Priva Blue ID Communication module RS485 Modular design An Priva Blue ID Communication module RS485 provides the system with two RS485 ports for serial communication and is used to connect field bus devices. Characteristics two RS485 ports for serial communication ports electrically isolated from system neutral ports electrically isolated from each other both ports have an A, B and 0 connection 24 V system power supply monitoring clear labelling of ports LED for communication status per port LED for status of module Priva Blue ID Lifeline text card for identification of ports All communication modules (A) have the same base (B). You simply click the base with module onto the DIN rail (C). Hot swappable A module can easily be removed from and placed back in the base without tools. This can be done live (hot swappable). Electrical isolation The module's ports are electrically isolated from the system neutral. In addition the RS485 ports are electrically isolated from each other. 1
Clear indication Legend A B C D E F Priva Blue ID Lifeline LED for status of port RS485-1 port RS485-1 LED for status of port RS485-2 port RS485-2 LED for status of module Priva Blue ID Lifeline The modules are equipped with blue LEDs. Together, these LEDs form the Priva Blue ID Lifeline. If the blue line is continuously on, the modules and bases are in the correct place according to the configuration in TC Engineer. LEDs for status of ports Per port, an LED clearly indicates the port's status. The LED is continuously green when the module is working. In other situations, the LED flashes or is off. In the event of a communication error, the LED is red as long as the error is present. LED for status of module The LED shows the status of the module. The LED is on continuously when the module is working correctly. If not, and in special circumstances, the LED flashes. Connection examples Making a two-wire connection Termination and connecting base circuit 2
module specifications General Module article description Module article number Base article description Base article number Number of RS485 ports Dimensions (XYZ)¹ Weight Maximum power consumption Typical power dissipation² MTBF³ Construction Mounting of base Material Priva Blue ID Communication module RS485 5040001 (V03:01 and higher) Priva Blue ID SC Communication base 5040101 (V01:00 and higher) 2 161.5 x 40 x 100.2 mm (6.36 x 1.57 x 3.94 inches) module: 110 grams base: 120 grams 2.0 W 1.7 W module: 4,380,000 hours base: 8,760,000 hours removable module on a base clicks onto DIN rail mixture of polycarbonate and ABS ¹ Excluding 1.1 mm room between the modules ² Dissipation under the following conditions: - I/O load of 50% - Energy saving mode on (LEDs off) ³ The MTBF is calculated according to the Telcordia SR-332 standard Issue 2 under the following conditions: - ambient temperature: 35 50 C - supply voltage: 24 VDC - time in operation per day: 24 hours - reliability level: 60 % 3
Communication Standard used Bus load Bias resistance Baud rates Other parameters Internal termination and bias circuit Functional isolation of voltage between the ports mutually, and in relation to system neutral Accuracy of internal temperature measurement Protection of ports Cable type required Cross section Maximum cable length Connector type (supplied 2 x) TIA/EIA-485 1/2 Unit Load 47 kω 1k2, 2k4, 4k8, 9k6, 19k2, 38k4, 57k6, 76k8 and 115k2 bps number of data bits: 7, parity: even, odd number of data bits: 8, parity: none, even, odd number of stop bits: 1 or 2 no if required, equip the network with an external termination and bias circuit 240 V ± 2 C protected against incorrect connection of ± 30 VDC and 30 VAC twisted pair 0.2 2.5 mm² (without ferrule connector) 0.25 2.5 mm² (with ferrule connector) 500 m three-pin pluggable screw connector with A, B and 0 connection Indication Priva Blue ID Lifeline red-green LEDs for status of ports green LED for status of module General specifications of controllers, modules and bases Housing IP code Flammability class Recycle code Colour Device type Installation and connection Installation DIN-rail type Maximum width of I/O modules, bus extension modules and controller IP30 (IEC 60529) V-0 (UL 94) 7 release surfaces of module and DIN rail release: blue (RAL5013) other parts: white (RAL9003) open device, for use in a pollution degree 2 environment in control panel: accessible to authorized personnel only can be clicked onto the DIN rail that is positioned horizontally or vertically on the mounting plate Note: The controller, SC module and SN module may only be mounted horizontally. in panel door integration in control panel: accessible to authorized personnel only can be clicked onto the DIN rail that is positioned horizontally on the mounting plate 35 x 7.5 mm (height x depth), in accordance with IEC 60715 20 m 4
Environment Permitted temperature inside control cabinet during normal operation with horizontally mounted modules only (without airflow) Permitted temperature inside control cabinet during normal operation with vertically mounted modules only (without airflow) 0 50 ºC 0 35 ºC Permitted temperature during transport and storage -20 70 ºC Permitted relative ambient humidity Shock and vibration resistance Installation category 10 % 95 % (non-condensing) IEC 61131-2 II Legislation and standards Canada / USA EMC Europe UL 508:2005 (industrial control equipment) UL 916:2007 (energy management equipment) UL 61010-1:2004 (measurement and control equipment) CSA C22.2 No 14-10: 2011 (industrial control equipment) CSA C22.2 No 205-12: 2012 (signal equipment) CSA C22.2 No 61010-1-04 (measurement and control equipment) complies with 47 CFR Part 15 Subpart B, Class B (FCC Rules) Operation is subject to the following two conditions: 1. This system may not cause harmful interference. 2. This system must accept any interference received, including interference that may cause undesired operation. ISM-system, complies with Canadian ICES-001 Low voltage directive 2006/95/CE: EN 61010-1:2010 (measurement and control equipment) EMC directive 2004/108/EC: EN 61326-1:2006 (measurement and control equipment) EN 61000-6-2:2005 (generic immunity standard) EN 61000-6-3:2007 (generic emission standard) RoHS directive 2011/65/EU complies with the WEEE directive 2002/96/EC International The Priva Blue ID S10 Controller is BTL registered at BACnet International. The Priva Blue ID S10 Controller is BACnet certified in accordance with ISO 16484-5/6. Priva is a member of the BACnet Interest Group Europe. 5
Europe Office: UK Office: Canada Office: Your Priva partner: Priva Zijlweg 3 P.O. Box 18 2678 ZG De Lier The Netherlands T +31 174 522 600 F +31 174 522 700 www.priva.nl sales.building@priva.nl Priva UK Ltd. 34 Clarendon Road WD17 1JJ Watford United Kingdom T +44 (0)1923 813 480 F +44 (0)1923 813 499 www.priva.co.uk sales@priva.co.uk Priva North America Inc. 3468 South Service Road Vineland Station Ontario LOR 2E0 Canada T +1(905) 562-7351 F +1(905) 562-7717 www.priva.ca contact.priva@priva.ca 5001113_01.007_09-2016