PPU Power Management (PPM)

Similar documents
Generator Protection Unit, GPU-3 DATA SHEET

Automatic Gen-set Controller Multi-line D

Generator Protection Unit, GPU Hydro Multi-line A SW version 2.4X.X

Generator Protection Unit, GPU-3 DATA SHEET

Generator Paralleling Controller, GPC-3 DATA SHEET

PPM Protection and Power Management DATA SHEET

DEIF A/S. Generator Paralleling Controller multi-line L. Type GPC / GS. Compact system in one unit

AGC 200 Advanced Gen-set Controller DATA SHEET

Generator Protection Unit, GPU-3 Gas Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions

Basic Gen-set Controller multi-line F SW version 2.31.X or later

DATA SHEET IOM 200 analogue interface for AGC 200

Generator Protection Unit, GPU-3 Generator protection (ANSI) Busbar protection (ANSI) M-Logic (Micro PLC) Display General

DATA SHEET Paralleling and Protection Unit, PPU-3

Generator Paralleling Controller, GPC-3 Gas Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

DATA SHEET. AGC PM Automatic Genset Controller, Plant Management

Generator Paralleling Controller, GPC-3 Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

AGC 200 Automatic Advanced Gen-set Controller DATA SHEET

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

Engine Controller EC-1

Generator Controller GC-1

No longer for sale. Generator Controller GC-1. Data sheet. Standard functions

Delomatic 4, DM-4 Land DATA SHEET

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

DATA SHEET Automatic Genset Controller, AGC-3

Delomatic 4, DM-4 Marine & Offshore DATA SHEET

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus

Generator Controller GC-1F

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

INSTALLATION INSTRUCTIONS

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

MIC-2 Multi-instrument DATA SHEET

INSTALLATION INSTRUCTIONS

Automatic Sustainable Controller, ASC Mounting Board slot positions Terminal strip overview I/O lists Wiring

DATA SHEET Genset Controller, GC-1F

MULTI-LINE 2 APPLICATION NOTES

Installation Manual. Multi Power Controller MPC-1 multi-line D

MIC-2 MKII, Multi-instrument DATA SHEET

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

DATA SHEET Automatic Genset Controller, AGC-4

DATA SHEET Compact Genset Controller, CGC 200

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version:

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

DATA SHEET DEPRECATED - PCM5 1. Document no.: N/A

General introduction Part 2, chapter 11

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version:

Engines & Gen-sets N, page 1 of 6

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

Engine & Genset Controls Z, page 1 of 12

NOT RECOMMENDED FOR NEW DESIGNS

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3

DATA SHEET Selectable AC transducer, TAS-321 DG

DEIF A/S. Description of options. Option C1 Generator add-on protection package Multi-line 2 version 2. Description of options. Functional description

DATA SHEET Selectable AC transducer, TAS-331DG

Multiple Generator Automatic Synchronising System

TYPE APPROVAL CERTIFICATE

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3

Genset control and protection with safety system

Option H3 Serial communication Profibus DP

DATA SHEET. Advanced Power Meter, APM 380 & APM 305

Multifunction Transducer MT440

GC2000 Generator Controller Power Management and Protection

DATA SHEET. Advanced Energy Meter, AEM 380 & AEM 305

GPM500 Generator Protection Module

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

QUICK START GUIDE Generator Protection Unit GPU 300

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

BACnet/IP Web Interface

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

Contact protection relay

Module 18plus. Description. 18plus

J7MN. Ordering Information. Motor Protection Circuit Breaker. Model Number Legend. MPCB system. Options. Motor Protection Circuit Breaker J7MN I-1

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC

1492-SP Supplementary Protectors

Comprehensive Modular Genset Controller

EngyVolt RV12 and RV15

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protectors Specifications Bulletin Number 1492, 1692

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

Electronic timer CT-ERD.12

29 $ Manual Motor Starters FREESHIPPING. MOTOR CONTROLS 25. Features: MMS-32H Frame. MMS-63H Frame.

Circuit Breakers, Type CTI 25M, CTI 45MB, CTI 100

Circuit Breakers Type CTI 25M, CTI 45MB

Electronic timer CT-AHD.22

Zelio Control-modular measurement and control relays 1

Overvoltage Protection Devices

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

MARINE & OFFSHORE SHIP ENERGY MONITORING SYSTEM

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

1.3. Miniature Circuit Breakers and Supplementary Protectors. Contents. WMZS Circuit Breaker. UL 1077 DIN Rail Supplementary Protectors

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Transcription:

PPU anagement (PP) 4921240291H Standard functions DEIF A/S management Load dependent start/stop Programmable start priority Heavy consumer control Blackout start sequence Supervision/control of a shore breaker Supervision/control of a bus coupler Additional operator panel (AOP) Symmetrical and asymmetrical load sharing Trip of non-essential load groups Generator protection Over- and undervoltage Over- and underfrequency Reverse power Overcurrent Fast overcurrent (> 42ms) Overload Current unbalance Voltage asymmetry Loss of excitation and overexcitation Busbar protection Over- and undervoltage Over- and underfrequency Engine control Start/stop sequences AVR/speed governor control Overspeed protection configurable alarm inputs with wire break supervision Display Push-buttons for start/stop Push-buttons for breaker operations Information messages Status text Alarm indication Start/stop priority change General ultiple AOP-2 in parallel Five standard languages (English, German, French, Spanish and Italian) Interfacing to alarm and monitoring systems (RS485 odbus RTU or TCP/IP odbus) interface from laptop Password protected parameter changes via display or PC software PC software as commissioning tool Configurable I/Os, set points, timers and alarms DEIF A/S

7 8 9 40 41 42 4 44 45 46 47 48 49 50 EngineCAN PS CAN Self check ok 51 52 5 54 55 56 57 58 59 60 6 1 62 6 64 emory Ser vice port Display 65 66 67 68 69 70 71 72 7 74 75 76 77 78 79 80 81 82 8 84 85 8 6 87 88 89 90 91 92 9 94 95 96 9 7 7 8 9 4 0 4 1 42 4 44 45 46 47 48 4950 51 52 5 54 55 56 57 58 59 60 61 62 6 64 65 66 6 7 68 69 70 7172 7 74 75 7 6 77 78 SEI- SHA FT SEI- PS CAN Et he rn et Self check ok S.POS.ON TB.POS.ON REQUEST ACKN. SHAFT PROG 1 NEL TRIP PROG 2 B B ALAR PS BLOCKED TRIP PE D LB. STOP BLOCK DG SHUTDOWN PROG 1 PROG 2 e mo ry Service port 79 80 81 82 8 84 85 86 8 7 88 89 90 91 9 2 9 9 4 95 96 97 LAP TEST Dis p la y 4155111096A 7 8 9 4 0 4 1 42 4 44 45 46 4 7 48 4 9 50 51 5 2 5 54 55 56 57 5 8 59 60 61 62 664 65 6 6 67 68 69 70 71 72 7 74 75 7 6 77 78 PS CAN Selfcheck ok Alarminhibit emory Service port SEI- SHAFT SEI- Di s play S.POS.ON TB.POS.ON REQUEST ACKN. SHAFT 7 9 80 81 8 2 8 8 4 85 86 87 88 89 9 0 9 1 92 9 94 95 96 97 PROG 1 NEL TRIP PROG 2 BB A LAR PS BLOCKED TRIPPED LB. STOP BLOCK DG SHUTDO WN PROG 1 PROG 2 LA P TES T 4155111096A 7 8 9 40 41 42 4 44 45 46 47 48 49 50 P S CAN US B Selfcheck ok 51 52 5 54 55 56 57 58 5 9 60 61 62 664 em ory Serv ic e port Display 65 66 67 68 69 70 71 72 7 74 75 76 77 78 79 80 81 82 8 8 4 85 86 87 88 89 90 91 92 9 94 95 96 9 7 7 8 9 4 0 41 42 4 44 45 46 47 48 49 50 51 52 5 54 55 56 5 7 5 8 59 60 61 62 6 64 65 66 67 68 69 70 71 72 7 74 75 7 6 77 78 PS CAN Self check ok emory Service port Di spl ay 79 80 81 8 2 8 8 4 85 86 87 88 8 9 9 0 91 92 9 94 9 5 96 97 7 8 9 40 41 42 4 44 45 46 47 48 49 50 P S CAN Self c hec k ok 51 52 5 54 55 56 5 7 58 59 6 0 61 62 6 64 em o ry Service port Display 65 66 67 68 69 70 71 72 7 74 75 76 77 78 79 80 81 82 8 84 85 86 87 88 89 90 91 92 9 94 95 96 9 7 7 8 9 40 41 42 4 44 45 4 6 4 7 4 8 49 50 51 52 5 54 5 5 56 57 58 59 60 61 62 6 64 65 6 6 6 7 68 69 70 7172 7 7 4 75 76 7 7 7 8 PS CAN Self check ok Alarminhibit U SB emory Service port Display 79 8 0 8 1 82 8 84 85 8 6 8 7 88 89 90 9 1 9 2 9 94 95 96 97 Data sheet PPU anagement (PP) Application illustrations SYSTE SYSTE OVERVIEW COENTS SYSTE 01 DG 1 + DG 2 + DGn inimum 2 diesel generators aximum 8 diesel generators SYSTE 02a SYSTE 02b DG 1 + DG 2 + DGn + SG DG 1 + DG 2 + DGn + SC inimum 2 diesel generators and 1 shaft generator/shore connection aximum 8 diesel generators and 1 shaft generator/shore connection SYSTE 0 DG 1 + DG 2 + DGn + SG + TB inimum 2 diesel generators, 1 shaft generator and 1 bus tie breaker aximum 8 diesel generators, 1 shaft generator and 1 bus tie breaker System 1 AOP CAN-bus Loadshare line DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2 Additional Diesel Generator System 2 (shaft) System 2 (shore) AOP CAN-bus Loadshare line DIESEL GENERATOR SET 1 DIESEL GENERATOR SET 2 Additional Diesel Generator Shore Connection DEIF A/S Page 2 of 11

PPU anagement (PP) System DEIF A/S Page of 11

Application The PPU anagement (PP) is a standard power management system for marine applications. The system has been designed to carry out generator control, supervision and protection functions of up to 8 generators running in parallel. The PP supports different main systems depending on the individual application. The system performs power management features such as load dependent start/stop, programmable start priority, heavy consumer control, blackout start sequence, supervision of a shore breaker and a bus coupler, symmetrical and asymmetrical load sharing, trip of non-essential load groups and programmable I/Os etc. (the PP system covers the requirements for most simple and medium-sized marine systems). Each unit contains all necessary -phase measuring circuits and presents all values and alarms on the LCD display. Besides the LCD display, the power management unit has an additional operator panel (AOP-2) with 8 pushbuttons and 16 LEDs. The AOP-2 has a CANbus connection to the display unit and can be placed anywhere in the switchboard (max. 200 m from display unit). ultiple AOP-2s can be connected to the CANbus line with parallel operation (X4 option). The AOP-2 enables status information over the system and includes plant mode control. Communication to an external alarm and monitoring system can be done via TCP/IP odbus, or RS485 odbus RTU. Display The display is a separate unit and can be mounted directly on the PP base unit or in the switchboard via the display cable. Up to displays can be connected to the same main unit (X2 option). Diesel generator PPU anagement (PP) anagement The power management functions are handled in a separate 2-bit processor. As default the P processor is placed in DG unit 1. The load dependent start/stop function can be adjusted as predicted available rated power (kw), as predicted available apparent power (KVA) or as percentage rated power (%). The start priority selection can either be handled from the P unit for the entire system or locally via a 1 st priority pushbutton on each display unit. The heavy consumer control is able to be adjusted as fixed load or variable load (e.g. thrusters). The output signal can also be adjusted as either pulse signal or steady signal. If a blackout situation occurs, the operator can define the following functions: - Start one or two diesel generators, - automatically change plant mode to SEI- or mode, and - in case of short circuit to activate one or no start attempts In case of an open bus coupling switch, the system can automatically be forced into switchboard control. This can be indicated at the AOP-2 and additionally at each display unit by a yellow PS control LED. The load dependent stop function can be blocked by either an external input or by a set point. Using the set point will only block the load dependent stop function in case of heavy consumer operation. and frequency control The PPU anagement (PP) can control speed governors/avrs by using relay or analogue output signals. The load sharing function has a separate analogue load share line. This allows placing of additional bus couplers anywhere in the switchboard and ensures active load sharing at open bus coupler positions. The following regulator functions are available: - Active load sharing - Reactive load sharing - Voltage control (option) - PF, VAR control (option) Additional operator panel (AOP-2) SEI- SHAFT S POS.ON FORCED SWBD REQUESTED NEL TRIP BB ALAR TRIPPED SECURED ON PS BLOCKED CONNECTED LD STOP BLOCK DG SHUTDOWN SEI- SHAFT SECURED ON SECURED OFF LAP TEST DEIF A/S Page 4 of 11

PPU anagement (PP) Available options Option Description Placed in Note D Voltage/var control D1 Selection between: Software option Not with EF2 - Constant voltage control (stand-alone) - Reactive load sharing (island paralleling with other generators) E Analogue controller outputs E1 +/-20mA for speed governor +/-20mA for AVR Slot #4 AVR: Only when option D is chosen Not with EF functions F Analogue transducer outputs F1 2 x 0(4)...20mA transducer outputs Slot #6 EF Combination outputs EF2 +/-20mA for speed governor Slot #4 Not with E1 1 x 0(4)...20mA transducer output EF4 +/-20mA for speed governor or AVR 2 x relay outputs for speed governor or AVR Slot #4 Not with E1, EF2 AVR: Requires D H Serial communication H2 odbus RTU (RS485) Slot #2 J Cables J2 Display cable with plugs, 6 m. UL94 (V1) approved Other J4 PC cable for option N programming ( cable crossed), m. Other UL94 (V1) approved. J7 PC cable m Other K Technical documentation K1 Hard copy (as standard enclosed as CD RO) Other L Display gasket for IP54 Configurable I/O extension cards 15 4 x 0(4) 20mA analogue inputs Slot #6 Not with F1, 16, 18 16 7 x binary inputs Slot #6 Not with F1, 15, 18 18 4 x relay outputs Slot #6 Not with F1, 15, 16 N Webarm functions N5 TCP/IP odbus Software option X Display X2 Additional display (DU-2) Other ax. displays per main unit X4 Additional operator panel (AOP-2) Other With same functions as standard AOP-2 for parallel operations in different locations For detailed information about hardware options, please see hardware overview on page 6. For detailed order information, please see order specifications on page 11. DEIF A/S Page 5 of 11

PPU anagement (PP) Hardware overview There can only be one hardware option in each slot. It is e.g. not possible to select option F1 and option 15 at the same time because all options require a P in slot #6. Besides the hardware options shown on this page it is possible to select the software options mentioned on page Error! Bookmark not defined. in this data sheet. Slot #4, term. 65-72 Slot #6, term. 90-97 In-/outputs Governor/AVR outputs (DG) Option 4 x relay outputs (standard) or Option E1/EF2/EF4 F1/15/16/18 Slot #2, term. 29-6 External comm. Option H2 Slot #1, term. 1-28 supply Standard 12/24V DC supply, 8W 1 x status output relay 5 x relay outputs 2 x pulse outputs (kwh, kvarh) 5 x binary inputs 7 8 9 40 41 42 4 44 45 46 47 48 49 50 51 52 5 54 55 56 57 58 59 60 61 62 6 64 65 66 67 68 69 70 71 72 PS CAN emory Service port Display Self check ok 7 74 75 76 77 78 79 80 81 82 8 84 85 86 87 88 89 90 91 92 9 94 95 96 97 Slot #8, term. 126-1 Internal comm. (CANbus) Standard Slot #7, term. 98-125 Engine I/F Standard x 4...20mA analogue inputs x alarm inputs (wire break supervision) 1 x magn. pick-up 9 x binary inputs x relay outputs Slot #, term. 7-64 Binary I/O (load sharing) Standard Slot #5, term. 7-89 AC measuring (std.) x generator voltage x generator current x busbar/mains voltage DEIF A/S Page 6 of 11

PPU anagement (PP) Technical specifications Accuracy: Class 1.0, to IEC/EN 60688 Operating temp.: Storage temp.: -25 70 C (-1...158 F) (UL/cUL Listed: ax. surrounding air temp.: 55 C/11 F) -40 70 C (-40...158 F) ounting: DIN-rail mount or base mount DEIF recommends base mounting for marine applications. If DIN-rail mounted in marine applications, additional means against excessive mechanical vibrations must be used. Climate: 97% RH to IEC 60068-2-0 eas. voltage: 100-690V AC +/-20% (UL/cUL Listed: 110-480V AC phase-phase) Consumption: ax. 0.25VA/phase eas. current: Consumption: Current overload: -/1 or -/5A AC (UL/cUL Listed: From CTs 1-5A) ax. 0.VA/phase 4 x I n continuously 20 x I n, 10 sec. (max. 75A) 80 x I n, 1 sec. (max. 00A) Load sharing lines: -5 0 +5V DC Impedance: 2.5k Analogue outputs: 0(4)...20mA and +/-25mA Galvanically separated Active output (internal supply) Load max. 500 (UL/cUL Listed: ax. 20mA output) Safety: To EN 61010-1, installation category (overvoltage category) III, 600V, pollution degree 2 To UL 508 and CSA 22.2 no. 14-05, overvoltage category III, 00V, pollution degree 2 eas. frequency: Aux. supply: 0 70Hz 8-6V DC ax. 11W consumption The aux. supply inputs are to be protected by a 2A slow blow fuse (UL/cUL Listed: AWG 24) Galv. separation: Between AC voltage, AC current and other I/Os: 250V AC, 50Hz, 1 min. Between analogue outputs and other I/Os: 500V DC, 1 min. Between binary input groups and other I/Os: 500V DC, 1 min. Binary inputs: Relay outputs: Open collector outputs: Analogue inputs: Optocoupler, bi-directional ON: 8 6V DC Impedance: 4.7k OFF: <2V DC Electrical rating: 250V AC/0V DC, 5A (UL/cUL Listed: 250V AC/24V DC, 2A resistive load) Thermal rating @ 50 C 2A: Continuously 4A: t ON = 5 sec., t OFF = 15 sec. (Unit status output: 1A) Supply 8 6V DC, max. 10mA -10 0 +10V DC Not galvanically separated Impedance: 100k (0)4 20mA Impedance: 50 Not galvanically separated EC/CE: To EN 61000-6-1/2//4 IEC 60255-26 IEC 605 power distr. zone IACS UR E10 power distr. zone Vibration: 1.2Hz: 2mmpp 1.2 100Hz: 0.7g To IEC 60068-2-6 & IACS UR E10 10 60Hz: 0.15mmpp 60 150Hz: 1g To IEC 60255-21-1 Response (class 2) 10 150Hz: 2g To IEC 60255-21-1 Endurance (class 2) Shock (base mount): 10g, 11msec, half sine To IEC 60255-21-2 Response (class 2) 0g, 11msec, half sine To IEC 60255-21-2 Endurance (class 2) 50g, 11msec, half sine To IEC 60068-2-27 DEIF A/S Page 7 of 11

Bump: aterial: 20g, 16msec, half sine To IEC 60255-21-2 (class 2) All plastic materials are selfextinguishing according to UL94 (V1) Plug connections: AC current: 0.2-4.0 mm 2 stranded wire (UL/cUL Listed: AWG 18) AC voltage: 0.2-2.5 mm 2 stranded wire (UL/cUL Listed: AWG 20) Relays: (UL/cUL Listed: AWG 22) Other: 2.5 mm 2 multi-stranded (UL/cUL Listed: AWG 24) Display: 9-pole Sub-D female PC: A-B : RJ45 Approvals: The PP is approved by the major classification societies. Contact DEIF for details. UL and cul PPU anagement (PP) UL markings: Governors: Wiring: Use 60/75 C copper conductors only ounting: For use on a flat surface of type 1 enclosure Installation: To be installed in accordance with the NEC (US) or the CEC (Canada) ulti-line 2 interfaces to all governors, including GAC, Barber- Colman, Woodward and Cummins See interfacing guide at www.deif.com Weight: ain unit: 1.5 kg (.40 lbs.) J1, cable m: 0.2 kg (0.45 lbs.) Option J2: 0.4 kg (0.90 lbs.) Option J7: 0.2 kg (0.45 lbs.) Display: 0.4 kg (0.90 lbs.) Protection: Unit: IP20 Display: IP52 (IP54 with gasket: Option L) (UL/cUL Listed: Type Complete Device, Open Type) To IEC 529 and EN 60529 DEIF A/S Page 8 of 11

PPU anagement (PP) Panel cutout (mm) DEIF A/S Page 9 of 11

PPU anagement (PP) Unit dimensions in mm (inches) Display size: H x W x D = 115 (4.528 ) x 220 (8.661 ) x 20 (0.787) External 24V DC to 5V DC converter for the AOP-2 DEIF A/S Page 10 of 11

Order information The PP system is ordered in two steps: Step 1: System information Please indicate your type of PS system and the number of DGs: PS system 1 2a (Shaft) 2b (Shore) Number of DGs (2 8) Step 2: Unit option information Unit DG DG2 DG DG4 DG5 DG6 DG7 DG8 TB Option D1 E1 F1 EF2 EF4 H2 J2 J4 J7 L 15 16 18 N5 X2 (0..2) @1 X4 (0..4) @2 SG @1: One display per PP unit is already included as standard, enter only the number of additional displays here @2: One AOP-2 is already included as standard, enter only the number of additional AOP-2s here Option K1: Documentation as hard copy (no. of sets) UK (Only one hard copy is included as standard). For detailed information about options, please see option list on page 5. DEIF A/S, Frisenborgvej DK-7800 Skive, Denmark Due to our continuous development we reserve the right to supply equipment which may vary from the described. Tel.: +45 9614 9614, Fax: +45 9614 9615 E-mail: deif@deif.com, URL: www.deif.com