DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

Similar documents
EM2020 Selectable AC transducer A (UK)

DATA SHEET Selectable AC transducer, TAS-331DG

DATA SHEET Selectable AC transducer, TAS-321 DG

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

DATA SHEET IOM 200 analogue interface for AGC 200

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

MIC-2 Multi-instrument DATA SHEET

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Installation Manual. Multi Power Controller MPC-1 multi-line D

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

Generator Protection Unit, GPU Hydro Multi-line A SW version 2.4X.X

SUBJECT TO CHANGE WITHOUT NOTICE

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview

DEIF A/S. Generator Paralleling Controller multi-line L. Type GPC / GS. Compact system in one unit

RTU500 series Data Sheet Power Supply CP-E 24/2.5

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions

Basic Gen-set Controller multi-line F SW version 2.31.X or later

MINI MCR-SL-PT100-UI-200

Power supply. Interface technology in modular housing DIN rail devices, IM series. Features

Power Supply HARTING pcon

MINI-PS AC/10-15DC/8

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

E-STOP relays, safety gate monitors

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Circuit diagram. Time ranges. Function. Function diagrams. Notes. Dimension diagram. Page 1

ASI QUINT /2.4 EFD

Power Supply HARTING pcon

VariTrans A The specialist for ±10 V and ±20 ma. With calibrated range selection and broad-range power supply.

Power supply CP-C 24/5.0

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

MIC-2 MKII, Multi-instrument DATA SHEET

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

Installation / Control Technique

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

Plug-in module SIRAX TV 808, 2 channels Isolating Amplifier unipolar/bipolar

Panorama rudder indicator TRI-2 Analogue or CAN input Approved according to MED Three extra large scales Long-life LED illumination Built-in dimmer

DATA SHEET Compact Genset Controller, CGC 200

PHOENIX CONTACT - 07/2006

QUINT-PS AC/24DC/10

Universal Power Supplies

High-Voltage Isolation Amplifiers / Shunt Isolators. VariTrans P 42000

E-STOP relays, safety gate monitors

Contact protection relay

VariTrans P The Problem The variety of tasks results in a large number of different devices.

STEP-PS/1AC/24DC/1.75

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

PHOENIX CONTACT - 01/2007

Generator Controller GC-1F

LED Driver DC-String

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

DATA SHEET. Advanced Power Meter, APM 380 & APM 305

Installation Instructions

STEP-PS/1AC/24DC/2.5. Extract from the online catalog. Order No.: DIN rail power supply of 24 V DC/2.5 A, primary switched, single phase.

DATA SHEET. Advanced Energy Meter, AEM 380 & AEM 305

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

MINI MCR-SL-CVS NC

02/11/2015

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output

QUINT-PS/ 1AC/24DC/ 5

VariTrans P Standard-Signal Isolators

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Power supply CP-E 48/1.25 Primary switch mode power supply

Non-communicating room controllers

E-STOP relays, safety gate monitors

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Industrial Power Supplies

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

Standard-Signal Isolation Amplifiers. VariTrans A 21000

ISOMETER isopv with coupling device AGH-PV

E-STOP relays, safety gate monitors

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

EngyVolt RV12 and RV15

LED Driver Linear / area fixed output

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Power supply CP-E 24/0.75 Primary switch mode power supply

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

Installation Manual Series PQ-L. Electronic Module. Bulletin /UK

E-STOP relays, safety gate monitors

Generator Controller GC-1

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

Displays Transducers. Displays and transducers

Engine Controller EC-1

No longer for sale. Generator Controller GC-1. Data sheet. Standard functions

Energy Management Energy Transducer Type ET112

Multifunction Transducer MT440

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Transcription:

Installation and start up instructions TAS-331DG Selectable AC transducer 4189300008G (UK) Watt or var transducer Supply and measuring voltage up to 690V DEIF A/S Configuration via PC-interface possible 35 mm DIN rail or base mounting DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com

Description TAS-331DG is a micro controller based power transducer with 1 analog output for measurement of Watt or var. The transducer holds no mechanical moving parts like potentiometers and therefore the calibration stability is excellent. Label The configured transducer is provided with a label with the following data: Coupling Type designation DEIF s order ack. no. To be stated when contacting DEIF Measuring range Primary values Condition of external voltage transformer Measuring range Secondary values Condition of external current transformer Output range Output limited to ±22mA Auxiliary voltage Max output load current output Min output load voltage output Distributor s ID Other information If special product The un-configured transducer is provided with a label with the following data: DEIF s order ack. no. can be found on a paper label on the transducer box. About configuration see special manual. Page 2 of 8 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-331DG Mounting instructions TAS-331DG is designed for panel mounting, being mounted on a 35 mm DIN rail, or by means of two 4-mm screws. Weight: Approx. 0.650 kg The design of the transducer makes mounting of it close to similar equipment possible, however make sure there is min. 50 mm between the top and bottom of the transducer and other equipment. The DIN rail must always be placed horizontally when several transducers are mounted on the same rail. Connection diagram With voltages above 480V phase-phase. The secondary side of the current transformer must be connected to earth. Alternatively a double insulated current transformer can be used. 4189300008G (UK)

It is not necessary to protect the measuring voltage inputs. But it is recommended to use a 2A fuse for the supply input (terminals 1 and 3). The transducer is protected against ESD (electrostatic electricity), and further special protection against this during the mounting of the transducer is not necessary. The below diagram illustrates how to connect a TAS-331DG in 2W3 configuration with a TAS-331DG in 2var3 configuration. L1 L2 L3 17 19 21 17 19 21 S2 24 23 24 23 S1 27 26 27 26 S2 30 29 30 29 S1 TAS - 331DG 2W3 TAS - 331DG 2var3 Page 4 of 8 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-331DG The voltage inputs are connected as follows, if the current transformers are placed in other phases than indicated in the above diagram: 2W3/2var3 External current transformer connected to L1 (23 + 24) and L2 (29 + 30) connected to L2 (23 + 24) and L3 (29 + 30) Connect L1 to term. No. 17 L2 to term. No. 17 L3 to term. No. 19 L1 to term. No. 19 L2 to term. No. 21 L3 to term. No. 21 Couplings 1W/1var and 1W4/1var4: Connect terminal No. 17 to the phase to which the external current transformer is connected. 1W3/1var3: External current transformer Connect - connected to L2 L2 to term. No. 17 - connected to L3 L3 to term. No. 17 L3 to term. No. 19 L1 to term. No. 19 L1 to term. No. 21 L2 to term. No. 21 Connection/set up The transducer is equipped with a red LED for indication of wrong phase connection or errors in the calibration / configuration. This LED is placed under the front plate. The function of the LED are as follows: Constant light. The wiring may be wrong. There is not equal power direction on all phases. There must be signal on all inputs to ensure correct testing and current flow in all phases. Note this function is only activated in coupling 2W3, 2var3 and 3W3(4), 3var3(4). Fast pulse 5Hz. The calibration data are corrupted. Contact DEIF. Slow pulse 1Hz. The configuration data are wrong or corrupted. Make a reconfiguration or contact DEIF. About configuration see special manual. 4189300008G (UK)

Opening of the unit The front panel is removed by means of a screwdriver. The front panel may be loosened in the right side first and is then totally demounted by moving the screwdriver towards left. Mounting of the front panel Press with a screwdriver as indicated by the arrow and press the front panel down with your thumb, simultaneously. It is recommended that one side of the front panel snaps into place before the other. Page 6 of 8 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation and start up instructions, TAS-331DG Technical specifications Accuracy: Class 0.5 (-10 15 30 55 C) according to IEC 688 Influence, phase angle: ±0.75 Meas. current (In) 0.75/1.5/3.0/6.0A Meas. range: 0 200% I n I n can be set between 0.375 6A Overload, currents: Load: Meas. voltage (Un): Overload, voltages: Load: Frequency range: Indication: Output: 20A max., continuously 75A max. for 10 s 240A max. for 1 s Max. 0.5VA per phase 73/140/254/400V phase to neutral Meas. range: 30 120%U n U n can be set between 57 400V 127/240/440/690V phase to phase Meas. range: 30 120%U n U n can be set between 100 690V 1.2 x U n max., continuously, 2 x U n max. for 10 s Min. 480k 30 45 65 80Hz Note: For fundamental frequency (1. harmonic) outside 20Hz 80Hz the input is fixed to 0 Red LED function: (The LED is located behind the front plate) Incorrect wiring = constant light, only active for coupling 1W3, 2W3, 3W3(4) and 1var3, 2var3, 3var3(4). Check at power up, in case of doubt disconnect supply and reconnect Calibration error = flash frequency 5Hz Configuration error = flash frequency 1Hz 1 analog output Standard range: Output (0...100%): 0...1mA, 0...5mA, 0...10mA, 0...20mA, 0...1V, 0...5V, 0...10V Output (10...100%): 0.1...1mA, 0.5...5mA, 1...10mA, 2...20mA, 0.1...1V, 0.5...5V, 1...10V Output (20...100%): 0.2...1mA, 1...5mA, 2...10mA, 4...20mA, 0.2...1V, 1...5V, 2...10V Output (-100...0...100%): -1...0...1mA, -5...0...5mA, -10...0...10mA, -20...0...20mA, -1...0...1V, -5...0...5V, -10...0...10V Other ranges possible 4189300008G (UK)

Limit: Output load: Output cable: Max. ±120% of nominal output Burden if current output: Max. 10V (max. 1k ) Burden if voltage output: Max. 20mA Max. length 30m Ambient temperature: -10 55 o C (nominal) -25 70 o C (operating) -40 70 o C (storage) Temperature coefficient: Max. ±0.2% of full scale per 10 C Response time: Ripple: Galvanic separation: Coupling 2W3/2var3, 3W3/3var3, 3W4/3var4 <225ms, typically 200ms Coupling 1W/1var, 1W4/1var4 <150ms, typically 125ms Coupling 1W3/1var3 <125ms, typically 100ms Twice the class index (peak to peak measurement) according to IEC 688 AC aux. supply models: Between inputs, outputs and aux. supply: 3750V-50Hz-1 min. DC aux. supply models: Between inputs and outputs: 3750V-50Hz-1 min. Between inputs and supply: 3750V-50Hz-1 min. Between supply and outputs: 1500V-50Hz-1 min. Supply voltage: 57.7-63.5-100-110-127-200-220-230-240-380-400-415-440- 450-480-660-690V AC ±20% 24-48-110-220V DC -25/+30% Consumption: (Aux. supply) 3.5VA/2W Climate: HSE, to DIN 40040 EMC: According to EN 61000-6-1/2/3/4 Protection: Housing: IP40. Terminals: IP20, to IEC 529 and EN 60529 Connections: Materials: Weight: Max. 2.5mm² multi stranded Max. 4.0mm² single-stranded All plastic parts are self-extinguishing to UL94 (V1) 0.650kg Page 8 of 8 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com