MULTIFUNCTION MICROPROCESSOR PROTECTION RELAY TYPE IM30-G DATA BASE

Similar documents
IM30-GOS. MULTIFUNCTION MICROPROCESSOR RELAY for PROTECTION TYPE IM30-GOS OPERATION MANUAL PROG/ I.R.F. INHIBIT BR. MODE SELECT + PROG.

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

FP5000. Refer to for the latest information on this constantly evolving product

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution

FP6000. Type ID Units Writable Possible Values. Count. TCP Register

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics

MiCOM P111. Three phase and earth fault overcurrent relays

CURRENT PROTECTION RELAY SMPR-1

MiCOM P122C Time-Overcurrent Protection

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

Protection relays.

System Protection and Control Subcommittee

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

INSTALLATION & COMMISIONING GUIDE

DEH-433. Warnings, Cautions, and Notes as used in this publication

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

CAN-Transceiver Data Register Map MODBUS Slave RTU

TECHNICAL NOTES By6150-S-485 MODBUS J BUS Communication

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

(1) Description of Operation 7SR224 Recloser Controller

750/760 Feeder Management Relay Instruction Manual

Reyrolle Protection Devices. 7SR210 & 7SR220 Argus Overcurrent Protection Relay. Answers for energy

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

Multifuncion Measuring Device 96x96 mm, connection via CT

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

GE Entellisys Low Voltage Switchgear. System Test Kit. User Manual

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

DNP Points List and Implementation

NPW800R RETROFITTING. Power and Volatge Protection Relay

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

SUMMARIZE MEASUREMENT AND PROTECTION RELAY SMPR-1

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

DNP3 Communications Protocol

7SR11 & 7SR12 Argus Overcurrent Relay Energy Management

SPM33. MODBUS Protocol and register List V1.5

7SR242 Duobias Transformer Protection Relay Answers for energy.

7SR191 Capa Capacitor Protection Relay Energy Management

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

User Manual. AQ-F215 Simulator

7SR11 and 7SR12 Description of Operation

ADDITIONAL INFORMATION MODBUS INSTRUCTION MANUAL. Request publication Request publication DNP 3.0 INSTRUCTION MANUAL

GE Power Management. MMII Intelligent MCC Controller

PSL Power Standards Lab 2020 Challenger Drive Alameda, CA USA TEL FAX

Reyrolle Protection Devices. 7SR242 Duobias Transformer Protection Relay. Energy Management. Unrestricted

DNP Points List and Implementation for Universal Controls

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

Modbus Protocol. for VASCO, VASCO Solar and MIDA devices. manmodbus_eng_00

Request publication Request publication DNP 3.0 INSTRUCTION MANUAL. Request publication

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

JKSSS COMMUNICATION HARDWARE LINK & SOFTWARE PROTOCOL (VER. C)

S o m e t h i n g b e t t e r t h a n p r o t e c t i v e r e l a y s. automation, control & communication

URC Utility Relay Company

Type SDR reclosers plus controllers and type B-2 recloser bypass switch assembly usa.siemens.com/mediumvoltage

7SR105 Rho User Manual Motor Protection Relay Energy Management

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

TNY Series-Multifunction Panel Meter

Power Xpert C445 Motor Management Relay Cheat Sheets

FP-5000 Feeder Protection

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

FPU-16 A-B PROTOCOL/DATA LOGGER MANUAL

MRA4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MRA4PDE

DNP Points List and Implementation

DIGITAL TEMPERATURE MONITOR MASTERTEMP ANSI I CATALOG

F650 Firmware Release Notes / History (Rev 10)

Protection Relays PHASE & RESIDUAL OVERCURRENT

UR Universal Relay Series

MPU-32 ETHERNET/IP INTERFACE

MiCOM P111 Numerical three phase and earth fault overcurrent relay description

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

7SR11 and 7SR12 Argus Overcurrent Relays Answers for infrastructure & cities.

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

Reyrolle Protection Devices. 7SR11 and 7SR12 Argus Overcurrent Relays. Answers for energy

Siprotec 7ST61 / 7ST63

MODBUS Protocol for MiCOM P30 Series

SINGLE-CHANNEL PROCESS INDICATOR series 8001

MIC-2 MKII, Multi-instrument DATA SHEET

OVERCURRENT / GROUND FAULT PROTECTION RELAY MPRB GF. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

InteliPro. Protection Relay for Parallel Applications. Technical Specification

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Softstarters. Type PST/PSTB Fieldbus communication Profibus DP V0 / V1. 1SFC132013M0201 January SFC132013M0201 1

Memshield Overcurrent Protection Relay (AOR1B)

www. ElectricalPartManuals. com MICROSHIELD O/Cä Multiphase Time-Overcurrent Relay Highlights

MICROSHIELD O/Cä Multiphase Time-Overcurrent Relay

750/760 Feeder Management Relay

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

ABB Inc. Instructions REF 550 Advanced Feeder Protection System

Power 004=0.4kW 015=1.5kW. Delta Variable Frequency Drive

Reyrolle Protection Devices. 7SG13 Delta Protection and Control Relays. Answers for energy

MCA4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MCA4PDE

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

MRI1-IU - Voltage controlled time overcurrent relay

Generator Management Relay COMMUNICATIONS GUIDE

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Transcription:

Pag. 1 of 6 MULTIFUNCTION MICROPROCESSOR PROTECTION RELAY TYPE DATA BASE

Pag. 2 of 6 1 - Supported MODBUS functions. Both the communication ports support the following MODBUS RTU commands: - Read N words (codes 3 and 4). - Write N words (code 16). 2 ACTUAL MEASUREMENTS 1 IA True R.M.S. value of the current of phase A displayed as primary Amps. Unit = A 2 IB As above, phase B Unit = A 3 IC As above, phase C. Unit = A 4 Io As above, earth fault current Unit = A 5 Us R.M.S. voltage as % of rated VTs secondary Unit = % 7 ϕ Symmetric phase displacement (IΛE). Unit = 360 = overflow 14 I2 R.M.S. Negative sequence current as % of basic setting Ib Unit = %Ib 3 MAX VALUES 1000 Max. value of phase A current after the first 100ms, displayed as p.u. of C.Ts rated Unit = 0.1 In IA current 1001 IB As above, phase B Unit = 0.1 In 1002 IC As above, phase C. Unit = 0.1 In 1003 Io As above, earth fault current Unit = 0.01 On 1004 Us Max. val. of input voltage after the first 100ms, as % of rated input Unit = % 1008 I2 As above, negative sequence current Unit = % Ib 1009 SA Max. current of phase A during the first 100ms. Unit = 0.1 In 1010 SB As above, phase B. Unit = 0.1 In 1011 SC As above, phase C. Unit = 0.1 In 1012 So As above, earth fault current. Unit = 0.01 On 1076 SU Max. input voltage during the first 100ms Unit = %

Pag. 3 of 6 4 LAST TRIP 2000 Cause Function which caused the last trip (Last Trip - 0) 1 2001 Ia Phase A current (as p.u. of C.T.'s rated current) (Last Trip - 0) Unit = 0.1 In 2002 Ib Phase B current (as p.u. of C.T.'s rated current) (Last Trip - 0) Unit = 0.1 In 2003 Ic Phase C current (as p.u. of C.T.'s rated current) (Last Trip - 0) Unit = 0.1 In 2004 Io Earth fault current (Last Trip - 0) Unit = 0.01 On 2005 Us Input voltage (Last Trip - 0) Unit = % 2013 I2 Negative sequence component ( as % of full load current) (Last Trip - 0) Unit = % Ib 5 COUNTERS 3000 I> Low set time delayed overcurrent - 3001 I>> High set time delayed overcurrent - 3002 Io> Low set time delayed earth fault - 3026 1Is Low set unbalance time delayed element - 3027 2Is High set unbalance time delayed element - 3041 Ir> Reverse power delayed element - 3042 Z< Under impedance delayed element - 6 SETTINGS All the following words can always be read. To write them the user must first write a password (2295) into word 8001. Such password is valid for 30 sec. 5000 NodeAddress MOBDUS node address. Min = 1 This is the relay s address for MODBUS communication. It Max = 250 is taken into account ONLY AT POWER UP 5001 FN System rated frequency 0 => 50Hz 1 => 60Hz 5002 In Rated primary current of the phasec.t.'s Unit = 1 Min = 1, Max = 9999 5003 On Rated primary current of the tore C.T. Unit = 1 Min = 1, Max = 9999 5005 Uns Rated secondary phase to phase voltage of system's P.Ts. Unit = 1 Min = 100, Max = 125 5006 Ib Generator s rated current as p.u. of Cts rated current Unit = 0.1 In Min = 5, Max = 110 5008 F(I>) Operation characteristic of the low set overcurrent element 0 => D 1 => SI 5009 I> Trip level of low-set overcurrent element Unit = 0.01 Ib Min = 100, Max = 250 251 => Disable 5010 ti> Trip time delay of low-set overcurrent element Unit = 0.01 sec Min = 5, Max = 3000

Pag. 4 of 6 5011 I>> Trip level of high-set overcurrent element Unit = 0.1 Ib Min = 10, Max = 120 130 = Disable 5012 ti>> Trip time delay of high-set overcurrent element Unit = 0.01 sec Min = 5, Max = 300 5015 O> Trip level of low-set earth fault element Unit = 0.01 On Min = 2, Max = 40 41 => Disable 5016 to> Trip time delay of low-set earth fault element Unit = 0.01 sec Min = 5, Max = 3000 5020 tbf Max reset time delay of the instantaneous element Unit = 0.01 sec Min = 5, Max = 50 5035 1Is Trip level of unbalance 1 element Unit = 0.01 Ib Min = 5, Max = 50 51 => Disable 5037 2Is Negative sequence current alarm level Unit = 0.01 Ib Min = 3, Max = 100 101 => Disable 5038 t2is Independent trip time delay of alarm element Unit = 1 sec Min = 1, Max = 100 5039 Ks Time multiplier of the I 2 t time-current curve Unit = 1 sec Min = 5, Max = 80 5040 tc Cooling time from trip level to cold state Unit = 1 sec Min = 10, Max = 1800 5098 α Impedance characteristic angle 0 => 0 R, 1 => 330 R+C, 2 => 300 R+C, 3 => 270 C, 4 => 240 C-R, 5 => 210 C-R, 6 => 180 -R, 7 => 150 L-R, 8 => 120 L-R, 9 => 90 L, 10 => 60 L+R, 11 => 30 L+R 5099 tz Trip time delay of the under impedance element Unit = 0.1 sec Min = 2, Max = 600 5100 ti Integration time Unit = 0.1 sec Min = 0, Max = 100 5101 K1 Diameter of the circle Unit = 1 % Min = 50, Max = 300 5102 K2 Offset of the circle including the under impedance tripping zone Unit = 1 % Min = 5, Max = 50 5103 Ir> Trip level of the reverse power element Unit = 0.01 In Min = 2, Max = 20 5104 tir> Independent trip time delay of reverse power element Unit = 0.01 sec Min = 10, Max = 6000

Pag. 5 of 6 7 OUTPUT RELAYS 5021 t2= The operation of the blocking input (2) can be programmed so that it lasts as long the blocking input signal is present (t 2=OFF) or so that, even with the blocking 0 => OFF 1 => 2tBF input still present, it only lasts for the set trip time delay of the function plus an additional time 2xtBF (t 2=2xtBF). 5023 2= The input (2) for blocking the time delayed elements relevant to phase and ground faults operate on I>(Il) or I>>(Ih) or O>(Io) as programmed 0 => Il, 1 => Ih, 2 => IlIh, 3 => Io, 4 => IoIl, 5 => IoIh, 6 => IoIhIl 5024 3= The blocking input (3) operate on function Z< or IR> as programmed 0 => Ir, 1 => Z, 2 => Z+Ir 5025 tfres The reset after tripping of the relays associated to the time delayed elements can take place: (A) automatically (M) manually. 0 => Man, 1 => Aut 6000 I> Instantaneous element of low-set overcurrent 4 6001 ti> As above, time delayed element 4 6002 I>> Instantaneous element of high-set overcurrent 4 6003 ti>> As above, time delayed element 4 6004 O> Instantaneous element of low-set earth fault element 4 6005 to> As above, time delayed element 4 6011 1Is First unbalance element (time delayed) 4 6012 2Is As above, second unbalance element 4 6043 Z< Under impedance time delayed element 4 6044 Ir> Reverse power time delayed element 4 6074 tbf Breaker Failure function operates 4 8 - TRIP STATUS 7000,0 I> Low-set overcurrent instantaneous element 0 => No Trip, 1 => Trip 7000,1 ti> Low-set overcurrent time delayed element 0 => No Trip, 1 => Trip 7000,2 I>> High-set overcurrent instantaneous element 0 => No Trip, 1 => Trip 7000,3 ti>> High-set overcurrent time delayed element 0 => No Trip, 1 => Trip 7000,4 O> Low-set earth fault instantaneous element 0 => No Trip, 1 => Trip 7000,5 to> Low-set earth fault time delayed element 0 => No Trip, 1 => Trip 7000,12 1Is Unbalance current 1st level instantaneous element 0 => No Trip, 1 => Trip 7000,13 t1is Unbalance current 1st level time delayed element 0 => No Trip, 1 => Trip 7000,14 2Is Unbalance current 2nd level instantaneous element 0 => No Trip, 1 => Trip 7000,15 t2is Unbalance current 2nd level delayed element 0 => No Trip, 1 => Trip 7002,15 Z< Underimpedence instantaneous element 0 => No Trip, 1 => Trip 7003,0 tz< Underimpedence time delayed element 0 => No Trip, 1 => Trip 7003,1 Ir> Reverse power instantaneous element 0 => No Trip, 1 => Trip 7003,2 tir> Reverse power time delay element 0 => No Trip, 1 => Trip 9 COMMANDS / DATETIME 8000 CMD Remote commands Commands are encoded as follows: 0 => No Command 1 => Test W/O trip 2 => Test W trip

Pag. 6 of 6 10 - DIAGNOSTIC STATUS The following bits are read only 9000,0 ALU_FLT C.P.U. ALU fault 1 => fault, 0 => no fault 9000,1 ADC_FLT Analog to Digital Converter fault 1 => fault, 0 => no fault 9000,2 E2P_FLT Non volatile memory fault 1 => fault, 0 => no fault 9000,4 KBD_FLT Keyboard fault (stuck key) 1 => fault, 0 => no fault 9000,6 DSP_FLT Display fault 1 => fault, 0 => no fault 9000,9 PRG Programming 1 => fault, 0 => no fault 9000,10 BRF BReaker Failure 1 => fault, 0 => no fault 11 - RELAY ID This word allows the host P.C. to identify the type of relay. 64647 REL_ID Id of Value = 22 Notes: 1) Trip causes are coded as follow: Code Cause 0 No trip 1 I> 2 I>> 3 O> 4 1Is 5 2Is 6 Ir> 7 Z< 2) --- 3) --- 4) F => relays words are encoded as follows: each element has its own F => relays word, whose bits 0, 1, 2, 3 respectively corresponds to output relays R4, R3, R2, R1. Bits 4..15 are ignored by the unit. 5) Date/time is expressed using 4 words containing BCD (Binary Coded Decimal) numbers. Each nibble represents a digit. The first word stores Years (in a 2 digits format), the second one Months and Days, the third one Hours and Minutes and the fourth one Seconds and Tenths of a second.