- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

Similar documents
DeviceNet Module. User Manual. 1 Important User Information. 2 Installation

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

- 15G0078B110 - PROFIBUS MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

Install the DeviceNet Module using the following procedure:

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure:

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Copyright: December 2017 Nidec Issue: E

Ethernet/IP Module. User Manual. Contents

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

Profinet Module. User Manual. Contents

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

- 15G0078B130 - USB MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

Copyright: December 2017 Nidec Issue: E

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

ETHERNET/IP & PROFINET MODULE

MCD 200 Series. MCD 200 DEVICENET Module OPERATING INSTRUCTIONS. MCD 200 DEVICENET Module. Order Code: 175G9002. Adjustment.

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

1. Introduction. 2. Installation MODBUS INTERFACE

Instructions. Modbus RTU Card (WSIQ-COM-MB)

PROFINET MODULE. Communications module. User Guide. This manual is to be given to the end user en / a. Power. Error. Status.

Installation Guide EtherNet/IP Module

Installation Guide Modbus TCP Module

OPERATING INSTRUCTIONS MCD

Installation Guide PROFINET Module

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents

Installation Guide EtherNet/IP Module

ASTAT XB/XBm Remote Operator

15P0102Q2 SINUS PENTA KEYPAD CONNECTED TO NETWORK RS485 USERS MANUAL

Opal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1

15P0097Q1 SINUS K - PENTA REMOTE MOUNTING THE KEYPAD MOUNTING GUIDE

Powered Roller Controller for DeviceNet

G3 Series DeviceNet TM Technical Manual

Copyright December 2017 Nidec Issue: D

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

DCREG INTERFACE VIA PROFIBUS-DP

INTEGRATED MICROSTEPPING MOTOR DRIVER AND HIGH PERFORMANCE MACHINE/PROCESS CONTROLLER

Diagnostics (Physical)

Section 1 Caution Statements... 3 Section 2 Introduction Section 3 Basic Setup Procedure... 5 Section 4 Installation... 6

USERS IMS2 SERIES SOFT STARTERS

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

MPCR Series DeviceNet Technical Manual

DeviceNet Drive Profile CFW-09

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

2002 Series DeviceNet Technical Manual

1. Introduction. 2. Installation INSTALLATION INSTRUCTIONS: MCD USB MODULE

01325T -- Robot Welder

CONTENTS IMS2 SERIES A. 2.1 Overview Feature List Part Number Format... 3

DeviceNet Expansion Board

CONTENTS. Basic Setup Procedure Section 1 Caution Statements Programming and Operation IMS2 SERIES H

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

Section 0.0 Warnings... 2 Section 1.0 Quick Set-up... 3 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

Section 0.0 Warnings... 3 Section 1.0 Quick Set-up... 4 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

L5351 DeviceNet Communications Interface

Diagnostics (Logical) Diagnostics (Physical)

CDN572-5 DEVICENET SPECIFICATIONS

Series SD6 with DeviceNet (Addendum)

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

1. Warnings Introduction Mechanical Installation Electrical Installation Application Examples...

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Softstarters Type PSTX Fieldbus communication, Anybus CompactCom DeviceNet

Opal Pro AB Ethernet IP. Opal Pro MS6 SERIES. AB Ethernet IP Interface Users Manual. Revision Page 1

SE-330 SERIES (NEW REVISION) DEVICENET INTERFACE

MicroNode I/O TM DeviceNet AI User Manual

SMART RELAY SRW 01 V4.0X

Allen-Bradley Automation

DeviceNet for Capacitance Diaphragm Gauge

Installation Instructions for DeviceNet E50 Limit Switches

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

METTLER TOLEDO DNB User Manual

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor Start-up Guide DeviceNet Adapter Module NDNA-02

DeviceNet System Installation manual rev. 3.0

Serial PROFIBUS Interface

Optidrive Applications Support Library

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

Thank you for purchasing ig5a Series DeviceNet Communication Module SAFETY PRECAUTIONS

Compact Multiprotocol I/O Module for Ethernet 16 Universal Digital Channels, Configurable as PNP Inputs or 2 A Outputs TBEN-L4-16DXP

ELC-CODNETM. Effective December Users Manual

MGate 5118 Quick Installation Guide

DeviceNet - ODVA Conformance Test Results

Operation manual. HDOM-Profibus-V0. More options please visit;

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

SSW06. Soft Starters.

EL731 DEVICENET INTERFACE

GSE Scale Systems A div of SPX Corporation

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

Device manual AS-i PowerSwitch ZB0028 ZB0040

DeviceNet Interface Card "OPC-F1-DEV"

Compact Multiprotocol I/O Module for Ethernet 8 digital PNP inputs, input diagnostics per channel TBEN-S1-8DIP-D

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

1782-JDC DeviceNet/Serial Gateway User s Manual

DeviceNett Option. for FlexDrive II, Flex+Drive II and MintDrive II. Reference Manual 10/02 MN1910

SINUS PENTA. USER MANUAL BACNet Programming Instructions-

DeviceNet Communication Manual

Transcription:

- 5G0078B0 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-/ASAB Issued on 5/06/ R. 0 This manual is integrant and essential to the product. Carefully read the instructions contained herein as they provide important hints for use and maintenance safety. This device is to be used only for the purposes it has been designed to. Other uses should be considered improper and dangerous. The manufacturer is not responsible for possible damages caused by improper, erroneous and irrational uses. Elettronica Santerno is responsible for the device in its original setting. Any changes to the structure or operating cycle of the device must be performed or authorized by the Engineering Department of Elettronica Santerno. Elettronica Santerno assumes no responsibility for the consequences resulting by the use of non-original spareparts. Elettronica Santerno reserves the right to make any technical changes to this manual and to the device without prior notice. If printing errors or similar are detected, the corrections will be included in the new releases of the manual. The information contained herein is the property of Elettronica Santerno and cannot be reproduced. Elettronica Santerno enforces its rights on the drawings and catalogues according to the law. Contents. Important User Information.... Installation... 3. Configuration... 3 4. Adjustment... 3 5. Connections... 4 6. LEDs... 4 7. DeviceNet Polled I/O Structure... 5 8. Trip Codes... 6 9. Parameter Object... 7 0. Specifications... 7 Elettronica Santerno S.p.A. S.S. Selice, 47 4006 Imola (BO) Italy Tel. +39 054 4897 Fax +39 054 4897 www.santerno.com, sales@santerno.com

078.B. Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.. Installation. Installation Procedure CAUTION Remove mains and control voltage from the soft starter before attaching or removing accessories. Failure to do so may damage the equipment. Install the DeviceNet Module using the following procedure:. Remove control power and mains supply from the soft starter.. Attach the module to the soft starter as illustrated. 3. Set the DeviceNet Module Node Address (MAC ID) and Data Rate. 4. Apply control power to the soft starter. 5. Insert the network connector into the module and power up the DeviceNet network.. Physical Installation. Fully pull out the top and bottom retaining clips on the module.. Line up the module with the comms port slot. 3. Push in the top and bottom retaining clips to secure the module to the starter. 3 CAUTION Network designs must decrease the maximum allowable cumulative dropline length by 400 mm for every module installed on the network. Failure to do so may result in network communication errors and decreased reliability. Example: ODVA specifies a maximum cumulative dropline length of 56 m on a network operating at 5 kb/s. If six modules were installed on this network, the total cumulative dropline length would need to be decreased to 53.6 m. /8 DeviceNet Module

Remove the module using the following procedure:. Take the module off-line.. Remove the DeviceNet connector. 3. Remove control power and mains supply from the soft starter. 4. Fully pull out the top and bottom retaining clips on the module. 5. Pull the module away from the soft starter. 3. Configuration The DeviceNet Module is a Group slave device, using a predefined master/slave connection set. I/O data is produced and consumed using polled I/O messaging. The soft starter must be added to the DeviceNet manager project using the EDS file and configuration/management software tool. This file is available from santerno.com. In order to operate successfully, the correct EDS file must be used. An on-screen graphics bitmap file (device.bmp) is also available. 4. Adjustment Changes to the rotary switch settings take effect when the DeviceNet network is next powered up. The factory default settings for the rotary adjustment switches are: DATA RATE 500 kb PGM 50 kb 5 kb NODE ADDRESS ( 00-63, PGM ) 4 0 PGM MSD 0 8 LSD 6 4 6 The Data Rate and Node Address (MAC ID) must be set locally on the module. These cannot be set using DeviceNet management software. When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the previously used valid on-line Data Rate and Node Address (MAC ID). DeviceNet Module 3/8

V - CAN_L Shield CAN_H V + V+ CAN_H Shield CAN_L V 030.B 604.B 5. Connections ASAC ASAB Rd Wh Bu Bk 3 3 3 ASAC ASAB (Remote mode) A, 0: Stop 56, 57: Stop 58, 57: Reset DeviceNet Module DeviceNet Module Standard connection onto DeviceNet network Standard connection onto DeviceNet network 6. LEDs ASAC: For the DeviceNet Module to accept serial commands, a link must be fitted across terminals A-0 on the soft starter. ASAB: Input links are required across the stop and reset inputs if the soft starter is being operated in Remote mode. In Local mode, links are not required. ASAB: Parameter Comms in Remote selects whether the soft starter will accept Start and Stop commands from the Serial Network Master while in Remote Mode. Refer to the soft starter user manual for parameter details. The Module LED indicates the condition of the power supply and module operation. The Network LED indicates status of the communication link between the DeviceNet Module and the network Master. LED State Description Off Network power off (Module) Green Normal operation Red Unrecoverable fault Red/Green flashing Self Test mode Off Duplicate MAC ID test has not been completed (Network) Green flashing Online but no connection with Master Green Online and allocated to a Master Red flashing One or more timed out I/O connections Red Failed communication between module and Master Red/Green flashing Communication faulted and received an Identity communication faulted request When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is set greater than zero. When communication is restored, the soft starter must be reset. 4/8 DeviceNet Module

7. DeviceNet Polled I/O Structure Once the EDS file has been loaded, the DeviceNet Module must be added to the scanner list with parameters shown in the following table: Parameter I/O connection type Poll receive size Poll transmit size Value Polled 4 bytes bytes Once the soft starter, module and Master have been set up, configured and powered up, the Master will transmit bytes of data to the module and receive 4 bytes of data from the module. Master > Slave polled I/O output data is as follows: Byte Bit Function 0 0 0 = Stop command = Start command 0 = Enable Start or Stop command = Quick Stop (ie coast to stop) and disable Start command 0 = Enable Start or Stop command = Reset command and disable Start command 3 to 7 Reserved 0 to 0 = Use soft starter remote input to select motor set = Use primary motor set when starting = Use secondary motor set when starting 3 = Reserved to 7 Reserved Only available on ASAB soft starters. Ensure that the programmable input is not set to Motor Set Select before using this function. Slave > Master polled I/O input data is as follows: Some soft starters do not support some functions. Byte Bit Function Value 0 0 Trip = Tripped Warning = Warning Running 0 = Unknown, not ready, ready to start or tripped = Starting, running, stopping or jogging 3 Reserved 4 Ready 0 = Start or stop command not acceptable = Start or stop command acceptable 5 Control from Net = Always except in Program mode 6 Local/Remote 0 = Local control = Remote control 7 At reference = Running (full voltage at the motor) 0 to 7 Status 0 = Unknown (menu open) = Starter not ready (restart delay or thermal delay) 3 = Ready to start (including warning state) 4 = Starting or running 5 = Soft stopping 7 = Trip 8 = Jog forward 9 = Jog reverse 0 to 7 Trip/Warning code Refer to Trip Codes 3 0 Initialised = Phase sequence bit is valid (bit ) after first start Phase sequence = Positive phase sequence detected to 7 Reserved 4 0 to 7 Motor current (low byte) Current (A) 5 0 to 7 Motor current (high byte) 6 0 to 7 Current %FLC (low byte) Current as a percentage of soft starter FLC setting (%) 7 0 to 7 Current %FLC (high byte) DeviceNet Module 5/8

8 0 to 7 % Motor temperature Motor thermal model 9 0 to 7 % Motor temperature Motor thermal model 0 0 to 7 % Power factor Percentage power factor (00 = power factor of ) 0 to 7 Power (low byte) Power low byte, scaled by power scale 0 to 3 Power (high nibble) Power high nibble, scaled by power scale 4 to 5 Power scale 0 = Multiply power by 0 to get W = Multiply power by 00 to get W = Power (kw) 3 = Multiply power by 0 to get kw 6 to 7 Reserved 3 0 to 3 Digital Input state For all inputs, 0=open, =closed (shorted) 0 = Start = Stop = Reset 3 = Input A 4 to 7 Reserved For models ASAB-0053B and smaller this value will be 0 times greater than the value displayed on the keypad. 8. Trip Codes Code Trip Type ASAC-0 ASAC- ASAB 0 No trip Input A trip/auxiliary Trip A 0 Motor overload (thermal model) Heatsink overtemperature 3 L phase loss 4 L phase loss 5 L3 phase loss 6 Current imbalance 8 Instantaneous overcurrent 9 Undercurrent 50 Power loss/power circuit 54 Phase sequence 55 Frequency 60 Unsupported option (function not available in inside delta) 6 FLC too high/flc out of range 6 Parameter out of Range 70 Miscellaneous 75 Motor thermistor 0 Excess start time 0 Motor connection 04 Internal fault x (where x is the fault code detailed in the table below). 05 Bypass fail (bypass contactor) 0 Input B trip/auxiliary Trip B 3 Starter communication (between module and soft starter) 4 Network communication (between module and network) 5 L-T shorted 6 L-T shorted 7 L3-T3 shorted 8 Motor overload (thermal model) 9 Time-overcurrent (Bypass overload) Battery/clock Thermistor circuit 3 Analog input trip For ASAB, time-overcurrent protection is only available on internally bypassed models. 6/8 DeviceNet Module

8. Internal Fault x The table below details the internal fault code associated with trip code 04. 9. Parameter Object Internal fault Message displayed on the keypad 70 ~ 7 Current Read Err Lx 73 Internal fault X Contact your local supplier with the fault code (X). 74 ~ 76 Motor Connection Tx 77 ~ 79 Firing Fail SCRx 80 ~ 8 VZC Fail Px 83 Low Control Volts 84 ~ 98 Internal fault X Contact your local supplier with the fault code (X). The DeviceNet Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and downloaded (read) using DeviceNet management software. When the DeviceNet Module is powered up, it automatically obtains parameter information from the soft starter. Detail Value (Hex) Comment Class 0F Parameter object address Instance ~ xxx xxx = maximum soft starter parameter number Attribute ID 0 Always 0x0 Get Service 0E Read single soft starter parameter value Set Service 0 Write single soft starter parameter value Only available on ASAB soft starters. For parameter details, refer to the soft starter User Manual. 0. Specifications Enclosure Dimensions... 40 mm (W) x 66 mm (H) x 90 mm (D) Weight... 50 g Protection... IP0 Mounting Spring-action plastic mounting clips (x ) Connections Soft starter... 6-way pin assembly Network... 5-way male and unpluggable female connector (supplied) Maximum cable size....5 mm Contacts... Gold flash Settings Node address (MAC ID) Setting... Rotary switches Range... 0 to 63 (63, factory default) Data rate Setting... Rotary switch Options... 5 kb, 50 kb, 500 kb (5 kb, factory default) Power Consumption steady state... 9 ma at 5 VDC... 3 ma at VDC in-rush (at 4 VDC)....8 A maximum for ms Galvanically isolated Certification CE... IEC 60947-4- C... IEC 60947-4- ODVA... DeviceNet Conformance Tested DeviceNet Module 7/8

8/8 DeviceNet Module