PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

Similar documents
PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-3200 MANUAL INSULATION MONITOR

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

SE-701 MANUAL GROUND-FAULT MONITOR

PGR-2601 MANUAL DC GROUND-FAULT RELAY

SE-703 MANUAL EARTH-LEAKAGE MONITOR

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR

SE-601 MANUAL DC GROUND-FAULT MONITOR

PGM-8134 MANUAL GROUND CONTINUITY MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

SB6100 MANUAL INDUSTRIAL SHOCK-BLOCK

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

SE-134C MANUAL GROUND-FAULT GROUND-CHECK MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Section 4 Ground-Fault Protection Devices

Contact protection relay

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

02/11/2015

EL731 PROFIBUS INTERFACE

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

Section Overview. Table of Contents Littelfuse POWR-GARD Products Catalog

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

STBEHC3020KC counter kit STB - 1 CH Hz - 2 I

Zelio Control-modular measurement and control relays 1

Measuring and Monitoring Relays

E1 Plus Electronic Overload Relay

SE-330 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR

Ordering Key. Type Rated Operational Rated operational Control Voltage Uc Options

XPSMP11123P module XPS-MP - 2 independent functions - 24 V DC

100% electricity. Automatic transfer switch controllers ATL series

02/11/2015

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

Rated operational Control Voltage Uc Supply Voltage Connection Rated operational current 40 C voltage Ue Us 25A AC-53a 32A AC-53a

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

Motor Controllers AC Semiconductor Motor Controller Type RSHR MIDI

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

sigma the power to protect Instruction Manual C-453EM

RM4TR31 three-phase network control relay RM4-T - range V

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

TM3AI4 module TM3-4 analog inputs

E-STOP relays, safety gate monitors

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

ISOMETER isoev425/isoev425hc with coupling device AGH420

em4 Accessories Digital expansions

Quick Start Guide TS A

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09.

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

920 Remote Control (RC) Switches

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

TM3TI8T module TM3-8 inputs temperature

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

SR2B201FU compact smart relay Zelio Logic - 20 I O V AC - clock - display

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations

24/48/120 VAC Interface Card Instruction Manual

PM Series Power Meter

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

RM35TF V AC

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

ATSU01N209LT soft starter for asynchronous motor - ATSU01-9 A V KW

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

EL731 MANUAL AC/DC SENSITIVE EARTH-LEAKAGE RELAY

TM3TI4 module TM3-4 inputs temperature

E-STOP relays, safety gate monitors

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

SR2A201BD compact smart relay Zelio Logic - 20 I O - 24 V DC - no clock - display

ISOMETER isoev425 with coupling device AGH420

EL731 DEVICENET INTERFACE

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

Making Hazardous Operations Safe and Productive

Automatic Transfer Switch OTM_C_20D. Installation and Operation Instructions

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

9926 Series Branch Rated Circuit Breakers AC Version

ict contactors EN 61095, IEC 1095 Interference

Earth Continuity Monitor

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

Classification Enclosure rating Input voltage Type of

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

SensoTrans DMS A 20220

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

Transcription:

Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 0-C-041918 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document Number: PM-1101-EN

PGR-6101 Ground-Fault & Insulation Monitor Page i This page intentionally left blank.

PGR-6101 Ground-Fault & Insulation Monitor Page ii TABLE OF CONTENTS LIST OF FIGURES SECTION PAGE FIGURE PAGE 1 General... 1 2 Operation... 1 2.1 Output Relay Operating Mode... 1 2.2 PGR-6101 Operating Mode... 1 2.2.1 Online Operation... 1 2.2.2 Offline Operation... 1 2.3 Front-Panel Controls... 1 2.3.1 Ground-Fault Trip Level... 1 2.3.2 Ground-Fault Trip Time... 1 2.3.3 Insulation Resistance Response... 1 2.3.4 Reset... 1 2.3.5 Test... 2 2.4 Front-Panel Indication... 2 2.4.1 Power... 2 2.4.2 > I... 2 2.4.3 CT... 2 2.4.4 Active... 2 2.4.5 <R... 2 2.5 Analog Outputs... 2 2.5.1 OUT I... 2 2.5.2 OUT R... 2 2.6 Remote Test... 2 2.7 Remote Reset... 2 2.8 CT Verification... 2 3 Installation... 2 3.1 PGH-5000 and PGH-6000... 4 4 Technical Specifications... 8 4.1 PGR-6101... 8 4.1.1 PGR-6101 Online Operation... 8 4.1.2 PGR-6101 Offline Operation... 8 4.2 PGH High Tension Couplers... 9 5 Ordering Information... 9 6 Performance Tests... 10 6.1 Ground-Fault Test... 10 6.2 Insulation Test... 11 Appendix A PGR-6101 Revision History... 12 1 PGR-6101 Outline and Mounting Details... 3 2 Typical Connection Diagram... 4 3 PGC-5000-Series Current Sensors... 5 4 PGH-5000 Outline and Mounting Details... 6 5 PGH-6000 Outline and Mounting Details... 7 6 PGA-0500 Analog Percent Current Meter... 9 7 PGA-0510 Analog Ohm Meter... 10 8 Ground-Fault-Test Circuit... 11 TABLE LIST OF TABLES PAGE 1 Ground-Fault-Test Record... 11 DISCLAIMER Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.

PGR-6101 Ground-Fault & Insulation Monitor Page iii This page intentionally left blank.

PGR-6101 Ground-Fault & Insulation Monitor Page 1 1. GENERAL The PGR-6101 Ground-Fault & Insulation Monitor can detect a motor ground fault whether the motor is running (Online mode) or stopped (Offline mode), and can be used to protect a motor supplied by a solidly grounded, resistance-grounded, or ungrounded system. On an ungrounded system, use only the Offline mode. On grounded systems, a current transformer (CT) is used to detect ground-fault current as low as 30 ma when the motor is running, and insulation resistance is measured to detect a fault when the motor is stopped. Online or Offline mode is selected with a digital input connected to a starter auxiliary contact. In the Online mode, ground-fault current is sensed by a PGC-5000-series zero-sequence CT. The trip level of the ground-fault circuit is selectable from 30 to 200 ma. Trip time is selectable from <50 to 250 ms. Additional currentdetection features include harmonic filtering, a relay output that can operate in the fail-safe or non-fail-safe mode, CTconnection detection, LED trip, power, and open-ct indication, autoreset or latching trips with front-panel and remote reset, a test button, and a 0- to 1-mA-analog output. In the Offline mode, insulation-resistance monitoring is enabled, with a selectable 60- to 600-k alarm-setting range. Additional insulation-monitoring features include a relay output that can operate in the fail-safe or non-fail-safe mode, LED active and low-resistance indication, and a 0- to 1-mA-analog output. The PGR-6101 can be directly connected to a supply up to 1.3 kv. For systems from 1.3 to 5 kv, use a PGH-5000 High Tension Coupler. For systems from 5 kv to 6 kv, use a PGH-6000 High Tension Coupler. 2. OPERATION 2.1 OUTPUT RELAY OPERATING MODE In the fail-safe mode the output relays energize when power is applied and the ground-fault and insulationresistance circuits are not tripped. Fail-safe mode is the factory setting. For non-fail-safe operation connect terminals 19-20 and 22-23. The respective output relay will energize when a fault occurs. See Fig. 2. 2.2 PGR-6101 OPERATING MODE Connect terminals 27 and 28 to a normally closed (Form B) auxiliary starter contact. When terminals 27 and 28 are open, Online mode (insulation monitoring off) is selected and when terminals 27 and 28 are connected, Offline mode (insulation monitoring active) is selected. 2.2.1 ONLINE OPERATION When the monitor is running, the PGR-6101 in conjunction with a PGC-5000-series zero-sequence current sensor operates as a sensitive ground-fault relay. 2.2.2 OFFLINE OPERATION The PGR-6101 changes mode by means of an auxiliary contact on the main contactor when the motor is off. It becomes an insulation-resistance monitor and imposes a small dc voltage to the motor windings and supply cable from the motor starter. Leakage to ground is detected. 2.3 FRONT-PANEL CONTROLS 2.3.1 GROUND-FAULT TRIP LEVEL The Leakage Current I selector switch is used to set the ground-fault trip level from 30 to 200 ma. For ground-fault detection, the switch setting must be set substantially below the prospective ground-fault current. To avoid sympathetic tripping, the switch setting must be above the charging current of the protected feeder. 2.3.2 GROUND-FAULT TRIP TIME The PGR-6101 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with upstream and downstream ground-fault devices. Trip time is selectable from < 50 ms to 250 ms. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault. 2.3.3 INSULATION RESISTANCE RESPONSE The PGR-6101 insulation resistance function has an adjustable alarm range of 60 to 600 k. There is no selectable time delay. The unit will operate in less than three seconds. 2.3.4 RESET The front-panel RESET button is used to reset latching trips. After a fault has been cleared, cycling the supply voltage will also reset the PGR-6101. To use the PGR-6101 in autoreset mode, connect terminals 18-19 and 21-22. See Fig. 2. The reset function is not instantaneous. Press the RESET button for several seconds.

PGR-6101 Ground-Fault & Insulation Monitor Page 2 2.3.5 TEST The TEST button will test both leakage-current and insulation-resistance circuits regardless of the selected operating mode. Press the TEST button for at least eight seconds to complete test. All LED s will light and relay contacts will change to fault/alarm state. In the default mode (latching), the tripped state will remain until reset. Allow eight seconds before operating the RESET push button. 2.4 FRONT-PANEL INDICATION 2.4.1 POWER The green LED labelled PWR indicates presence of supply voltage. 2.4.2 > I The red LED labelled > I indicates a ground-fault trip. 2.4.3 CT The red LED labelled CT indicates that a PGC-5000-series current sensor is not connected. See Section 2.8. 2.4.4 ACTIVE The green LED labelled ACTIVE indicates that the Offline monitoring function is active. The insulation monitoring or lockout function is active when terminals 27 and 28 are connected. See Section 2.2. 2.4.5 <R The red LED labelled <R indicates a low resistance. 2.5 ANALOG OUTPUTS 2.5.1 OUT I A non-isolated, 0- to 1-mA output (terminals 24 and 25) indicates ground-fault current sensed by the CT. The fullscale value corresponds to the ground-fault trip setting. For example, if the ground-fault trip setting is 30 ma, then 1 ma output will be indicated when the measured current is 30 ma. The output is linear between zero and full scale. See Figs. 2 and 6. 2.5.2 OUT R A non-isolated, 0- to 1-mA output (terminals 25 and 26) indicates insulation resistance. The metering output relates to an insulation-resistance range of 0 to infinity. See Figs. 2 and 7. 2.6 REMOTE TEST Use external switches to test the current-sensor detection, insulation-monitoring activation, and insulationmonitoring functions. See Fig. 2. Response to a test input can take several seconds. 2.7 REMOTE RESET For remote reset, connect a switch or pushbutton with a normally closed contact between the neutral side of the supply voltage and terminal 5. See Fig. 2. For an alternate configuration, connect a normally open, double-pole, single-throw switch across terminals 18 and 19, and terminals 21 and 22. A momentary connection across these terminals will reset the PGR-6101. 2.8 CT VERIFICATION A ground-fault trip will occur and the red CT LED will light when a PGC-5000-series CT is not connected to terminals 16 and 17. 3. INSTALLATION NOTE: Mounting, terminal block connections and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation. This ground-fault monitoring system consists of a PGR- 6101-series Ground-Fault & Insulation Relay, a PGC- 5000-series CT, and for systems over 1.3 kv, a PGH-5000 or PGH-6000 High Tension Coupler connected as shown in Fig. 2. A PGR-6101 can be surface or DIN-rail mounted. See Fig. 1. Use terminal 6 (L1) as the line terminal for a 120 or 240 Vac supply. Use terminal 7 as the line terminal for a 24 Vac supply. Use terminal 5 (L2/N) as the neutral terminal. Connect terminal 30 to ground. Pass the phase conductors through the CT window and position them in the centre of the opening (for four-wire and single-phase systems, also pass the neutral conductor through the CT window). Do not pass ground conductors through the CT window. In applications that require shields or drain wires to pass through the CT window, return them through the CT window before connecting them to ground. CT connections are not polarity sensitive. Applications in electrically noisy environments require twisted- or shielded-twisted-pair CT-secondary conductors. Connect the CT-secondary leads to terminals 16 and 17, and connect the shield to terminal 17. See Fig. 3 for PGC-5000-series CT dimensional drawings. If insulation monitoring is required, connect terminals 27 and 28 to a normally closed contact on the motor starter. For systems up to 1.3 kv connect terminal 2 to one phase of the load side of the starter. Connect optional PGA-0500 Analog Current Meter and PGA-0510 Analog Ohm Meter as shown in Fig. 2. Meter outline, dimensions, and cutout size are shown in Figs. 6 and 7.

FIGURE 1. PGR-6101 Outline and Mounting Details. PGR-6101 Ground-Fault & Insulation Monitor Page 3

PGR-6101 Ground-Fault & Insulation Monitor Page 4 3.1 PGH-5000 AND PGH-6000 For 5-kV and 6-kV systems, connect the PGR-6101 to the monitored circuit with a PGH-5000 and PGH-6000 respectively. See Fig. 4 for PGH-5000 outline and mounting details. See Fig. 5 for PGH-6000 outline and mounting details. Connect protective-ground terminal ( ) to ground. Connect terminal E to ground or to PGR-6101 terminal 30, which must be grounded. Connect terminal M to PGR-6101 terminal 29. (PGR-6101 terminal 2 is not used.) For PGR-6101 to PGH-5000/PGH-6000 distances greater than 10 m (30 ), use shielded cable, and connect the cable shield to the second PGH-5000/PGH-6000 terminal E. Connect terminal A to one phase on the load side of the motor starter. See Fig. 2. The PGH-5000/PHG-6000 includes 915 mm (36 ) of high-voltage conductor. FIGURE 2. Typical Connection Diagram.

FIGURE 3. PGC-5000-Series Current Sensors. PGR-6101 Ground-Fault & Insulation Monitor Page 5

FIGURE 4. PGH-5000 Outline and Mounting Details. PGR-6101 Ground-Fault & Insulation Monitor Page 6

FIGURE 5. PGH-6000 Outline and Mounting Details. PGR-6101 Ground-Fault & Insulation Monitor Page 7

PGR-6101 Ground-Fault & Insulation Monitor Page 8 4. TECHNICAL SPECIFICATIONS 4.1 PGR-6101 Supply: 120 Option... 5 VA, 120/24 Vac, (+10, -15%) 50/60 Hz Operation Class... Continuous K1 and K2 Relay Contacts: Configuration... N.O. and N.C. (Form C) Operating Mode... Fail-Safe or Non-Fail-Safe UL Contact Rating... 5 A Resistive, 125 Vac Switching Capacity... 625 VA Supplemental Contact Ratings: Carry Continuous... 5 A, maximum Break: 30 Vdc... 5 A 110 Vdc... 0.3 A Trip Mode... Latching or Autoreset Reset... Front-Panel Button and Remote N.C. Contact Test... Front-Panel Button and Remote Contacts Terminals... Wire Clamping, 12-22 AWG (0.3 to 2.5 mm 2 ) conductors Tightening Torque...0.40 N m (3.54 lbf in) Conductor Type... Copper, Solid or Stranded with Ferrules Conductor Rating... 60/75 C Dimensions: Height... 75 mm (3.0 ) Width... 100 mm (3.9 ) Depth... 113 mm (4.4 ) Including DIN rail... 115 mm (4.5 ) Shipping Weight... 0.45 kg (1 lb) Environment: Operating Temperature... -10 to 60 C (14 to 140 F) Storage Temperature... -40 to 80 C (-40 to 176 F) Humidity... 85% Non-Condensing Enclosure Rating... IP20 Altitude... 2,000 m (6,562 ft)... maximum Overvoltage Category... II Pollution Degree... 2 Certification... UL Listed UL508 Industrial Control Equipment FCC 4.1.1 PGR-6101 ONLINE OPERATION Trip-Level Settings (ΔI)... 30, 60, 100, and 200 ma Trip-Time Settings... <50, 150, 200, and 250 ms Input: CT... PGC-5000-Series CT Detection... Open-Circuit Detection Analog Output: Mode... Self Powered Range... 0-1 ma Output impedance... 5 k maximum 4.1.2 PGR-6101 OFFLINE OPERATION Maximum System Voltage: Direct Connection... 1,300 V With PGH-5000... 5,000 V With PGH-6000... 6,000 V Measuring Voltage... 12 Vdc Measuring Current... 20 A maximum DC Resistance... 600 k AC impedance at 50-60 Hz... > 1 M Response-Level Settings... 60 to 600 k Response Delay... < 3 s Maximum Leakage Capacitance to Ground... < 1 F Maximum Stray Voltage... 1,000 Vdc Analog Output: Mode... Self Powered Range... 0-1 ma Impedance... 5 k maximum

PGR-6101 Ground-Fault & Insulation Monitor Page 9 4.2 PGH HIGH TENSION COUPLERS Maximum Line Voltage: PGH-5000... 5,000 Vac PGH-6000... 6,000 Vac 5. ORDERING INFORMATION Current to Ground... 2.5 ma maximum Terminal M Maximum Voltage... 50 Vac Terminals: E, E, and M... Wire Clamping, 22 to 12 AWG (0.2 to 2.5 mm 2 ) conductors... Wire Clamping, 10 AWG (5.26 mm 2 ) maximum High Tension Lead A... 8 AWG (8.36 mm 2 ), 40 kvdc, 915 mm (36 ) PGA-0500...Analog Percent Current Meter PGA-0510...Analog Ohm Meter PGC-5025...Current Sensor, 25.0 mm (0.98 ) window PGC-5060...Current Sensor, 60.8 mm (2.39 ) window PGC-5095...Current Sensor, 95.0 mm (3.74 ) window PGC-5130...Current Sensor, 130.0 mm (5.12 ) window PGC-5200...Current Sensor, 200.0 mm (7.87 ) window PGH-5000...5 kv High Tension Coupler PGH-6000...6 kv High Tension Coupler FIGURE 6. PGA-0500 Analog Percent Current Meter.

PGR-6101 Ground-Fault & Insulation Monitor Page 10 FIGURE 7. PGA-0510 Analog Ohm Meter. 6. PERFORMANCE TESTS 6.1 GROUND-FAULT TEST Some jurisdictions require periodic ground-fault performance tests. A test record form is provided for recording the date and the result of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel. a) Evaluate the interconnected system in accordance with the overall equipment manufacturer s detailed instructions. b) Verify proper location of the PGC-5000-series CT. Ensure the cables pass through the CT window. This check can be done visually with knowledge of the circuit. The connection of the current-sensor secondary to the PGR-6101 is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths. d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled groundfault current. To simulate ground-fault current, use CT-primary current injection. Fig. 8 shows a test circuit using the SE-400 Ground-Fault-Relay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Fig. 8 shows the use of resistors that reduce the injected current to 10% of the SE-400 setting. Set the test current to 120% of the PGR-6101 setting. Inject the test current through the CT window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and re-test until the proper reaction is verified.

PGR-6101 Ground-Fault & Insulation Monitor Page 11 e) Record the date and the results of the test on the attached test-record form. NOTE: Do not inject test current directly into CT-input terminals 16 and 17. 6.2 INSULATION TEST Perform this test with the starter open and appropriate lock-out procedures. Connect a 10-k resistor between one phase and ground at the line side of the starter or motor terminal box. Select a phase that is not connected to PGR-6101 terminal 2 (or the PGH-5000 or PGH-6000). The PGR-6101, operating in Offline mode as indicated by the green ACTIVE LED, will alarm, operating the K1 low insulation output relay and lighting the red <R LED. FIGURE 8. Ground-Fault-Test Circuit. TABLE 1. GROUND-FAULT-TEST RECORD DATE TEST RESULTS Retain this record for the authority having jurisdiction.

PGR-6101 Ground-Fault & Insulation Monitor Page 12 MANUAL RELEASE DATE April 19, 2018 February 6, 2014 APPENDIX A PGR-6101 REVISION HISTORY MANUAL REVISION 0-C-041918 0-B-020614 PRODUCT REVISION (REVISION NUMBER ON PRODUCT LABEL) November 22, 2013 0-A-112213 00 MANUAL REVISION HISTORY REVISION 0-C-041918 SECTION 4 Specifications added. REVISION 0-B-020614 SECTION 3 Fig. 3 updated. SECTION 4 UL Certification and contact rating specifications added. REVISION 0-A-112213 Initial release. PRODUCT REVISION HISTORY PRODUCT REVISION 01 UL Certification. PRODUCT REVISION 00 Initial release. 01