DS BAS /99 UNC 596 BUILDING AUTOMATION SYSTEM UNIVERSAL NETWORK CONTROLLER FEATURES

DS A MN LCD I/A SERIES MICRONET LCD APPLICATION SPECIFICATION

DS A 10/99 MN 500 I/A SERIES MICRONET MN 500 CONTROLLERS APPLICATION SPECIFICATION

IQ21x Series Controllers

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

Installing Sentor. Hardware Installation

ATU800. Technical specification

lighting control. Each controller switches up to 48 high voltage, 20-amp lighting circuits, using

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

S66 Series Electronic Fan Speed Control

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

Features. Description. Physical

APP 700 Technical Specification

Non-communicating room controllers

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Product Data Sheet. BMS/Graphics Interface. Features

LCI User Manual mantracourt.com

Millenium II +: general characteristics

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

BACnet. b3810 Series Local Controllers

Andover ContinuumTM Infinet II

R310 & N310 R320 & N320 Digital Indicator

FX Input/Output (I/O) Modules XM07 and XM14

LC2300 Level Controller Installation and Maintenance Instructions

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

DS Type: MAXIM III Controller

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

using optional EMX 190 expansion modules), and makes access decisions based on its own distributed

Satchwell MicroNet. Building Management System MicroNet 50 Series

EP/2 Installation Instructions

Fibre Modem - Single-mode

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

Non-communicating room controllers

BACnet. b3867 Terminal Controllers

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

Sigma XT Ancillary Board (K588)

Model HM-535 Power Supply Installation and Service Instructions

DRAFT. Customer site gravity factor. Filtering parameters. Five points for linearity correction to ensure maximum accuracy

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

DS October MAXIM 1010 Controller

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications

LASERMET SLIMJIM LED SIGN INSTRUCTION MANUAL LEDS-SJ XXX

Temperature controller Ducted systems

High Performance Output Filter Instruction Manual

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

TALON Network Manager- 2 & 6 Express

MRC 7000 Proven Recording Reliability that Became the Industry Standard!

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Artistic Licence. Rail-Switch II. User Guide. Rail-Switch II User Guide. Version 5-5

RXTH DUAL ROOM SENSOR / SWITCH

Andover ContinuumTM Infinet II

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

RXTP ROOM TEMPERATURE

ORB TM 4-20 ma Input Box Installation & Operation Manual

LASERMET ULTRA LED SIGNS INSTRUCTION MANUAL. Single Aspect Illuminated Sign LEDS-ULT-790

Operating instructions. Standstill monitor A / / 2011

RTD-W Installation Instructions

The information in this chapter will enable you to: Understand the product's basic functions & features

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

Model DMX8DIM Installation and Operations Manual

XT-9100 Technical Bulletin

Lab and Central Plant Controller

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

FC-DIN DIN-Rail Mount Fan Speed Controller

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

RТTH DUAL ROOM SWITCH

MAINSLINK-RX. Features: Quick and Simple to Install. Up to 500m range outdoor. Up to m range in buildings* Reliable high end radio link

Technical specification Marine Master Clock

MCX08M2 Programmable controller

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

D/E Remote Relay Panel User Guide

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Tempco Instruction Manual

AC5160 SiPass integrated controller kit

Installation instructions Inclination sensor EC2019 EC / / 2013

VDI Pro Voltage & Dry Contact Interface Installation and programming Guide MODEL VDI MK2

IV-30 Operating Manual for Pulse Distributor Cassette with potential separation

Mega_Link Telemetry Communication System

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

IntesisBox SMS - Mitsubishi Electric air conditioners

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

LCI Load Cell Junction Box with Fault Monitor

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

User Interface Terminal for nvent RAYCHEM NGC Systems Installation Instructions DESCRIPTION TOOLS REQUIRED. Nonhazardous Locations LR67275

Instruction Sheet Board Style Low Water Cutoff

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Transcription:

DS 13.310 BAS 08/99 UNC 532 BUILDING AUTOMATION SYSTEM UNIVERSAL NETWORK CONTROLLER The Universal Network Controller (UNC 532) is a fully intelligent standalone* outstation specifically designed for sites and applications with low point counts. The UNC 532 incorporates 16-bit microprocessor technology permitting true 'peer to peer' communications directly between any of the elements on a network. Each controller can monitor and control upto 32 individual items of plant. The inputs and outputs can be configured to match the monitoring and control requirements of plant. The UNC 532 continually surveys sensors, logs data, checks status and automatically decides on any control action necessary. After initial programming, outstations perform independently of other system components. Each outstation incorporates a clock, calendar and memory to allow completely stand-alone operation. This standalone operation may be further secured and assured by the EEPROM data back up option. The optional Electrically Erasable Programmable Read Only Memory (EEPROM) is available to store the pointfile permanently in the outstation in addition to the site specific data (pointfile) stored in the battery retained memory. The integral keyboard and display, also available as a retrofit option, offers an extensive range of local overrides and interrogation of plant conditions. * After initial programming from a BAS terminal, the UNC 532 can be used in a stand-alone configuration. In the event of a power failure the EEPROM option will hold the configuration until power is restored. FEATURES 32 configurable input/output points Cycle time: Typically <1 scan per second, also configurable for each point Fully stand-alone* outstation Compact and cost effective Cable management system 16-bit microprocessor technology Two communication ports Optional EEPROM data back up Local displays and overrides Retrofit keyboard option Upto 50 software points SMT (Surface Mount Technology) based Maximum Demand/Load Shedding control capability. An Invensys company

DS 13.310 2-6 08/99 SPECIFICATIONS Type: UNC 532 Outstation, Opto-isolated BAS LAN with keyboard, 579-1-861 UNC 532 Outstation, Non-isolated BAS LAN with keyboard, 579-1-862 UNC 532 Outstation, Opto-isolated BAS LAN, 579-1-863 UNC 532 Outstation, Non-isolated BAS LAN, 579-1-864 Optional Extras: EEPROM Point file 579-1-490 Keyboard 579-1-489 Optional trunking mounting kit Spec. no. 579-1-479 (sufficient for two knock-outs) UNC Keyboard Guide Spec. no. 868-1-703 Power Supply: 230V ±10% Switch selectable to 115V ±10%, 50Hz ( 10%) to 60Hz (+10%) Consumption: 24 VA max. (Triac outputs require a separate 24Vac supply) Heat Dissipation: 25W max. Fuse: 400mA anti-surge Power Failure Reserve: Points: Ambient Temperature Limits: Relative Humidity Limits: (non-condensing) Microprocessor: EPROM: RAM: EEPROM: Ports: Nickel metal hydride rechargeable battery (continuously trickle charged) giving a typical 90 day power failure back up of point file data stored in RAM and for real time clock (assuming the battery is in good condition). Configuration data is stored permanently in EEPROM. Up to 32 hardware points and 50 software points Operating: 0 to 50 C Storage & Transit: 10 to 55 C Operating: 10 to 90% rh Storage & Transit: 5 to 95% rh NEC V25+, 16-bit running at 10MHz 512k bytes 512k bytes 1M byte (allows permanent storage of site configuration data and telephone numbers if applicable). Optional EEPROMs available to permanently back up the complete outstation pointfile. 512k bytes Specification no. 579-1-490 1 RS232/RS485 (BAS LAN) configurable - RS485 (BAS LAN) is non-isolated or opto-isolated according to specification. 1 RS232 INPUTS Analogue 8 off 0 to 10k Ohms (a span of at least 1kΩ should be used for adequate resolution). Configurable for Voltage or current by use of the following resistor kits: Range Kit Model No. 0 to 10V 833-1-601 0 to 20mA 833-1-602 Analogue inputs can be used as digital inputs as follows: Voltage Free SPST contacts (Open/Closed) capable of switching 15Vdc Digital 10 off, Voltage Free SPST Contacts (open/closed) <10k Ohms closed 1M Ohms open Max 15V dc Pulse Totalisation All 10 Digital Inputs may be used for pulse totalisation. Maximum pulse frequency 10Hz. OUTPUTS Analogue 6 off 0 to 10V dc signals (1mA per channel max. at 10V output). Analogue outputs can be used as Digital outputs by using the Digital Output Module see DS 13.355. Triac 8 Off Triac Outputs, 24Vac, 0.6A max. Minimum switching current 20mA @ 24Vac External plant should be switched via externally mounted contactors. APPLICATION AND ENERGY MANAGEMENT FEATURES Provides Distributed Direct Digital Control (3DC) Multi Password Access (from the central terminal) Energy Management Programmes Time Schedules Holiday Schedules Optimum start/stop of plant Automatic Power up of plant System and Plant Alarms Real Time System Logs Calculation Points Rotation Points Programmable points for user-defined control strategies Degree Day Calculations Maximum Demand Control/Load Shedding

08/99 3-6 DS 13.310 EQUIPMENT EEPROM: 512k bytes EEPROM - 579-1-490 - Point file EEPROM - used to permanently back-up the complete outstation pointfile (site specific data). Retrofit Keyboard and 579-1-489 Display: Trunking Mounting Kit: Allows easy installation to trunking system 579-1-479 User Guide: Keyboard Guide 868-1-703 Terminal: BAS 2800+ See DS 13.001 NIU: Autodial/Autoanswer Modem: External Input/Output Modules: CONSTRUCTION To allow convenient connection to local area networks and remote modems (see DS 13.410). See DS 13.401 (for autodial modem operation outside the UK contact your local Satchwell agent). When required externally mounted input/output modules are available to enhance outstation operation see DS 13.355. Case: Protection Class: Terminals: Cable Entry: Indication: Metal chassis with plastic side panels. IP40 by use of the trunking kit. Hard wired to pluggable screw terminal blocks. Accept 0.5 to 1.3mm 2 conductor. Chassis knockouts in top, back, sides and bottom. Trunking kit is intended for use with the knockouts in the chassis bottom Two LEDs gives an indication that the outstation is operational. KEYBOARD AND DISPLAY Operation: Display: Keyboard: The 8 keys give access to all functions of the outstation allowing it (after initial programming) to be fully standalone. The keyboard is password protected for security. It is not possible to access other outstations on the Local Area Network from the keyboard. Liquid Crystal Display (LCD), 2 lines, 40 characters per line. Default display on keyboard provides continuous indication of value or status of connected points. 8 key membrane keyboard.

DS 13.310 4-6 08/99 INSTALLATION LOCATION Select a position which is reasonably clean and free from damp and condensation. Wiring entry points are in the top, bottom, sides and back of the case. If the case is mounted outside of an enclosure it is recommended that the trunking installation kit is used. The wall should be capable of supporting the weight of the outstation. If it is to be housed in an enclosure, ensure that the heat generated can be dissipated without raising the ambient temperature of the space above the maximum temperature limit. MOUNTING 1. Drill fixing holes into the wall to the dimensions given below. If the trunking kit is used then a template is supplied showing trunking entry positions. 2. Remove both plastic side panels to expose wiring terminals and fixing holes. 3. Mount the outstation securely to the wall using the fixing holes provided. 4. Connect wiring to the outstation in accordance with the appropriate system diagram. WARNING - DO NOT SWITCH ON POWER SUPPLY UNTIL COMMISSIONING HAS BEEN CARRIED OUT BY A COMPETENT SATCHWELL ENGINEER OR AN APPROVED SATCHWELL AGENT. WIRING PRECAUTIONS All wiring to the outstation input/output terminals must be twisted pair screened wiring (not required for Triac outputs) with the screen earthed at the outstation earth terminals only. The outstation must have a verified good earth. It is recommended that the internal wiring in the outstation is loomed and identified to aid servicing and extensions to the system. A full wiring specification is available from Satchwell Control Systems Ltd. or your local Satchwell agent on request. COMMISSIONING This unit should be commissioned as part of a BAS System by a competent Satchwell engineer or an approved Satchwell agent. LCD and keyboard RS232 and RS485 Terminals Input/Output Terminals Input/Output Terminals Reset Switches Analogue Outputs Digital Inputs Triac Power Inputs FIXING HOLE DIMENSIONS Dimensions in mm Triac Outputs Analogue Inputs Fig.1

08/99 5-6 DS 13.310 TYPICAL CONNECTION DIAGRAMS BASIC HARDWIRED SYSTEM 2 1 BAS TERMINAL NIU TYPE 2 (DS 13.410) OUTSTATION UNC 532 - DS 13.310 OUTSTATION UNC 496 - DS 13.320 UNC 596 - DS 13.321 Fig.2 OUTSTATION CONNECTED TO A REMOTE MODEM BAS TERMINAL 2 NIU TYPE 2 (DS 13.410) 3 OUTSTATION UNC 532 - DS 13.310 MODEM (DS 13.401) PUBLIC SWITCHED TELEPHONE NETWORK MODEM (DS 13.401) 2 Fig.3

08/99 6-6 DS 13.310 DIMENSION DRAWING 20mm knock-out Dimensions in mm Panel knock-out Satchwell Control Systems Limited Farnham Road Slough Berkshire SL1 4UH United Kingdom Telephone +44 (0)1753 550550 Facsimile +44 (0)1753 824078 www.satchwell.com An Invensys company WARNINGS - THE UNC OUTSTATION IS A MAINS OPERATED DEVICE. LOCAL WIRING REGULATIONS AND USUAL SAFETY PRECAUTIONS MUST BE OBSERVED. NOTE EARTHING REQUIREMENTS - SEE Page 4. DO NOT SWITCH ON POWER SUPPLY UNTIL COMMISSIONING HAS BEEN CARRIED OUT BY A COMPETENT SATCHWELL ENGINEER OR AN APPROVED SATCHWELL AGENT. THIS PRODUCT CONTAINS A NICKEL METAL HYDRIDE BATTERY WHICH IS COMPLETELY SAFE WHILST IN NORMAL OPERATION. BATTERIES MUST BE DISPOSED OF IN AN AUTHORISED LANDFILL SITE. Cautions The UNC should be installed, commissioned and serviced by a competent Satchwell engineer or an approved Satchwell agent. Observe wiring precautions on Page 4. Observe maximum ambient temperature. Interference with those parts under sealed covers renders the guarantee void. It is possible that this publication may contain reference to, or information about, Satchwell products (hardware and software), programming or services that are not announced in your country. Such references or information must not be construed to mean that Satchwell intend to announce such products, programming or services in your country. Design and performance of Satchwell equipment is subject to continual improvement and therefore liable to alteration without notice. Information is given for guidance only and Satchwell do not accept responsibility for the selection or installation of its products unless information has been given by the company in writing relating to a specific application. A periodic system check of the management system is recommended. Please contact your local Satchwell service office for details. 1995 Satchwell Control Systems Limited (revised August 1999) All rights reserved. Unauthorised copying of any part of the contents is prohibited. Printed in England. 08/99