NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V

Similar documents
NKQB24-1, NKQX24-1 On/Off, Fail-Safe, Operation, Direct Coupled, 24V

A CLOSER LOOK. Electronic Fail-Safe Series Direct Coupled Actuators. The Belimo Difference. Brushless DC Motor for Added Accuracy and Controllability

Minimum 360 in-lb torque - GK. Minimum 54 in-lb torque - NKQ. Minimum 101 lbf - AHQ. Electronic Fail-Safe Series Direct Coupled Actuators

Functional data Factory settings Variable Setting Torque Inhibiting torque

Power consumption In operation At rest For wire sizing

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Functional data Nominal torque min. 180 in lb [20 NM] Communicative control Cloud: (call for clientapi )

Functional data Position indication reflective visual indicator (snap on) Communicative control Cloud: (call for clientapi )

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Technical data sheet. Technical data

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Power consumption In operation At rest For wire sizing. Torque Inhibiting torque. 150 s / C Sound power level Motor

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Overview of types. Technical data

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency. Draft

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manuelle Auslösung der Adaption durch Drücken der Taste «Adaption» oder mit dem PC-Tool

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

s Spring return C / max C

AF24-MFT (-S) US Proportional damper actuator, Spring Return Fail-Safe, Multi-Function Technology

Technical data sheets

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

Cables. U.S. Registered Trademark EN0B-0341GE51 R0402 Copyright 2002 Honeywell Inc. All rights reserved

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Brief description. Type overview

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Products no longer available

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

N05, N10 SERIES NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING CONTROL

ECON-ZIP-BASE. ZIP Economizer Base Module

Compact Electric Actuators AC and DC Voltages 18 Nm/160 inch lbs

Fast Route to Reliable Energy Savings ZIP Economizer

ECM3000. Control Motor

THERMOSTATS & CONTROLLERS

Use. Functions. OpenAir TM. Linear version, modulating, AC 24 V

Brief description. Type overview

AV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range

Control Motor ECM3000

599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control

Products no longer available

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

Linear Actuators (235N)

Output signal active note. Output signal. temperature DC V, DC V DC V, DC V DC V

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview

N20010-SER. NON-SPRING RETURN DAMPER ACTUATOR 20 Nm (177 lb-in) FOR ADJUSTABLE MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA

Rotary version, three-position control

599 Series Zone Valve Actuator SF Series Electronic Valve Actuator, 2-position Control

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

N20, N34 SERIES. NON-SPRING RETURN DAMPER ACTUATOR 20/34 Nm (177/300 lb-in) FOR FLOATING / 2-POSITION CONTROL SPECIFICATIONS GENERAL FEATURES

Available with actuator function: POWER OPEN - POWER CLOSE FAILSAFE MODULATING FAILSAFE MODULATING. Overview

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT

N20010, N NON-SPRING RETURN DAMPER ACTUATOR 20/34 Nm (177/300 lb-in) FOR MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA

Technical data. PRCA-BAC-S2-T en-gb subject to changes 1

J3C-H20DPS 25Nm Smart Electric Actuator Type: J3C Model: H20DPS

General-Purpose Photoelectric Sensor

VA-7700 Series. Electric Valve Actuators. Product Bulletin

clarity 3 VAV Programmable Controller

Digital ac/dc (24V) Input Module

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

RA Electric Rotary Actuator 20 Nm to 60 Nm for butterfly valves

N05010/N10010 NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / 2-POSITION CONTROL SPECIFICATIONS

N0524/N1024, N POS/N POS

ML7421A,B Electric Linear Valve Actuators

ASI Systems ML5740A Series

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

I ntroduction. RA Fast Running Electric Actuator. Features and Benefits

Standard. Functions Functions MFT. Multi-Function Technology. Fully Customizable. Proportional Control. Pre-Set Configuration.

Air damper actuators

Output Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W

Electric Actuators Type 5824 (without fail-safe action) Type 5825 (with fail-safe action)

SIAC-PS 3G SIGNAL ISOLATOR WITH POWER SUPPLY (PART NO. 8890) INSTALLATION INSTRUCTIONS

VAV system solution for non-pressure dependent applications in enclosed spaces

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Proportional Control Unit (PCU)

ECON ELECTRIC ACTUATOR Fig. 7907, type ELA

ASI Systems ML5720A Series

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

Installation, Operation and Maintenance Manual

60 mm sq. (2.36 inch sq.)

Transcription:

NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V orque min. 54 in-lb for control damper surfaces up to 12 sq ft. Application For on/off, fail-safe control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer's specifi cations. Control is On/Off from an auxiliary contact or a manual switch. he actuator is mounted directly to a damper shaft up to 1.05" in diameter by means of its universal clamp. A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft. echnical Data NKQB24-1, NKQX24-1 Power supply 24VAC ±20% 50/60Hz 24VDC ±10% Power consumption 11W (3W) ransformer sizing 22VA (class 2 power source) Electrical connection 18 GA plenum rated cable ½" conduit connector protected NEMA 2 (IP54) 3 ft [1m] 10 ft [3m] 16 ft [5m] Overload protection electronic throughout 0 to 95 rotation Operation range Y on/off Input impedance 1500 Ω Angle of rotation max. 95, adjustable with mechanical stop electronically variable orque 54 in-lb [6 Nm] Direction of rotation reversible with switch Fail-safe position adjustable with dial, 0 to 1 in 10 increments Position indication refl ective visual indicator (snap-on) Manual override external push button Running time normal operation fail-safe 4 seconds (default), variable 4 to 10 seconds 4 seconds Humidity 5 to 95% RH non-condensing (EN 60730-1) Ambient temperature -22 F to +122 F [-30 C to +50 C] Storage temperature -40 F to +176 F [-40 C to +80 C] Housing NEMA2, IP54, UL enclosure type 2 Housing material UL94-5VA Agency list culus acc. to UL 60730-1A/-2-14 CAN/CSA E60730-1:02 CE acc. to 2004/108/EC and 2006/95/EC Noise level < 60dB(A) Servicing maintenance free Quality standard ISO 9001 Weight 2.4 lbs [1.10 kg] Initial charge 9 to 15 seconds Bridge time 0 second delay before fail-safe activates Operation he NKQ..24-1 actuator provides 95 of rotation and a visual indicator shows the position of the actuator. When reaching the damper or actuator end position the actuator automatically stops. he gear can be manually disengaged by pressing the black button located on the actuator cover. he NKQ..24-1 actuators use a brushless DC motor, which is controlled by an Application Specifi c Integrated Circuit (ASIC). he ASIC monitors and controls the actuators rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in a holding mode. he actuator is electronically protected against overload. he anti-rotation strap supplied with the actuator will prevent lateral movement. Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto the actuator body for signaling and switching functions. Fail-Safe Indication LED status indicator lights sequence: Yellow off / Green on: operation ok, no faults Yellow off / Green blinking: fail-safe mechanism is active Yellow on / Green off: fault is detected Yellow off / Green off: not in operation / capacitors charging Yellow on / Green on: adaption running Dimensions (inches [mm]) 2.05 [52] 1.18 [30] 5.47 [139] 6.30 [160] 1.61 [41] 3.15 [80] 3.86 [98] D321 199

NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V Accessories K-AM25 ¾" [20mm] Shaft Clamp ZG-102 Multiple Actuator Mounting Bracket ZG-NMA Crank arm Adaptor Kit ZG-JSA (-1,2,3) Jackshaft Adaptors for Hollow Jackshafts ZS-100 Weather Shield - Steel ZS-150 Weather Shield - Polycarbonate ZS-260 Explosion Proof Housing ZS-300 (-1) (-5) NEMA 4X Housing ool-06 8 and 10 mm Wrench PS-100 Actuator Power Supply Simulator S1A, S2A Auxiliary Switch(es) P370 Shaft Mount Auxiliary Switch P A Feedback Potentiometers ZG-X40 ransformer Note: When using NKQB24-1 and NKQX24-1 actuators, only use accessories listed on this page. ypical Specifi cation On/off control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to shaft up to 1.05" diameter. Actuators shall have Brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be culus listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. Wiring Diagrams 1 Provide overload protection and disconnect as required. 2 CAUION Equipment Damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC. Meets UL requirements without the need of an electrical ground connection. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. W399 no_org On/Off control 200

NKQB24-SR, NKQX24-SR Proportional Control, Electronic Fail-Safe, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20mA orque min. 54 in-lb for control damper surfaces up to 12 sq ft. Application For fail-safe, proportional control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer s specifi cations. he actuator is mounted directly to a damper shaft up to 1.05 in diameter by means of its universal clamp. A crank arm and several mounting brackets are available for applications where the actuator cannot be direct coupled to the damper shaft. he actuator operates in response to a 2 to 10 VDC or, with the addition of a 500 resistor, a 4 to 20 ma control input from an electronic controller or positioner. A 2 to 10 VDC feedback signal is provided for position indication. Not to be used for a master-slave application. echnical Data NKQB24-SR, NKQX24-SR Power supply 24VAC ±20% 50/60Hz 24VDC ±10% Power consumption 11W (3W) ransformer sizing 22VA (class 2 power source) Electrical connection 18 GA plenum rated cable ½" conduit connector protected NEMA 2 (IP54) 3 ft [1m] 10 ft [3m] 16 ft [5m] Overload protection electronic throughout 0 to 95 rotation Operation range Y 2 to 10 VDC, 4 to 20mA Input impedance 100kΩ (0.1 ma), 500Ω Feedback output U 2 to 10VDC, 0.5mA max Angle of rotation max. 95, adjustable with mechanical stop electronically variable orque 54 in-lb [6 Nm] Direction of rotation reversible with switch Fail-safe position adjustable with dial, 0 to 1 in 10 increments Position indication refl ective visual indicator (snap-on) Manual override external push button Running time normal operation fail-safe 4 seconds (default), variable 4 to 10 seconds 4 seconds Humidity 5 to 95% RH non-condensing (EN 60730-1) Ambient temperature -22 F to +122 F [-30 C to +50 C] Storage temperature -40 F to +176 F [-40 C to +80 C] Housing NEMA2, IP54, UL enclosure type 2 Housing material UL94-5VA Agency list culus acc. to UL 60730-1A/-2-14 CAN/CSA E60730-1:02 CE acc. to 2004/108/EC and 2006/95/EC Noise level 60dB(A) Servicing maintenance free Quality standard ISO 9001 Weight 2.40 lbs [1.1 kg] Initial charge 9 to 15 seconds Bridge time 0 second delay before fail-safe activates Operation he NKQ..24-SR actuator provides 95 of rotation and a visual indicator shows the position of the actuator. When reaching the damper or actuator end position the actuator automatically stops. he gear can be manually disengaged by pressing the black button located on the actuator cover. he NKQ..24-SR actuators use a brushless DC motor, which is controlled by an Application Specifi c Integrated Circuit (ASIC). he ASIC monitors and controls the actuators rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in a holding mode. he actuator is electronically protected against overload. he anti-rotation strap supplied with the actuator will prevent lateral movement. Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto the actuator body for signaling and switching functions. Fail-Safe Indication LED status indicator lights sequence: Yellow off / Green on: operation ok, no faults Yellow off / Green blinking: fail-safe mechanism is active Yellow on / Green off: fault is detected Yellow off / Green off: not in operation / capacitors charging Yellow on / Green on: adaption running Dimensions (inches [mm]) 2.05 [52] 1.18 [30] 5.47 [139] 6.30 [160] 1.61 [41] 3.15 [80] 3.86 [98] D321 201

NKQB24-SR, NKQX24-SR Proportional Control, Electronic Fail-Safe, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20mA Accessories K-AM25 ¾" [20mm] Shaft Clamp ZG-102 Multiple Actuator Mounting Bracket ZG-NMA Crank arm Adaptor Kit ZG-JSA (-1,2,3) Jackshaft Adaptors for Hollow Jackshafts ZS-100 Weather Shield - Steel ZS-150 Weather Shield - Polycarbonate ZS-260 Explosion Proof Housing ZS-300 (-1) (-5) NEMA 4X Housing ool-06 8 and 10 mm Wrench PS-100 Actuator Power Supply Simulator S1A, S2A Auxiliary Switch(es) P370 Shaft Mount Auxiliary Switch Note: When using NKQB24-SR and NKQX24-SR actuators, only use accessories listed on this page. ypical Specifi cation Proportional control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to shaft up to 1.05" diameter. Actuators must provide proportional damper control response to a 2 to 10 VDC or, with the addition of a 500Ω resistor, a 4 to 20 ma control input from an electronic controller or positioner. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be culus listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. Wiring Diagrams 1 Provide overload protection and disconnect as required. 2 CAUION Equipment Damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC. Meets UL requirements without the need of an electrical ground connection. he ZG-R01 500 Ω resistor may be used. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. W399_08 Electrical Installation Wiring diagram Note Connect via safety isolation transformer.! Parallel connection of other actuators possible. Note performance data for supply. ~ + 1 2 3 5 Y U DC 0... 10 V DC 2... 10 V Cable lengths Note When several actuators are connected in parallel, the maximum cable length must be divided by the number of actuators. ~ Y U 1 2 3 5 N L AC 230 V AC 24 V Y L 2 L 1 U C L tot A C VDC/4-20 ma L 1 Note here are no special restrictions on installation if the supply and data cable are routed separately. 1 2 3 5 A Cable colors: 1 = black 2 = red 3 = white 5 = orange A = Actuator C = Control unit L1 = Belimo connecting cable, 1 m (4 x 0.75 mm 2 ) L2 = Customer cable Ltot = Maximum cable length Cross section L2 Max. cable length Example for DC Ltot t = L1 + L2 / AC DC 0.75 mm 2 <30 m <5 m 1 m (L1) + 4 m (L 2) 1.00 mm 2 <40 m <8 m 1 m (L1) + 7 m (L 2) 1.50 mm 2 <70 m <12 m 1 m (L1) + 11 m (L 2) 2.50 mm 2 <100 m <20 m 1 m (L1) + 19 m (L 2) ~ A = Actuator C = Control unit L1 = Belimo connecting cable, 1 m (4 x 0.75 mmm 2 ) 202

NKQX24-MF Proportional Control, Electronic Fail-Safe, Direct Coupled, 24V, Multi-Function echnology orque min. 54 in-lb for control damper surfaces up to 12 sq ft. Application For fail-safe, proportional control of dampers in HVAC systems. Actuator sizing should be done in accordance with the damper manufacturer s specifi cations. A feedback signal is provided for position indication. Default/Confi guration Default parameters for 2 to 10 VDC applications of the NKQ..-MF actuator are assigned during manufacturing. If required, custom versions of the actuator can be ordered. he parameters noted in the echnical Data table are variable. hese parameters can be changed by three means: MF MULI-FUNCION ECHNOLOGY Pre-set or custom confi gurations from Belimo. Confi gurations set by the customer using the most current MF PC tool software application. Handheld ZH-GEN. echnical Data NKQX24-MF Power supply 24VAC ±20% 50/60Hz 24VDC ±10% Power consumption 11W (3W) ransformer sizing 22VA (class 2 power source) Electrical connection 18 GA plenum rated cable ½" conduit connector protected NEMA 2 (IP54) 3 ft [1m] 10 ft [3m] 16 ft [5m] Overload protection electronic throughout 0 to 95 rotation Operation range Y 2 to 10 VDC, 4 to 20mA (default) variable (VDC, on/off) Input impedance 100 kω (0.1 ma), 500 Ω 1500 Ω (on/off) Feedback output U 2 to 10VDC, 0.5mA max, VDC variable Angle of rotation max. 95, adjustable with mechanical stop electronically variable orque 54 in-lb [6 Nm] Direction of rotation reversible with switch Fail-safe position adjustable with dial or tool 0 to 100% in 10% increments Position indication refl ective visual indicator (snap-on) Manual override external push button Running ime normal operation fail-safe 4 seconds (default), variable 4 to 10 seconds 4 seconds Humidity 5 to 95% RH non-condensing (EN 60730-1) Ambient temperature -22 F to +122 F [-30 C to +50 C] Storage temperature -40 F to +176 F [-40 C to +80 C] Housing NEMA2, IP54, UL enclosure type 2 Housing material UL94-5VA Agency list culus acc. to UL 60730-1A/-2-14 CAN/CSA E60730-1:02 CE acc. to 2004/108/EC and 2006/95/EC Noise level 60dB(A) Servicing maintenance free Quality standard ISO 9001 Weight 2.40 lbs [1.1 kg] Initial charge 9 to 18 seconds Bridge time programmable 0 to 5 second (0 seconds default) delay before fail-safe activates Operation he NKQ..24-MF actuator provides 95 of rotation and a visual indicator shows the position of the actuator. When reaching the damper or actuator end position the actuator automatically stops. he gear can be manually disengaged by pressing the black button located on the actuator cover. he NKQ..24-MF actuators use a brushless DC motor, which is controlled by an Application Specifi c Integrated Circuit (ASIC). he ASIC monitors and controls the actuators rotation and provides a digital rotation sensing (DRS) function to prevent damage to the actuator in a stall condition. Power consumption is reduced in a holding mode. he actuator is electronically protected against overload. he anti-rotation strap supplied with the actuator will prevent lateral movement. Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto the actuator body for signaling and switching functions. Fail-Safe Indication LED status indicator lights sequence: Yellow off / Green on: operation ok, no faults Yellow off / Green blinking: fail-safe mechanism is active Yellow on / Green off: fault is detected Yellow off / Green off: not in operation / capacitors charging Yellow on / Green on: adaption running Yellow blinking / Green on: communication with programming tool Dimensions (inches [mm]) 2.05 [52] 1.18 [30] 5.47 [139] 6.30 [160] 1.61 [41] 3.15 [80] 3.86 [98] D321 203

NKQX24-MF Proportional Control, Electronic Fail-Safe, Direct Coupled, 24V, Multi-Function echnology Accessories K-AM25 ¾" [20mm] Shaft Clamp ZG-NMA Crank arm Adaptor Kit ZG-JSA (-1,2,3) Jackshaft Adaptors for Hollow Jackshafts ZS-100 Weather Shield - Steel ZS-150 Weather Shield - Polycarbonate ZS-260 Explosion Proof Housing ZS-300 (-1) (-5) NEMA 4X Housing ool-06 8 and 10 mm Wrench PS-100 Actuator Power Supply Simulator S1A, S2A Auxiliary Switch(es) P370 Shaft Mount Auxiliary Switch P A Feedback Potentiometers SGA24 Min positioners in NEMA 4 Housing SGF24 Min positioners for fl ush panel mounting ZG-R01 Resistor for 4 to 20 ma Conversion ZG-X40 ransformer Note: When using NKQX24-MF actuators, only use accessories listed on this page. ypical Specifi cation Proportional control damper actuators shall be electronic direct-coupled type, which require no crank arm and linkage and be capable of direct mounting to shaft up to 1.05" diameter. Actuators must provide proportional damper control response to a 2 to 10 VDC or, with the addition of a 500Ω resistor, a 4 to 20 ma control input from an electronic controller or positioner. Actuators shall have brushless DC motor technology and be protected from overload at all angles of rotation. Actuators shall have reversing switch and manual override on the cover. Run time shall be constant and independent of torque. Actuators shall be culus listed, have a 5-year warranty, and be manufactured under ISO 9001 International Quality Control Standards. Actuators shall be as manufactured by Belimo. Wiring Diagrams 1 Provide overload protection and disconnect as required. 2 CAUION Equipment Damage! Actuators may be connected in parallel if not mechanically mounted to the same shaft. Power consumption and input impedance must be observed. 3 Actuators may also be powered by 24 VDC. Meets UL requirements without the need of an electrical ground connection. he ZG-R01 500 Ω resistor may be used. WARNING Live Electrical Components! During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualifi ed licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. W399_13 VDC/4-20 ma On/Off control W399_13 204