Heating Circuit Controller

Similar documents
Heating Circuit Controller

ERF910. RF Repeater. Synco living

RF adapter plugs, dimming

Room Temperature Controller

Room Temperature Controller

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Room Temperature Controllers

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Electrical Actuators

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Semi Flush-mount Room Temperature Controllers with LCD

Electrical Actuators

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Electrical Actuators

Semi flush-mounted room temperature controllers with LCD

Temperature Controller

Semi flush-mounted room temperature controllers with LCD

Immersion Temperature Sensors

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

RDF301 RDF CE1N3171en 02 Jun 2010 Building Technologies

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

Room unit with PPS2 interface

7-day room temperature controller

Non-communicating room controllers

Temperature controller Ducted systems

Electromotoric actuators

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Room Temperature Controller with 7-Day Time Switch, LCD and opt. Remote Temperature Sensor

7-day room temperature controller

Heating Controllers. Siemens Building Technologies HVAC Products. Synco 700

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Electromotoric actuators

Weekday / weekend room temperature controller

Switching and Monitoring Device

Room thermostat with KNX communications For VAV heating and cooling systems

Power supply module, bus connection module

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

Universal Controller

Radiator Valves. Building Technologies HVAC Products. NF norm, for 2-pipe heating systems

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Electrical actuators

Master room unit for RRV controllers

Status display unit with P-bus connection

Electromotoric actuators

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Temperature Controller (Heat Pumps)

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

Resistance measuring module

Electromotoric actuators

Non-communicating room controllers

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

M-Bus Central Unit. Use

Extension module for lighting control

Room thermostats with KNX communications

Room unit with PPS2 interface

Compact Universal Controllers

Communication module to connect M-bus devices to POL6xx.xxx controllers.

Room thermostats with KNX communications

OP10. Pre-programmed, configurable controller for simple applications

Weekday / weekend room temperature controller

24-hour room temperature controller

SEH62.1. Digital Time Switch

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Electromotoric actuator

Compact universal controllers

Web interface BACnet/IP

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Compact room automation stations, BACnet/IP, AC 230 V

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

Rotary actuators for ball valves

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8RB. TX-I/O Blinds module

Temperature controller for multi-zone ducted systems

Room unit with PPS2 interface

Central control unit

Electromotive actuators for combi valves

EYE 200: DDC single-room controller, ecos200

OCI Service Tool. Siemens Building Technologies HVAC Products. ACS plant operating software and OCI700 service interface

Room unit with PPS2 interface

Rotary version, three-position control

Island bus expansion module

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

Central Communication Unit OZW775

VAV compact controller KNX / PL-Link

Air damper actuators

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

OCI Service tool. As of ACS790 V9.00. Service case with software and service interface

Fast running actuators for air dampers

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

HERZ Actuator 7708, 7990

VAV modular controller

7-day room temperature controller

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4.

Positioning modules with DC V output signals, and storage of positioning value

Switching module for AC V and up to three load stages, with manual switching

RТTH DUAL ROOM SWITCH

Zelio Control-modular measurement and control relays 1

Transcription:

2 705 Synco 900 Heating Circuit Controller RRV912 RF-controlled heating circuit controller for up to 2 heating circuits RF communication based on KNX standard (868 MHz, bidirectional) Connection facility for one 3- or two 2-position actuators Mains-powered AC 230 V 2 universal relay outputs 1 universal input 1 universal output DC 0 10 V Use For integration into the Siemens Synco 900 system Suited for use in heating plant: With central heat distributors (e.g. underfloor heating or soft steel piping system) For use with motorized radiator valves (e.g. with sill covers) Heating circuit control with 2- or 3-position actuators Universal relay outputs, e.g. for control of the apartment pump, DHW heating, or fan speeds Universal input, e.g. for connection of a DHW temperature sensor or an alarm Universal output DC 0 10 V for forwarding the heat demand signal CE1N2705en 26.07.2006 Building Technologies HVAC Products

Equipment combinations The RRV912 heating circuit controller is designed for use with the Siemens Synco 900 system. For more detailed information about equipment combinations, refer to the Data Sheet covering the central apartment unit (CE1N2707en). The RRV912 can be used in connection with the following types of actuators from Siemens, depending on the application: Heat distributor with individual room control RRV912 2705S01 Type of actuator STA21 STP21 SSA31* Thermal Thermal Electromotoric Data Sheet no. N4877 N4878 N4893 Normal state NC NO Depending on Y1/Y2 Type of valve Depending on the type of heat distributor, connection M30 x 1.5 mm * Only one heating circuit possible Heat distributor with zone control RRV912 2705S02 Type of actuator SSP31* SSB31* Electromotoric Electromotoric Data Sheet no. N4864 N4891 Normal state Depending on Y1/Y2 Type of valve VVP47 VXP47 VMP47 * Only one heating circuit possible Depending on Y1/Y2 VVP45 VXP45 VMP45 2/10

Radiators 2705S03 RRV912 Type of actuator STA21 STP21 SSA31* Thermal Thermal Electromotoric Data Sheet no. N4877 N4878 N4893 Normal state NC NO Depending on Y1/Y2 Type of valve * Only one heating circuit possible VDN, VEN, VUN, VPD, VPE Also refer to Data Sheet CE1N2100en covering small valves, actuators and accessories. Ordering When ordering, please give quantity, product name and type reference. Scope of delivery The RRV912 is supplied complete with Mounting Instructions. Product documentation The Operating and Commissioning Instructions for the RRV912 are contained in the product documentation of the central apartment unit. Functions Main function Universal relay outputs Universal input Universal output DC 0 10 V In operation, the RRV912 maintains the required room temperature of the individual heating circuits. The central apartment unit delivers the relevant data via RF. The universal relay outputs can be used to control different types of devices. Release is controlled via the central apartment unit and delivered via RF. 1 The universal input is used for connection of the DHW temperature sensor, for example. The data are forwarded to the central apartment unit via RF. 1 The RRV912 converts percentage-scaled signals from the central apartment unit (e.g. heat demand) to analog DC 0 10 V signals. 1 1 For detailed information about assignment options for the inputs and outputs, refer to the Synco 900 Mounting and Commissioning Instructions (CE1C2707en). 3/10

Parallel operation Antilime function Summer operation Window airing function Frost protection for the room Binding State query RF binding test Resetting a channel Supply state RF failure Mains failure Several heating circuits can be assigned to one room and, therefore, operated in parallel. In that case, the first heating circuit ensures the actual room control and, at the same time, controls the other assigned heating circuits. The antilime function is triggered by the central apartment unit. When receiving an antilime command, the heating circuit valve will be fully opened and then closed again. When the antilime function is completed, the valve will return to the previous control position. Summer operation is triggered by the central apartment unit. When receiving a command to start summer operation, the heating circuit valve will be opened or closed, depending on the position predefined by the central apartment unit. If the antilime function is activated in summer operation, it will be performed. When completed, the control loops will resume summer operation. The window airing function is triggered by the central apartment unit. The function interferes in the control process in a way that overheating of the room will be avoided both during and after the window airing time. Frost protection for the room becomes active if the room temperature drops below the frost protection setpoint. It remains active until the room temperature returns to a level 1 K above the frost protection setpoint. The binding of the first selected channel is used by the RRV912 to sign on at the central apartment unit, thus ensuring integration into the RF system. Then, the other channels can be assigned to other rooms or function groups. The binding process is triggered via the multifunction button and indicated by the multifunction LED. The multifunction button can be used to query the state of the configured control channels. The state is indicated by the multifunction LED. The multifunction button can be used to trigger a binding test per channel. The test is made to check the radio link to the central apartment unit. The RF binding test is indicated by the multifunction LED. The multifunction button can be used to reset a configured channel to its supply state. Then, the channel must be reconfigured. The state is indicated by the multifunction LED. The multifunction button can be used to reset the RRV912 to its supply state. Then, the RRV912 must be reintegrated into the system. If radio transmission between the RRV912 and the central apartment unit breaks down, control is no longer ensured. The heating circuit valves will open. When radio transmission is reestablished, the RRV912 will return to control mode. In the event power supply to the RRV912 is interrupted, control is no longer ensured. The positions of the individual actuators can only be changed manually on the actuators themselves. When mains supply is restored, the RRV912 will return to control mode. 4/10

Error messages The following error messages are delivered by the RRV912: Error messages Communication error (no communication for one hour) Operating and indicating elements Multifunction LED Channel LED Mains LED s RRV912 NC 3P NO B U Q1 Q2 Y1 Y2 CH 2705Z01en Multifunction button Actuator selector Channel selection button Slot for opening the terminal cover Function of operating elements Operating elements Multifunction button Actuator selector Channel selection button Function State query of channel configuration RF binding test Binding Disconnection of channels from the system Restoration of supply state Selection of the type of actuator Channel selection Function of indicating elements Indicating element Multifunction LED Channel LED's: B U Q1, Q2 Y1 / Y2 Mains LED Function Indication of channel configuration RF binding test Binding process Disconnection of channel from the system Indication of channel configuration / status indication: Universal input Universal output Universal relay outputs Controller outputs Power supply For more detailed information about the functions and operation of the RRV912, refer to the product documentation covering the central apartment unit. 5/10

Notes on engineering and operation Mounting location Installation Due to its compact design, the RRV912 can be fitted directly in the heat distribution panel*, on the ceiling in the cellar, or in the cable riser The permissible environmental conditions must be observed The RRV912 must not be exposed to dripping water. For notes relating to engineering and mounting RF devices of the Siemens Synco 900 system, refer to Data Sheet CE1N2708en When mounting the RRV912, ensure that there is sufficient space by the connection terminals to introduce the cable ( 30 mm) At the top of the unit, a minimum clearance of 50 mm must be observed 30 mm to ensure that the operating elements can be accessed and that the terminal cover can be easily opened * Plastic covers are used in place of metal covers to support radio communication The RRV912 is designed for: Mounting on top hat rails conforming to EN 60715-TH35-7,5 Fitting with the help of 2 fixing screws 2705Z02de 50 mm Note Prior to applying power, connect all heating circuits and the inputs and outputs. Commissioning Maintenance Disposal Prior to commissioning, check to ensure that the RRV912 is correctly mounted, that all wiring is correctly made, and that power is switched on. The RRV912 is maintenance-free. In terms of disposal regulations, the RRV912 is classified as electronic scrap conforming to the European Directive 2002/96/EG (WEEE) and must not be disposed of as domestic waste. Local and currently valid legislation must be observed. Warranty Application-related technical data are only warranted in connection with the Siemens Synco 900 system. For equipment combinations, refer to the Data Sheet of the central apartment unit (CE1N2707en). When using the RRV912 together with third-party devices, correct functioning must be ensured by the user. In that case, Siemens will assume no responsibility for service and warranty. 6/10

Technical data Power supply Operating voltage AC 230V (± 10%) Frequency 50 Hz Power consumption (with no external load) max. 7 VA Fusing of supply line 10 A RF RF Range Protocol 868 MHz (bidirectional) typically 30 m inside buildings KNX RF-compatible Universal input Permissible cable length to sensor or external contact Universal relay output Universal output Controller output Electrical connections Type LG-Ni 1000 (on / off) Quantity 1 Measuring range 0 120 C Copper cable 0.6 mm dia. max. 20 m Copper cable 1 mm 2 max. 80 m Copper cable 1.5 mm 2 max. 120 m Type NO contact AC 24 230 V, AC 0.02 2 (2) A Quantity 2 Type DC 0 10 V, max. DC 1 ma Quantity 1 Type triac AC 230 V, max. AC 30 ma Quantity 2 Permissible cable length max. 10 m Screw terminals for max. 2.5 mm 2 Type of controller 2-position 3-position PID PID Standards Protection conformity to EEC directive - Immunity - Emissions Low-voltage directive - Electrical safety RTTE Radio & Telecom. Equipment Radio communication Safety class II to EN 60730 Housing IP30 to EN 60529 Degree of pollution 2 to EN 60 730 89/336/EC - EN 61000-6-1/2 - EN 61000-6-3/4 73/23/EC - EN 60730-1 99/5/EEC - EN 300220-1, EN 300220-3, EN 301489-3 Dimensions Weight Housing material Housing color Unit complete with accessories Upper / lower housing section refer to Dimensions 0.455 kg plastic PC+ABS RAL 7035 light-grey RAL 5014 dove-blue 7/10

Environmental conditions operation transport storage IEC 60721-3-3 EN 60721-3-2 EN 60721-3-1 Climatic conditions class 3K5 class 2K3 class 1K3 Temperature 0 +50 C -25 +70 C -20 +65 C Humidity 5 95 % r.h. (noncondensing) <95 % r.h. 5 95 % r.h. Mechanical conditions class 3M2 class 2M2 class 1M2 Elevation above sea level min. 700 hpa, corresponding to max. 3,000 m above sea level Connection terminals B M U M Q13 Q14 Q23 Q24 L N Y1 N Y2 N Legend L Operating voltage, live wire AC 230 V N Operating voltage, neutral conductor AC 230 V B Universal input M Ground for universal input U Universal output DC 0 10 V M Ground for universal output Q13, Q14 Universal relay output (NO) for AC 24 230 V (relay 1) Q23, Q24 Universal relay output (NO) for AC 24 230 V (relay 2) Y1 Output controller 1, AC 230 V Y2 Output controller 2, AC 230 V N Neutral conductor for controller output Note: With controller outputs Y1 and Y2, the live wire (L) is switched. The neutral conductor is internally connected. The relay outputs are potential-free. Connection diagram 3-position control N1 B M U M Q13 Q14 Q23 Q24 L N Y1 N Y2 N 1) 2) 3) Y1 N Y2 Y1 Legend L N AC 230 V 2705A01 N1 Heating circuit controller RRV912 Y1 Actuator (electromotoric valve actuator) 1) Universal input, can be used for temperature acquisition / digital input 2) Universal output DC 0 10 V 3) Universal potential-free relay output, can be used for mains or low-voltage 8/10

2-position control Legend N1 Heating circuit controller RRV912 Y1 / Y2 Actuator (thermal valve actuator) 1) Universal input, can be used for temperature acquisition 2) Universal output DC 0 10 V 3) Universal potential-free relay output, can be used for mains or low-voltage Dimensions Dimensions in mm 180 50 1 49 1,5 98 90 8 27,4 35,3 3 8,5 20,2 ø 5 27,4 7,2 165,6 2705M01 9/10

10/10 2006 Siemens Switzerland Ltd Subject to change