INSTALLER'S GUIDE ECON-IN-30B 18-HE60D83-3. Accessory Economizer Downflow

Similar documents
INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps

Downflow Economizers Z1ECON30 (98W09) ECONOMIZERS

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

INSTALLATION INSTRUCTIONS ECOHPRS Series Horizontal Economizer for York PRESTIGE for ZX 04-07; ZY 04-06

IN STAL LA TION IN STRUC TION

Field Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

MODELS DSH/DSV R-410A AIR SIDE ECONOMIZER KIT

INSTALLATION INSTRUCTIONS

Installation Instructions

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

READ COMPLETELY BEFORE INSTALLING!!!

Installation Instructions

Replacement Instructions. Backplane PCA for the HP Router 650

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

Removal and Installation8

Installation Instructions

G12/G12x USER S MANUAL

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

INSTALLATION MANUAL FOR CARRIER/BRYANT 3-15 TON ECONOMIZERS 3-6 TON MODELS

INSTALLATION INSTRUCTIONS ECOHAFF1860 Series Horizontal Economizer for York Affinity 3-5 Ton Units. Before Starting Installation Warning

120Ra-1 Pentium III Processor Installation Insert

Installation, Start-up and Operating Instructions

Contents. Cabinet Components " Exploded View... 1 " Usage List U.S. Models... 2 " Usage List Canadian Models... 3 " Blank Page...

imac Intel 27" EMC 2639 Hard Drive

CPH Series. Submittal Data Form. 7½- to 12½-Ton Self-Contained. Packaged Heat Pump. with R-410A

Removing and Replacing Parts

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:

Reflowing Xbox 360 Motherboard

Vacuum Maintenance Manual (EXCERPT Tim Benedict)

Installing and Removing SDRAM and DRAM

Megatouch FORCE Monitor Chassis Board Replacement

INSTALLATION INSTRUCTIONS

TABLE OF CONTENTS SECTION 1 TABLETOP CONFIGURATION SECTION 2 TABLETOP CONFIGURATION ACCESSORIES SECTION 3 SLIDE CONFIGURATION

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

Installing the Cisco ADE 2130 and 2140 Series Appliance Hardware Options

OPERATION INSTRUCTIONS

Replacing the Power Supply

DCC Commercial. Submittal Data Form Tons Packaged Air Conditioners

Manual No: Revision: D. Mag Retrofit Probe. Installation Guide

Installing Power Modules

Blackout Shutter Kits with Breathable Wall Light Traps

ETM-2050/ETM-2051 Service Manual

Series Amp Pad Mount Quick Connect Input and Output Power Panels

Installation Instructions

Z-Truck (Vertical Moving) Z-truck Flag. Y-Truck (Horizontal Moving) FIGURE 1: VIEW OF THE Z-TRUCK. Flexshaft Assembly

Installation and Start-Up Instructions

Mac mini Mid 2011 Hard Drive Replacement

Macro View All in One Scope Description. 2. Features. 3. Package Contents

P160 User s Manual Manuel de l utilisateur Anwenderhandbuch Manuale per l operatore Manual del usuario

PoE/FPR Kit for Auto-Sync Time Clock. The Auto-Sync Time Clock is a validated time system with a Web interface and auto discovery.

INSTALLATION INSTRUCTIONS

HVAC unit. Spacerfor. ILL. 3 1" filter. Screw

Zone Manager INSTALLATION MANUAL 40KMC KMQ QNC QNQ

Description: Detailed procedure on removing old bushing and installing new Brake Bushing Replacement Kit 10447

N20, N34 Series Non-Spring Return Direct Coupled Actuators

DCG Commercial. Submittal Data Form

4.1 General 4 Replacement Procedures

Installation and Maintenance Manual IM

Blackout Shutter Kits with Breathable Wall Light Traps

JADE Economizer Module (MODEL W7220)

HARMONi G3. Quick Start Guide for HARMONi G3. imac Processor/FireWire Upgrade

Series 3700 Screw Terminal Assemblies Installation Instructions

Dell Networking S4100-ON Series. Set-Up Guide

Mac mini Mid 2011 IR Sensor Replacement

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Options Overview. February 6, Ben Newell

Installing the Cisco SFS 3504 Server Switch

Dell Latitude C800 Service Manual

INSTALLATION INSTRUCTIONS MODELS (-)XRD-01RJHCM3 HORIZONTAL AIRFLOW ECONOMIZERS

VFC. Operating manual TROX air terminal units Type VFC volume flow controllers. General information 2. VFC series volume flow controllers

Plasma Panel Replacement Guide DU-42PX12X

Navigator II INstallatIoN MaNUal For static and PaN/tIlt configurations

Mounting on the Ceiling Using Flush Mount (Face Down)

Serial ATA Hot Swap Drive Cage Upgrade Kit for: Intel Server Chassis SC5200 Intel Server Chassis SC5250-E

SCSI Cable Installation Instructions

CubePro. Main PCB Replacement Guide. Prosumer 3D Printer. Original Instructions

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

Gateway Profile 4 service guide

2015 SIMMCONN LABS, LLC. All rights reserved. NewScope-T1 Operation Manual

AE R6 July 2018 Electronic Unit Controller

OPTICAL HEADEND PLATFORM OTOHP-CH 3RU CHASSIS OTOHP-PS POWER SUPPLY MODULE OTOHP-BP BLANK PANEL INSTRUCTION MANUAL

Agilent G3199 Series Quiet Cover

INSTALLATION & OPERATING INSTRUCTIONS. ECONOMIZERS WITH EXHAUST for EQUIPMENT BUILDING APPLICATIONS

ASI Systems ML5720A Series

ASI Systems ML5740A Series

Power Supply and Fan Module Installation

[GSE25SETACSS] FREEZER DOOR

Actuating Terminal Equipment Controller (ATEC) VAV with Reheat - Cooling and Heating, Application Application Note

EASTERN LABS. Instructions Model RM /25/2007. Operation. Junction Box Assembly. Different Types of Switch Installations

Cabinet Features Heavy-gauge, galvanized-steel cabinet with UV-resistant powder-paint finish Full perimeter rail Sloped drain pan

E1135C PDU and Pod Upgrade Procedure

Series Amp Quick Connect Input and Output Power Panels

Oracle <Insert Picture Here>

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY WARNINGS I INTRODUCTION II SAFETY.

Removal and Installation 8

Transcription:

INSTALLER'S GUIDE Customer Property Contains wiring, service, and operation information. Please retain. Models: BAYECON061B BAYECON062B BAYECON063B BAYECON075A Used With: YC,TCD103C,120B,150C & WCD120B, YC,TCD121C,150D,151C,180B,210C & WCD150B,180B YC,TCD181C,211C,240B,241C, 300B,301C & WCD240B YC,TCD102C,120C ECON-IN-30C 18-HE60D83-3 Library Service Literature Product Section Unitary Product Unitary Accessories Model Econ., Dmprs., Motors, Etc. Literature Type Installation Sequence 30C Date July 2002 File No. SV-UN-ACC-ECON-IN-30C 7/02 Supersedes ECON-IN-30B Accessory Economizer Downflow Since the manufacturer has a policy of continuous product improvement, it reserves the right to change specifications and design without notice. The installation and servicing of the equipment referred to in this booklet should be done by qualified, experienced technicians. American Standard Inc. 2002 1

Shipping Inspection Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days. If concealed damage is discovered, stop unpacking the shipment. Figure 1 Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery. Notify the carrier s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee. Note: Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative. Field Installed Economizer Each economizer ships partially assembled. The following steps for installation are illustrated throughout this section. Refer to the illustrations as the steps are performed. Figure 1 illustrates the major components of the economizer when shipped for field installation. As the economizer is un-crated, locate the following parts: 1. Outside air damper assembly (with wire harness) 2. Return air damper assembly (Preassembled on 102C,120C units) 3. 2 Mist eliminators 4. 1 Block-off, 2 Block-offs for 102,120C units only. 5. Barometric relief hood 6. Plastic bag of miscellaneous parts: a) Screws b) Supply air temperature sensor c) 1 Tube of sealant d) 1 Edge protector e) Installation and operation manual f) rubber grommet Verify that all of the parts are available for installation Open and lock the unit disconnect switch before installing this accessory. Failure to do so could result in severe injury or death due to electrical shock or contact with moving parts. 1. Remove the filter/fan compartment access panel. 2. Remove the unit end panel (evaporator end). 3. Place the return air damper assembly into the return air opening as illustrated in Figure 2. Damper Assembly reassembled on BAYECON075A. Insure the damper is positioned with the sheet metal lip in the upward position. 4. Attach the pivotal brackets to the unit using 2 screws per bracket, as illustrated in Figure 2. Not required on 102,120C 5. Raise the damper and rods into the vertical position. Not required for BAYECON075A. Tie the damper rods to the filter rack to prevent them from interfering with the positioning of the economizer as illustrated in Figure 2.. 6. Insure damper is positioned with sheet metal lip in the upward position,as illustrated in Figure 2. On 102C, 120C Units, secure RA blockoff to bottom filter rack blockoff with screws. 7. Attach the barometric relief hood to the back of the economizer assembly, using 2 screws at the top, as illustrated in Figure 3. Note: If barometric relief is desired, remove the shipping screw that holds the barometric relief damper blade and ensure that the damper swings freely, before attaching the barometric hood. 8. Install the block-off as illustrated in Figure 4. The blockoff is designed to close the opening created, between the economizer and the base, when the economizer assembly is in it's operating position. Holding the block-off with the holes at the bottom and the bottom angle outward press the bottom of the blockoff against the unit and line up the holes. Using the provided screws, secure it into place. 9. Remove approximately 3" of gasket material from the bottom of each corner post to expose the holes used to attach the economizer assembly to the unit, as illustrated in Figure 4, Detail "A". Note: There are two holes, a (large) clearance hole and a (small) engagement hole. The usage of each hole will be discussed as the process continues. 2

Figure 2 Figure 4 10. With the barometric relief hood attached to the economizer assembly, place the assembly into the opening with the back right flange, on the economizer, behind the corner post flange, as illustrated in Figure 5. Position the left side flange, on the economizer, in front of the corner post flange. With the screws provided, secure the bottom right hand side of the economizer assembly by inserting the screws, through the clearance holes in the corner post, into the engagement holes in the economizer assembly, as illustrated in Figure 4, Detail "A". 10. Before the right hand return air linkage bracket can be installed, two (2) outside air damper screws must be removed as illustrated in Figure 5, Detail "A". Align the return air linkage bracket with these holes and reinstall the two (2) screws. Install the left hand return air linkage bracket using the engagement holes in the outside air damper. Assembly not required on BAYECON075A 11. Manually operate the dampers, slowly; to ensure no binding exists. 12. The economizer comes pre-wired from the factory. Figure 5 Secure the bottom left hand side of the economizer assembly by inserting the screws, through the clearance holes in the economizer assembly, into the engagement holes of the corner post. Refer to Figure 4, Detail"A". Figure 3 3

Route the wire harness on the economizer assembly from the economizer module (UEM) panel to the polarized plug connector and control wires located in the unit.,refer to Figure 6 for plug and control wire location depending on unit size. Detail A : Unit size YCD/TCD103C,120B,150C, WCD120B Note: Ensure the directional arrow on the mist eliminator is pointing in the same direction as the airflow. Figure 6 Detail B : Unit size YCD/TCD102C,120C,121C, 150D,151C, 180B,210C, WCD150B,180B Detail C : Unit size YCD/TCD181C,211C,240B,241C, 300B,301C, WCD240 (Install the plastic edge protector to protect wiring anywhere it passes over a sharp sheet metal edge). 13. Connect the the polarized from the economizer wiring harness to the polarized plug in the unit. Connect the two control wires with 1/4" connectors from the economizer wiring harness to the 1/4" connectors in the unit. 13.1 On Heat Pump Units (WCD), in addition to the unit harness, there will be a 3-wire harness complete with a 3-pin connector from the defrost module in the control box. This harness will be located next to the polarized plug of the unit wiring harness. It will be coiled up and held in place with a wire tie. Figure 7 13.2 Cut the wire tie holding the 3-wire harness in this location, and route over the coil and down to the economizer. Connect to the J4 pins marked DEF of the unitary economizer module (UEM). The J4 pins are located on the left hand side of the module. See Figure 15. Note: There are two extra wires in the unit wiring harness with 1/4 inch quick connects terminals. These wires are for use when additional accessory items, pressure sensing devices, are being installed. 14. Route the sensor wires with its 2-pin female connector, to the economizer module (UEM) panel and connect it to the J2 terminal connector marked, SA (supply air). 15. Install the rubber grommet, provided with the sensor, into the hole on the fan assembly channel, as illustrated in Figure 7. 16. Insert the supply air temperature sensor through the grommet, approximately one half (1/2) inch, with the end pointing toward the coil, as illustrated in Figure 7. Important Note: when unit is equipped with a TCI (Communication Interface), the supply air sensor must be located downstream of the heat source for a true reading, and to utilize the supply air tempering feature. This requirement also applies when the unit is used with any Intergrated ComfortÔ System (ICS) device such as Tracker, Tracer, or ComforTracÔ 17. Install the mist eliminators with the directional arrow pointing up. Loosen the screws holding the mist eliminator angles and adjust them to hold the mist eliminators in position. Tighten the screws. Important Note: On Heat Pump Model Only (WCD), remove the compressor access panel and the control box cover. The unitary economizer module (UEM), must be connected in-line between the defrost module (DFM) and the unitary control processor (UCP). This is accomplished by locating the polarized plug (PPF8) from the UCP and the polarized plug (PPM8) from the DFM in the control box. They are connected to each other,and located between the UCP and the DFM. 4

Important Note: On Heat Pump Model Only (WCD) These polarized plugs are not marked as PPF8,PPM8 etc., but their wires are numbered as shown in the Existing Plug View. Refer to Existing Plug View to assist in identifying. Next locate the PPF10 and the PPM9 polarized plugs. These plugs are not connected but will be located in the same area. Refer to Reconnected Plug View to assist in identifying. Next separate the polarized plugs(ppf8 and PPM8). Connect the PPF8 plug to the PPM9 plug and the PPM8 plug to the PPF10 plug.refer to Reconnected Plug View. Existing Plug View PPF10 114A (PR) 1 113A (BK) 2 115A (BL) 3 4 PPF8 PPM8 107E (YL) 1 1 W26 (PR) 108E (YL) 2 2 W25 (BK) 109E (YL) 3 3 W27 (BL) 125A (YL) 4 4 125B (PR) 18. Install the end panel, removed in step 2, onto the economizer as follows: a. bend the top of the end panel, at the crease line, outward to approximately 45 degrees. b. place the end panel over the economizer and slide the top of the panel under the roof panel. Replace the screws along the top, as illustrated in Figure 8. c. while pushing in at the crease in the end panel, reinstall the two (2) screws along each side above the crease in their original location, as illustrated in Figure 8. d. align the upper row of three (3) screw holes with the holes in the bottom of the economizer frame, as illustrated in Figure 8. Note: Do not use the original 5 lower screw holes in the end panel. 19. Using the sealant that shipped with the economizer, seal along each side, bottom, and any other areas that could be a potential air leak, as illustrated in Figure 8. 20. Replace the filter/fan access panel. 21. Complete the setup and checkout procedures in the "Final Economizer Setup" section. Figure 8 Reconnected Plug View PPM9 1 107C (YL) 2 108C (YL) 3 109C (YL) 4 PPF8 PPM9 107E (YL) 1 1 107C (YL) 108E (YL) 2 2 108C (YL) 109E (YL) 3 3 109C (YL) 125A (YL) 4 4 PPF10 PPM8 114A (PR) 1 1 W26 (PR) 113A (BK) 2 2 W25 (BK) 115A (BL) 3 3 W27 (BL) 4 4 125B (PR) Replace the control box cover and the compressor access panel. 5

Factory Installed Economizer Figure 10 Each economizer ships inside the unit and requires partial assembling and setup. The following steps are illustrated throughout this section. Refer to the illustrations as the steps are performed. Open and lock the unit disconnect switch before performing the following procedures. Failure to do so could result in severe injury or death due to electrical shock or contact with moving parts. 1. Remove the filter/fan compartment access panel. 2. Remove the five (5) or nine (9) lower screws in the end panel, as illustrated in Figure 9. Note: Do not remove the three (3) or five (5) screws in the upper row of the end panel. 3. Grasp the bottom of the end panel and pull the economizer assembly outward into the operating position, as illustrated with the arrow in Figure 9. 4. Remove approximately 3" of gasket material from the bottom of each corner post to expose the holes used to attach the economizer assembly to the unit, as illustrated in Figure 10. 5. With the screws provided, secure each side of the economizer assembly by inserting a screw, through the clearance hole in the bottom of the corner post, into the engagement hole in the economizer assembly. Refer to Figure 10. Figure 9 6. From inside the evaporator fan compartment, remove the following parts; a. block-off angle (located in drain pan) b. plastic bag containing; 1. one tube of sealant 2. screws c. barometric relief hood 7. The barometric relief hood ships in two (2) sections and is secured during shipping with brackets. Discard the brackets after removing the hood and install it, as follows; Note: If barometric relief is desired, remove the shipping screw from the barometric relief damper blade and ensure that it swings freely, before attaching the barometric hood. a. Attach the larger section of the barometric relief hood to the back of the economizer assembly, using 2 screws at the top and to the drain pan support using 2 screws at the bottom, as illustrated in Figure 11. b. Attach the outer section of the hood to the larger section, previously installed. c. With both sections assembled together, secure the completed hood at the top with two (2) screws provided, as illustrated in Figure 11. 6

Figure 11 Detail A : Unit size YCD/TCD103C,120B,150C, WCD120B Detail B : Unit size YCD/TCD102C,120C,121C,150D 151C, 180B,210C, WCD150B,180B Detail C : Unit size YCD/TCD181C,211C,240B,241C, 300B,301C, WCD240 Figure 13 8. Install the block-off underneath the economizer, as illustrated in Figure 12. The block-off is designed to close the opening created, between the economizer and the base, when the economizer assembly is in its operating position. Figure 12 a. Holding the block-off with the holes at the bottom and the bottom angle outward, tilt the top forward and insert it into the opening between the economizer and the unit base. b. Press the bottom of the block-off against the unit and line up the holes. Using the provided screws, secure it into place. 11. Ensure that the two wires with the 1/4" quick connectors are connected and the sensor wires with the 2-pin female connector terminates at the J2 terminal connector marked, SA (supply air), inside the economizer module panel. 12. Replace the filter/fan access panel. 13. Complete the setup and checkout procedures in the "Final Economizer Setup" section. Final Economizer Setup 9. Using the sealant that shipped with the economizer, seal along each side, bottom, and any other areas that could be a potential air leak, as illustrated in Figure 12. 10. To prevent possible economizer operation before field setup, the economizer wiring harness was not connected at the factory. Connect the wire harness on the economizer assembly from the economizer module (UEM) panel to the polarized plug connector located in the unit.,refer to Figure 13 for plug location depending on unit size. 7

To adjust the outside air "minimum position" potentiometer and to check out the economizer, the power must be turned "On". Should the system communications fail between the TCI and a Building Management System, or; if a Building Management System designates "minimum position control" to be local verses remote - the economizer will default to the potentiometer setting on the Unit Economizer Module (UEM). Adjust the potentiometer as follows: 1. Close the unit disconnect switch. To prevent injury or death from electrocution or contact with moving parts, it is the responsibility of the technican to recognize these inherent hazards and use extreme caution when performing service procedures with the electrical power energized. 2. Initiate a unit test mode utilizing the test terminals. Refer to the unit Installation, Operation, & Maintenance Manual for information. 3. Select "Fan Only" test mode. This will allow the economizer actuator to open the outside air damper to the "minimum ventilation position" setpoint. 4. To access the Unit Economizer Module (UEM), Actual percentage of outside air is dependent on the system design and can be determined by airflow measurements or by using proper temperature measurements. Example: Temperature Method, where: 1) % Outside Air = Mix Air Temp - Return Air Temp Ambient Temp - Return Air Temp X 100 or; 2) Mixed Air Temp = % Outside Air X (Ambient Temp - Return Air 100 Temp) + Return Air Temp Step 1, Measure the; Ambient Temperature = 85 O F Return Air Temperature= 75 O F (in the return air duct) Mixed air temperature = 78 O F (entering the filters) Step 2, Input the temperature measurements into formula 1, and complete the calculations, to determine the amount of outside air that is actually entering the system. Input the "desired amount" of outside air and the temperature measurements requested in formula 2, and complete the calculations, to determine the appropriate mixed air temperature. Figure 14 Taking several temperature readings for each input a. remove the fresh air adjustment panel located on the unit end panel, as illustrated in Figure 14. b. remove the sheetmetal cover from the economizer control panel to expose the Economizer module. 5. Turn the potentiometer located on the UEM, clockwise to increase the amount of ventilation" or counterclockwise to decrease the amount of ventilation". Refer to the UEM illustration in Figure 15 for the potentiometer location. For checkout purposes, there is a drive indicator light located at the lower left corner of the unit economizer module. This light will be energized anytime the motor is driving the damper, either open or closed. Refer to the illustration in Figure 15. When adjusting minimum position, the damper may move to the new setting in several small steps. Allow at least 10 to 15 seconds for the actuator to drive the damper to the new position. When the arrow on the potentiometer s adjustment screw is pointing toward 8 o clock, the minimum position should be approximately zero (0) percent. When pointing toward 12 o clock it should be approximately twenty five (25) percent. When pointing toward 4 o clock it should be approximately fifty (50) percent, as illustrated in Figure 16. The damper will open to this setting each time the supply fan circuit is energized. Calculating "Ventilation Air" 8

and averaging them, will enhance the accuracy of obtaining the proper amount of ventilation air. When the supply fan circuit is de-energized, the damper closes. 6. Open and lock the unit disconnect switch before continuing to the following procedures. Open and lock the unit disconnect switch before performing the following procedures. Failure to do so could result in severe injury or death due to electrical shock or contact with moving parts. Figure 15 Economizer "Dry Bulb" Switch Settings Under stand-alone control, the dry bulb change over temperature is field selectable at the UEM. Remote control may be selected by the Building Management System, in which case the decision to enable "economizer cooling" is made by the building management system. In this mode the dry bulb setting at the UEM will be ignored. Three dry bulb change over temperatures (55, 60, or 65 degrees F) may be selected by setting SW1 and SW2 on the UEM. See the Table below for the switch settings and Figure 15 for the switch location. "OFF" position is towards the edge of board and "ON" is towards the center of board. Figure 16 9

Switch Setting Table Switch 1 Switch 2 Temperature Setting OFF OFF 60 (Factory Set)* OFF ON 55 ON OFF 65 ON ON Not Used Economizer Control Options Control Option Enable Conditions* Optional Sensors Required** Dry Bulb (standard) Outdoor Air temp below 60 F None Reference Enthalpy Outdoor Air Enthaply below Outdoor Humidity Reference Enthalpy set on UEM (BAYENTH003A) Comparative Enthalpy Outdoor Air Enthalpy below Outdoor Humidity Return Air Enthalpy Return Humidity Return Temperature (BAYENTH004A) * - Economizing is enabled when these conditions are met ** - Conditions level will be configured when optional sensors are connected. Close unit disconnect and set zone sensor to desired setting for normal operation. 10

11

American Standard Inc. 2002 Technical Literature Printed in USA 12