S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

Similar documents
S&C IntelliRupter PulseCloser Outdoor Distribution (15.5 kv and 27 kv)

S&C Scada-Mate Switching Systems Outdoor Distribution (14.4 kv through 34.5 kv)

S&C IntelliRupter PulseCloser. Outdoor Distribution 14.4 kv and 25 kv

S&C IntelliRupter PulseCloser Fault Interrupter

Elastimold Molded Vacuum Recloser - MVR

S&C 6801M Automatic Switch Operator

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

DNP Points List and Implementation

SmartClose 3-phase, Synchronous Close Vacuum Capacitor Switch

DNP Points List and Implementation

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Primary Injection Test Procedure

DNP Points List and Implementation for Universal Controls

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

Specifications. S&C Pad-Mounted Style IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv and 27 kv)

Specifications. S&C Loadbuster Disconnect Switches Outdoor Distribution (14.4 kv through 34.5 kv)

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches

S&C Micro-AT Source-Transfer Controls PHOTO SHEET. For use in S&C Metal-Enclosed Gear

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

Specifications. S&C Scada-Mate Switching System Outdoor Distribution (14.4 kv through 34.5 kv) For Remote Supervisory Control

Reclosers. Functional Specification Guide PS280026EN. Form 6 Rack/Yard-Mount Recloser Control

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

WiAutoLink Frequently Asked Questions

Performance. Reliability. Simplicity. A smarter grid requires an intelligent recloser.

Effective May 2018 Supersedes October 2017

Rapier GX Gas Enclosed Load Break Switch and Sectionaliser up to 38kV with automation or remote control options ENGINEERING BRILLIANT SOLUTIONS

DNP Points List and Implementation for the 6802 Vista Control

INSTALLATION PRODUCTS CAA GROUP OCTOBER 2018 Elastimold. Tru-Break switchgear module

IntelliTeam II Automatic Restoration System

PG&E Points List for Universal Controls

Specif ications. S&C Remote Supervisory Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)

PTAD Poletop Motor and Controller for Unitized Overhead Switches

LineScope. Smart Power Monitor. Bulletin DB50C18. US Patent Nos , , and B2

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

NU-LEC. Loop Automation. Reclosers & Sectionalizers

Products Portfolio. Pole mounted Vacuum Recloser

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

Specifications. S&C Regulator Bypass Switches Type XL (Sequenced) and Type NL (Nonsequenced) Outdoor Distribution (14.

SERIES SD3800 / SD3810 SPECIFICATION

APL/UPL, 205/295 Series Magnetic Circuit Protectors

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

High-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY

OSM PRODUCT GUIDE. OSM AUTOMATIC CIRCUIT RECLOSER 15kV, 27kV & 38kV Models

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution

Vacuum-Break Switches

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

Source-Transfer Application Guide

COOPER POWER. Types GN3E and GN3VE electronically controlled, manually closed sectionalizers SERIES. Sectionalizers Catalog Data CA270001EN

Siemens Fusesaver and Remote Control Unit 3AD8

SPECIAL SPECIFICATION 6274 Microwave Vehicle Detection System

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers

209/219/229 Multi-Pole Circuit Protectors 202 branch circuit applications such as EDP, air conditioners, panel boards

Installation. Section Page Section Page NOTICE

Underground Distribution Switchgear

Functional specification for Form 6 pole-mount recloser control

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

Form 6 Pole Mount Microprocessor-Based Recloser Control Technical Specifications

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

Versa-Tech II Recloser

TECHNICAL SPECIFICATION FOR MEDIUM VOLTAGE METAL-CLAD SWITCHGEAR (15 KV)

Specifications. S&C Loadbuster Disconnects a Outdoor Distribution (14.4 kv through 34.5 kv)

VisoVac padmount fault interrupter

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

SECTION SWITCHBOARDS

Maximum Reliability & Excellent Value. Features. UL Listed Withstand & Close-On Ratings. Series 300 Power Transfer Switches

Electrical Demand Specification (Reference SOP: )

1. Coordination of series-rated devices is permitted where indicated on Drawings.

Solid Dielectric Switchgear

Operation. S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Table of Contents

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

Operating and Diagnostic Instructions for IntelliTeam SG Automatic Restoration System

SECTION PANELBOARDS

2.1 The NOVA-TS Triple-Single Recloser and Form 6-TS control shall be designed in accordance with the following standards as applicable:

Specifications. S&C Scada-Mate CX Switching System Outdoor Distribution (14.4 kv and 25 kv)

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

Solid Dielectric Switchgear Catalog S-trid13

INSTRUCTIONS For Installation and Operation

Autodaptive Capacitor Control M 2501B

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

Instrument Current Transformers

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Lightweight and flexible recloser control for single-phase applications

MiCOM P122C Time-Overcurrent Protection

MINI-PS AC/10-15DC/8

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

IIM Warwick Court. Williamsburg VA REV 5

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

MONITORING AND CONTROL REQUIREMENTS FOR DISTRIBUTED GENERATION FACILITIES

Collector System Design Considerations for Wind Farms. Sean Carr Ernst Camm S&C Electric Co.

ASCO 920 Remote Control (RC) Switches

Transcription:

Overhead Source-Transfer Application Detailed Functional Specification Guide 1.0 GENERAL 1.01 The automated distribution fault-interrupting system shall conform to the following specification. 1.02 The fault-interrupting system shall be an outdoor, three-pole device incorporating vacuum fault interrupters individually operated by magnetic latching actuators capable of 2-millisecond close-open (pulse) operation; an integral power module(s); an integral protection and control module; an integral communication module; and integral sensors. All components shall be mounted on a unitized stainless steel base. 1.03 The unitized base shall be furnished with single-point lifting means to facilitate installation. 1.04 The unitized base shall include provisions for mounting and grounding three surge arresters on each side. No additional grounding connections shall be required for the surge arresters. 1.05 Optionally, polymer-housed metal-oxide surge arrestors shall be factory-installed and wired on both sides of the fault-interrupting system. 1.06 Appropriate venting shall be provided to prevent gas and moisture buildup within the unitized base. Vents and seals shall prevent insects, dust, wind-driven rain, and fluid from pressure-washing from entering the base, protection and control module, and communication module. 1.07 The fault-interrupting system shall be furnished in the Non-Disconnect Style, in the Upright- or Crossarm mounting configuration. 1.07 The fault-interrupting system shall be furnished in the Disconnect Style, in the Upright-Crossarm mounting configuration. The integral three-pole group-operated disconnect shall provide a visible air gap. It shall be interlocked to permit operation only when the fault interrupters are open. The disconect shall include: (1) Maintenance-free wiping contacts to prevent operational difficulties arising from corrosion or frost (2) Maintenance-free bearings (3) Low-resistance contacts indicating the Open and Closed positions of the disconnect 1.08 Control power shall be derived from an integral power module fed from one phase on one side of the fault-interrupting system. or 1.08 Control power shall be derived from two integral power modules, each fed from a different phase on both sides of the fault-interrupting system. 1.09 The integral power module(s) shall provide all control power for the fault-interrupting system in standalone (non-communicating) applications. No batteries shall be required, but ac line voltage must be available to the integral power module(s). 1.10 Optionally, wildlife protection shall be furnished for the fault-interrupting system to reduce wildlife-related nuisance outages. 1.11 The fault-interrupting system shall be suitable for application in an ambient temperature range of Supersedes Information Sheet 766-452 dated 6-15-2009 October 17, 2016 S&C Electric Company 2009-2016, all rights reserved Information Bulletin 766-452

-40 F (-40 C) to +104 F (+40 C). 1.12 The manufacturer shall have a minimum of 20 years experience in the production of distribution automation and protection equipment. 1.13 The manufacturer shall supply all internal wiring for the fault-interrupting system. 1.14 The following design tests shall have been performed on the fault interrupter, and certified test reports shall be provided upon request: Interrupting:...ANSI C37.60-2003 Dielectric:...ANSI C37.60-2003 Temperature Rise:...ANSI C37.60-2003 Short Time:...ANSI C37.60-2003 Fault Closing:.............................................ANSI C37.60-2003 Mechanical Endurance:...ANSI C37.60-2003 The following design tests shall have been performed on the control, and certified test reports shall be provided upon request: Electrostatic Discharge:...IEC 801.2 (IEC 1000-4-2) Fast Transient:...IEC 801.4 Power Line Surge:... ANSI C62.41 Surge Withstand:...ANSI C37.90.1 Radio-Frequency Interference:...ANSI C37.90.2 Electromagnetic Interference:...FCC Part 15 Class B Electromagnetic Compatibility:...EN 61000-4-3 Dielectric:... ANSI C37.90 2.0 FAULT INTERRUPTERS 2.01 Each fault interrupter shall be furnished with a magnetic latching actuator, described in Section 3.0, providing a close-open (pulse) of 2 milliseconds or less. 2.02 The fault interrupter housing shall be molded from cycloaliphatic epoxy resin. 2.03 The fault interrupter and actuator shall be maintenance-free. They shall have been tested and rated for at least 10,000 mechanical close-open operations. 2.04 A color-coded open/close indicator shall be provided for each fault interrupter, on the underside of the unitized base, that indicates green for open and red for closed. The indicator shall be readily visible from the ground. or 2.04 A color-coded open/close indicator shall be provided for each fault interrupter, on the underside 2 S&C Information Bulletin 766-452

of the unitized base, that indicates red for open and green for closed. The indicator shall be readily visible from the ground. 2.05 Mechanical loading from jumpers to the fault interrupter terminal pads shall not exceed 90 lbs. in-line and 30 lbs. perpendicular to the terminal pads, per IEEE Standard ANSI C37.32-1996 Section 8.8.2.2. 2.06 Ratings Select the appropriate ratings from the following tables: 60-Hz APPLICATIONS Ratings kv1 Amperes, RMS Minimum Maximum BIL Continuous2 Interrupting, Sym. 11.43 18.81 15.5 27 110 125 630 12 500 1 Minimum and maximum ratings ensure adequate power from the integral power module(s). 2 Allowable continuous current capability: 800 amperes with a minimum wind velocity of 2 ft./sec. 50-Hz APPLICATIONS Ratings kv1 Amperes, RMS Minimum Maximum BIL Continuous2 Interrupting, Sym. 10 20 17.5 24 110 125 630 12 500 1 Minimum and maximum ratings ensure adequate power from the integral power module(s). 2 Allowable continuous current capability: 800 amperes with a minimum wind velocity of 2 ft./sec. 3.0 MAGNETIC LATCHING ACTUATORS, OPERATING MECHANISM, AND EXTERNAL CONTROL LEVERS 3.01 The magnetic latching actuators shall be capable of electrically opening and reclosing the fault interrupters and performing circuit testing using a pulse. 3.02 Circuit testing using a pulse shall rapidly close and open the interrupters to produce a current pulse of 2- to 8- millisecond duration. Detection algorithms shall analyze the current pulse to determine whether a fault is present. The fault-interrupting system shall not close if the fault is still present. S&C Information Sheet 766-452 3

3.03 The operating mechanism shall have the option to provide three-phase or single-phase tripping of the vacuum interrupters and shall have the option to provide three-phase or single-phase lookout. 3.04 An external Open/Close/Ready lever shall be provided, allowing manual three-phase tripping of the vacuum interrupters using a standard or extendible hookstick. Control power shall not be required. 3.05 When the interrupters have been tripped by means of the Open/Close/Ready lever, electrical closing of the interrupters by the magnetic latching actuators shall be mechanically blocked until the lever is returned to its Ready position. The Open/Close/Ready lever shall have provision for tagging or locking in the Open position. 3.06 The magnetic latching actuators shall be electrically interlocked with the integral disconnect discussed in Section 1.07, when furnished, such that the magnetic actuators can only be operated when the disconnect is in the fully Open or fully Closed position. The disconnect shall be mechanically interlocked such that it can only be operated when the fault interrupters are open. 3.07 An external lever shall be provided to allow manual application of a hot line tag. The lever shall have a provision for tagging or locking in the hot line tag Active position. It shall only be possible to remove a manually applied hot line tag using this lever. If the lever is operated to give a second Remove command, it shall also remove a hot line tag applied by a SCADA or secure Wi-Fi command. 4.0 CONTROL AND COMMUNICATION 4.01 A control group, consisting of a protection and control module and a communication module, shall be located in the base of the fault-interrupting system. The modules shall be removable with a module-handling fitting attached to a standard 8-foot hookstick. 4.02 The communication module shall communicate via a secure Wi-Fi connection to a user-furnished laptop computer within range. Required configuration software shall be provided with the faultinterrupting system. The control program shall permit the selection of Local or Remote operation. It shall also indicate the Open/Closed position of each fault interrupter, phase voltages and currents, reason for a phase trip, etc. When local operation has been selected, the control program shall command local electrical opening and closing of the fault interrupters. 4.03 The control program shall indicate the position of the integral disconnect discussed in Section 1.07, when furnished. 4.04 The communication module shall include an integrated Global Positioning System clock for 1-millisecond accurate event time-stamping of events. 4.05 A status light on the protection and control module shall provide local indication of normal operation, Wi-Fi connection and disconnection, and loss of control voltage. The status light shall also provide local indication that the Open/Close/Ready lever has been moved from the Ready position to the Open position, from the Open position to the Ready position, and from the Ready position to the Closed position. 4.06 A hot line tag light on the protection and control module shall provide local indication of hot line tag application or removal. 4.07 A female N-Type antenna connector with integral surge suppressor shall be mounted to the unitized base for use with a radio in SCADA applications. The connector shall permit installation of a remotely located antenna. 4 S&C Information Bulletin 766-452

4.08 A non-volatile memory module installed in the unitized base shall back up configuration data and site-specific information, such as the device identifier, sensor calibration data, and operation counter reading. If the protection and control module is replaced, site-specific information shall be loaded in the new module and, as an option, the module shall be fully configured automatically upon insertion in the base. Sensor-calibration data and the operation-counter reading shall not change when new set points are loaded in the memory module. 4.09 The IntelliTeam SG Automatic Restoration System SpeedNet control group shall be furnished with an S&C SpeedNet Radio, providing high-speed network communication via DNP 3.0 Protocol, and IntelliTeam SG software. Userreplaceable batteries in the communication module shall support operation for a minimum of four hours after loss of ac line voltage on both sides of the fault-interrupting system, permitting extended dead-line switching and SCADA communication. 4.10 The control shall include the following protection and control elements: (1) Simultaneous independent directional phase, ground, and negative-sequence time-overcurrent elements (2) Simultaneous independent directional phase, ground, and negative-sequence instantaneous overcurrent elements (3) Simultaneous independent directional phase, ground, and negative-sequence definite-time elements (4) Directional blocking overcurrent elements (5) Intelligent fuse saving overcurrent elements (6) Overvoltage/undervoltage elements The protection and control elements shall enable sequence coordination, phase-unbalance detection, and synchronization check functions, and include a cold-load pickup modifier. 5.0 SOURCE-TRANSFER CONTROL OPERATION DESCRIPTION 5.01 Ready Condition The Ready condition shall occur with the normally closed fault-interrupter switch energizing the high-voltage bus and the normally open fault-interrupter switch and its associated circuit available to supply the bus. The normally closed and normally open designations shall be field configurable through a setup-software interface. 5.02 Transfer on Loss of Primary Source Voltage Automatic switching shall be initiated when voltage at the normally closed fault-interrupter switch is lost (or reduced to a predetermined level) for a predetermined period of time sufficient to confirm the loss is not transient. Automatic switching shall open the normally closed fault interrupter switch and then close the normally open fault-interrupter switch to restore power to the high-voltage bus. Transfer shall be initiated when the fault-interrupter switch opens for: extended loss-of-voltage, phase-loss detection, or voltage-loss counts. S&C Information Sheet 766-452 5

5.03 Return to Normal on Return of Primary Source Voltage return to normal mode Closed Transition When voltage returns to the normally closed fault-interrupter switch for a preset time, automatic switching shall be initiated to close the normally closed fault-interrupter switch and open the normally open fault-interrupter switch. 5.04 Return to Normal on Return of Primary Source Voltage return to normal mode Open Transition When voltage returns to the normally closed fault-interrupter switch for a preset time, automatic switching shall be initiated to open the normally open fault-interrupter switch and then close the normally closed fault-interrupter switch. 5.05 Return to Normal on Return of Primary Source Voltage return to normal mode None When voltage returns to the normally closed fault-interrupter switch no automatic operation will occur. While the normally open fault-interrupter switch is closed and energizing the high-voltage bus, automatic switching shall be initiated when voltage at the normally open fault-interrupter switch is lost (or reduced to a predetermined level) for a predetermined period of time sufficient to confirm that the loss is not transient. Automatic switching shall open the normally open faultinterrupter switch and then close the normally closed fault-interrupter switch to restore power to the high voltage bus. Transfer is initiated when the fault-interrupter switch opens for: extended loss-of-voltage, phaseloss detection, or voltage-loss controls. 5.06 Fault Isolation When a fault is detected through the fault-interrupter switch providing power to the high-voltage bus, the fault-interrupter switch shall operate in accordance with the active protection elements. If the fault is temporary in nature and the fault-interrupter switch is able to successfully reclose, the source-transfer system shall remain ready to transfer. If the fault is permanent and the faultinterrupter switch locks out, automatic operation shall be disabled and require manual intervention to return the transfer system to a Ready condition. 5.07 Open Source Time To Trip shall be configurable from 1 to 600 seconds. 5.08 Voltage-loss counts shall be configurable from 1 to 10 counts. 5.09 Automatic return shall be configurable for 1 to 60 minutes in 1 minute increments. 5.10 The number of breaker operations needed to open the closed switch shall be configurable. 5.11 Phase-loss protection shall be provided and operate for the loss of one or two phases. 5.12 Phase-loss voltage threshold shall be configurable in RMS volts. 5.13 Phase-loss current threshold shall be configurable in amperes. 6.0 SCADA 6.01 The fault-interrupter switch shall be capable of SCADA communication using DNP 3.0 Protocol. 6.02 The fault-interrupter switch shall have an optional factory-installed radio or fiber-optic communication device. 6.03 The fault-interrupter switch shall have a SCADA input point for the Ready condition. 6 S&C Information Bulletin 766-452

6.04 The fault-interrupter switch shall have a SCADA input point for low battery. 6.05 The fault-interrupter switch shall have a SCADA control point to disable and enable automatic operation. 6.06 All fault-interrupter switch analog and status indications shall be available as SCADA input points. 6.07 The fault-interrupter switch shall have optional user interface software that provides remotesetup capability to allow setup over the radio system or a dial-up modem. 7.0 SENSORS 7.01 Voltage and current sensors shall be integrally molded into the fault-interrupter housings. 7.02 The sensors shall provide three-phase monitoring of line current and three-phase monitoring of system line voltage on both sides of the fault-interrupting system. 7.03 Total system voltage sensing accuracy shall be within ±0.5% across the tested temperature range of --40 F (-40 C) to +104 F (+40 C). 7.04 Total system current sensing accuracy shall be within ±0.5% across the tested temperature range of -40 F (-40 C) to +104 F (+40 C), and linear over the full range of load and fault current. S&C Information Sheet 766-452 7