CPX terminal. Electronics Manual. CPX field bus node. Type CPX FB32. Field bus protocol EtherNet/IP. Manual [ ]

Similar documents
CPX terminal. Manual Electronics. CPX field bus node. Type CPX FB11. Field bus protocol DeviceNet. Manual en 0503b [ ]

CPX terminal. Electronics Manual. CPX I/O modules, sub bases, pneumatic. electronic modules. Types: CPX...DE... CPX...DA CPX 8DE 8DA CPX AB...

CPX terminal. Bus node CPX-FB38. Electronics description. Network protocol EtherCAT. Description en 1301a [ ]

CPX terminal. Manual Electronics. Digital CPX I/O modules and Connection blocks Types: - CPX-8DE-8DA - CPX-AB- CPX pneumatic interfaces Types:

CPX terminal. Description Electronics. CPX fieldbus node. Type CPX-FB6. Fieldbus protocol: Interbus in accordance with EN 50254

CPX terminal. Manual Electronics. CPX bus node. Type CPX-M-FB20 and CPX-M-FB21. Fieldbus protocol: Interbus Rugged Line fibre optic cable remote bus

Terminal CPX. Bus node CPX-FB40. Description Electronics. Network protocol Ethernet POWERLINK NH [ ]

CPX terminal. US patent no. 6,216,738. Electronics manual. CPX CP interface. Type CPX CP 4 FB. Manual [ ]

CPX terminal. Electronics manual. CPX field bus node. Type CPX FB6. Field bus protocol: Interbus as per EN Manual en 0402b [ ]

Compact performance. Electronics manual. System manual. Installing and commissioning CP systems. Manual en 0010b

Terminal CPX. Bus node CPX FB36. Description. Network protocol EtherNet/IP Modbus TCP. Industrial Ethernet 2-Port en 1611a [ ]

CPX Terminal. Manual electronics. CPX control block. Type CPX SF34 Type CPX SF35. PC WORX integrated Network protocol PROFINET IO.

CPX-Terminal. Brief description. CPX analogue I/O modules CPX-4AE CPX-2AA. English e [ ]

Compact Performance CP system Installation and commissioning

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV...-DI02 PROFIBUS-DP CPV...

Terminal CPX. Bus node CPX-FB14. Description. CANopen networkprotocol en 1411d [ ]

CPX terminal Electronics manual Manual

CPX terminal. Description Electronics. System manual. Installing and. terminals. Description en 0902e [742939]

CPX Terminal. Manual Electronics. CPX Bus Node. Type CPX FB33 Type CPX FB34. Network protocol PROFINET IO. Manual [ ]

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

CDVI-DN Valve Terminal (Type 15) DeviceNet

Terminal CPX. Bus node CPX-FB37. Description. Network protocol EtherCAT NH [ ]

Terminal CPX. Electrical interface CPX-CTEL-2-M12-5POL-LK. Description Electronics NH [ ]

Compact performance. Electronics manual. CP modules. Input modules type CP E08 M12 CL type CP E08 M8 CL type CP E16 KL CL

CPA SC/CPV SC PROFIBUS DP

Electronics manual. Universal handheld. Commissioning and diagnosing CPX terminals. Manual [ ]

Compact performance. Description. Programming and diagnosis. CP fieldbus node 8. Fieldbus connection: Allen Bradley Remote I/O link Type CP FB08 03

Compact performance. Elektronics manual. CPV valve terminal with field bus direct connection. Types: CPV... DI02 PROFIBUS DP CPV...

Valve terminal types 03/04-B

Valve terminal type 03/05 Electronics Manual Field bus connection FB13

Compact performance. Electronics manual. CPV valve terminal with direct connection. Type CPV.. GE DN2 8. Field bus protocol: DeviceNet

Compact Performance. Description. Electronics. CP fieldbus node 5. Programming and diagnosis. Type CP FB5 E

Valve terminal type 03/05 Electronics Manual Field bus connection FB17

Valve terminal type 03/05 Electronics Manual Field bus connection FB15

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ]

Compact performance. Programming and diagnostics manual. CP field bus node 11 Type CP FB11 E. Field bus protocol: DeviceNet

Terminal CPX. Bus node CPX-(M)-FB33/34/35/41. Description. Network protocol PROFINET IO en 1410d [ ]

Valve terminal type 03/05 Electronics Manual Field bus connection FB16

Smart Positioning Controller SPC200 Stepping motor indexer module

Compact Performance CPV valve terminal with direct connection Electronics

Valve terminal type 03/05 Electronics Manual Field bus connection FB14

Valve terminal type 03/05 Electronics Manual Control block SB-202

Valve terminal type 03 and type 44/45

CPX Terminal. Electronics Manual. CoDeSys Controller. Type CPX CEC C1. Manual [ ]

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ]

Compact performance. Manual Electronics. CPV valve terminal with direct connection. Type CPV..-GE-DN-8. Field bus protocol: - DeviceNet

Control blocks CPX-CEC- -V3

SPC200 Smart Positioning Controller

1) Examine exterior of package for signs of damage. Report any damage to shipping carrier.

Valve terminal type 03/04 B

Motor controller SFC-DC

PROFIBUS for motor controller CMMS/CMMD

Valve terminal types 03/04-B

Motor unit MTR-DCI. Brief overview MTR-DCI. English d [ ]

Documentation ZB8610. Fan cartridge for EtherCAT and Bus Terminals. Version: Date:

Compact Performance. Electronics manual. CPV valve terminal with direct connection Type CPV.. GE CC 8. Field bus protocol: CC link.

Operating instructions RFID evaluation unit DTE / / 2016

BNI EIP Z016. IP67 Modules, 8 Outputs BNI EIP Z016 BNI EIP Z016 IP67 Modules, 16 Outputs User s Guide

Terminal CPX. Input module CPX-F8DE-P. Description en 1505NH [ ]

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

Modular electrical terminal CPX

Documentation. CU20xx, CU22xx. Ethernet Switch. Version: Date:

Valve island VM10 with EtherNet/IP Interface 8, 10, 12 or 16 stations. Operation & Service Manual

Quick Start Manual G2-2 Series with Ethernet Interface

Modular electrical terminal CPX

Quick Start Guide EAx580 EtherNet/IP encoder

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

For the configuration of the I/O-modules in a control system an EDS-file is required. The names of the files are as follows:

User Manual Gateway component for EtherNet/IP

Terminal CPX. Control block CPX-CM-HPP. Description. FHPP interface. Description b [ ]

Modular electrical terminal CPX

CPX-FB36 in Ethernet/IP Mode

Motion Terminal VTEM. Description. Motion App #04. Model-based proportional pressure regulation [ ]

SUBCON-PLUS-PROFIB...

End-position controllers CPX-CMPX

SK CU4-EIP-C Part number:

SIMATIC S7-300 Programmable Controller Getting Started Edition 04/2000 First Steps for Installation and Commissioning Totally Integrated Automation

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

System CPX-E. Bus module CPX-E-EC. Description. Protocol EtherCAT. Function Parameterisation [ ]

Type Quickstart

BNI PNT Z015 BNI PNT Z015 BNI PNT Z015 BNI PNT Z015. IP67 Modules User s Guide

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366

Measuring modules CPX-CMIX

Modular electrical terminal CPX-P

Manual. Local control unit DLP-VSE-... DLP-VSE-...-DP DLP-VSE-...-ASI. Manual en 9910NH

CJ Series EtherNet/IP TM Connection Guide. SMC Corporation Solenoid Valve (SI Unit EX600-SEN#) P657-E1-01

Supplementary device manual EtherCAT interface in the AS-i controllere A AC1391 AC1392

G3 Series EtherNet/IP TM Technical Manual

PROFIBUS for motor controller

CPX-E-System CPX-E-CEC-...-PN. Description. Function Commissioning Parameterisation [ ]

Motion Terminal VTEM. Description. Motion App #02. Proportional directional control valve [ ]

Operating instructions for AX5801. TwinSAFE drive option card for the AX5000 servo drive. Version: Date:

BNI EIP Z016 IP67 Modules, 16 In-/Outputs User s Guide

Programmable Valve Terminal type 02 Electronics Manual Control block SF 3

US patent no. 6,085,632 CPX Terminal

Modular electrical terminal CPX

G3 Series DeviceNet TM Technical Manual

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

Transcription:

CPX terminal Electronics Manual CPX field bus node Type CPX FB32 Field bus protocol EtherNet/IP Manual 541 305 en 0605NH [693 135]

Contents and general instructions Original....................................... de Edition................................. en 0605NH Designation....................... P.BE CPX FB32 EN Order no.................................. 541 305 (Festo AG & Co. KG, D 73726 Esslingen, Federal Republic of Germany, 2006) Internet: http://www.festo.com E Mail: service_international@festo.com The reproduction, distribution and utilization of this document as well as the communicaton of its contents to others without express authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility module or design. I

Contents and general instructions EtherNet/IP RSLogix SPEEDCON TORX is a registered trade name of ControlNet International Ltd. and the Open DeviceNet Vendor Association. Inc. (ODVA) is a registered trade name of Rockwell Automation is a registered trade name of PHOENIX CONTACT GmbH & Co. KG, 32825 Blomberg, Germany is a registered trade name of CAMCAR TEXTRON INC., Rockford, Ill., USA II

Contents and general instructions Contents Designated use........................................................ Target group.......................................................... Service............................................................... Notes on the use of this manual........................................... Important user instructions.............................................. VII VII VII VIII IX 1. Installation................................................... 1 1 1.1 General instructions on installation................................ 1 3 1.2 Settings of the DIL switches on the field bus node.................... 1 6 1.2.1 Removing and fitting the cover over the DIL switches........... 1 6 1.2.2 Settingthe DIL switches................................... 1 7 1.3 Connecting the Ethernet field bus.................................. 1 12 1.3.1 Ethernet cable.......................................... 1 12 1.3.2 Field businterface of the CPX FB32......................... 1 13 1.3.3 Setting the IP address.................................... 1 14 1.3.4 Extended Ethernet settings................................ 1 16 1.3.5 Use the Webserver functions of the CPX FB32................ 1 16 1.4 Pin assignment of power supply................................... 1 17 III

Contents and general instructions 2. Commissioning................................................ 2 1 2.1 Addressing.................................................... 2 3 2.1.1 Ascertaining the address range............................ 2 4 2.1.2 Address assignment of the CPX terminal..................... 2 9 2.1.3 Address assignment after extension/conversion.............. 2 16 2.2 Bus configuration............................................... 2 19 2.2.1 Registering slave properties in the configuration program...... 2 19 2.2.2 Overview of configuration on the EtherNet/IP................. 2 22 2.2.3 Configuration with RSLogix 5000........................... 2 23 2.3 Parametrizing.................................................. 2 26 2.3.1 Methods of parametrizing................................. 2 28 2.3.2 Parametrizing via Configuration Assembly (method 1).......... 2 29 2.3.3 Parametrizing via software (method 2a)..................... 2 29 2.3.4 Parametrizing with the Handheld (method 2b)................ 2 29 2.3.5 Parametrizing via the PLC user program (method 3)............ 2 30 2.3.6 Parametrizing with EDS files (method 4)..................... 2 31 2.4 Notes on parameters for Idle mode and Fault mode................... 2 32 2.5 Check list for commissioning the CPX terminal with FB32............... 2 33 3. Diagnosis..................................................... 3 1 3.1 Overview of diagnostic possibilities................................ 3 3 3.2 Diagnosis via LEDs.............................................. 3 4 3.2.1 CPX specific LEDs....................................... 3 6 3.3 Diagnosis via status bits......................................... 3 13 3.4 Diagnosis via I/O diagnostic interface.............................. 3 14 3.5 Diagnosis via EtherNet/IP........................................ 3 15 3.6 Fault treatment................................................. 3 17 IV

Contents and general instructions A. Technical appendix............................................. A 1 A.1 Technical specifications of field bus node type CPX FB32............... A 3 A.2 Accessories.................................................... A 4 B. Ethernet/IP Objects of the CPX FB32.............................. B 1 B.1 Overview of Ethernet/IP Objects of the CPX FB32..................... B 3 B.2 Objects for network settings...................................... B 7 B.2.1 Port Object............................................. B 7 B.2.2 TCP/IP Interface Object................................... B 8 B.2.3 Ethernet Link Object..................................... B 9 B.3 Objects for the I/O connection.................................... B 10 B.3.1 Assembly Object........................................ B 10 B.4 Objects for system data and diagnosis.............................. B 15 B.4.1 Identity Object.......................................... B 15 B.4.2 System Object (for operating mode Remote I/O).............. B 16 B.4.3 Status and Diagnostic Object.............................. B 19 B.4.4 Diagnostic Trace Object.................................. B 20 B.4.5 Diagnostic Trace Status Object............................. B 21 B.4.6 General Module Parameter Object.......................... B 23 B.4.7 Force parameter........................................ B 26 B.4.8 Fail safe and Idle parameters.............................. B 31 B.4.9 Configuration Array Object................................ B 36 B.4.10 Slave Size Object (for operating mode Remote Controller)...... B 36 B.5 Examples...................................................... B 37 B.5.1 Example: Forcing inputs.................................. B 37 B.5.2 Example: Parametrizing with the general Modul Parameter Object.................................. B 39 C. Index......................................................... C 1 V

Contents and general instructions VI

Contents and general instructions Designated use The field bus node type CPX FB32 described in this manual has been designed exclusively for use as a slave on the EtherNet/IP. The CPX terminal may only be used as follows: as designated in industrial applications without any modifications by the user. Only the conver sions or modifications described in the documentation supplied with the product are permitted. in faultless technical condition. The maximum values specified for pressures, temperatures, electrical data, torques etc. must be observed. If additional commercially available components such as sensors and actuators are connected, the specified limits for pressures, temperatures, electrical data, torques, etc. must not be exceeded. Please comply with national and local safety laws and regulations. Target group This manual is intended exclusively for technicians trained in control and automation technology who have experience in installing, commissioning, programming and diagnosing slaves on the EtherNet. Service Please consult your local Festo repair service if you have any technical problems. VII

Contents and general instructions Notes on the use of this manual Further information on the EtherNet/IP can be found in: www.odva.org Information on master manufacturers can be found in: www.rockwellautomation.com General basic information on the method of operation, on fitting, installing and commissioning CPX terminals can be found in the CPX system manual. VIII

Contents and general instructions Important user instructions Danger categories This manual contains instructions on the possible dangers which may occur if the product is not used correctly. These instructions are marked (Warning, Caution, etc.), printed on a shaded background and marked additionally with a picto gram. A distinction is made between the following danger warnings: Warning This means that failure to observe this instruction may result in serious personal injury or damage to property. Caution This means that failure to observe this instruction may result in personal injury or damage to property. Please note This means that failure to observe this instruction may result in damage to property. The following pictogram marks passages in the text which describe activities with electrostatically sensitive compo nents. Electrostatically sensitive components may be damaged if they are not handled correctly. IX

Contents and general instructions Marking special information The following pictograms mark passages in the text containing special information. Pictograms Information: Recommendations, tips and references to other sources of information. Accessories: Information on necessary or sensible accessories for the Festo product. Environment: Information on environment friendly use of Festo products. Text markings The bullet indicates activities which may be carried out in any order. 1. Figures denote activities which must be carried out in the numerical order specified. Hyphens indicate general activities. X

Contents and general instructions Design Title Manual Electronics Manual Software package System manual" type P.BE CPX SYS... CPX field bus node" type P.BE CPX FB... CPX I/O modules" type P.BE CPX EA... CPX analogue I/O modules" type P.BE CPX AX... CPX CP interface" type P.BE CPX CP... Handheld" type P.BE CPX MMI 1... CPX FEC" type P.BE CPX FEC... FST" Overview of structure, components and method of operation of CPX terminals; installation and commissioning instructions as well as basic principles of parametrizing Instructions on fitting, installing, commissioning and diagnosing the relevant field bus node Notes on connection types and instructions on fitting, installing and commissioning input and output modules of type CPX..., the MPA pneumatic modules, as well as MPA, CPA and Midi/Maxi pneumatic interfaces Notes on connection types and instructions on fitting, installing and commissioning CPX analogue I/O modules Instructions on fitting, installing, commissioning and diagnosing CP systems with the CP interface type CPX CP 4 FB Instructions on commissioning and diagnosing CPX terminals with the Handheld type CPX MMI 1 Instructions on fitting, installing, commissioning and diagnosing the CPX Front End Controller. Programming in Statement List and Ladder Diagram for the FEC Tab. 0/1: Manuals on the CPX terminal part 1 XI

Contents and general instructions Design Title Manual Pneumatics Manual Valve terminals with MPA pneumatics" type P.BE MPA... Valve terminals with CPA pneumatics" type P.BE CPA... Valve terminals with Midi/Maxi pneumatics" type P.BE MIDI/MAXI 03... Valve terminal with VTSA/ISO pneumatics" type P.BE VTSA 44... Instructions on fitting, installing, commission ing, maintaining and converting the MPA pneu matics (type 32) Instructions on fitting, installing, commission ing, maintaining and converting the CPA pneu matics (type 12) Instructions on fitting, installing, commission ing, maintaining and converting the Midi/Maxi pneumatics (type 03) Instructions on fitting, installing, commission ing, maintaining and converting the VTSA/ISO pneumatics (type 44) Tab. 0/2: Manuals on the CPX terminal part 2 XII

Contents and general instructions The following product specific terms and abbreviations are used in this manual: Term/abbreviation A0 h AI AO CP modules CPX terminal DI DIL switch DO FEC Field bus node Handheld / MMI IB, IW I/O modules I/Os OB, OW Pneumatic interface Meaning Hexadecimal numbers are marked by a low set h" Analogue input Analogue output Common term for the various modules which can be incorporated in a CPX terminal. Complete system consisting of CPX modules with or without pneumatics. Digital input Dual in line switches consist of several switch elements with which settings can be made. Digital output Front End Controller Provides the connection to specific field buses. Transmits control signals to the connected modules and monitors their ability to function. Handheld programmer for commissioning and service purposes Input byte, input word Common term for the CPX modules which provide digital inputs and outputs. Digital inputs and outputs Output byte, output word The pneumatic interface is the interface between the modular electrical periphery and the pneumatics. Tab. 0/3: CPX specific terms and abbreviations XIII

Contents and general instructions XIV

Installation Chapter 1 1 1

1. Installation Contents 1. Installation................................................... 1 1 1.1 General instructions on installation................................ 1 3 1.2 Settings of the DIL switches on the field bus node.................... 1 6 1.2.1 Removing and fitting the cover over the DIL switches........... 1 6 1.2.2 Settingthe DIL switches................................... 1 7 1.3 Connecting the Ethernet field bus.................................. 1 12 1.3.1 Ethernet cable.......................................... 1 12 1.3.2 Field businterface of the CPX FB32......................... 1 13 1.3.3 Setting the IP address.................................... 1 14 1.3.4 Extended Ethernet settings................................ 1 16 1.3.5 Use the Webserver functions of the CPX FB32................ 1 16 1.4 Pin assignment of power supply................................... 1 17 1 2

1. Installation 1.1 General instructions on installation Warning Before carrying out installation and maintenance work, switch off the following: the compressed air supply the operating voltage supply for the electronics/sensors the load voltage supply for the outputs/valves. You can thereby avoid: uncontrolled movements of loose tubing. unexpected movements of the connected actuators non defined switching states of the electronic components. Caution The CPX field bus node contains electrostatically sensitive components. Do not therefore touch any contacts. Observe the regulations for handling electrostatically sensitive components. You will then prevent the electronics from being damaged. Please note Use a protective cap or blanking plug to seal unused connections. You will then comply with protection class IP65/IP67. Information on fitting the CPX terminal can be found in the CPX system manual (P.BE CPX SYS...). 1 3

1. Installation Electrical connecting and display elements The following connecting and display elements can be found on field bus node CPX FB32: 4 1 3 2 1 Bus status specific and CPX specific LEDs 2 Field bus interface: Ethernet connection (4 pin M12 socket, D coded) 3 Transparent cover for the DIL switches 4 Service interface for the Handheld (V24) Fig. 1/1: Connecting and display elements on the CPX field bus node 1 4

1. Installation Dismantling 1 Field bus node CPX FB32 2 Manifold base with contact rails 3 Torx T10 screws Dismantling and fitting The field bus node is fitted in a manifold base of the CPX terminal (see Fig. 1/2). Dismantle the field bus node as follows: 1. Loosen the 4 screws in the field bus node with a Torx screwdriver size T10. 2. Pull the field bus node carefully and without tilting away from the contact rails of the manifold base. 3 1 2 Fig. 1/2: Dismantling/fitting the field bus node Fitting Fit the field bus node as follows: 1. Place the field bus node in the manifold base. Make sure that the grooves with the power contact terminals on the bottom of the field bus node lie above the contact rails. 2. Push the field bus node carefully and without tilting as far as possible into the manifold base. 3. Tighten the screws at first only by hand. Place the screws so that the self cutting threads can be used. 4. Tighten the screws with a Torx screwdriver size T10 with torque 0.9... 1.1 Nm. 1 5

1. Installation 1.2 Settings of the DIL switches on the field bus node In order to set the CPX field bus node you must first remove the cover over the DIL switches. Caution The CPX field bus node contains electrostatically sensitive components. Do not therefore touch any contacts. Observe the regulations for handling electrostatically sensitive components. You will then prevent the electronics in the node from being damaged. 1.2.1 Removing and fitting the cover over the DIL switches In order to set the CPX field bus node you must first remove the cover over the DIL switches. Removing 1. Switch off the power supply. 2. Unscrew the two fastening screws in the switch cover. 3. Lift up the cover. Fitting 1. Place the cover carefully on the node. Please note Make sure that the seal is seated correctly. 2. Tighten the two fastening screws at first by hand and then with torque 0.4 Nm. 1 6

1. Installation 1.2.2 Settingthe DIL switches You can set the following parameters with the DIL switches under the cover (see Fig. 1/3): Operating mode Diagnostic mode or number of I/O bytes IP addressing Procedure 1. Switch off the power supply. 2. Remove the cover over the DIL switches (section 1.2.1). 3. Carry out the setting as described on the following pages. 4. Fit the cover again (section 1.2.1). 1 DIL switch 1: Operating mode 2 DIL switch 2: Diagnostic mode or number of I/O bytes for Remote Controller 1 2 3 3 DIL switch 3: IP addressing Fig. 1/3: DIL switches in the field bus node 1 7

1. Installation Setting the operating mode with DIL switch 1 You can set the operating mode of the field bus node with switch element 1 of DIL switch 1: Operating mode Setting DIL switch 1 Operating mode Remote I/O All functions of the CPX terminal are controlled directly by the master. An FEC integrated in the CPX terminal works as a passive function module without controller. DIL 1.1: OFF DIL 1.2: OFF (factory setting) Operating mode Remote Controller An FEC integrated in the CPX terminal takes control of the I/Os. This operating mode is only useful if an FEC is integrated in the CPX terminal. DIL 1.1: ON DIL 1.2: OFF Tab. 1/1: Setting the operating mode with DIL switch 1 1 8

1. Installation Setting the diagnostic mode or the data size for Remote Controller with DIL switch 2 The function of this DIL switch depends on the set operating mode of the CPX terminal (see also Tab. 1/1): In the operating mode Remote I/O the diagnostic mode is set; in the operating mode Remote Controller the number of I/O bytes is set. Diagnostic mode (operating mode Remote I/O) The I/O diagnostic interface and the status bits are switched off (+ 0 I/O bits) The I/O diagnostic interface is switched on 1) (+ 16 I/O bits) The status bits are switched on (+ 16 I bits (8 used)) Setting DIL switch 2 2.1: OFF 2.2: OFF (default) 2.1: ON 2.2: OFF 2.1: OFF 2.2: ON Reserved for future extensions 2.1: ON 2.2: ON 1) The I/O diagnostic interface occupies an additional 16 I/O bits. Tab. 1/2: Setting the diagnostic mode with DIL switch 2 (operating mode Remote I/O) 1 9

1. Installation Number of I/O bytes (operating mode Remote Controller) 8 bytes I / 8 bytes O for communication of the field bus node with the CPX FEC Reserved Setting DIL switch 2 2.1: OFF 2.2: OFF (default) 2.1: ON 2.2: OFF 16 bytes I / 16 bytes I for communication of the field bus node with the CPX FEC 2.1: OFF 2.2: ON Reserved 2.1: ON 2.2: ON Tab. 1/3: Setting the number of I/O bytes with DIL switch 2 (operating mode Remote Controller) 1 10

1. Installation Setting the IP addressing with DIL switch 3 With DIL switch 3 you can set the type of addressing or the IP address of the field bus node. Dynamic addressing via BOOTP/DHCP or saved addressing Fixed addressing via DIL switch 1 2 3 4 5 6 7 8 Setting: All switches OFF (factory setting) 1 2 3 4 5 6 7 8 Setting: Host ID of the IP address Tab. 1/4: Settings of DIL switch 3 for different types of addressing The factory setting is the dynamic addressing. Note the detailed information on addressing in section 1.3.3. 1 11

1. Installation 1.3 Connecting the Ethernet field bus 1.3.1 Ethernet cable Please note If installation has not been carried out correctly and if high baud rates are used, data transmission errors may occur as a result of signal reflections and attenuations. Causes of the transmission faults may be: incorrect screening/shield connection branches transmission over long distances unsuitable cables. Observe the cable specifications. Refer to your controller manual for information on the type of cable to be used. Cable specification Screened flexible Ethernet round cable of category 5 Max. outer diameter: 5.4 mm Core diameter: 0.89... 1.0 mm AWG24 26 User made: plug screwed on, type NECU M S D12G4 C2 ET, part no. 543 109 Please note If the CPX terminal is fitted onto the moving part of a machine, the field bus cable on the moving part must be provided with strain relief. Please observe also the relevant regulations in EN 60204 part 1. The specifications for Ethernet networks as per ANSI/TIA/ EIA 568 B.1 apply for the field bus length. 1 12

1. Installation 1.3.2 Field businterface of the CPX FB32 There is a 4 pin M12 socket with D code on the field bus node for connecting the valve terminal to the field bus. The socket is compatible with SPEEDCON plugs. M12 socket EtherNet/IP Pin assignment Explanation Pin equivalent with RJ45 plug 1. TX+ 2. RX+ 3. TX 4. RX Housing: Screening/ shield Transmitted data + Received data + Send data Receive data 1 3 2 6 Tab. 1/5: Pin assignment of the field bus interface of the CPX FB32 (M12 4 pin) Connection with field bus plugs from Festo You can connect the CPX terminal to the field bus with the field bus plug from Festo (type NECU M S D12G4 C2 ET, part no. 543 109). 1 13

1. Installation 1.3.3 Setting the IP address There are three possibilities of setting the IP address of the CPX FB32. Please note If the network settings of the CPX FB32 are modified, the Modify LED M" will flash yellow: Start the CPX FB32 again in this case with Power OFF/ON. Dynamic addressing via BOOTP/DHCP Factory setting In the factory setting all switch elements of DIL switch 3 are set to OFF and BOOTP/DHCP is activated in the CPX FB32. The dynamic addressing via BOOTP/DHCP is then set (see Tab. 1/4). For the dynamic addressing there must be a BOOTP/DHCP server in the network. If you wish to change from another type of addressing back to dynamic addressing: 1. Set all switch elements of DIL switch 3 to OFF (see Tab. 1/4). 2. Activate DHCP with the Handheld (CPX MMI) or with the program BOOTP DHCP Server" from Rockwell Automa tion. Use the network setting saved in the CPX FB32 The CPX FB32 offers the possibility of saving the network settings in a non volatile memory. DHCP/BOOTP is thereby deactivated. 1. Set all switch elements of DIL switch 3 to OFF (see Tab. 1/4). 1 14

1. Installation 2. Set the network settings with the Handheld (CPX MMI) or with the program BOOTP DHCP Server" from Rockwell Automation. The saving of the network settings is then activated. Fixed addressing via DIL switch Tip The fixed setting of the IP address is to be recommended for test purposes during commissioning or for small networks. Setting If a (binary coded) number not equal to 0 or 255 is set with the switch elements of DIL switch 3, the IP address is as signed fixed. The set number specifies the host ID of the address 192.168.1.xxx" (see Fig. 1/4). Example: set IP address: 192.168.1.005 Example: set IP address: 192.168.1.038 1 2 3 4 5 6 7 8 2 0 + 2 2 = 1 + 4 = 5 1 2 3 4 5 6 7 8 2 1 + 2 2 + 2 5 = 2 + 4 + 32 = 38 Fig. 1/4: Examples of set IP addresses (binary coded) with fixed addressing The settings of the network mask and the Gateway are set with fixed addressing as follows and cannot be modified: Network mask: 255.255.255.0 Gateway: 0.0.0.0 1 15

1. Installation 1.3.4 Extended Ethernet settings Via the Ethernet Link Object" (see appendix B.2.3) you can undertake further settings for the Ethernet connection. Confi gure the Ethernet Link Object via your Ethernet/IP master or scanner. The extended Ethernet settings are described below. Automatic setting (factory setting) The field bus baud rate and the Duplex mode are recognized as standard by the CPX FB32. Baud rate The field bus baud rate can be switched via EtherNet/IP and is set via Attribute no. 6 (Interface Speed) of the Ethernet Link Object. The following settings are possible: 10 MBd 100 MBd Duplex mode The full Duplex mode can be activated/deactivated. 1.3.5 Use the Webserver functions of the CPX FB32 A Webserver is incorporated in the CPX FB32. The Webserver can be used freely. You can copy files onto the Webserver via FTP. Information on using the FTP can be found in the appen dix A.1. Use the CPX Web Monitor" software (part number 545 413), in order to use all the functions of the Webserver optimally and user friendly. With the CPX Web Monitor you can load a visualization pack age on an HTLM basis into the Webserver of the FB32. User friendly diagnostic possibilities are then available via the Ethernet network. 1 16

1. Installation 1.4 Pin assignment of power supply Warning For the power supply use only PELV circuits as per IEC/ DIN EN 60204 1 (Protective Extra Low Voltage, PELV). Take into account also the general requirements for PELV circuits as per IEC/DIN EN 60204 1. Use only power packs which guarantee reliable electri cal isolation of the operating voltage as per IEC/DIN EN 60204 1. By the use of PELV power units, protection against electric shock (protection against direct and indirect contact) is guar anteed in accordance with IEC/DIN EN 60204 1 (electrical equipment of machines, general requirements). The current consumption of a CPX terminal depends on the number and type of integrated modules and components. Read the information on power supply as well as on the earthing measures to be carried out in the CPX system manual. 1 17

1. Installation System supply, additional supply and valve supply The CPX terminal is supplied with operating and load volt ages via the manifold bases with system supply, additional supply and valve supply types CPX GE EV S, CPX GE EV Z or CPX GE EV V. Plug Pin assignment of manifold base with... system supply module type CPX GE EV S... additional supply module type CPX GE EV Z... valve supply module type CPX GE EV V... 4 1 2 1: 24 V EL/SEN 2: 24 V VAL / 24 V OUT 3: 0 V EL/SEN / 0 V VAL / 0 V OUT 4: Earth connection 1: not connected 2: 24 V OUT 3: 0 V OUT 4: Earth connection 1: not connected 2: 24 V VAL 3: 0 V VAL 4: Earth connection M18 3 B C D A: 24 V EL/SEN B: 24 V VAL / 24 V OUT C: Earth connection D:0 V EL/SEN / 0 V VAL / 0 V OUT (incoming) A: not connected B: 24 V OUT C: Earth connection D:0 V OUT (incoming) A: not connected B: 24 V VAL C: Earth connection D:0 V VAL (incoming) 7/8" 4POL A Pin assignment: Note the specifications on the plug. 3 4 2 1 1: 0 V VAL / 0 V OUT 2: 0 V EL/SEN 3: Earth connection (incoming) 4: 24 V EL/SEN 5: 24 V VAL / 24 V OUT 1: 0 V OUT 2: not connected 3: Earth connection (incoming) 4: not connected 5: 24 V OUT 7/8" 5POL 5 V EL/SEN : Operating voltage for electronics/sensors V OUT : Load voltage for outputs V VAL : Load voltage for valves Tab. 1/6: Pin assignment for system supply, additional supply and valve supply 1 18

Commissioning Chapter 2 2 1

2. Commissioning Contents 2. Commissioning................................................ 2 1 2.1 Addressing.................................................... 2 3 2.1.1 Ascertaining the address range............................ 2 4 2.1.2 Address assignment of the CPX terminal..................... 2 9 2.1.3 Address assignment after extension/conversion.............. 2 16 2.2 Bus configuration............................................... 2 19 2.2.1 Registering slave properties in the configuration program...... 2 19 2.2.2 Overview of configuration on the EtherNet/IP................. 2 22 2.2.3 Configuration with RSLogix 5000........................... 2 23 2.3 Parametrizing.................................................. 2 26 2.3.1 Methods of parametrizing................................. 2 28 2.3.2 Parametrizing via Configuration Assembly (method 1).......... 2 29 2.3.3 Parametrizing via software (method 2a)..................... 2 29 2.3.4 Parametrizing with the Handheld (method 2b)................ 2 29 2.3.5 Parametrizing via the PLC user program (method 3)............ 2 30 2.3.6 Parametrizing with EDS files (method 4)..................... 2 31 2.4 Notes on parameters for Idle mode and Fault mode................... 2 32 2.5 Check list for commissioning the CPX terminal with FB32............... 2 33 2 2

2. Commissioning 2.1 Addressing Before configuring, ascertain the exact number of available inputs/outputs. A CPX terminal consists of a different number of I/Os, depending on what you have ordered and on the con figuration of the field bus node. The I/Os will be assigned automatically within the CPX terminal. Please note Maximum 10 electric modules including the field bus node plus a pneumatic interface or MPA pneumatic modules are permitted on a CPX terminal. If you configure the CPX terminal with an EDS file, the field bus node in the first location must be installed as module 0. The CPX terminal has an address range of up to 64 bytes of inputs and 64 bytes of outputs. 2 3

2. Commissioning 2.1.1 Ascertaining the address range Address assignment of the modules Electric modules The individual modules are displayed with their identifier on the handheld. In the case of the I/O modules, the identifier is also shown in the LED viewing window. With the aid of this identifier, you can read the type of module and therefore the number of inputs and outputs occupied by the module. Electric modules Type Module identifier 1) Assigned addresses Inputs Outputs Field bus node FB32 CPX FB32 FB32... Digital 4 input module CPX 4DE 4 DI 4 I 2) Digital 8 input module CPX 8DE 8 DI 8 I Digital 8 input module with channel diagnosis CPX 8DE D 8 DI D 8 I Digital 16 input module CPX 16DE 16 DI 16 I Digital 8 input module n switching CPX 8NDE 8 NDI 8 I Digital 4 output module CPX 4DA 4 DO 4 O 2) Digital 8 output module CPX 8DA 8 DO 8 O Digital multi I/O module CPX 8DE 8DA 8 DI / 8 DO 8 I 8 O 1) Module identifier in the handheld 2) 8 bits are always assigned Tab. 2/1: Overview of electric CPX modules (part 1) 2 4

2. Commissioning Electric modules 1) Type Module Assigned addresses identifier Inputs Outputs Analogue 2 input module CPX 2AE U I 2AI 32 I Analogue 4 input module CPX 4AE I 4AI I 64 I Analogue 4 input module (temperature module) CPX 4AE T 4AI T 32/64 I 2) Analogue 2 output module CPX 2AA U I 2AO 32 O CP interface CPX CP 4 FB CPI 128 I 3) 128 O 3) Front End Controller CPX FEC FEC 64/128 I 4) 64/128 O 4) 1) Further modules in preparation 2) Number of inputs which can be switched between 2 and 4 3) Maximum number (actual assignment depends on the string assignment) 4) With the CPX FB32 can be set via DIL switch (see section 1.2.2) Tab. 2/2: Overview of electric CPX modules (part 2) The address assignment within the individual I/O modules can be found in the manual for the I/O modules. Details on the CP interface can be found in the manual for the CP inter face. 2 5

2. Commissioning Pneumatic modules and pneumatic interfaces The following table shows the number of output addresses occupied by the pneumatic modules: Pneumatic modules and pneumatic interfaces 1) Type Module identifier 2) Assigned addresses Inputs Outputs Pneumatic interface for MPA valves (type 32) MPA1 pneumatic module (type 32) without electrical isolation MPA1 pneumatic module (type 32) with electrical isolation MPA2 pneumatic module (type 32) without electrical isolation MPA2 pneumatic module (type 32) with electrical isolation MPA1 pneumatic module (type 32) without electrical isolation with diagnostic function D2 MPA1 pneumatic module (type 32) with electrical isolation with diagnostic function D2 MPA2 pneumatic module (type 32) without electrical isolation with diagnostic function D2 MPA2 pneumatic module (type 32) with electrical isolation with diagnostic function D2 VMPA FB EPL... VMPA1 FB EMS 8 3) MPA1S 8 O VMPA1 FB EMG 8 3) MPA1G 8 O VMPA2 FB EMS 4 3) MPA2S 4 O 4) VMPA2 FB EMG 4 3) MPA2G 4 O 4) VMPA1 FB EMS D2 8 3) MPA1S D 8 O VMPA1 FB EMG D2 8 3) MPA1G D 8 O VMPA2 FB EMS D2 4 3) MPA2S D 4 O 4) VMPA2 FB EMG D2 4 3) MPA2G D 4 O 4) 1) Further modules in preparation 2) Module identifier in the handheld 3) Type of electronic module used 4) 8 bits are always assigned Tab. 2/3: Summary of pneumatic modules and pneumatic interfaces (part 1) 2 6

2. Commissioning Pneumatic modules and pneumatic interfaces Type Module identifier 1) Assigned addresses Inputs Outputs Pneumatic interface for CPA valves (type 12) with setting: 3) 1...8 valve coils 1...16 valve coils 1...24 valve coils (22 can be used) CPX GP CPA 10 CPX GP CPA 14 CPA10/14 8 O 16 O 24 O Pneumatic interface for Midi/Maxi valves (type 03) with setting: 2) 1...8 valve coils 1...16 valve coils 1...24 valve coils 1...32 valve coils (26 can be used) CPX GP 03 4.0 TYPE3 8 O 16 O 24 O 32 O Pneumatic interface for VTSA pneumatics (ISO, type 44) 2) 1...8 valve coils 1...16 valve coils 1...24 valve coils 1...32 valve coils VABA 10S6 x1 ISO PlugIn or type 44 3) 8 O 16 O 24 O 32 O 1) Module identifier in the Handheld 2) Setting with DIL switch in the pneumatic interface (see manual for CPX I/O modules) 3) Depending on the version of the Handheld Tab. 2/4: Overview of pneumatic modules and pneumatic interfaces (part 2) The address assignment within the pneumatic modules can be found in the manual for the valve terminal pneumatics. Further information on MPA pneumatic modules can be found in the manual for the CPX I/O modules (P.BE CPX EA...). 2 7

2. Commissioning Calculating the number of inputs/outputs Use the following table for calculating the number of inputs and outputs on your CPX terminal. Input/output modules and system diagnosis Inputs Outputs 1. I/O diagnostic interface, if set + 16 I/O + I + O 2. Number of input modules CPX 4DE + x 8 I 1) + I 3. Number of input modules CPX 8DE, 8NDE, 8DE D + x 8 I + I 4. Number of input modules CPX 16DE + x 16 I + I 5. Number of output modules CPX 4DA + x 8 O 1) + O 6. Number of output modules CPX 8DA + x 8 O + O 7. Nnumber of multi I/O modules CPX 8DE 8DA + x 8 I/O + I + O 8. Number of analogue input modules CPX 2AE U I + x 32 I + I 9. Number of analogue input modules CPX 4AE I + x 64 I/ x 32 I + I 10.Number of analogue input modules CPX 4AE T + x 64 I + I 11.Number of analogue output modules CPX 2AA U I + x 32 O + O 12.Number of inputs and outputs of other modules (e.g. CP interface) + I/O + I + O 13.Midi/Maxi, CPA or VTSA pneumatic interface: Number of configured valve solenoid coils (+8 O, 16 O, 24 O, 32 O) 32 O (Midi/Maxi) or 24 O (CPA) are configured at the factory. + O 14.Number of MPA1 or MPA2 pneumatic modules + x 8 O 1) + O 15.Total sum of inputs/outputs to be configured Sum of 1 to 14: = I = O 1) 8 bits are always assigned (4 remain unused). Tab. 2/5: Ascertaining the number of inputs and outputs 2 8

2. Commissioning 2.1.2 Address assignment of the CPX terminal Please note If necessary, status bits or an I/O diagnostic interface can be activated by DIL switch (see Tab. 1/2): If the 8 status bits are activated, they will occupy the first 16 inputs in the address range (8 used). If the I/O diagnostic interface is activated, it will occupy the first 16 inputs and outputs in the address range. If you configure the CPX terminal with an EDS file, the field bus node must be installed in the first location as module 0. Basic rules for addressing The address assignment of the inputs does not depend on the address assignment of the outputs. Counting is from left to right, addressing in bytes: Modules with less than 8 bits occupy 8 bits address space, but do not use all this space. The field bus node counts as a module with 0 inputs and 0 outputs when the status bits and the I/O diagnostic interface are deactivated. The I/Os of different module types are assigned separately from each other. The sequence in the following table then applies: 2 9

2. Commissioning Sequence of addressing Description 1. I/O diagnostic interface 1) Can be activated by DIL switch. If the interface is activated, it will occupy the first 16 inputs and outputs in the address range. 2. Analogue modules Modules with analogue inputs/outputs 3. Technology modules e.g. CP interface, Front End Controller CPX FEC 4. Digital modules Modules with digital inputs/outputs 1) Depending on the setting, this address range can also be occupied by status bits (see note above and Tab. 1/2). Tab. 2/6: Sequence of addressing Configuration examples Example 1: CPX terminal with MPA1 and MPA2 pneumatics The following diagram shows as an example a CPX terminal with MPA pneumatics and the following setting: Status bits and I/O diagnostic interface deactivated Module no.: 0 1 2 3 4 5 6 8DI 4DO 8DI 8DO 8 O 8 O 4 O 4 O 1 2 3 4 1 Field bus node CPX FB32 2 MPA pneumatic interface 3 MPA1 pneumatic modules (8 DO each) 4 MPA2 pneumatic modules (4 DO each) Fig. 2/1: Example terminal 1 (with MPA1 and MPA2 pneumatics) 2 10

2. Commissioning The following table shows the address assignment for the CPX terminal in Fig. 2/1: Module no. Module Input address Output address 0 Field bus node CPX FB32 1 Digital 8 input module CPX 8DE I0... I7 2 Digital 4 output module CPX 4DA O0... O7 *) 3 MPA1 pneumatic module (8 DO) O8... O15 4 MPA1 pneumatic module (8 DO) O16... O23 5 MPA2 pneumatic module (4 DO) O24... O31 *) 6 MPA2 pneumatic module (4 DO) O32... O39 *) *) 8 bits occupied, 4 bits used Tab. 2/7: Addressing the example terminal 1 (see Fig. 2/1) If modular EDS is used, the addresses will be assigned in bytes. In the example above, the output addresses therefore change as from modules 2, 5 and 6. 2 11

2. Commissioning Example 2: CPX terminal with CP interface The address assignment for this CPX terminal can be found on the next page in Tab. 2/8. The settings are: Status bits and /I/O diagnostic interface deactivated Module no.: 0 1 2 3 4 5 6 8DI 4DO 8DI 8DO 1 8 O 8 O 3 2 4 5 6 1 Field bus node CPX FB32 2 CPV valve terminal (16 DO) on the CP interface (string 1) 3 CP input module (16 DI) 4 Sensor 5 Cylinder 6 CP output module (16 DO) on the CP interface (string 4) Fig. 2/2: Example terminal 2 (with CP interface) 2 12

2. Commissioning Module no. Module Input address Output address 0 Field bus node CPX FB32 1 Digital 8 input module CPX 8DE I32... I39 2 Digital 4 output module CPX 4DA O128... O135 *) 3 CP interface CP I, here: 4 bytes I, 16 bytes O 4 Digital multi I/O module CPX 8DE 8DA I0... I32 I40... I47 O0... O127 O136... O143 5 MPA1 pneumatic module (8 DO) O144... O151 6 MPA1 pneumatic module (8 DO) O152... O159 *) 8 bits occupied, 4 bits used Tab. 2/8: Addressing the example terminal 2 (see Fig. 2/2) 2 13

2. Commissioning Example 3: CPX valve terminal with analogue module and VTSA pneumatics The address assignment for this CPX terminal can be found on the next page in Tab. 2/9. The settings are: Status bits activated and /I/O diagnostic interface deactivated On the pneumatic interface set with DIL switch to 1...8 valve coils (8 DO). Module no.: 0 1 2 3 4 5 6 8DI 8DI 4DO 8DI 8DO 2AO 8 O 1 2 3 1 Field bus node CPX FB32 (with DIL 3.2 to ON for status bits) 3 VTSA pneumatics (type 44) 2 Pneumatic interface (set with DIL switch to 1...8 valve coils) Fig. 2/3: Example terminal 3 (with analogue module and VTSA pneumatics) 2 14

2. Commissioning Module no. Module Input address Output address 0 Field bus node CPX FB32 with status bits I0... I15 1) 1 Digital 8 input module CPX 8DE I16... I23 2 Digital 8 input module CPX 8DE I24... I31 3 Digital 4 output module CPX 4DA O32... O39 2) 4 Digital multi I/O module CPX 8DE 8DA I32... I39 O40... O47 5 Analogue 2 output module CPX 2AA O0... O31 6 VTSA pneumatic interface set with DIL switch to 1...8 valve coils 1) 16 bits occupied, 8 bits used 2) 8 bits occupied, 4 bits used O48... O55 Tab. 2/9: Addressing the example terminal 3 (see Fig. 2/3) 2 15

2. Commissioning 2.1.3 Address assignment after extension/conversion A speciality of the CPX terminal is its flexibility. If the demands placed on the machine change, the equipment fitted on the CPX terminal can also be modified. Caution If the CPX terminal is extended or converted at a later stage, the input/output addresses may be shifted. This applies in the following cases: if additional modules are inserted between existing modules. if existing modules are removed or replaced by other modules which have more or fewer input/output ad dresses. if manifold sub bases (CPA) or pneumatic sub bases (Midi/Maxi) for single solenoid valves are replaced by manifold bases for double solenoid valves or vice versa (see pneumatics manual). if additional manifold sub bases (CPA) or sub bases (Midi/Maxi) are inserted between existing sub bases if status bits or the I/O diagnostic interface is activated/ deactivated. 2 16

2. Commissioning Example terminal 3 modified The next diagram shows with terminal 3 as an example (see Fig. 2/3) the effects of modifications to the address assignment. The following has been changed: The status bits have been deactivated. In the case of module no. 1 an 8 input module has been replaced by a 16 input module. The pneumatic interface has been set to 16 O, in order to reserve addresses for an extension to the pneumatics. Module no.: 0 1 2 3 4 5 6 16DI 8DI 4DO 8DI 8DO 2AO 16 O 1 2 1 Modified: Status bits deactivated 2 Modified: 8 DI module replaced by 16 DI module 3 3 Modified: Pneumatic interface (now set with DIL switch to 1...16 valve coils) Fig. 2/4: Example terminal 3 after extension/conversion (compare with Fig. 2/3) 2 17

2. Commissioning Module no. Module Input address Output address 0 Field bus node CPX FB32 with deactivated status bits Depends on DIL switch settings (see Tab. 1/2) 1 Digital 16 input module CPX 16DE I0... I15 2 Digital 8 input module CPX 8DE I16... I23 3 Digital 4 output module CPX 4DA O32... O39 1) 4 Digital multi I/O module CPX 8DE 8DA I24... I31 O40... O47 5 Analogue 2 output module CPX 2AA O0... O31 6 VTSA pneumatic interface with DIL switch set to 1...16 valve coils heavy type = modified module 1) 8 bits occupied, 4 bits used O48... O63 Tab. 2/10: Addressing the example terminal 3 after extension/conversion (see Fig. 2/4) 2 18

2. Commissioning 2.2 Bus configuration General instructions on commissioning Configuration of the CPX terminal demands a very accurate procedure, as different configuration specifications are some times necessary for each slave on the EtherNet/IP due to the modular structure. Note here the specifications in the sec tions which follow. 2.2.1 Registering slave properties in the configuration program When you commission a new EtherNet/IP slave the first time, you must inform your configuration program about certain properties of the slave. The properties of the various slaves are usually administered by the configuration program in a list or library e.g. EDS li brary (EDS for electronic data sheets). The following possibilities are available for extending an EDS library: Installing EDS files The EDS file serves simply for identify ing the CPX FB32 in the network. Enter slave properties manually (only by using the parameter settings set at the factory). Reference source Reference soure for EDS files Current EDS files, icon files and information on the EDS files can be found under the following address in Internet: www.festo.com/fieldbus 2 19

2. Commissioning Installing EDS files You will require the following files for the CPX terminal: File type File name Language Description EDS cpx_fb32.eds English Provides the communication adapter in the configuration program. ICO cpx_fb32.ico Icon file for representing the CPX terminal or mode in the configuration program. Tab. 2/11: Configuration files (EDS) for CPX terminal for EtherNet/IP Installing EDS files Install the files with your configuration program. Iconlfiles Depending on the configuration program used, you can assign icon files (format.ico) to the CPX terminal or the CPX modules. The CPX terminal or the modules will then be represented accordingly in the configuration program. Notes on installing the EDS files and the icon files can be found in the documentation for your configuration program. 2 20

2. Commissioning Enter slave properties manually When an EDS file is installed, the following information about the EtherNet/IP slave is added to the EDS library. This informa tion can also be entered manually if the CPX terminal is to be operated with the parameter settings preset at the factory. Information Vendor name Description Festo Corporation Vendor ID 26 D 1A H Device type 12 D C H Product code (depends on operating mode) Remote I/O Remote Controller 13002 D 32CA H 13003 D 32CB H Major revision / Minor revision 1.2 Input size / Output size Product name Depends on CPX equipment CPX FB32 Catalogue number 541302 Extended Ethernet / IP slave properties Request Packet Interval (RPI) Connections: Exclusive Owner Input only Listen only 10 ms max. 1 max. 16 max. 16 Tab. 2/12: Slave properties Please note If the slave properties are entered manually, individual parametrizing of the CPX terminal is not possible. 2 21

2. Commissioning When the EDS library has been extended, the CPX terminal is entered in the slave list as a possible EtherNet/IP slave. It can now be added to a network. 2.2.2 Overview of configuration on the EtherNet/IP When the slave properties have been configured (e.g. by installation of the EDS file), the following steps are required for parametrizing (depending on the configuration program): 1. Install your CPX terminal and set the network addressing according to section 1.3.3. 2. Create a connection to an EtherNet/IP slave. In order to do this, use with RSLogix the profile Generic Ethernet Device". 3. Assign the Instances of the Assembly Object: Instance 101: Inputs Instance 100: Outputs Instance 102: Configuration data, if used (Configuration Assembly) 4. Select the data format SINT. 5. Enter the IP address, if necessary. 2 22

2. Commissioning 2.2.3 Configuration with RSLogix 5000 1. Click in RSLogix 5000 in the I/O Configuration" on the right on the Ethernet/IP bridge and select New Module": 1 1 Insert CPX FB32 as new module in Ethernet/IP Fig. 2/5: Configuration with RSLogix 5000 2 23

2. Commissioning 2. Select the ETHERNET MODULE Generic Ethernet Module" in the window Select Module Type" and confirm with OK. Fig. 2/6: Insert CPX FB32 as Generic Module 3. Enter the following in the window Module Properties" (Fig. 2/7): the name for the field bus node (as desired) the Instances for inputs: 101 outputs: 100 the Instance for Configuration Assembly: 102 The standard setting is 0" (Configuration Assembly not used). Operating mode Remote I/O: If you undertake parametrizing via the Configuration Assembly: Enter the sum of the assigned bytes (see section 2.3.1). Operating mode Remote Controller: Leave the stan dard setting 0". 2 24

2. Commissioning Data format SINT IP address Confirm the entry. 1 Name (freely selectable) 1 2 2 Assembly Instances 3 Size of the Configuration Assembly" (see explanation in the text) 4 IP address 5 Data format 5 4 3 Fig. 2/7: Enter values for Module Properties" Please note For the configuration with RSLogix 5000 at least one input must be assigned: for the Instances for inputs ( 2 in Fig. 2/7) enter at least 1 or if your CPX terminal does not contain any input modules, activate the status bits with the DIL switches (see Tab. 1/2). 2 25

2. Commissioning 2.3 Parametrizing Caution A different parametrizing will result in a different reaction. Check especially when replacing CPX terminals to see which settings are necessary and make sure that these are restored (e.g. in the start up phase by the higher order PLC/IPC). The CPX terminal is supplied from the factory with preset parameters. The system reaction of the CPX terminal can be adapted to the relevant application. You can set the reaction of the CPX terminal as well as the reaction of individual modules and channels by parametrizing. A distinction is made between the following parametrizings: System parametrizing, e.g.: Switching out fault messages, setting reaction times, etc. Module parametrizing (module and channel specific), e.g.: Monitoring, settings in the event of faults, settings for Forcing. Parametizing the diagnostic memory. A detailed description of the individual parameters as well as basic information on application can be found in the CPX sys tem manual (P.BE CPX SYS...). The module parameters which are available for the various modules can be found in the manual for the relevant module (e.g. manual for CPX pneumatic interfaces and CPX I/O mod ules (P.BE CPX EA...). 2 26

2. Commissioning Prerequisites for parametrizing With the system parameter System start" you can influence the starting reaction. If possible select the setting System start with default parametrizing and current CPX system equipment". The desired parametrizing can then be carried out in the initialisation phase or user controlled (depending on the field bus used). Please note The CPX terminal can only be parametrized if the system parameter System start" has the setting System start with default parametrizing and current CPX system equipment". If the M LED lights up permanently after the system start, then System start with saved parametrizing and saved CPX system equipment" is set. In this case, no other parametriz ing can be carried out. Caution In the case of CPX terminals on which the M LED lights up permanently, the parametrizing will not be restored auto matically by the higher order system if the CPX terminal is replaced during servicing. In these cases, check before replacement to see which settings are required and carry out these settings. 2 27