authorized by the company will invalidate the warranty. This warranty is in lieu of all other warranties expressed or implied. C O R P O R A T I O R 20 ew Dutch Lane, Fairfield, J 07004 973-575-4004 Fax 973-575-4052 http://www.heat-timer.com 059260-00 Rev.D