EtherNet/IP Configuration for a Moxa MGate 5105-MB-EIP and an Allen-Bradley CompactLogix L32E. Copyright 2013 Moxa Inc Released on July 15, 2013

Similar documents
2013 Moxa Inc Released on Sep 15, 2013

MGate EIP 3000 Series to connect RSLinx with the. Allen-Bradley SLC 500/Micrologix family

Using an AIMCO Gen 4 Controller on a Rockwell PLC with EtherNet IP

Communicating To Acromag Series 9xxEN-6xxx Ethernet Modules In An Allen Bradley CLX5555 Control System

Communicating To Acromag Series 9xxEN-6xxx and XTxxx2-xxx Ethernet Modules In An Allen Bradley ControlLogix System

1 Application Description System Topology Hardware and Software Requirements About KingSCADA

Replacing the AB 1761-NET-ENI with the MGate EIP3000 to perform an EIP-to-DF1 conversion

Integration of Dimetix D Series Laser via Ethernet IP with Allen Bradley Systems PLC July 19, 2018

Application Note: 105U/905U-G-ET1 EtherNet IP & CompactLogix PLC

Using an AIMCO Gen 4 Controller on a Rockwell PLC with Profibus

Application Note. Adding an MPiec Controller as an EtherNet/IP Adapter to Allen Bradley CompactLogixL32E. Applicable Product: MPiec, CompactLogix5332E

How to Use the TIA Portal to Set a Siemens PLC and the MGate 5103

Using NI LabVIEW with iologik E2210 servers

CM-EIP-1 G9SP Safety Controller EtherNet/IP Adapter Application and Setup Guide

Configure an X-Gateway EtherNet/IP Adapter with RSLogix 5000

eth1000_large.jpg Using ICC ETH-1000 EtherNet/IP Interface with Mitsubishi iq PLC

How to Upgrade or Recover the Firmware of the UC-7400 Series Embedded Computers

Operating a Power Xpert C445 Global Motor Management Relay with a Rockwell PLC via Ethernet/IP

One Gateway That Can Do It All

APPLICATION NOTE. Reading/writing data from an X-gateway EtherNet/IP using ControlLogix5000 MSG instruction SCM HMS Industrial Networks

eth1000_large.jpg Using ICC ETH-1000 EtherNet/IP Interface with Mitsubishi iq PLC

1. System Topology Required Equipment and Components PcVue SCADA Modbus Slave MGate 5109 Setting...

APPLICATION NOTE: Reading/writing data from Anybus-S EtherNet/IP using ControlLogix5000 MSG instruction. HMS Industrial Networks

Technical Application Note

Copyright Information. Copyright ThePlcCorner.com

Application Note. Adding an MPiec Controller as an EtherNet/IP Adapter to Allen Bradley ControlLogix 5555

Setting up Pinnacle Ethernet IP communication with Allen Bradley PLCs

EIP ET200 Configuration Tool User Reference Guide

Field Upgrading Bulletin 1404 Power Monitor Version 4.2x base and 4.1x Ethernet Communications Firmware

Kontakt. Internet: Web Kontakt-Formular:

EN7000 & Anybus Communicator EIP/MODBUS-RTU user guide 1

D0 DEVNETS and Allen Bradley Set up. RSNetworx

TeSys T LTM R EtherNet/IP with a Third-Party PLC Quick Start Guide

Connecting the iologik 2000 to a SolarWinds NPM

How to Configure the Allen Bradley CompactLogix for EtherNet/IP Communications to MultiRanger/ HydroRanger 200 HMI

Technical Note. Typical Scenario Performance Test

How to Configure the MGate 5114 with IEC SCADA. 1 System Topology Protocol Simulators... 4

1. System Topology Required Equipment and Components Hardware Equipment Software Equipment... 6

Using a RESTful API to Connect to Remote I/Os

Using NI LabVIEW with iologik E2210 servers

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

CP1W-EIP01-US CP1L / CP1H EtherNet/IP Adapter To Allen-Bradley ControlLogix or CompactLogix with EtherNet/IP Setup Guide

For the configuration of the I/O-modules in a control system an EDS-file is required. The names of the files are as follows:

20-COMM-H RS485 HVAC Adapter Firmware Revision 2.010

How to Upload Device Data to a Remote Database Using the Log Upload Function

1. SELECTING NEW PROTOCOLS

Tritex II EtherNet/IP - Option

CENTERLINE 2100 Motor Control Centers EtherNet/IP Network Adapter

Operating a PowerXL DC1/DE1 Drive with a Rockwell PLC on Ethernet/IP

PLX51-DF1-ENI. DF1 Router DF1 to EtherNet/IP TM Router USER MANUAL

Your Global Automation Partner. Startup. Getting Started Guide

P2 Configuration Guide

1.0 01/02/07 QuickStart_EtherNet/IP comm with Rockwell PLCs

Sherpa R-IN32M3 EtherNet/IP adapter communication stack for Renesas Electronics Corporation s R-IN32M3 series industrial Ethernet controller

Brad SST Ethernet and Serial Communication Module for ControlLogix

EtherNET/IP Software Help File

ControlLogix Redundancy Update and Module Replacement Guidelines

DeviceNet - Getting Started User's Manual

OMRON Rockwell CompactLogix or ControlLogix

FEN20 Start-up Guide. Date: Version: 1.4. Created By: Division 3

DL7000-ETH/DH+ Application Note

Addendum to Verbatim Gateway Owner's Manual How to configure a Verbatim EtherNet/IP with RSLogix 5000

Electronic Displays, Inc. EDV111 Series LED Signs Allen Bradley AOI (Add on Instruction) Software Manual

Version 2.0. January For Firmware versions 4.25 and 5.2

Integration of In-Sight with AB PLCs running RSLogix

Gateway for EIP - DF1 Allen-Bradley PLC

ivu Plus Industrial Ethernet Instruction Manual

Technical Note. ACSI Motor/Drive/Controller & ACS Drive with Allen Bradley RSLogix 5000 EtherNet/IP Setup Guide. Contents

How to Build an IoT Application with Moxa's ThingsPro and AWS IoT Service

Building a groov HMI for Allen-Bradley Logix Systems. About groov. Building a groov HMI for Allen-Bradley Logix. A-B Systems and groov

Communication Setting Sample

Addendum to Catalyst Owner's Manual How to configure a Catalyst EtherNet/IP with RSLogix 5000

QUICK START GUIDE. Configuration of the MTR-ECI-EP-SA with integrated EtherNet/IP. Rev 003

Using the WAGO as Remote I/O with a ControlLogix Ethernet/IP Bridge Module Application note

EtherNet/IP DEVICE CONFIGURATION. A Step by Step Guide

Introduction to ControlNet with ControlLogix

PowerFlex 753 Drives (revision )

Application Note. Using the Yaskawa V1000 AC Drive and SI-N3/V DeviceNet Option Kit with AB CompactLogix Programmable Controller. Applicable Product:

AKD Ethernet IP: Using Compactlogix or Contrologix With No Cyclic Poll ( Explicit Messaging Only )

Using the WagoAppEtherNetIP_Adapter library with a CompactLogix Controller A500930

Outline. EtherNet/IP Introduction EtherNet/IP products EtherNet/IP Ring Topology Implicit and Explicit Message Applications

User Manual APAX Software Manual

20-COMM-E EtherNet/IP Adapter Firmware Revision 4.002

WebAccess AB LOGIX PLC Ethernet Driver Guide. Advantech WebAccess. - AB LOGIX PLC Ethernet Driver Guide Version: 1.02

WebAccess Driver Configuration Manual

Pluto Gateway Rockwell PLC Integration Manual (RSNetWorx for DeviceNet)

Technical Note. MVI56(E)-MNETR Add-On Instruction Installation Guide

How to Build a Real-Time IIoT Application with Moxa's ThingsPro and Cirrus Link's Sparkplug

SMG-1100/6100 User s Manual

# Byrne Rd, Burnaby, BC, V5J 3J1, Canada Phone: or

Communicating To Acromag Series 9xxEN-60xx Ethernet Modules From Legacy Allen Bradley or Rockwell Automation Devices

Configuration for General DIP Devices. Setting Up RSLinx

20-COMM-E EtherNet/IP Adapter Firmware v4.001

PowerMonitor 5000 Unit Catalog Number Upgrade

PowerFlex 20-HIM-A6 and 20-HIM-C6S HIM Firmware Revision 1.006

EtherNet/IP - Getting Started User's Manual

Powermonitor 1000 Unit

20-COMM-H RS485 HVAC Adapter Firmware Revision 2.009

echochange Setting up data exchange between a Siemens S7-300 and an Allen-Bradley ControlLogix, using Siemens PUT and GET functions How to...

PowerFlex 753 Drives (revision 9.002)

Transcription:

a Moxa MGate 5105-MB-EIP and an Allen-Bradley CompactLogix L32E Contents Moxa Technical Support Team support@moxa.com 1. Introduction... 2 2. Applicable products... 2 3. System requirements... 2 4. System overview... 3 5. Moxa s PROFIBUS device configuration... 3 5.1. Device configuration with MGate Manager... 3 6. PLC configuration... 9 6.1. Install the EDS file... 9 6.2. Configure the EtherNet/IP network...12 6.3. Create RSLogix 5000 project...14 6.4. Create an Ethernet Module for MGate 5105-MB-EIP...15 6.5. Download Configuration to PLC...19 7. Communication Test... 21 7.1. Monitor / Modify Test...21 Copyright 2013 Moxa Inc Released on July 15, 2013 About Moxa Moxa manufactures one of the world s leading brands of device networking solutions. Products include serial boards, USB-to-serial hubs, media converters, device servers, embedded computers, Ethernet I/O servers, terminal servers, Modbus gateways, industrial switches, and Ethernet-to-fiber converters. Our products are key components of many networking applications, including industrial automation, manufacturing, POS, and medical treatment facilities. How to Contact Moxa Tel: +886-2-8919-1230 Fax: +886-2-8919-1231 Web: www.moxa.com Email: info@moxa.com

1. Introduction This application note will explain how to configure a Moxa MGate gateway as an EtherNet/IP Adapter and an Allen-Bradley CompactLogix L32E as an EtherNet/IP Scanner. On the Modbus RTU side, this note will also explain how to connect a Moxa iologik R2110 as a Modbus RTU slave with 12 digital inputs and 8 digital outputs. 2. Applicable products Product Line MGate 5000 series Model Name MGate 5105-MB-EIP, MGate 5105-MB-EIP-T 3. System requirements Description Model / File Name Version Allen-Bradley 1769-L32E controller 1769-L32E CompactLogix5332E 18.12 Rockwell single control platform RSLogix 5000 18.02.00 Moxa RS-485 remote I/O with 12 digital inputs iologik R2110 1.2 and 8 digital outputs Moxa EtherNet/IP-to-Modbus gateway MGate 5105-MB-EIP 1.1 Software utility to configure Moxa devices MGate Manager 1.8 Copyright 2013 Moxa Inc. Page 2 of 21

4. System overview This application note will use the Moxa MGate 5105-MB-EIP for illustration purposes. The system architecture is shown below. 5. Moxa s PROFIBUS device configuration 5.1. Device configuration with MGate Manager 5.1.1. Start MGate Manager on your host computer and click the Search button to locate the Moxa MGate 5105-MB-EIP gateway on your network. Copyright 2013 Moxa Inc. Page 3 of 21

5.1.2. Select the MGate gateway and click the Configuration button to configure it. If MGate Manager requests a password, moxa is the default password. 5.1.3. Select the Network tab to configure the IP address and netmask of the MGate 5105-MB-EIP gateway. In this example, the IP address is 192.168.33.10 and the default netmask is 255.255.255.0. Copyright 2013 Moxa Inc. Page 4 of 21

5.1.4. Select the Serial tab to configure the serial parameters to be the same as the parameters on the Modbus device, which is the iologik R2110 in this example. 5.1.5. Select the Protocol tab to configure the protocol conversion settings. The first sub-tab is Protocol Conversion and shows which protocols are going to be converted. In this demo, select EtherNet/IP <-> Modbus RTU/ASCII from the dropdown menu. Copyright 2013 Moxa Inc. Page 5 of 21

5.1.6. Select the EtherNet/IP tab to configure EtherNet/IP settings. 5.1.7. Since we will use the Allen-Bradley PLC as the EtherNet/IP Scanner, select Adapter for the MGate 5105-MB-EIP s Mode selection. 5.1.7.1. Then select Automatic for I/O data size configuration so that the MGate 5105-MB-EIP will automatically map the I/O data. 5.1.7.2. Select the Modbus RTU/ASCII tab to configure Modbus RTU/ASCII settings and Modbus commands. Refer to the iologik R2110 user s manual to understand how to read the DI status information from the iologik R2110 and write DO statuses to the iologik R2110. 5.1.8. You will need to configure two Modbus commands. Start by clicking the Add button to create a new Modbus command. Copyright 2013 Moxa Inc. Page 6 of 21

5.1.8.1. Name the new command Command1 and configure it to read the DI status from the iologik R2110. Then click OK to add the command. 5.1.8.2. Next, configure Command2 to write the DO status to iologik R2110, and then click OK to add the command. 5.1.8.3. Return to the Modbus RTU/ASCII tab to view a summary of the commands we just added. Copyright 2013 Moxa Inc. Page 7 of 21

5.1.9. Then, click the OK button to save all the configurations we just added and the MGate 5105-MB-EIP will restart automatically for the new settings to take effect. Copyright 2013 Moxa Inc. Page 8 of 21

6. PLC configuration 6.1. Install the EDS file 6.1.1. Open the EDS hardware Installation Tool to install the EDS files for the MGate 5105-MB-EIP. Click Add to choose the folder where the EDS files will be stored. 6.1.2. You will need to install two separate EDS files one for EtherNet/IP Scanner and another for EtherNet/IP Adapter in a new directory. Create a new directory by selecting Register a directory of EDS files and clicking the Browse button to select the appropriate folder to store the files. Copyright 2013 Moxa Inc. Page 9 of 21

6.1.3. Click Next > to view the EDS files that are going to be installed. 6.1.4. Click Next > to view the devices on which the EDS files will be installed. Copyright 2013 Moxa Inc. Page 10 of 21

6.1.5. Click Next > to see a summary of the installation. 6.1.6. Click Next > and then Finish to complete the installation process. Copyright 2013 Moxa Inc. Page 11 of 21

6.2. Configure the EtherNet/IP network 6.2.1. Start RSLinx Classic and create a new project by selecting File Open Project 6.2.2. Click the New button to create a new DDE project for this demo. Enter Demo for the Project Name. 6.2.3. Select Communications Configure Drivers to configure the EtherNet/IP network. Copyright 2013 Moxa Inc. Page 12 of 21

6.2.4. There may be a default driver already installed, as shown in the screenshot below. You may configure a new driver or check if the default settings are suitable for the network topology of the application. Select the appropriate driver and click the Configure button. 6.2.5. Choose the proper Ethernet interface then click the OK button. Copyright 2013 Moxa Inc. Page 13 of 21

6.2.6. Return to the main window and select Communications RSWho to detect all the EtherNet/IP devices on the network. 6.2.7. In the left column tree menu, expand the AB_ETHIP-1, Ethernet driver to confirm that all the devices were detected. In this example, you should see the Allen-Bradley PLC and Moxa MGate 5105-MB-EIP. 6.3. Create RSLogix 5000 project 6.3.1. Start RSLogix 5000 and create a new project by selecting File New. Copyright 2013 Moxa Inc. Page 14 of 21

6.3.2. You must choose the proper controller type and controller firmware version. In this example, we are using the 1769-L32E CompactLogix5332E Controller and Revision 18. In addition, you should also assign a name for this project. For this example, enter Demo as the Project Name. 6.4. Create an Ethernet Module for the MGate 5105-MB-EIP 6.4.1. When the new project opens, find the Controller Organizer window. Copyright 2013 Moxa Inc. Page 15 of 21

6.4.2. In the Controller Organizer tree menu, expand the I/O configuration field and right-click on Ethernet. Select New Module from the pop-up menu to add an Ethernet module to the MGate 5105-MB-EIP. 6.4.3. A new dialog box will appear for you to select modules to add. Expand the Communications category Copyright 2013 Moxa Inc. Page 16 of 21

6.4.4. Then select ETHERNET-MODULE and click the OK button. 6.4.5. Enter the module s information, including the Name, Comm Format, IP address, and Connection Parameters. 6.4.5.1. For this example, enter MGate_5105 for the Name, and 192.168.33.10 for the IP address. 6.4.5.2. Since we are simply testing the iologic R2110, configure the Comm Format as Data SINT, and the Assembly Instance to only read and write 8 bits. The Assembly Instance Input of 110 and Assembly Instance Output of 100 are fixed by the MGate 5105-MB-EIP. Copyright 2013 Moxa Inc. Page 17 of 21

6.4.5.3. After clicking the OK button, you can configure the Requested Packet Interval (RPI), or keep the default settings on this page. 6.4.5.4. Lastly, click the OK button to finish the configuration. 6.4.6. Select the Controller Tags under Controller Demo to view all the tags you created. Verifying whether all the necessary tags have been created. Copyright 2013 Moxa Inc. Page 18 of 21

6.5. Download Configuration to PLC 6.5.1. Select File Save to save this project. 6.5.2. Select Communications Who Active to find the target PLC. 6.5.3. In the Who Active tree menu, expand the EtherNet/IP network field and select Backplane, CompactLogix Processor. On the right-hand side of the tree menu, click the Download button to download the above settings onto the PLC. Copyright 2013 Moxa Inc. Page 19 of 21

6.5.4. A warning message will pop up to remind you to that you are downloading an offline project onto the PLC. Click the Download button to proceed. 6.5.5. When downloading completes, you will be prompted to change the PLC to Remote Run mode. Click Yes to continue. 6.5.6. Return to the main window of the RSLogix 5000. The indicators should all be green. Copyright 2013 Moxa Inc. Page 20 of 21

7. Communication Test 7.1. Monitor / Modify Test 7.1.1. Modify the DO data and check if the LED indicators on the iologik R2110 have changed. 7.1.2. Monitor the DI data for changes when you send an input signal from the iologik R2110. Copyright 2013 Moxa Inc. Page 21 of 21