POWERWISE INDAC SETUP MANUAL

Similar documents
CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

User Manual. cmt-svr Startup Guide

Connecting a Cisco Reader Module

User Manual. cmt-svr Startup Guide

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

iologik E1200H Series

Features and Benefits. Certifications

icex-cmtm General specs and Installation guide

GreenEye Monitor. Introducing AVAILABLE IN TWO VERSIONS: FEATURES. Residential Single/Split Phase Systems. Three Phase commercial, light industrial

GreenEye Monitor Specifications

256 MB RAM. 256 MB 32 bits RISC Cortex-A8 600MHz SD Card Slot. N/A USB Host. N/A USB Client

Measurement Systems Datascan Installation and User Guide

Installation & Operation Guide

Table of Contents 1 ABOUT THIS GUIDE CONTACT INFORMATION ANTENNA INSTALLATION... 4

MGate 4101-MB-PBS Series

Warranty. Warning. Copyright. Contact Us

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

RTU560 Connections and Settings DIN Rail RTU 560CIG10

DSP240-LPI Inverter Controller Card. Technical Brief

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

Manual# Installation Manual. 200E Series. DCU 210E/208E Engine Panel RP 210E/220E Remote Panel

LAUREL. Laureate Pulse or Analog Input Batch Controller Automatic batch control for repetitive liquid fill operations ELECTRONICS, INC.

Intelligent Devices IDI 6005 Speed Sign Controller Technical Manual

LAUREL. Laureate Dual-Channel Pulse Input Totalizer With Two Independently Scalable Input Channels & Presets ELECTRONICS, INC. Features.

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

Modbus TCP/RTU Gateway

7I44 MANUAL 8 CHANNEL RS-422 INTERFACE

The TRSUN is the complete solution for the remote monitoring of photovoltaic plants.

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

7I74 MANUAL 8 CHANNEL RS-422 INTERFACE

EA500. Installation Instructions Transponder

Industrial 1-port RS422/485 Modbus Gateway IMG-110T

MODEL: R1M-P4. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

Serial Data DIN Fiber Link System

NETAFIM WILL NOT ACCEPT RESPONSIBILITY FOR DAMAGE RESULTING FROM THE USE OF NETAFIM'S PRODUCTS OR THE USE OF THIS MANUAL.

Stellar Instruments. SC1 Controller & Display System. General User s Manual. Copyright 2013 Stellar Instruments 1

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

Y800 Plus Frequency, Rate & Period Meter With dual, independently field-scalable channels

DECK All-In-One Enclosure. Quick Installation Guide for Field Installers

USB1. Encoder Data Acquisition USB Device Page 1 of 6. Description. Features

Manual 601: : USB/RS232. Specifications. Contents. Options

MOTION COORDINATOR MC403 / MC403-Z Quick Connection Guide

JNIOR Series 4. A Network I/O Resource Utilizing the JAVA Platform. JNIOR Series 4 with 4 Relay Output Expansion Module. Version 5.

HRM-0800 Instruction Manual

KAUGJUHTIMISSÜSTEEMID TELECONTROL SYSTEMS MODEM TELEM-GSM/GPRS 3G. User manual

w w w. z i g s e n s e. c o m. a u

SunSpec Reference Architecture SunSpec CEA 2045 Inverter Adaptor

HVG400. Installation Guide

CDN220 HIGH DENSITY I/O ADAPTER USER GUIDE

Ethernet to Digital I/O +RS232 +Switch

LAUREL. Laureate Rate Meter & Totalizer with Functions A+B, A-B, AxB, A/B, A/B-1 ELECTRONICS, INC. Features. Description

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

Hardware Manual 1240i-485

PBSCONTROL. AMS-R4000 Modular RTU. Remote Terminal Unit

Owner s Hardware Service Manual Frank Control Computer System

G303 RIO (REMOTE I/O) AND LOW END RTU

EasyIO FC20 User Reference v1.3. EasyIO FC 20 DDC User Reference V1.3

4.8 Expansion Module MAC00-FS1/FS4

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

LAUREL ELECTRONICS, INC.

Features and Benefits. Certifications

Slick Line Acquisition System Manual

ioselect Z-NET Z-SG Bridge Input Isolating I/O Module

and/or b. an optional internal Iridium satellite modem.

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

MICROFUSION FEATURES OPTIONS CERTIFICATIONS (PENDING) THREE PHASE SCR POWER CONTROLLERS

MGate MB3000 Modbus Gateway User s Manual

FVT/FVR20D2I1C4E INSTALLATION AND OPERATION MANUAL

Installation and Operation Manual. INTEGRA BTU Meter System

SNAP PAC Redundancy Option Kit

BLUE LOG XM / XC. Quick Start Guide. Version

Suprex Fiber Optic. Reader-Extender SPX-7400 SPX Product Manual. Reader-Extender. Manual. SPX-7400 Series EXP Suprex_FiberOptic_MAN_170502

Dupline. Data Logger. Types G , G Product Description. Ordering Key G Type Selection. Input/Output Specifications

EZ-Bv4 Datasheet v0.7

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

INTRODUCTION - DISPLAYS, DATA LOGGERS AND SOFTWARE

The INJ-102GT-24V PoE Injector is an advanced IEEE802.3at compliant device with intelligent detection that provided

Serial/Ethernet Converter

Ethernet Interface Module

JNIOR Series 4 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 2.0 NOTE: JANOS OS 1.1 or greater required

Industrial Media Converters

iologik 2500 Series Quick Installation Guide

EnerSure Installation Guide

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions

Suprex Ethernet SPX-7200 Ethernet Reader-Extender

MODBUS TCP/IP TO MODBUS SERIAL GATEWAY. MODEL No: MGate-1024-DC VER 2.0

connecdim Gateway G1 Ethernet TCP/IP to DALI

STT41AS1 v7.0 FUNCTIONAL DESCRIPTION

MC CO MODBUS ADDRESSABLE SENSOR

Intelligent 4 Port RS-422/485 to 2 Port Ethernet Serial Device Server with PoE

Product Catalog. senseware.co Tysons Boulevard Floor 5 Tysons VA, 22102

ST400C-NT USER S GUIDE. Table of Contents

RN-174 WiFly Super Module

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

ICD105A 1008 page 1/ r001 ICD105A. Industrial RS-232 to RS-422/485 Converter

Intelligent Devices IDI 1100 Series Technical Manual

Transcription:

POWERWISE INDAC SETUP MANUAL REVISION: 2.2 INDAC & EMONITOR GATEWAY An installation guide for the PowerWise indac. 2013 PowerWise, Inc. This manual may contain proprietary information about the product described. The manual is for instruction in setting up and using the PowerWise indac. Any proprietary information illustrated or described in it for the purpose of helping you set up and use the product remains the protected intellectual property of PowerWise, Inc. This manual may not be copied, reproduced, or distributed in any way in any form without express written permission of PowerWise, Inc. 1

Sensor Controller Overview: The PowerWise indac is a microcontroller designed for data acquisition and control of a wide of building systems. This data acquisition hardware features Modbus RTU communication protocol for connection to Modbus enabled gateway devices allowing for local or cloud storage. The indac s feature two serial connection types: RS-232 and RS-485 enabling expansion of inputs and outputs. The hardware accommodates both analog and digital sensor inputs allowing for integration to a wide variety of sensors. Each device features the following inputs and outputs: 6 Analog Input (0-5 VDC, 12 bit resolution) 4 Pulse Inputs (1 khz max, sinking, 24 VDC max) 4 Digital Inputs (sinking, 24 VDC max) 4 Digital Outputs (sinking, 24 VDC max) 20 1-Wire Sensor ID s The following is a guide on how to connect the indac to a gateway device and wire a variety of building monitoring sensors. Table of Contents: 1. indac Connection o Power & Serial Connections o Embedded Server Connection o InDAC Terminal Layout o Counter Input/Connection o Analog Input Connection o Digital Input Connection o Digital Output Connection o 1-Wire Connection 2. indac Dimensions/ Mounting 2

indac Connection: Powering Up & Communication Connection: The indac needs to be powered by a 9-16 VDC power supply rated to a minimum of 1 amp. The system comes standard with a +12 VDC 18 Watt wall transformer with the neutral connected to ground. There is a connector located on the left hand side of the enclosure. A DIN rail mountable industrial power supply can be supplied/used, which allows for multiple indac s to be powered by one source. Figure 1 shows the communication connection diagram for the indac and emonitor Gateway. Figure 1. indac communication connection diagram. A single indac should be connected via the RS-232 Serial port on the emonitor gateway. If Powerwise has provided you with a RS-232 cable the connection should be made like that shown in Table 1. All custom made cables should follow this pin out but do not have to use the same color code/convention. indac Cable emonitor Gateway (RJ11) GND Blue White GND (6) TX Orange RX (5) RX Orange White TX (4) Table 1. RS-232 Connection The emonitor gateway supports up to 5 indac s per connected emonitor connected in parallel via RS-485. Figure 2 shows connection of two indac s to an emonitor gateway. 3

Figure 2. indac RS-485 connection diagram. The following Table 2 shows the connection of RS-485 to the indac when daisy chaining up to 5 devices together. indac Cable RS485-RS232 Converter Cable emonitor Gateway (RJ11) RS-485 RS-232 GND Blue GND GND Blue-White GND (6) B+ Green R+ Pin 2 Orange-White RX (4) A- Green-White R- Pin 3 Orange TX (5) +5V Red Vcc Pin 5 - - Table 2. RS-485 Connection indac Unique Address Selection: The indac(s) need to have a unique address set via the DIP switch on the right hand side of the case. Figure 3 shows how the DIP switches should be arranged to acquire the correct address. 1 3 5 2 4 4

Each indac needs a unique address set unlike that of another indac on a single emonitor Gateway. This address will be indicated on the embedded server explained below. Once the proper connections have been made as stated above, power up the indac(s) and emonitor gateway. The power light (PWR) on the indac(s) should blink green and the power light on the emonitor gateway should be solid green. Next connect the ethernet cable (if hardwired version, blinks red lights upon power up) or provision the wireless network (if wifi version, blinks green on power up (page 22 emonitor manual)). Connection can be verified on emonitor gateway by solid green/linking yellow LINK light. Indicator lights on each indac can confirm connection and communication to the emontior gateway as well. The Rx (receive) and Tx (transmit) lights should blink in succession every second indicating proper RS-232 connection. RS-485 communication will be indicated by a blinking power and Rx light every second and the Tx light will blink three times for one indac and move on to the next indac blinking three times until it cycles back to the original indac. Next connect to the embedded server. Embedded Server Connection: The emonitor Gateway has an embedded server that can be accessed (when connected to the local network) to help during setup and commissioning of the product. Data uploaded to the server is averaged over one minute intervals whereas data seen on the embedded server is updated every 3-5 seconds. Connection to the embedded server is obtained by connecting to the gateways unique IP address. This can be found on your routers DHCP/connected devices list or found on your emonitor dashboard by clicking the STATUS link the in the upper left hand corner. Once the correct address has been obtained enter it in your browser window like that shown in Figure 3. IP ADDRESS SENSOR TAB Figure 3. Gateway Embedded Server Some browsers respond better to the embedded server (Chrome, Firefox) than others (Internet Explorer). Once connection has been made to the embedded server select the Sensors tab to view all sensor data shown in Figure 4. 5

InDAC Address Figure 4. Gateway Embedded Server with indac support. The indac will show up under Remote Sensors on the embedded server. The first indac will automatically be found. To add additional indac s the Rescan Modbus button needs to be pressed. Make sure to wait up too 30 seconds for the indac to show up under Remote Sensors. Once all indac s have been found all data points can be verified from the table. The following heading denotes the values and ranges that can be expected for each data type. InDAC Unique Address: Each indac should be setup to have a unique address compared to the other indac s on a single Gateway. This value is set using the DIP switch and explained in the indac Unique Address Selection above. Version: The firmware version present on the specific indac. The firmware version is only needed for troubleshooting if a problem should arise. Status: The indac communicates with the Gateway via serial communication. Tx indicates the number of successful transmits to the Gateway. Error indicates the number of attempted but failed communications with the Gateway. Under normal conditions the Tx should count up every couple of seconds and the error should remain static. If the Error is counting regularly make sure to check connections. Counters: There are four (4) counter inputs per indac that are cumulative. Once the maximum value (65535) is reached this will reset and start again. Channels 1 through 4 go from left to right, respectively. Analogs: There are six (6) analog inputs per indac with an input range from 0 to 4.999 volts. Channels 1 through 6 go from left to right, respectively. 6

Inputs: The indac has four (4) digital inputs. When connected to ground the indicator will change from red OFF to green ON. Outputs: The indac has four (4) digital outputs. When triggered the indicator will change from red OFF to green ON pulling the channel to ground. 1-Wire: 20 unique 1-Wire devices can show up in this window. The Rescan Remote 1-Wire button should be toggled if new sensors are to be added to an existing set. InDAC Terminal Layout In Figure 5 below is the layout of the indac depicting all points of connection for analog, digital, and serial communication. Figure 5. indac Terminal Layout. The board is equipped with a regulated +5V DC power supply to be used for excitation voltages. There is also unregulated +12V DC power available, which is passed through from the power supply powering the indac. 7

Counter Inputs/Connections: The indac has four (4) counter cumulative inputs labeled CT1 CT4 rated to a maximum switching frequency of 1000 samples per second (1 khz) and protected to 24 VDC input. These inputs need to be setup with sinking logic and will register a pulse/switch when connected to ground. Common sensors include hall-effect flow meters, reed switch flow meters, speed sensors, and contact closures. Figure 6 shows the typical connection diagram for sensors. Figure 6. Counter Connection Diagram For additional sensor specific wiring diagrams please visit the PowerWise Technical Documents page located at www.powerwisesystems.com. 8

Analog Input Connection The indac has six (6) inputs labeled AIN1 AIN6 with an input range of 0 5 VDC with 12 bit resolution. The ports are optically isolated with overvoltage protection up to 24 VDC. Although the indac records only raw data locally scaling factors are applied on the PowerWise website under the settings page. Figure 7 is the typical connection to the analog input port. Figure 7. Analog Input Connection Diagram Analog sensors such as level sensors, HVAC equipment control set points, etc. will integrate into these channels. Integration into 4 20 ma output devices can be accomplished by installing a 250 ohm resistor between the signal and ground of the port. For additional sensor specific wiring diagrams please visit the PowerWise Technical Documents page located at www.powerwisesystems.com. 9

Digital Input Connection: Four (4) digital input channels are found at connections IN1 IN4 of the PowerWise indac. The digital inputs should be used to tell whether a sensor is On or OFF. These inputs are triggered when connected to ground indicating ON. The ports are optically isolated with overvoltage protection up to 24 VDC. Figure 8 shows the common connection for a digital 2-wire input. Figure 8. Digital Input Connection Diagram These inputs will work with a variety of building sensors such as AC switches, DC switches, optical sensors, flame detectors, etc. For additional sensor specific wiring diagrams please visit the PowerWise Technical Documents page located at www.powerwisesystems.com. 10

Digital Output Connection: Digital outputs are located on channels labeled OUT1 OUT4 on the sensor controller. Each of the four channels are rated to100 ma maximum and isolated to 24VDC max. These channels are designed to offer basic control of various building systems. Figure 9 shows the basic connection for any digital output sensor or device. Figure 9. Digital Output Connection Diagram The output can also be connected to a 12VDC or 24VDC power source as long as the current is limited to 100mA. This connection should only be used to power very low consumption devices and is designed primarily to trigger relays, HVAC equipment controls, indictors, etc. For additional sensor specific wiring diagrams please visit the PowerWise Technical Documents page located at www.powerwisesystems.com. 11

1-Wire Connection: 1-Wire devices are digital sensors that communicate through the 1-Wire communication protocol. Each individual sensor is hard coded with a 64 bit unique id that should be recorded before installation. Each 1 Wire device can be connected in parallel with a maximum of 20 unique id s. Figure 10 below shows typical connection of 1-Wire devices. Figure 10. 1-Wire Connection Diagram PowerWise Systems offers a range of custom devices to record building conditions. Temperature sensors come in a small stainless steel barrel and are used to measure ambient temperature, flow media in pipes, and surface temperatures. PowerWise also offers a relative humidity/temperature (RH/T) combined device as well as a Multisensor, which reports volatile organic compound (VOC) or carbon dioxide (C02). The RH/T and Multisensor require external power supplied by the +12V DC port shown in Figure 10. The number of unique ID s per 1-Wire device is shown in Table 3 below. Device Unique ID(s) Temperature Sensor 1 (28) Relative Humidity & Temperature Sensor 2 (28 & 26) Multisensor (CO2 & VOC) 2 (28 & 26) Table 3. 1-Wire ID(s) (Note: A 1WT is added to each sensor label on dashboards. ) NOTE: Each indac can have a maximum of 5x (26 ID s) and 15x (28 ID s) 12

indac Dimensions/ Mounting The PowerWise indac is packaged for installation on either 35mm DIN rail or mall mounted. Figure 11 shows the overall dimensions and mounting options. Top View Bottom View: R.078 in R.156 in 2.930 in 4.290 in 4.146 in Side View: 2.148 in Figure 11. indac Drawing 13