Creating an Energy-Efficient, Automated Monitoring System for Temperature and Humidity at a World-Class Data Center

Similar documents
CyrusOne Case Study About CyrusOne

survey, 71% of respondents listed Improving capacity planning as a top driver for buying DCIM 1.

Improved Reliability Through Wireless Monitoring and Control

HPC Solutions in High Density Data Centers

Saving Critical Space. Cable Management Solutions

SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers

:: While reducing energy costs remains a factor, the most commonly reported driver of DCIM investment plans is capacity planning -Gartner*

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

RF Code Delivers Millions of Dollars in Annual Power & Cooling Savings for CenturyLink

Xerox. Manufacturing. Case Study. About Xerox. Manufacturing

Running Your Data Center Under Ideal Temperature Conditions

Smart Data Center Solutions

Extend Your Reach. with. Signature Core Fiber Optic Cabling System

Effectiveness and Implementation of Modular Containment in Existing Data Centers

Panduit Unified Operations Center

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Cisco Nexus 9396 Thermal Duct and Cabling Guide

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

2 visit

ENCLOSURE HEAT DISSIPATION

Making Your Data Center More Efficient

AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings

Chilled Water Computer Room Air Handler (CRAH) Critical Infrastructure for the World s Leading Data Centers

APC APPLICATION NOTE #74

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

CenturyLink Data Center Services Herndon, Virginia

<Insert Picture Here> Austin Data Center 6Sigma DC CFD Model

Reducing Data Center Cooling Costs through Airflow Containment

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

CenturyLink Data Center Services Omaha, Nebraska

The Drivers Behind High-Density Systems

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Data Center Cooling An Owner s Perspective. 11 February 2016

Data Center Optimized Controls

Physical Infrastructure Management Solutions

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

Measurement and Management Technologies (MMT) for more energy efficient Data Center and Telecommunication Facilities

Next Generation Cooling

November/December 2011

Close-coupled cooling

World Class. Globally Certified. High Availability.

Why would you want to use outdoor air for data center cooling?

Precision Cooling Mission Critical Air Handling Units

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Green IT and Green DC

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

Power & Cooling Considerations for Virtualized Environments

Harsh Environment Solutions

84 kw, Tier 3, Direct Expansion, 937 ft 2

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Variable Density, Closed-Loop, Water-Cooled Data Center Solution

Data Center Infrastructure Management (D.C.I.M.)

Impact of Air Containment Systems

INNOVATE DESIGN APPLY.

INNOVATE DESIGN APPLY.

Where s the Heat Coming From. Leland Sparks Global Account Technical Consultant Belden

Optimizing Cooling Performance Of a Data Center

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Reclaim Wasted Cooling Capacity Now Updated with CFD Models to Support ASHRAE Case Study Data

TIER 3+ CARRIER NEUTRAL DATA CENTER TELEPOINT SOFIA EAST THE LATEST ADDITION TO OUR FAST-GROWING DATA CENTER LOCATIONS.

Optimiz Chilled January 25, 2013

Cisco Lab Setpoint Increase. Energy Efficient Data Center Demonstration Project

FOM 2.4 The Performance Indicator: Assessing & Visualizing Data Center Cooling Performance

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Liebert DCW CATALOGUE

ECOBAY: Closed loop water cooled server cabinet for data centers

Overcoming the Challenges of Server Virtualisation

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Planning a Green Datacenter

Recapture Capacity for Existing. and Airflow Optimization

SmartRow Solution Intelligent, Integrated Infrastructure for the Data Center

SMART SOLUTIONS TM INTELLIGENT, INTEGRATED INFRASTRUCTURE FOR THE DATA CENTER

Application of TileFlow to Improve Cooling in a Data Center

STULZ Micro DC. with Chip-to-Atmosphere TM Liquid to Chip Cooling

16 and 32 Amp PanView iq TM (PViQ TM ) Switched and Environmental Power Outlet Units

20 Amp PanView iq TM (PViQ TM ) Switched and Environmental Power Outlet Units

Smart Data Centres. Robert M Pe, Data Centre Consultant HP Services SEA

30, 50, and 60 Amp PanView iq TM (PViQ TM ) Switched and Environmental Power Outlet Units

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

MEASURE MONITOR UNDERSTAND

The Four 4R s. of Data Center Airflow Management. About Upsite Technologies

Survey and Audit Service Schedule. Airflow and Thermal Imaging Survey Service Schedule. Data Centre Solutions Expertly Engineered

Liquid Cooling Package LCP Cooling Systems

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Measurement and Management Technologies (MMT)

Data Center Airflow Management Basics: Comparing Containment Systems

Precision Cooling. Precision Cooling Advantages

Liebert : The Right Cooling For IT Environments

WIRELESS ENVIRONMENTAL MONITORS

Energy Efficient Data Centers

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

M+W Group s Visionary Delta Datacenter

Thermal management. Thermal management

Cost Model Energy Benefits DirectAire & SmartAire Overview & Explanation

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

REPORT. Energy Efficiency of the San Diego Supercomputer Center and Distributed Data Centers at UCSD. Prepared for:

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

Transcription:

About CyrusOne CyrusOne is a world-renowned enterprise data center provider that offers 40 data centers across the U.S., Europe and Asia with a three million-plus square feet of total net rentable space. Since 2001, the company has been designing, building and operating certified, highly secure and reliable multi-tenant data centers for mission-critical IT environments. As a result, over the past 15 years, CyrusOne has grown to become the third largest data center provider in the U.S. with over 925 customers worldwide. Global firms, Fortune 20 corporations and companies of all sizes seeking colocation trust CyrusOne to provide scalable, reliable and secure data centers and connectivity solutions to meet their ever-changing needs.

Company CyrusOne Country United States Industry Data Center Solutions Business Challenges To offer customers a more costeffective, energy efficient data center by implementing a state-of-the art automated monitoring system. Panduit Solution The Active Control feature of the SynapSense SynapSoft Software, a modular cooling platform, is a technology that provides energy savings and increased efficiency by continuously aligning cooling capacity with changes in IT load. Business Benefits A data center infrastructure management system that increases cooling and operational efficiencies while providing CyrusOne with the ability to exceed power and cooling standards for its customers. Creating an Energy-Efficient, Automated Monitoring System for Temperature and Humidity at a World-Class Data Center Panduit SynapSense Solution helps CyrusOne improve cooling efficiency while increasing operational effectiveness and decreasing energy costs Business Challenges CyrusOne s Austin Data Center II is one of 11 locations in Texas alone: located in the Met Center business park, this 70,000 square-foot facility is the first of an optional four-phase, 288,000 square-foot data center campus. Since it is conveniently located just seven minutes from Austin-Bergstrom International Airport, it is in an ideal location for production and co-production server environments for national, international, and local companies. To optimize Data Hall 1 within the data center (a 20,000 square-foot facility), CyrusOne needed to monitor temperature and humidity for its customers SLAs, and to conserve as much energy as possible. Even though the data center had been built only a few years prior, CyrusOne felt that it could make its state-ofthe-art facility even better. Panduit s SynapSense helps us improve efficiency and sustainability. It provides our customers with visibility into what s going on with their servers and is a key part of our SLAs. Plus, we recover cooling capacity that helps us to realize additional operational and power efficiencies. Jason Dingess Program Manager, Datacenter Systems, CyrusOne 2

Strategic Objectives CyrusOne s main goals for Data Hall 1 at the Austin Data Center II site were to provide environmental monitoring and optimize the space by improving operational reliability and energy savings. By doing this, CyrusOne could achieve its end goal, which was to lower its operating costs while exceeding power and cooling standards for its customers. In addition, the data center was equipped with 13 chilled water cooling units that were not working at their highest efficiency. This needed to be addressed as it was causing the other 11 units to work at a faster rate, therefore burning more energy. Panduit Solution CyrusOne chose the SynapSense Active Control feature to help achieve their goals. The Active Control feature is a technology that provides energy savings and increased efficiency by continuously aligning cooling capacity with changes in IT load. Its granular deployment of wireless sensors measure server inlet temperature and sub-floor pressure differential to manage computer room air handler (CRAH) return temperature set points and variable fan speeds. This unique approach optimizes cooling capacity and saves a great deal in cooling costs by minimizing the fan energy needed to meet server CFM and ASHRAE requirements. After conducting a careful and thoughtful assessment of the data center, the Panduit team first turned on the two Stulz units which had not been in use. This helped prevent air leaks in the sub-floor and caused the other units to run at a slower rate. Then they installed and ran all of the 13 chilled water cooling units with the Active Control feature and replaced 63 perforated tiles with solid floor tiles, which allowed them to raise the sub-floor pressure and lower the fan speeds. The Active Control feature works alongside the existing Computrols Building Automation System (CBAS). Because CBAS was already wired into the data center s Stulz units, communicating via Modbus, Panduit was able to streamline the process by sending its control set points to CBAS and having CBAS pass the set points to the Stulz units. This setup left all the existing BMS functionality in place while providing another layer of (continued) 3

4

Panduit Solution (continued) redundancy should the Active Control feature experience downtime for any reason. Because the Active Control does not make any control decisions based on humidity, the humidification and dehumidification settings on the Stulz units were disabled. This ensures that the Stulz units do not override the Active Control fan speed set points by going into dehumidification mode. A Stulz representative was onsite to make any necessary changes. At the same time, he also increased the fan speed and valve position limits. Initially, the fan speeds were limited to 60-80% and the valves from 25-100%. Today, the limits are 50-100% and 0-100%, respectively. The Active Control feature uses two redundant control servers, with only one being active and issuing commands. If the primary server fails or loses communication, the second server will take over seamlessly with no interruption to the control system. If the Active Control loses communication to CBAS for longer than 15 minutes, CBAS will take control of the Stulz units and hold the last set points received from Active Control until communication is restored and an operator issues a command to relinquish control back to Active Control. If the Stulz units lose communication to both CBAS and the Active Control, they will default to their own local settings, which are a 70-degree Return Air Temperature (RAT) set point and 80% fan speed. As for environmental monitoring, Panduit installed a number of sensors throughout the data center s cabinet, including temperature sensors in both the front and back as well as humidity and pressure sensors. Panduit also installed CRAH nodes that measure the supply and return temperatures as well as the return air s relative humidity. The following products represent the solution that Panduit deployed: 178 SynapSense Wireless Mesh ThermaNode EZ sensors consisting of one temperature sensor in the front of the cabinet and one sensor in the rear of the cabinet 25 SynapSense Wireless Mesh ThermaNode EZ-H sensors which are the same as the above but have an additional humidity sensor in the front of the cabinet 44 SynapSense Wireless Mesh Pressure Nodes measure the static differential pressure in the sub-floor 13 CRAH wireless mesh sensors that measure supply and return temperatures as well as return air relative humidity 3 SynapSense Wireless Mesh Gateways 5

Business Benefits Before Panduit implemented the Active Control feature, there were 11 CRAH units running with an average fan speed of 73%, all with return air temperature set points of 70 F. The two fan units that were turned off were not sealed, and cold air from the sub-floor was blowing back into the return plenum. After implementing the Active Control feature, all 13 fans were running with an average speed of 62%, which brought the power used down from 64.3kW to a startling 37.9kW. This is especially impressive since the 64.3kW accounted for 11 out of 13 fans working, while the 37.9kW is representative of Panduit turning on the two fans that were turned off, bringing the fan total to 13. At the start of the project, the average rack inlet temperature in the data hall was 67 F and the average under-floor pressure was slightly under 0.030 inches of H 2 O. Panduit set the target point for the rack inlet temperatures at 78 F and the control system increased the return air temperature (RAT) set point to meet this inlet temperature, since the majority of the rack inlet temperatures were below recommended values. Today, CyrusOne is experiencing a 2-7 F increase in the RAT set points throughout the data hall, with the refrigeration power decreased to 137.4kW from 149.9kW. In addition, the floor pressure is perfectly balanced. 6

LiveImaging Pressure Map, Pre/Post Active Control, Pressure Before After Map Legend of Pressure Differential in Inches of H 2 0 0.01.03.04.05.06 After optimization and implementation of the Active Control feature, there was a decrease in fan speeds over all 11 units that were previously on, even though the average floor pressure in the data hall increased (see Figure 1). There was also a 2-7 F increase in the return air temperature (RAT) set points throughout the data hall. Sub-Floor Temperatures Before and After the Active Control Feature Before After Map Legend 50 60 70 80 90 100 This LiveImaging Temperature map illustrates the increase sub-floor temperatures resulting from the increased RAT set points sent by the Active Control feature. The upper portion of the data center remains cold due to the dense IT load in that area and corresponding high return temperatures. 7

Panduit Corp. World Headquarters Tinley Park, IL 60487 cs@panduit.com US and Canada: 800.777.3300 Europe, Middle East, and Africa: 44.20.8601.7200 Latin America: 52.33.3777.6000 Asia Pacific: 65.6305.7575 www.panduit.com 2018 Panduit Corp. ALL RIGHTS RESERVED. Printed in the U.S.A. CPCS67-SA ENG 1/2018