UC2000 Installation Manual Copyright 2003. All rights reserved.
Table of Contents Specifications 2 Enclosure for the UC2000 Controller 3 Unicorn Access Control System Configuration 4 UC2000 Controller Layout 5 UC100 Layout 6 Cable Connection for UC100 to Computer and to Modem 7 Direct Cable Connection for UC2000 to Computer and to Modem 7 20mA Loop Communication Wiring for Single Panel 8 20mA Loop Communication Wiring for more than one Panel 9 Card Reader Wiring 10 Door 1 Wiring (One Panel for Two Doors) 11 Door 2 Wiring (One Panel for Two Doors) 12 IN / OUT Reader for Single Door Wiring (One Panel for One Door) 13 Important Notice 14 1
Specifications Power Requirements: The UC2000 Controller requires an 11.4Vac 12.6Vac 700mA minimum power supply. Sealed Lead Battery Requirements: The UC2000 Controller requires a 12Vdc 4 7 AH Sealed Lead Battery to provide up to 8 24 hours of full operational backup (depending on the load and the battery). Memory Backup: An internal rechargeable gold capacitor can retain the controller memory for up to 5 days upon loss of both primary and backup battery power. Output Power: Unregulated 12Vdc (10 to 16 volts) 200mA maximum for 12Vdc Card Readers. Regulated 5Vdc (4.75 to 5.25 volts) 100mA maximum for 5Vdc Card Readers. Fuses: 2 amp, 20 x 5mm, fast blow. Input Points: 5 nonsupervised input points (named I1, I2, I3, I4 and I12) are provided. I1 and I2 are for Magnetic Contacts (Door Status Sensors) of Door 1 and Door 2 respectively. I3 and I4 are for Exit Buttons of Door 1 and Door 2 respectively. I12 is wired to the enclosure tamper. Output Points: 2 DPDT relay outputs (named O1 and O2) rated at 24Vdc 1A are provided for door lock control of Door 1 and Door 2 respectively. Reader Interfaces: 2 Wiegand Card Reader Interfaces are provided for the Card Readers of Door 1 and Door 2. Operating Temperature: 35 F to110 F (2 C to 43 C). Operating Relative Humidity: 0 to 90% noncondensing. Dimensions: 33cm x 28cm x 7.6cm ( H x W x D) with lock and key. Enclosure tamper switch is provided. Weight: 6 pounds (2.7 kg) (Sealed Lead Battery is not included.). 2
Enclosure for the UC2000 Controller 12Vac SW1 SW2 3
Unicorn Access Control System Configuration Up to 600m between UC100 and UC2000 or between UC2000 and UC2000 Door Lock UC2000 Magnetic Contact Exit Button UCSOFT Up to 150m between UC100 UC2000 and Reader RS232 Wiegand Compatible Card Reader Up to 8 com ports can be used 20mA Loop (Up to 63 UC2000 Controllers per loop) UC2000 RS232 UC100 Modem Modem Other remote loop Modem UC2000 8bit Wiegand Keypad Reader UC2000 4
UC2000 Controller Layout Reader 2: Green LED (Brown) O14 Reader 2: Data 1 (White) Reader 2: Data 0 (Green) 5V Output (100mA max.) Common Unregulated 12V Output (200mA max.) Reader 1: Data 0 (Green) Reader 1: Data 1 (White) Reader 1: Green LED (Brown) O13 20mA Loop: T (Green) 20mA Loop: T (White) 20mA Loop: R (Black) 20mA Loop: R (Red) CN2 CN1 1 2 3 4 5 6 7 8 CN1 1 2 3 4 5 6 7 8 9 10 11 12 13 COM O1A NC O1A NO O1A NO O1B NC O1B COM O1B COM O2A NC O2A NO O2A NO O2B NC O2B COM O2B 1 1 1 2 3 4 5 6 7 8 SW1 ON 1 & 2: Baud Rate J5 Baud Rate 1 2 1200 OFF OFF 1 2 3 2400 OFF ON 4800 ON ON 12: 20mA Loop 9600 ON OFF 23: RS232 3 to 8: Panel Address Address 3 4 5 6 7 8 1 ON ON ON ON ON OFF 2 ON ON ON ON OFF ON 3 ON ON ON ON OFF OFF 63 OFF OFF OFF OFF OFF OFF SW2 CPU Reset CN2 1 2 3 4 J2 12: Normal 23: Clear all memory 3 2 1 12Vac 700mA AC 2 AC 1 12V 47AH Bettery Battery RS232: Pin5 Common RS232: Pin3 Tx RS232: Pin2 Rx I1 (Door 1 Magnetic contact) Common I2 (Door 2 Magnetic contact) I3 (Door 1 Exit Button) Common I4 (Door 2 Exit Button) I12 (Tamper Button) Common 12 11 10 9 8 7 6 5 4 3 2 1 K1 K2 5
UC100 Layout T (Black) T (Red) R (Green) R (White) 9Vac 300mA 1A To Modem (for Dialup Remote Site) To Computer (for Local Site) RS232: Pin5 Common RS232: Pin3 Tx RS232: Pin2 Rx RS232: Pin7 Common RS232: Pin3 Tx RS232: Pin2 Rx 6
Cable Connection for UC100 to Computer and to Modem A. Local Site ( Computer to UC100 ) 9Pin Female Socket ( connected to Computer COM Port ) Pin2 Rx Pin3 Tx Pin5 Common B. Dialup Remote Site ( UC100 to Modem ) 9Pin Female Socket ( connected to UC100 ) Pin2 Rx Pin3 Tx Pin5 Common 25Pin Male Socket ( connected to UC100 ) Pin2 Rx Pin3 Tx Pin7 Common 25Pin Male Socket ( connected to Modem ) Pin2 Rx Pin3 Tx Pin7 Common Direct Cable Connection for UC2000 to Computer and to Modem without UC100 C. Local Site ( Computer to UC2000 ) for Single Panel and Distance less than 50 feet only 9Pin Female Socket ( connected to Computer COM Port ) Pin2 Rx 9Pin Female Socket ( connected to UC2000 ) Pin2 Rx Pin3 Tx Pin5 Common Pin3 Tx Pin5 Common D. Dialup Remote Site ( UC2000 to Modem ) for Single Panel and Distance less than 50 feet only 9Pin Female Socket ( connected to UC2000 ) Pin2 Rx 25Pin Male Socket ( connected to Modem ) Pin2 Rx Cable Requirements: 3 conductors 1822 AWG Pin3 Tx Pin5 Common Max. Distance: 50 feet between UC100 and Computer or between UC100 and Modem 50 feet between UC2000 and Computer or between UC2000 and Modem without UC100 Pin3 Tx Tips: Check SW1 and J2 of each Panel Pin7 Common 1. Default baud Rate is 4800bps for Local Site (Pin 1 & 2 of SW1 is at ON ON position); change to 9600bps for dialup Remote Site (Pin 1 & 2 of SW1 is at ON OFF position respectively). 2. Push Reset Button SW2 after changed the baud Rate or the Address. 3. The J5 of Panels must be at 12 position for 20mA Loop Communication with UC100 or at 23 position for Direct Cable Connection without UC100. 7
20mA Loop Communication Wiring for Single Panel Data Flow Direction 1 13 T (Black) T (Red) R (Green) R (White) SW1 1 T (Black) T (Red) R (Green) R (White) 1 2 3 J5 8 SW2 Cable Requirements: Shielded Twisted pair 4 conductors (2 twisted pairs), one pair for transmission and the other for reception 1822 AWG Max. Distance: 2000 feet between UC100 and UC2000 Other Requirement: Single end grounding for every Cable Shield Tips: Check SW1 and J2 of each Panel 1. Default baud Rate is 4800bps for Local Site (Pin 1 & 2 of SW1 is at ON ON position); change to 9600bps for dialup Remote Site (Pin 1 & 2 of SW1 is at ON OFF position respectively). 2. Push Reset Button SW2 after changed the baud Rate or the Address. 3. The J5 of Panels must be at 12 position for 20mA Loop Communication. 8
20mA Loop Communication Wiring for more than one Panel Data Flow Direction 1 13 T (Black) T (Red) R (Green) R (White) SW1 1 T (Black) T (Red) R (Green) R (White) 1 2 3 J5 8 SW2 Cable Requirements: Shielded Twisted pair 4 conductors (2 twisted pairs), one pair for transmission and the other for reception 1822 AWG Max. Distance: 2000 feet between UC100 and UC2000 2000 feet between UC2000 and UC2000 Other Requirement: Single end grounding for every Cable Shield 1 T (Black) T (Red) R (Green) R (White) 13 SW1 1 1 2 3 J5 8 SW2 Tips: Check SW1 and J2 of each Panel 1. The baud Rate of Panels in the same loop must be the same (default is 4800bps for Local Site, Pin 1 & 2 of SW1 is at ON ON position; change to 9600bps for dialup Remote Site, Pin 1 & 2 of SW1 is at ON OFF position respectively). 2. The Address of Panels (Pin 3 to 8 of SW1) in the same loop must be different (from 1 to 63). 3. Push Reset Button SW2 after changed the baud Rate or the Address. 4. The J5 of Panels must be at 12 position for 20mA Loop Communication. 9
Card Reader Wiring Wiegand Card Reader Cable Requirements: Shielded 5 or 6 conductors 1822 AWG Max. Distance: 500 feet between Reader and UC2000 Other Requirement: Single end grounding for every Cable Shield 1 2 3 4 5 6 7 8 9 Reader 2: Green LED (Brown) Reader 2: Data 1 (White) Reader 2: Data 0 (Green) 5V Output (100mA max.) Common Unregulated 12V Output (200mA max.) Reader 1: Data 0 (Green) Reader 1: Data 1 (White) Reader 1: Green LED (Brown) SW2 Tips: 1. Check the required input voltage of the Card Reader if it is 5V or 12V before connecting to UC2000 Panel. 2. At least 8 16 inches distance between Card Readers to prevent the interference between each other. 3. The UC2000 Panel supports 26, 32, 34 or 36bit Wiegand Card Format. 4. The UC2000 Panel supports 8bit Wiegand Keypad Format plus 26, 32, 34 or 36bit Wiegand Card Format for the KeypadCard Reader to provide "Pin and Card" function. 10
Door 1 Wiring (One Panel for Two Doors) Cable Requirements: Shielded Twisted pair 2 conductors 1822 AWG Max. Distance: 500 feet between Door Lock and UC2000 500 feet between Exit Button and UC2000 500 feet between Magnetic Contact and UC2000 Power Source for Door Lock 12Vdc or 24Vdc Magnetic Contact ( Door Status Sensor ) 1N4007 Door Lock Other Requirement: Single end grounding for every Cable Sheld Entry Reader Exit Button 1 2 4 5 3 1 Tips: 1. A diode 1N4007 MUST be installed across every electrical switching device (Door Lock) run through a relay contact on the UC2000 Panel. The diode protects the UC2000 Panel from the power generated by the collapsing magnetic field of the electrical load device. 2. DON'T power door locks with the 12V output of the UC2000 Panel or with the same power supply used for the UC2000 Panel. 11
Door 2 Wiring (One Panel for Two Doors) Cable Requirements: Shielded Twisted pair 2 conductors 1822 AWG Max. Distance: 500 feet between Door Lock and UC2000 500 feet between Exit Button and UC2000 500 feet between Magnetic Contact and UC2000 Power Source for Door Lock 12Vdc or 24Vdc Magnetic Contact ( Door Status Sensor ) 1N4007 Door Lock Other Requirement: Single end grounding for every Cable Shield Entry Reader Exit Button 2 3 5 6 9 7 Tips: 1. A diode 1N4007 MUST be installed across every electrical switching device (Door Lock) run through a relay contact on the UC2000 Panel. The diode protects the UC2000 Panel from the power generated by the collapsing magnetic field of the electrical load device. 2. DON'T power door locks with the 12V output of the UC2000 Panel or with the same power supply used for the UC2000 Panel. 12
IN / OUT Reader for Single Door Wiring (One Panel for One Door) Cable Requirements: Shielded Twisted pair 2 conductors 1822 AWG Max. Distance: 500 feet between Door Lock and UC2000 500 feet between Exit Button and UC2000 500 feet between Magnetic Contact and UC2000 Power Source for Door Lock 12Vdc or 24Vdc Magnetic Contact ( Door Status Sensor ) 1N4007 Door Lock Other Requirement: Single end grounding for every Cable Shield Entry Reader Exit Reader Exit Button (Optional) 1 2 4 5 3 1 Tips: 1. A diode 1N4007 MUST be installed across every electrical switching device (Door Lock) run through a relay contact on the UC2000 Panel. The diode protects the UC2000 Panel from the power generated by the collapsing magnetic field of the electrical load device. 2. DON'T power door locks with the 12V output of the UC2000 Panel or with the same power supply used for the UC2000 Panel. 13
Important Notice 1. A diode 1N4007 MUST be installed across every electrical switching device (Door Lock) run through a relay contact on the UC2000 Panel (Fig. 1). The diode protects the UC2000 Panel from the power generated by the collapsing magnetic field of the electrical load device. 2. Use a separate 12Vac power supply (DON'T use 12Vdc power supply) or transformer to power the UC2000 panel. 3. DON'T power door Locks with the 12V output of the UC2000 Panel or with the same power supply used for the UC 2000 Panel. COM NC NO COM NC NO 1N4007 1N4007 Door Lock Door Lock Power Source for Door Lock 12Vdc or 24Vdc Fig. 1 Correct 1N4007 Installation COM NC NO COM NC NO 1N4007 Door Lock Door Lock Fig. 2 Wrong 1N4007 Installation Power Source for Door Lock 12Vdc or 24Vdc The 1N4007 DOES NOT provide any protection function ABSOLUTELY for this installation. COM NC NO COM NC NO Door Lock Door Lock Fig. 3 Wrong 1N4007 Installation Power Source for Door Lock 12Vdc or 24Vdc 1N4007 The 1N4007 DOES NOT provide any protection function ABSOLUTELY for this installation. 14