E2 Modbus RTU Register Map

Similar documents
E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

Optidrive VTC Modbus RTU Register Map

Optidrive Applications Support Library

3GV M Modbus RTU Register Map

Optidrive Applications Support Library

lnvertek Drives.com ct,ve ELECTRICAL SUPPLIERS LTD

1. PRODUCT OVERVIEW GENERAL INFORMATION STANDARDS & EMC ELECTRICAL RATINGS MECHANICAL INSTALLATION...

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10

Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM) radio-frequency equipment (EMC)

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

Optidrive Plus 3 GV. Advanced User Guide. Vertical Market Solution : Industrial Washing Machines. Revision 1.00

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Issue 06

Installation and Operating Instructions

OPTIDRIVE PLUS 3 GV 3 rd Generation Vector Control AC Variable Speed Drive kW

Tongta Inverter TDS-F8

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

Modbus Protocol. for VASCO, VASCO Solar and MIDA devices. manmodbus_eng_00

1. Introduction About the Vacon 5X drive Identifying the drive by model number Drive model numbers...7

QUICK REFERENCE GUIDE

OptiDrive Advanced Technical Manual

Firmware Manual - EC Series Drives

The RS-485 user manual for B800 series communication

SMD SERIES INVERTER MODBUS CONTROL OPERATION MANUAL. Document: SLmod-e2

MCW Application Notes 24 th February 2017

vacon nx ac drives brake chopper unit (bcu) application user s manual

Powered to Perform. Everyday Reliability. Exceptional Value. Expertise and Support

Compact 2. User Guide (Preliminary) Installation and Operating Instructions. AC Variable Speed Drive kW (1.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

User manual. MODBUS-RTU SV-iC5

Power Xpert C445 Motor Management Relay Cheat Sheets

Section 16. Drives AF-650GP General Purpose Drive. Standard Specifications. Environmental Conditions. Logic Controller (LC) Sequencer

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Quick Start Guide Cutler-Hammer SVX9000 Drives from Eaton Corporation CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and

vacon se2 user's manual

Installation and Commissioning Instructions AC drive VersiDrive i... /E

QD:CT Plus & QD:VT Installation and Operating Instructions

Instructions. Modbus RTU Card (WSIQ-COM-MB)

User Guide. IP20 & IP66 (NEMA 4X) AC Variable Speed Drive kW V

PowerXL DG1 Firmware Release Note

STOCK DRIVES CATALOGUE

N700E Inverter RS485 Interface Instruction Manual

Quick Start Guide For GVX9000 AF Drives

Before using the product, thank you for using our Ethernet module board. Safety Instruction

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

AirCare General Purpose ModBus Interface ACM1001. OptiDrive Modbus Module Product Specification. For assistance call

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

SCF Series Drives Modbus Communications Reference Guide

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

GPD 506 / Modbus RTU Technical Manual

Step 1: Choose the Appropriate CPU Step 2: Make the Connections

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Basic Drive Programming PowerFlex 755 Basic Start Up

EXD-TEVI Economizer Controller for Tandem Compressors

SC2004MBS 20x4 Characters MODBUS RTU Slave LCD

smd Series Drives Modbus Communications Reference Guide

Softstarters. Type PSTX Fieldbus communication, Anybus Modbus TCP. 1SFC132087M0201 March SFC132087M0201 1

1.1.1 Software Version Introduction About this Manual References 2

A66N2 Installation and Programming Manual

Modbus Protocol For FTS/FTM 3x&8x

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

1. Safety Danger Warnings Earthing and earth fault protection... 4

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

1. Introduction. 2. Installation MODBUS INTERFACE

DC1 Series 1 Hour Product Overview Eaton Corporation. All rights reserved.

Contents. Index 35. VLT HVAC Drive Metasys N2

The benefits are ease of set-up, more data available for the user from the drive, fast control, and state of the art technology.

RS485 MODBUS Module 8AO

PowerFlex 40 Sample Specification

FnIO S-Series. FnIO MODBUS Adapter Specification Rev 1.00 NA-9473 (MODBUS/RS485) Page 1 of 30. NA-9473 (MODBUS/RS485) Adapter

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU

A66SM Installation and Programming Manual

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

Easy To Use OEMS Take Note

RS485 MODBUS Module 16I-M

Motors I Automation I Energy I Transmission & Distribution I Coatings N2 CFW501. User s Manual

User Guide. IP20 & IP66 (NEMA 4X) AC Variable Speed Drive. Installation and Operating Instructions. 1 Quick Start Up kW (0.

MCH Series Drives Modbus Communications Reference Guide

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

CATALOG SELECTION / PRODUCT SELECTION

GV3000/SE AC Drive Quick Reference Version 6.06

Status line The top line of the LCD display shows the basic status information of the drive.

Chapter. Modbus. In This Chapter...

Profinet Module. User Manual. Contents

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU. 1SFC132092M0201 June SFC132092M0201 1

SENSORLESS VECTOR CONTROL

User Manual. PROFIBUS-DP Option Board for SV-iS5 Series. LG Industrial Systems

SOFTWARE FUNCTIONAL REQUIREMENTS SPECIFICATION. Athena DeviceNet Interface Module Revision /26/2001

RS485 MODBUS Module 8I8O

MODBUS Protocol. The ecode Encoders contain both single register (16 bit) and double register (32 bit) values.

ModBus Communication protocol. The ModBus protocol is an industrial communications and distributed control system

OPTIDRIVE. look no wires... just total control

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

MC Series Drives Modbus Communications Reference Guide

TR600 with RS485 Appendix 1

AF-600 FP AC Drive AC Adjustable Frequency Drive Guide-Form Specification

ASTAT XB/XBm Remote Operator

DC BRUSHLESS MOTOR CONTROLLER BLSD-20/BLSD-50

Transcription:

Application Note AN ODE 01 E2 Modbus RTU Register Map Author: Peter Evans, Invertek Drives Ltd Revision: 1.02 11 June 2008 Software Version: 1.02 General This document details the Modbus RTU memory mapping that is implemented in the Optidrive E2 drives, detailing which addresses are used to read and write data to / from Optidrive E2 in a Modbus RTU network. Note that for E2 drive, once the Modbus control/monitor is enabled (P-36>0), the Optibus network function will be disabled, therefore disabling the Optiport E2 remote keypad and Optistick. : For control & monitoring of the drives the following parameters should be set correctly: P-12 : (set to 3 for Modbus without ramp control or 4 for Modbus with ramp control ) P-36 : (communication address, baud rate and comms loss trip time) P-15 (Analog and Digital input configuration) For monitoring of the drives the following parameters should be set correctly: P-36 : (communication address, baud rate and comms loss trip time) P-15 (Analog and Digital input configuration) Please see User Guide for more information on these parameter settings The Fieldbus Gateways (Profibus, DeviceNet & Ethernet) also use the Modbus interface. In this case, the baud rate must be set to 57.6kbps. For more information regarding the fieldbus gateway, please contact your local distributor, or visit our web site: www.invertek.co.uk Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date information, the information contained in this document should be used for guidance purposes only and does not form the part of any contract. AN-ODE-01 Page 1 of 11 12/06/2008

MODBUS RTU Protocol Specification The following table highlights the specification for the Modbus RTU implementation in E2 Protocol Error check Baud rate (P-36) Data format Physical signal Modbus RTU CRC 9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 1 start bit, 8 data bits, 1 stop bits, no parity. RS 485 (2-wire) RJ45 Data Connection Pin Configuration For drives with software V1.00 & V1.01 For drives with software V1.02 & later Typical MODBUS configuration AN-ODE-01 Page 2 of 11 12/06/2008

Memory Map Table 1: Control and status registers Register Upper byte Lower Byte Command Type 1* Command 03,06 Read/Write 2* Speed reference 03,06 Read/Write 3* Reserved 03,06 Read/Write 4* Modbus ramp control time 03,06 Read/Write 5 Reserved 03 Read Only 6* Error code Drive status 03 Read Only 7* Motor speed 03 Read Only 8* Motor current 03 Read Only 9* Reserved 03 Read Only 10 Reserved 03 Read Only 11 Digital input status 03 Read Only 12 Rating ID 03 Read Only 13 Power rating 03 Read Only 14 Voltage rating 03 Read Only 15 IO processor software version 03 Read Only 16 Motor control processor software version 03 Read Only 17 Drive type 03 Read Only 18 Reserved 03 Read Only 19 Reserved 03 Read Only 20 Analog 1 input result 03 Read Only 21 Analog 2 input result 03 Read Only 22 Speed reference value 03 Read Only 23 DC bus voltages 03 Read Only 24 Drive temperature 03 Read Only 25 to 30 Reserved 03 Read Only * When using the external fieldbus gateways (PROFIBUS, DEVICENET, ETHERNET) these registers are available. AN-ODE-01 Page 3 of 11 12/06/2008

Control and Status Register Descriptions Read and write registers Register 1: Drive command 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 High byte Low byte Bit 0: Bit 1: Bit 2: Bit 3: Run/Stop command: Set to 1 to enable the drive. Set to 0 to stop the drive. Fast stop request. Set to 1 to enable drive to stop with 2 nd deceleration ramp. Reset request. Set to 1 in order to reset the drive if drive is under trip condition. User must clear this bit when drive is under normal condition to prevent un-expected reset. Coast stop request. Set to 1 to issue a coast stop command. For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0). For example if user set command as 0x0009, drive will do a coast stop rather than run. For normal run/start, just set this register to 1. Note that stat/stop(bit 0), fast stop(bit 1) and coast stop(bit 3) only works if P-31= 0 or 1. Otherwise, start/stop function is controlled by drive control terminals. Reset function(bit 2) works all the time as long as drive is operated under Modbus control mode (P-12=3 or 4). Register 2: speed reference setup This register holds the speed reference value. The input data is 16bits integer and it also includes one decimal place. For example, value 500 represents the 50.0Hz, value 123 gives 12.3Hz. To get negative speed reference, user needs put negative value into this register. For example, -1(0xFFFF) gives -0.1Hz. -234(0xFF16) gives -23.4Hz. The input value range from -5000 (0 for single phase output drive) to +5000, however the drive output speed will be limited by the maximum speed set by P-01. Register 4: Modbus ramp control time This register specifies the drive acceleration and deceleration ramp time. User can only write to this register when P-12 is set to 4. The input data range is from 0 to 60000 (0.00s to 600.00s) Read only registers Register 6: Drive status and error code High byte gives drive error code. (Valid when drive tripped, see appendix for details) Low byte gives drive status (0: drive stopped, 1: drive running, 2: drive tipped) Register 7: Motor speed information This register gives motor speed information. The data is 16bits integer with one decimal place. E.g. value 123 gives 12.3Hz. Value -234 (0xFF16) gives -23.4Hz. Register 8: Motor current This register gives motor current information. The data is 16bits integer with one decimal place. E.g. 156 = 15.6A, 12 = 1.2A. Register 11: Digital input status AN-ODE-01 Page 4 of 11 12/06/2008

The value in this register represents the drive terminal digital input status (Digital input 1 to 4). Lowest bit indicates digital input 1 status. Register 12: Rating ID The value in this parameter includes specific drive ID information, and is not recommended to be used by customer. For more information regarding this parameter, please contact Invertek Drives Ltd directly. Register 13: Power rating This gives the drive power rating information, value includes two decimal places. The unit of this register depends on the drive type (KW/HP) Register 14: Voltage level This register gives the rated input voltage for the drive. i.e. 230 : 230V 400: 400V 460: 460V Register 15: IO software version This register contains the drive IO software version info. Value includes two decimal places. i.e. 100 means version 1.00 Register 16: Motor control processor software version This register contains the software version info of the motor control processor. Value includes two decimal places. E.g. 100 means version 1.00 Register 17: Drive type This register gives drive internal type code. Register 20: Analog input 1 value This register gives drive analog input 1 value after scaling and offset control. Value 4096 = 100%. Register 21: Analog input 2 value This register gives drive analog input 2 value after scaling and offset control. Value 4096 = 100%. Register 22: Speed reference value This register contains the reference speed information that being used by the drive for motor speed control. The data is in Hz and with one decimal place ( i.e. 234 = 23.4Hz) Register 23: DC bus voltage This register contains drive internal DC bus voltage information. Data unit is Volt. Register 23: Drive temperature This register contains drive temperature information. Data is in Celsius with no decimal place. AN-ODE-01 Page 5 of 11 12/06/2008

Table 2: Parameter registers (Support command 03 and 06) Adr Par Description Data range Data format 129 01 Max speed limit 0 to 50 * P-09 Internal value (3000 = 50.0Hz) 130 02 Min speed limit 0 to P-01 Internal value (3000 = 50.0Hz) 131 03 Accel ramp time 0 to 60000 One decimal place 300=3.00s 132 04 Decel ramp time 0 to 60000 One decimal place 300=3.00s 133 05 Stop mode select 0 to 2 0: Ramp to stop 1: Coast to stop 2: Ramp to stop 134 06 Energy save 0,1 0: Disable 1: Enable 135 07 Motor rated voltage 0, 20 to 250 V 0, 20 to 500 V 136 08 Motor rated current Drive dependent One decimal place 300=30.0A 137 09 Motor rated frequency 25 to 500 Data unit is in Hz 138 10 Motor rated speed 0 to Sync speed 139 11 Boost voltage value 140 12 Control mode 0 to 6 141 13 Trip log Size 1-0 to 200 Size 2-0 to 150 Size 3-0 to 100 142 14 Access code 0 to 9999 Maximum value equals to the sync speed of a typical 2-pole motor 100 = 10.0% 0: Terminal 1: Keypad forward only 2: Keypad forward and reverse 3: Modbus control mode 4: Modbus control with ramp control 5 : PID control 6 : PID control with analog speed sum Last four trips (See Appendix for details ) 143 15 Digital input function 0 to 12 See user guide for function details 0: 0 10V 1: b 0 10V 144 16 Analog input format 0 to 6 6: r 20 4mA 2: 0 20mA 3: t 4 20mA 4: r 4 20mA 5: t 20 4mA 145 17 Effective switching frequency 0 to 5 and it is 0 = 4KHz, 1 = 8KHz, 2 = 12Khz drive dependent 3 =16KHz, 4 = 24KHz, 5 = 32KHz 146 18 Relay output function 0 to 7 See user guide for function details 147 19 Digital output limit 0 1000 100 = 10.0% 148 20 Preset speed 1 -P-01 to P-01 Internal value (3000 = 50.0Hz) 149 21 Preset speed 2 -P-01 to P-01 Internal value (3000 = 50.0Hz) 150 22 Preset speed 3 -P-01 to P-01 Internal value (3000 = 50.0Hz) 151 23 Preset speed 4 -P-01 to P-01 Internal value (3000 = 50.0Hz) 152 24 2 nd deceleration ramp 0 to 2500 250 = 25.0s 153 25 Analog output function 0 to 9 See user guide for function details 154 26 Skip frequency 0 to P-01 Internal value (3000 = 50.0Hz) 155 27 Skip freq band 0 to P-01 Internal value (3000 = 50.0Hz) 156 28 V/F adjust voltage 0 to P-07 100 = 100V 157 29 V/F adjust frequency 0 to P-09 50 = 50Hz 158 30 Start mode select 0 to 6 0: Edgr-r 1: Auto_0 2 6: Auto_1 to Auto_5 AN-ODE-01 Page 6 of 11 12/06/2008

Adr Par Description Data range Data format 159 31 Keypad restart mode 0 to 3 See user guide for details 160 32 DC injection enable 0 to 250 250= 25.0s 161 33 Spin start enable 0 or 1 162 34 Brake circuit enable 0 to 2 See user guide for function details 163 35 Analog input scaling 0 to 5000 100 = 10% Drive address (Low byte) 0 to 63 Drive comms address 164 36 Baudrate select 1 to 6 1 = Optibus fixed baudrate 2 = 9K6 3 = 19K2 4 = 38K4 5 = 57K6 6 = 115K2 Trip time setup 0 to 8 See user guide for more information 165 37 Access code definition 0 to 9999 166 38 Parameter lock 0 or 1 0: Unlock 1: Locked 167 39 Analog input offset -5000 to 5000 One decimal place 300=30.0% 168 40 Display scaling factor 0 to 6000 100 = 0.100 169 41 User PI P gain 1 to 300 10 = 1.0 170 42 User PI I time constant 0 to 300 10 = 1.0s 171 43 User PI mode select 0 or 1 See user guide for more information 172 44 User PI reference select 0 or 1 See user guide for more information 173 45 User PI digital reference 0 to 1000 100 =10.0% 174 46 User PI feedback select 0 to 3 See user guide for more information 0: 0...10V 1: 0 20mA 175 47 2 nd an input format 0 to 5 2: t 4...20mA 3: r 4...20mA 4: t 20...4mA 5: r 20...4mA AN-ODE-01 Page 7 of 11 12/06/2008

Appendix Drive error code information in Register 6: Drive Error Code 0x00 Drive Display Fault Code stop Description Drive healthy no fault present When the drive is disabled the display will STOP. The display will change if drive is running. 0x01 OI-b Brake channel over current 0x02 OL-br Brake resistor overload Over current on drive output. O-I 0x03 Excess load on the motor. Over temperature on the drive heatsink 0x04 I. t-trp Drive has tripped on overload after delivering >100% of value in P-08 for a period of time. 0x05 PS-Trp Internal power stage fault 0x06 O.Uo1t Over voltage on DC bus 0x07 U.Uo1t Under voltage on DC bus 0x08 O-t Heatsink over temperature 0x09 U-t Under temperature 0x0A P-def Factory Default parameters have been loaded 0X0B E-triP External trip (on digital Input 3) 0X0C SC-trP Serial communications loss trip 0X0D RESERVED 0X0E P-LOSS Input phase loss trip 0X0F SPIN-F Spin start failed 0x10 th-flt Faulty thermistor on heatsink. 0X11 data-f Internal memory fault. 0X12 4-20 F Analog input current out of range (4-20mA) AN-ODE-01 Page 8 of 11 12/06/2008

Dataflow example: 1) Read data from register 6: Request: [01] [03] [00] [05] [00] [01] [94] [0B] (Drive Addr) (Command) (Reg start addr) (No. of Registers) (Checksum) Reply: [01] [03] [02] [00] [00] [B8] [44] (Drive Addr) (Command) (No of data bytes) (Data) (Checksum) Note: The actual start address of register 6 is 5. All data in [ ] is in 8bits Hex format. 2) Write start command to the register 1 (suppose P-12 = 3, P-15 =0 and digital input 1 is closed): Request: [01] [06] [00] [00] [00] [01] [48] [0A] (Drive Addr) (Command) (Reg addr) (Data value) (Checksum) Reply: [01] [06] [00] [00] [00] [01] [48] [0A] (Drive Addr) (Command) (Reg addr) (Data value) (Checksum) Note: The actual address of register 1 on the data link is 0. All data in [ ] is in 8bits Hex format. Reply can be error message depending on drive parameter settings and digital input status. AN-ODE-01 Page 9 of 11 12/06/2008

Analog and Digital Input Configurations when in MODBUS control mode (P12 = 3 or 4) By changing the value in P-15 adjusts the functionality of the control terminals as below: P-15 Digital input 1 (T2) Digital input 2 (T3) Digital input 3 (T4) Analog input (T6) Comments 0..2, 4..5, 8..12 Open: Stop (disable) Closed: Run (enable) 1) Open: Stop (disable) 3 Closed: Run (enable) 1) Open: Stop (disable) 6 Closed: Run (enable) 1) Open: Stop (disable) 7 Closed: Run (enable) Example Wiring Run and stop commands given via the RS485 link and Digital input 1 must be closed for the drive to run. Connect external External trip input : Open: Trip, Closed: Run No effect thermistor type PT100 or similar to digital input 3 No effect No effect No effect Open : Master speed ref Closed : Preset speed 1 Open : Master speed ref Closed : Analog input Open : Master speed ref Closed : keypad speed ref External trip input : Open: Trip, Closed: Run External trip input : Open: Trip, Closed: Run Analog input reference No effect Master Speed Ref - start and stop controlled via RS485. Keypad Speed Ref - drive auto runs if digital input 1 closed, depending on P-31 setting AUTO MODBUS Speed HAND Preset Speed 1 AUTO MODBUS Speed HAND Analog Speed ref (potentiometer) AUTO MODBUS Speed HAND Keypad Speed ref (UP & DOWN keys on drive) AN-ODE-01 Page 10 of 11 12/06/2008

Register Changes for E2 Single Phase Output Drives The Optidrive E2 Single Phase Output drive has some registers that are different to the stand Optidrive E2, for this reason the Registers/Parameters are listed below: Adr Par Description Data range Data format 134 06 Reserved 148 20 Preset speed 1 0 to P-01 Internal value (3000 = 50.0Hz) 149 21 Preset speed 2 0 to P-01 Internal value (3000 = 50.0Hz) 150 22 Preset speed 3 0 to P-01 Internal value (3000 = 50.0Hz) 151 23 Preset speed 4 0 to P-01 Internal value (3000 = 50.0Hz) 160 32 Boost Frequency 0 to P09 50 = 50Hz 161 33 Boost Period Duration 0 to 150s 100 = 10.0 seconds --- End --- AN-ODE-01 Page 11 of 11 12/06/2008