CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B

Similar documents
LCI AUXILIARY I/O TERMINAL BOARD DS200DDTBG_A

High Frequency Power Supply Board IS200HFPRG_A

GE Drive Systems. Replacement Procedure For Motor Field Control/Power Supply Board V -

GE Industrial Systems

GATE DISTRIBUTION AND STATUS BOARD DS200FCGD1A

Gate Drive Amplifier/Interface Board IS200DAM_G_

Bridge Application Interface Board IS200BAIAH_B

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1

Resolver to Digital Expansion Board

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

INSTRUCTIONS. D20A6 expanded I/O. for AV-300i Drives. 12 Digital Inputs 8 Digital Outputs 2 Analog Inputs 2 Analog Outputs (V) 2 Analog Outputs (I)

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Model 2657A-LIM-3 LO Interconnect Module

PS/IO Circuit Board Retrofit

Model 2380 Rack-Mount Kit

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

KBMG MULTI-SPEED BOARD

INSTRUCTIONS. D14A4F expanded I/O. for AV-300i Drives. 8 Digital Inputs 6 Digital Outputs 2 Analog Inputs 2 Analog Outputs 1 Frequency Input

PCL451. Manual Preset Indexer. User s Guide E Landon Drive, Anaheim, CA

AD-7830 Servo Amplifier

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

DBK48. Multipurpose Isolated Signal-Conditioning Module. Description. Supports up to Sixteen 8B Modules

Installation Instructions

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

ETM-2050/ETM-2051 Service Manual

2260B-RMK-Series Rack Mount Kit

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

Upgrading and Servicing Guide

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V Voltage 1, 2, 3 Pump Piston (D, E, F, G)

LVDT Test Device. Product Manual (Revision B) Original Instructions. Testing and Calibration of LVDT Feedback Devices on PG Governors

Instruction Sheet WPC 2000 Option 1

Model 2380 Rack-Mount Kit

PMDX Axis Breakout/Motherboard for Gecko Stepper Motor Drivers User s Manual

COOPER POWER SERIES. 600 A U-OP visible break connector system operation instructions. Deadbreak Apparatus Connectors MN650022EN

Integrated Battery Control System LBCS Step-by-Step Setup Guide

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Digital Signal Processor Control Board IS200DSPXH_A C

PMDX-108-Output. 8-Channel Isolated Output Board for PC parallel port pins 2-9. User s Manual

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

Upgrading and Servicing Guide

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

AirTest Model CN9000 Series Sensor Controller

RGU Main Control Board Replacement Firmware Version 3.01

5504 Thermocouple Analog Input Module

********SERVICE MANUAL******** MODELS:

Install Motor Controller User Manual

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

Model 7705 Control Module

Upgrading and Servicing Guide

PowerLogic ION7550 / ION7650 Hardware Lockable Meter

Replacing the Power Supply

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Installation NOTICE. S&C IntelliCap Automatic Capacitor Control. Table of Contents. Instruction Sheet

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Table of Contents Product Overview Before using the product Installation Procedure... 5

GPIB-232CT-A IBCL EPROM Installation Guide

RTK3 Logic Controller User Manual Revised

Service Instructions. Conductor 420

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

Series 3700 Screw Terminal Assemblies Installation Instructions

MANUAL FOR THE UNIVERSAL MANUAL CONTROLLER UMC - 31

Technical Manual SMART TRAC PS Card

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

TD-700 FLUOROMETER SERVICE MANUAL

Model HM-535 Power Supply Installation and Service Instructions

Film-Tech. The information contained in this Adobe Acrobat pdf file is provided at your own risk and good judgment.

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

HV-CS kv Edge Mount Triaxial Jack

PACSystems* RX3i IC695PSA040

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:

MOTOR DRIVE AMPLIFIER

Agilent Technologies E5339A 38-Pin Low-Voltage Probe

Analog Monitor Installation Manual

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Instructions for Testing Magnum DS Trip Units Using PACB Test Kit Styles 87C0270G01-G03

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board

InView Firmware Update

(Catalog Numbers 1394-FK10TS and -FK22TS)

MODULUS 21 Power Distribution Unit (PDU) Replacement. Overview A. Introduction

User Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents.

Smart Multivariable Transmitter (SMV 3000) Electronics Module Replacement Kit Instruction

Shutter Assembly Guide Frame Accessory

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01

Serial ATA Hot Swap Drive Cage Upgrade Kit for: Intel Server Chassis SC5200 Intel Server Chassis SC5250-E

PC-250B Solid State Vital Biased Code Following Track Relay

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Microprocessor Module Replacement Kit for Multi-Zone Leak Monitors Instruction Manual

Technical Manual SMART TRAC PG Card

G540 User Manual. Date Modified: March 5, 2012 Page 1 of 10

OPERATING AND SERVICE MANUAL. Universal Interface Device 45

Transcription:

(Supersedes GEI-100182A) CONTACTOR DRIVER BOARD DS200CDBAG1A and DS200CDBAG1B These instructions do not purport to cover all details or variations in equipment, nor to provide every possible contingency to be met during installation, operation, and maintenance. If further information is desired or if particular problems arise that are not covered sufficiently for the purchaser s purpose, the matter should be referred to GE Industrial Control Systems. This document contains proprietary information of General Electric Company, USA and is furnished to its customer solely to assist that customer in the installation, testing, operation, and/or maintenance of the equipment described. This document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of GE Industrial Control Systems. CONTENTS Safety Symbol Legend...1 Functional Description...1 Pot RV1 Setting...2 Board Groups...2 Application Data...2 Board Hardware...2 Potentiometer (Pot)...2 Configurable Jumpers (JP)...2 LED Indicator...2 Testpoints...2 Board Connectors...3 Board Identification...7 Warranty Terms...7 Warranty Parts And Service...7 Procedure For Replacing Boards...7 NOTE SAFETY SYMBOL LEGEND WARNING CAUTION Indicates a procedure, practice, condition, or statement that, if not strictly observed, could result in personal injury or death. Indicates a procedure, practice, condition, or statement that, if not strictly observed, could result in damage to or destruction of equipment Indicates an essential or important procedure, practice, condition, or statement. FUNCTIONAL DESCRIPTION This equipment contains a potential hazard of electric shock or burn. Only adequately trained persons who are thoroughly familiar with the equipment and the instructions should install or maintain this equipment. INTRODUCTION WARNING The DS200CDBA Contactor Driver Board (CDBA) interfaces the drive control to a high speed contactor. This allows fast dropout protection in the drives. The CDBA board provides power to open and close a contactor that is controlled by the DS200DCFB Power Supply Board (DCFB), DS200SDCI Dc Power Supply and Instrumentation Board (SDCI), or Feedback Acquisition and Power Supply Board (DCVA). Each CDBA board can operate one high speed contactor. Jumper JP2, on revision G1BBA to present boards, provides coordination with other CDBA boards (and their contactors) in a multibridge system so that all contactors will operate together. An LED indicates local contactor close command status when coordinated operation is selected. (See Figure 1 and Table 1.) The CDBA board is powered from 75 140 V ac/dc and the input power is fused by FU1. Contactors used with the CDBA board must have coil voltages of 30 to 40 V dc.

Contactor Driver Board To close a contactor, the CDBA board applies 105 V dc for 250 milliseconds to force the contactor to close. The CDBA then regulates the contactor drive current at the level set by potentiometer (pot) RV1 to keep the contactor closed. This can be measured at testpoint TP3, REFA. (See Figure 1 and Tables 2 and 3.) CAUTION When replacing the CDBA board, pot RV1 on the new (replacement) board must be set to the same position as that on the board being replaced. For DS304-type contactors, failure to adjust the pot as described in the following section may cause the contactor coil to fail. POT RV1 SETTING Pot RV1 determines the amount of current that will drive the associated contactor. RV1 is typically set to regulate the contactor drive current at 1.5 amps. For DS304-type contactors, the drive current must be set at 0.75 amps. See Table 2 for RV1 settings and Table 3 for testpoint descriptions. BOARD GROUPS There is only one group of the CDBA board, G1. However, the G1 board has two revision levels, G1A and G1B. All G1A revision boards do not have the coordinated operation feature and JP2 and LED1 are not included on the boards. G1BBA to present revision boards provide coordinated operation and include JP2 and LED1. COORDINATED OPERATION Revision G1BBA to present CDBA boards provide for coordinated contactor operation. JP2 selects coordinated operation and LED1 provides status information when in coordinated mode. Placing JP2 in the 2.3 position allows the control inputs at 1TB-9 and 1TB-10 to operate contactors in a coordinated manner. By connecting the inputs of these associated CDBA boards in parallel, the associated contactors will operate together (coordinated) when all of the associated CDBA board s 1TB-1 and 1TB-2 inputs are enabled. There is a normally-closed solid-state switch that is enabled when JP2 is in the 2.3 position. This switch opens when 1TB-1 and 1TB-2 are energized and allows the current input at 1TB-9 and 1TB-10 to energize the contactor. See Table 1 and Table 4. BOARD HARDWARE APPLICATION DATA The CDBA board includes a potentiometer, two configurable jumpers, an LED indicator, three testpoints, a fuse, and wiring connectors (terminal boards and plug connectors) as part of the board. These items are described in the following paragraphs of this section. POTENTIOMETER (POT) All CDBA boards include an adjustable pot for setting contactor driver current. Refer to Figure 1 for location, Table 2 for description, and the Pot RV1 Setting paragraph. CONFIGURABLE JUMPERS (JP) All G1A revision CDBA boards include one configurable jumper for factory test selection. Revision G1BBA to present CDBA boards include two configurable jumpers for factory test selection and for coordinated operation selection. Refer to Figure 1 for the location of the jumpers (JP), to Table 1 for the settings for the jumpers, and the Coordinated Operation paragraph. LED INDICATOR Revision G1BBA to present CDBA boards include one red LED (LED1) for coordinated operation indication. LED1 is lit when JP2 is in the 2.3 position and the signal on 1TB1 and 1TB2 is de-energized. LED1 is not lit if JP2 is in the 1.2 position. See Figure 1 for the location of the LED indicator. TESTPOINTS Three testpoints are present on the CDBA board to allow checking of the REFA voltage signal (determined by pot RV1), CDBA board common (ACOMA, that is different from drive common), and the board s +15 V dc power supply (referenced to ACOMA). See Figure 1 for the locations of the testpoints and Table 3 for the descriptions. 2

Contactor Driver Board GEI-100182B FUSE (FU1) The CDBA board includes one protective fuse, FU1, on the input power to the board. FU1 is a 4 amp, 125 V, 2AG slow-blow fuse. If FU1 continually blows, the CDBA board is probably defective (and should be replaced) or the board s associated contactor coil is shorted. See Figure 1 for the location of FU1. BOARD CONNECTORS The CDBA board receives input signals/power and sends output signals via one terminal board (that consists of four sections) and three plug connectors. See Figure 1 for a CDBA board layout diagram showing the locations of these connectors and see Tables 4 through 7 for the signal descriptions of the terminal board and connectors. NOTE: Revision G1B board shown; G1A revision does not include JP2 or LED1. Figure 1. CDBA Board Layout Diagram Revision Name Description Table 1. CDBA Board Jumper (JP1 and JP2) Settings All JP1 Factory test jumper JP1 position 2.3 allows the current output scaling to be lowered for factory board test purposes. If not in factory board test; JP1 must be 1.2. 1.2 Normal operation 2.3 Special setting for factory board test BBA- Present JP2 Provides for coordinated operation of multiple CDBA boards For coordinated operation (2.3 position), apply parallel voltage to 1TB-9 and 1TB-10. This circuit was designed for 12 circuits using 340 ohms in series with the 24 volt power supply. All 12 CDBA inputs can be connected together (coordinated) so that all contactors will pick up and drop out together. 1.2 Normal non-coordinated CDBA board operation 2.3 Coordinated operation 3

Contactor Driver Board Revision Name Description Table 2. CDBA Board Potentiometer (RV1) Settings All RV1 Contactor coil current reference pot Pot RV1 controls the amount of current that will drive the contactor coil, as measured using testpoints REFA and ACOMA (see NOTE below). This pot is set at the factory and varies depending on the particular contactor to be driven. The following calibration information is for the CDBA board. Consult the factory for the proper setting if RV1 is suspected to be set incorrectly. REFA to ACOMA Coil RV1 Position Voltage (V dc) Current (A) 0.00 0.60 Fully counterclockwise 0.12 0.75 -------- 0.70 1.50 Approximately 11 o clock 1.50 2.50 Fully clockwise NOTE: All CDBA board testpoints are referenced at CDBA common (ACOMA), that is different from drive common. Therefore, all test measurements must be performed using isolated test equipment that is suitable for measuring floating p otentials. Table 3. CDBA Board Testpoints Testpoint Nomenclature Description TP1 ACOMA Common reference point for CDBA board. NOTE: All CDBA board testpoints are referenced at CDBA common (ACOMA), that is different from drive common. Therefore, all test measurements must be performed using isolated test equipment that is suitable for measuring floating potentials. TP2 P15A Testpoint for CDBA +15 V dc (± 20%) power supply referenced to ACOMA. TP3 REFA Testpoint for contactor driver reference voltage (referenced to ACOMA) that sets the amount of current that will drive the contactor. This voltage is set using pot RV1 (see Table 2). RV1 is set at the factory for the appropriate contactor to be driven. Consult the factory if the setting is suspected to be incorrect. 4

Contactor Driver Board GEI-100182B Revision Pin No. Description Table 4. Connector 1TB, CDBA Board Contactor Control Connections All All All All AAA Pres. BBA Pres. 1TB-1 1TB-2 1TB-3 1TB-4 1TB-5 1TB-6 1TB-7 1TB-8 1TB-9 1TB-10 1TB-9 1TB-10 Coil Driver Series Interlock Inputs 1TB-1 and 1TB-2 are connection points for an interlock to be wired in series with the coil driver signal from connector MACPL. (MACPL is intended for factory wiring only.) Contactor Normally-Open Interlocks 1TB-3, 1TB-4 are normally-open auxiliary contacts from the MD contactor. Contactor Normally-Closed Interlocks 1TB-5, 1TB-6 are normally-closed auxiliary contacts from the MD contactor. Contactor Normally-Open Interlocks 1TB7, 1TB-8 are normally-open auxiliary contacts from the MD contactor. Contactor Normally-Closed Interlocks 1TB-9, 1TB-10 are normally-closed auxiliary contacts from the MD contactor. These normally-closed contacts are internally wired to the CDBA control circuitry, and should not be used on these revision boards. Contactor Normally-Closed Interlocks 1TB-9, 1TB-10 are normally-closed auxiliary contacts from the MD contactor. These normally-closed contacts are internally wired to the CDBA control circuitry, and should be used only for multibridge coordination function (JP2 = 2.3). All 1TB-11 Input Power (CPH) Hot (or positive, +) input power for the CDBA board. 1TB-11 and 1TB-12 are electrically parallel with RMPL pins 1 and 2 respectively. RMPL is intended for factory daisy chain wiring of control power (see Table 7). All 1TB-12 Input Power (CPN) Neutral (or negative, ) input power for the CDBA board. 1TB-11 and 1TB-12 are electrically parallel with RMPL pins 1 and 2 respectively. RMPL is intended for factory daisy chain wiring of control power (see Table 7). 5

Contactor Driver Board Table 5. Connector MACPL, I/O Between CDBA Board and DCFB (or SDCI) Board Pin No. Description 1 MD #1 contactor control common output. 2 MD #1 contactor control 24 V dc output. 3 MD #2 contactor control common output. (Not connected on SDCI.) 4 MD #2 contactor control 24 V dc output. (Not connected on SDCI.) Table 6. Connector MPL, Contactor Driver Circuit Connector (From SHVI Board*) Pin No. Nomenclature Description MPL-1 -------- Contact driver #1 positive (+), connected to stab terminal M1. MPL-2 -------- Contact driver #1 negative ( ), connected to stab terminal B1. MPL-3 -------- Contact driver #2 positive (+), connected to stab terminal M2. MPL-4 -------- Contact driver #2 negative ( ), connected to stab terminal B2. *May not be used in some applications. Table 7. Connector RMPL, Contactor Driver Circuit Connectors (From SHVI Board*) Pin No. Nomenclature Description RMPL -1 -------- Contactor power positive (+). RMPL -2 -------- Contactor power negative ( ). RMPL -3 -------- Contactor power positive (+). RMPL -4 -------- Contactor power negative ( ). *May not be used in some applications. 6

Contactor Driver Board GEI-100182B DS 200 CDBA G# A A A A board revision (artwork change) that is backward compatible. A board revision (functional change) that is backward compatible. A board revision (functional change) that is not backward compatible. Essentially a new catalog number. A group, or variation, of a particular board. Board functional acronym. Indicates that the board does not contain firmware. (215 indicates the board contains firmware and/or other components added to the base level board.) Identifies GE Industrial Control Systems. Figure 2. Sample Board Part Number, DS Series RENEWAL/WARRANTY REPLACEMENT BOARD IDENTIFICATION A printed wiring board is identified by an alphanumeric part (catalog) number stamped on its edge. For example, the Contactor Driver Board is identified by part number DS200CDBAG#ruu. (See Figure 2 for part number breakdown.) NOTE All digits are important when ordering or replacing any board. WARRANTY TERMS The GE Industrial Control Systems Terms and Conditions brochure details product warranty information, including the warranty period and parts and service coverage. The brochure is included with customer documentation. It may be obtained separately from the nearest GE Sales Office or authorized GE Sales Representative. WARRANTY PARTS AND SERVICE Fuse FU1 is the only end-user replaceable component on the CDBA board. If any other components on the board fail, the board needs to be replaced as a unit. To obtain a replacement board, or service assistance, contact the nearest GE Service Office. Please have the following information ready to exactly identify the part and application: GE requisition or shop order number Equipment serial number and model number Board number and description PROCEDURE FOR REPLACING BOARDS WARNING Potentially lethal voltages are present on the CDBA board when powered. To prevent electric shock, turn off power to the drive, then test to verify that no power exists on the board before touching it or any connected circuits. CAUTION To prevent equipment damage, do not remove boards or connections, or re-insert them, while power is applied to the drive. Treat all boards as static-sensitive. Use a grounding strap when changing boards or software chips, and always store boards in anti-static bags or boxes they were shipped in. 7

Contactor Driver Board To replace a CDBA board: 1. Turn off all power to the drive, then wait several minutes for all the power supply s capacitors to discharge. Test any electrical circuits before touching them to ensure the power is off. 2. Open the drive s cabinet door to access the printed wiring boards and locate the CDBA board. NOTE Connector 1TB consists of four two-section connectors (1TBA 1TBD). One section of the connector is mounted on the CDBA board and the other section, that contains the screw terminals, plugs into the board-mounted section. Do not disconnect the individual wires from the screw terminal section. Instead, after noting the location of each connector, use a screwdriver to carefully pry the two sections apart. 3. Carefully disconnect all cables from the CDBA board as follows: Verify cables are labeled with the correct connector name (as marked on the board) to simplify reconnection. For cables with pull tabs, carefully pull the tab. Pry the two sections of the 1TB connectors apart using a screwdriver. NOTE The CDBA board is typically mounted on a bracket using standoffs. It may be necessary to first remove the bracket/board assembly from the drive to gain access to the board standoffs. 4. Remove the four screws that secure the CDBA board to the four standoffs and remove the board. NOTE Because of upgrades, boards of different revision levels may not contain identical hardware. However, GE Industrial Control Systems assures compatibility of its replacement boards. 5. Verify that all pots and jumpers on the new (replacement) CDBA board are set in the exact same position as they were on the old board. If a board revision has added or eliminated a configurable component, or readjustment is needed, refer to Table 1 and Table 2. CAUTION When replacing the CDBA board, pot RV1 on the new (replacement) board must be set to the same position as that on the board being replaced. For DS304-type contactors, failure to adjust the pot as described in this instruction book may cause the contactor coil to fail. 6. Pry apart the 1TBA through 1TBD connectors on the new CDBA board and set the screw terminal sections aside. 7. Orient the new CDBA board in the same position as the one removed and install it onto the four standoffs with the screws removed in step 4, then fully tighten the four screws. 8. Reinstall the bracket/board assembly if removed. 9. Reconnect all of the terminal board sections from the old CDBA board (with wires still connected) to the respective connector section on the new board. Ensure that each connector section is in the correct location and that it is properly seated. 10. Reconnect all cables to the CDBA board as labeled that were disconnected in step 3. Ensure that cables are properly seated at both ends, then close the drive cabinet door. 8

Contactor Driver Board GEI-100182B Notes: 9

Contactor Driver Board Notes: Issue Date: December 1997 1997 by General Electric Company, USA. All rights reserved.