EXOcompact Third Generation Manual

Similar documents
EC-PU4. Processor unit with 4 communication ports

EXOcompact. Third generation freely programmable controllers

EXOcompact. Freely programmable controller

EXOcompact. Manual ONE STEP FURTHER...

AIAS. Technical description

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

FEATURES DESCRIPTION FEATURES

6ES7212-1BD30-0XB0. permissible range, lower limit (DC) permissible range, upper limit (DC)

mark150s mark150/485s DDC controllers Summary

MXPLC. Compact PLC process station. Summary. Application HVAC control systems, data acquisition, interfacing 3 rd party systems.

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Supply voltage. Input current. Encoder supply. Memory

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

Pre-programmed room controller with display and communication

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

General information. Display. Supply voltage. Input current. Encoder supply. Power losses

The ECL Apex 20 is operated by means of either a PC or the ECL Apex Web Panel. Temperature input signals are based on Pt 1000 or 0-10 V.

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

PBSCONTROL. AMS-R4000 Modular RTU. Remote Terminal Unit

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

General information. Display. Supply voltage. Input current

XT-9100 Technical Bulletin

General information. Display. Supply voltage. Input current. Encoder supply. Output current

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

Features and Benefits. Certifications

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current

IMIO100 IMIO105. DDC controllers. Summary

General information. Display. Supply voltage

General information. Supply voltage. Input current. Encoder supply. Power loss. Memory

Supply voltage. Input current. Encoder supply. Memory SIMATIC S7-200, CPU 221 COMPACT UNIT, DC POWER SUPPLY 6 DI DC/4 DO DC, 4 KB CODE/2 KB DATA,

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Engineering with. Supply voltage. Load voltage L+ Input current. Power losses. Memory. Work memory.

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

General information. Display. Supply voltage. Input current. Encoder supply. Output current

TM241CE40R controller M IO relay Ethernet

General information. Display. Supply voltage. Input current

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

BMKC Controller for Parabolic Trough, 8 DI 12 DO 4 AI

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

Pre-programmed room controller with display and communication

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage

General information. Display. Supply voltage. Input current

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

General information. Display. Supply voltage. Input current. Encoder supply. Output current

VersaMax Micro and Nano Technical Product Presentation

TM241CE40R controller M IO relay Ethernet

General information. Display. Supply voltage

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

TM221CE40T controller M IO transistor PNP Ethernet

General information. Display. Supply voltage. Input current. Encoder supply. Output current. Power loss. Memory

TM241CE40R controller M IO relay Ethernet

TM221CE24R controller M IO relay Ethernet

TM221CE40R controller M IO relay Ethernet

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

Product Information on the Manual

Product type designation. General information. Supply voltage. Input current

TM221ME32TK controller M IO transistor PNP Ethernet

TM241CE24T controller M IO transistor PNP Ethernet

TM241CEC24R controller M IO relay Ethernet CAN master

TM241CE40T controller M IO transistor PNP Ethernet

DSP240-LPI Inverter Controller Card. Technical Brief

T E C H N I C A L D O C U M E N T A T I O N E X O f l e x EXOflex Manual

BACnet Controller for General-purpose Building Applications

TM241CE24T controller M IO transistor PNP Ethernet

Andover ContinuumTM. b3850 Series Terminal Controllers

iologik 4000 Series Modular remote I/O Introduction iologik E4200 Specifications Remote I/O Slice Form Factor and Flexible I/O Variety

TM241CE24U controller M IO transistor NPN Ethernet

General information Engineering with Programming package. Display with display

ProData data logger. Ethernet. Pulse inputs and Pulse outputs. Thermistor input. Modbus-Ethernet gateway. Memory 32 MB. Threshold value monitoring

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

iologik E2200 Series Smart Ethernet remote I/O with Click&GO Logic Introduction Remote I/O PC-Free Alarm and Control Intelligence

General information. Supply voltage

iologik 4000 Series (M) Modules

General information. Display. Supply voltage. Input current

Product type designation. General information. Supply voltage

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

Transducers for Pt-100/1000, Resistors

Installation & Operation Guide

TM221M16R controller M IO relay

General information. Display. Supply voltage. Input current

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

Expansion Module HZS 541-1S

9500 and 9600 I/O Card Installation Instructions

TM221M16TG controller M IO transistor PNP spring

Central processing units CPU 221, CPU 222, CPU 224, CPU 224 XP, CPU 224 XPsi, CPU 226

General information. Display. Supply voltage. Input current

BMKC Controller for Power Tower, 8 DI 8 DO 2 HSC

Z-GPRS2-SEAL THE SIMPLEST REMOTE MANAGEMENT SYSTEM FOR UNIVERSAL APPLICATIONS GSM/GPRS DATALOGGER WITH BUILT-IN I/O S AND TELECONTROL FUNCTIONS

Submittal Data Sheet WAGO Node for itm

TM241C40R controller M IO relay

Andover ContinuumTM Infinet II

S800 I/O ABB Automation

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

MIC-2 MKII, Multi-instrument DATA SHEET

Transcription:

EXOcompact Third Generation Manual

DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. AB Regin however, makes no warranties as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification. The software described in this document is supplied under license by Regin and may be used or copied only in accordance with the terms of the license. No part of this document may be reproduced or transmitted in any form, in any fashion, electronically or mechanically, without the express, written permission of Regin. COPYRIGHT AB Regin. All rights reserved. TRADEMARKS EXOdesigner, EXOreal, EXO4, EXOscada, EXOcompact, EXOflex and EXOline are registered trademarks of AB Regin. Windows 7, Windows 8, Windows 2000, Windows XP, Windows Server 2003, and Windows Vista are registered trademarks of Microsoft Corporation. Some product names mentioned in this document are used for identification purposes only and may be the registered trademarks of their respective companies. May 2014 Document Revision: 2013-1-01

Table of Contents Chapter 1 Introduction 4 Chapter 2 Technical Specifications 5 Chapter 3 Installation 7 General Connections 7 With AC Supply and Mixed Loads on DO 7 With DC Supply and Mixed Loads on DO 8 I/O Description 9 Using the unisolated port 11 Chapter 4 Maintenance and Service 12 Changing the Battery 12 Resetting the Application Memory 13 Updating the operating system 13

Chapter 1 Introduction EXOcompact is a range of freely programmable controllers, fully compatible with other products in the EXO system. They can easily be integrated with EXOflex, EXOscada and EXO4 in large automation systems. The general functions and specifications for EXOcompact third generation are described in the product sheet which can be downloaded from Regins homepage, www.regin.se. This manual, EXOcompact Third Generation, describes additional technical information. 4 EXOcompact Third Generation

Chapter 2 Technical Specifications CPU & Memory Operating system... EXOrealC Application SRAM memory... approx. 480 kb Application flash memory (TCP/IP)... 8 MB (304 kb reserved by EXOreal) Application flash memory (no TCP/IP)... 4 MB (304 kb reserved by EXOreal) Real-time clock (RTC)... max ±20 sec./month. Battery Type... Lithium, CR2032 Battery backup of RAM, RTC... 5 years Battery monitoring... status LED + software accessible Communication ports Port 1 Type... RS485 built-in protocol... EXOline other protocols... contact Regin Control signals, RS485... E Speed... configurable, 1200-38400 bps standard... 9600 bps Galvanic isolation, common mode voltage... max. 150 V Port 2 (Models with built-in M-Bus) Type... M-Bus Speed... configurable, 1200-9600 bps standard... 2400 bps Max. number of meters with speed 1200-2400 bps... 8 Max. cable length with speed 1200-2400 bps... 1000 m Max. number of meters with speed 4800-9600 bps... 4 Max. cable length with speed 4800-9600 bps... 200 m Port 2 (Models without built-in M-Bus) Type... RS485 built-in protocol... EXOline other protocols... contact Regin Control signals, RS485... E Speed... configurable, 1200-38400 bps standard... 9600 bps Galvanic isolation... no TCP/IP Port Type... 10Base-T/100Base-TX auto-negotiation built-in protocol EXOreal 3.1-1-01 or later... EXOline over TCP slave, BACnet/IP, HTTP, SMTP EXOreal 3.1-1-00 or earlier... EXOline over TCP slave, HTTP, SMTP Auto MDIX... yes Fast connector... RJ45 Supported standards... IEEE 802.3u and IEEE 802.3x full-duplex flow control Max. cable length... 100 m (min CAT 5) Analog Inputs, AI Mains frequency filter... configurable, 50 or 60 Hz Basic ADC resolution... 12 bit EXOcompact Third Generation 5

Measurement range... program selectable/channel Temperature (PT1000)... -50-+150 C.. accuracy (excluding sensor)... +-0.4 C Temperature (Ni1000 DIN)... -40-+105 C.. accuracy (excluding sensor)... +-0.4 C Temperature (Ni1000 L&G)... -40-+120 C.. accuracy (excluding sensor)... +-0.4 C Current... 0 (4) - 20 ma, requires external 10 or 500 Ohm shunt.. measurement range... 0 (40) - 200mV with 10 Ohm or 0 (2) - 10 V with 500 Ohm.. accuracy... depends on external shunt Voltage...0-10 V.. input resistance... 10 MOhm.. accuracy (% of full scale)... +-0.15% Voltage... 0-200 mv.. input resistance... 10 MOhm.. accuracy (% of full scale)... +-0.15% Conversion Time for all channels max 66+n*40 ms (frequency 50 Hz, where n is the number of active channels, including activated UI channels. UI, Universal Inputs, AI or DI selectable See AI or DI depending on selection, except for the below specific UI parameters: Voltage... 0-10V and 0-200 mv.. input resistance... 1 MOhm Analog Outputs, AO Basic DAC resolution...12 bit Output level... 0-10 V DC Update cycle... 300 ms Max load... 5 ma, short circuit proof Digital Inputs, DI Type... 24 V DC, floating contact, powered from +C (24 V DC) output, pin 4 Logic 0... 0-5 V DC input current at 0V... 0 ma input resistance... 8 kohm Logic 1... 12-24 V DC input current at 24 V DC... 3 ma Frequency range... Normally 2 Hz. Max 50 Hz requires Task with cycle time 1 te Shortest pulse length for detection (transient flag)... 8 ms Digital Outputs, DO Type... MOSFET Output...24 V AC or DC Max continuous load... 2 A The sum of current through all DO... 8 A Update cycle... 50 ms 6 EXOcompact Third Generation

Chapter 3 Installation General Connections With AC Supply and Mixed Loads on DO The general connections of EXOcompact with AC supply are illustrated in Figure 1 and Figure 2 below. Communication line Port 2 Inductive transducer PNP-type 230VAC G (24VAC) G0 (OV) Communication line Port 1 +C G0 + - Out (Damper) Actuator N L SM230A-SR Y (Valve) Actuator (-) (+) RVAx-24A Y U Contact Meter 50 51 52 53 B A N E Port 1 RS485 60 61 62 63 B A N E Port 2 RS485 conn. 4P4C Ext.disp. 71 72 73 74 75 76 77 78 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI1-8 90 91 92 93 94 95 Agnd AO1 AO2 AO3 AO4 A05 AO1-5 Position indication 2-10V UI1-4 24V AC/DC + _ G G0 +C DO1-7 G DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 AI1-4 Agnd AI1 AI2 Agnd AI3 AI4 Agnd :AI5/DI9 :AI6/DI10 UI1 UI2 Agnd :AI7/DI11 :AI8/DI12 UI3 UI4 TCP/IP RJ45 1 2 3 4 10 11 12 13 14 15 16 17 30 31 32 33 34 35 40 41 42 43 44 45 24VAC 3-point actuator 24VAC Relay 24VAC Relay 24VDC + +C Shunt Contact 0V +24V 24VDC Power supply N L _ + HRTN- 420 2 1 230VAC 230VAC Temp sensors Pt1000 Humidity transmitter 4-20 ma Figure 1 General connections for EXOcompact third generation without built-in M- bus EXOcompact Third Generation 7

Figure 2 General connections for EXOcompact third generation with built-in M-bus With DC Supply and Mixed Loads on DO The general connections of EXOcompact with DC supply are illustrated in Figure 3. For the rest of the connections, see Figure 1 and Figure 2. Figure 3 Connection with DC supply 8 EXOcompact Third Generation

I/O Description AC Power Supply The 24 V AC supply, typically a 230V/24V transformer, is connected to contacts G0 (2) signal ground and G (1), phase. The EMI earth ( ) must be connected to the earth rail or similar to protect against disturbances. Each process connection has active transient protection, which is led to the EMI earth ( ). The +C output is used to power supply auxiliary equipment requiring 24 V DC power. DC Power Supply The 24 V DC supply, typically a stabilised power supply, is connected to the contacts - (2) and + (1). The EMI earth ( ) must be connected to the earth rail or similar to protect against disturbances. Each process connection has active transient protection, which is led to the EMI earth ( ). AI Process Connections The connection of four passive sensors like PT1000 and an active 2-wire transmitter is shown in the figure at the beginning of this chapter. Note that low level sensors are returned to the Agnd, high quality ground. This type of input is mainly intended for use with sensors using voltage outputs and resistance elements for measuring temperature. Voltage signals must be connected between the input and Agnd. A shielded cable is recommended. The cable screen should be connected to the ground bar. External transmitters for 4-20 ma can be powered from the +C output. A fast fuse should be fitted in serial with the transmitter to protect the input from short circuits in the transmitter. All Agnds are internally connected to each other and to G0. To attain maximum accuracy according to specifications, each respective Agnd should be used as a reference for the measuring. AO Process Connections The AO terminals supply 0-10 V with reference to the Agnd terminal (= Internal Signal Ground). The outputs are internally powered. Figure 1 shows the connection of a 24 V AC powered control valve actuator, which is referenced to G0, a 230 V AC powered damper actuator and an example with a simple voltmeter, both referenced to Agnd. This type of output is mainly intended for use with damper motors, shunt valves, frequency inverters and other analog actuators for 0 10 V. Each output is current limited and short circuit proof. Normal, high-ohm loads are connected between the output and Agnd. Other types of loads for special applications with low-ohm loads are best connected between the output and G0. See the example with the Actuator that is connected to G0. All Agnds are internally connected to each other and to the G0 terminal. EXOcompact Third Generation 9

DO Process Connections The example shows actuators, AC relays and similar connected to GDO in one end. An active DO connects the other end of the load to G0 (-). Standard 24 V DC DI Floating (potential free) contacts and two wire pressure switches, proximity switches and similar are powered from the +C (4) terminal which supplies +24 V DC. This type of input is used for reading floating (potential free) contacts. They are active high. One end of the external contact is connected to the input and the other to +C. The +C output is current limited and short circuit proof. The connection of an inductive pressure transducer is shown in the figure at the beginning of this chapter. 10 EXOcompact Third Generation

Using the unisolated port Figure 4 Example when using the unisolated port EXOcompact models with two serial ports, have an unisolated RS485 communication port (Port #2). Except for the isolation all other characteristics are compatible with EXOline and the two types could be mixed in a network without any problem. If you connect two controllers (master slave) with un-isolated communication ports, please observe the following demands: When using the same power supply for two controllers connected with un-isolated communication ports, you must connect G0 to G0 and G to G. They must not be crossconnected! See an example with EXOcompact Dual Port and Regio Midi in the above figure. The longest communication cable length is 300 m between un-isolated master/slave ports. The communication cable must be well separated from power cables and other possible sources of interference (EMI). A maximum of 32 controllers is allowed on the same communication line without a repeater. A repeater with isolated power supply (e.g. Repeat485 from Regin) is recommended to prolong the communication distance and number of controllers. EXOcompact Third Generation 11

Chapter 4 Maintenance and Service Changing the Battery When the battery indicator is lit, the battery for backup of program memory and the real-time clock has become too weak. The battery is replaced as described below. A backup capacitor saves the memory and keeps the clock running for at least 10 minutes after the power supply is removed. Thus, if battery replacement takes less than 10 minutes, there will be no need to reload the program and the clock will continue to run normally. The replacement battery must be according to the Technical Specifications above. This procedure requires knowledge of proper ESD protection; i.e. an earthed wristband or similar protection must be used! Figure 5 Battery location Grip the battery firmly with your fingers and lift it upwards until it rises from its holder. Press the new battery firmly down into place. Note that to preserve correct polarity, the battery must be inserted the right way round. If the battery is placed the wrong way round, the P/B led will change to red to indicate a battery error when the controller is connected to the power supply. 12 EXOcompact Third Generation

Resetting the Application Memory This procedure should only be carried out by qualified resellers since the current application will stop running and the controller will return to its factory application. To reset the processor s program memory (application programs) the controller has to be connected to the power supply. Use the reset button accessed through the small hole on the right side of the unit. A tip is to use a paper-clip to access the reset button. If the controller is not possible to reset in this way for some reason it should be powered down. Then keep the reset button pressed in while reconnecting the power. Figure 6 Resetting the application memory For EXOcompact third generation the controller has to be connected to the power supply during resetting. Updating the operating system The EXOreal operating system can be updated from any RS485 EXOline Slave port, or TCP/IP with EXOdesigner. EXOcompact Third Generation 13