Room unit with PPS2 interface

Similar documents
Room unit with PPS2 interface

Room unit with PPS2 interface

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

Room unit with PPS2 interface

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

Digital input modules

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

9283P01. Extension module. Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

USB-KNX Interface OCI702. USB-KNX interface with cables and service bag

Extension module for lighting control

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Room Temperature Controller

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Power supply module, bus connection module

Extension module for Web functions generic

PXR11 PXR12. System controllers DESIGO PX

Extension module for graphic Web functions for one automation station

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

TXM1.8RB. TX-I/O Blinds module

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

OCI Service tool. As of ACS790 V9.00. Service case with software and service interface

BACnet/IP Web Interface

Island bus expansion module

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Semi flush-mounted room temperature controllers with LCD

Resistance measuring module

RMZ790. Operator Unit. Building Technologies. Synco 700

Interface converter for VAV compact controllers

Super universal modules

VAV modular controller

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Web interface BACnet/IP

Master room unit for RRV controllers

Room Temperature Controllers

Rotary version, three-position control

VAV compact controller

QMX3.P30 QMX3.P70 QMX3.P02 QMX3.P34 QMX3.P74 QMX3.P37. Wall-mounted sensors and room operator units for KNX PL-Link, KNX S-mode and KNX LTE-Mode

Non-communicating room controllers

Room Temperature Controller

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Freely configurable flush-mounted room operator unit for KNX PL-Link

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

Rotary actuators for ball valves

Handheld Tool for VAV compact and modular controllers

Semi Flush-mount Room Temperature Controllers with LCD

Electromotoric actuators

Communication module to connect M-bus devices to POL6xx.xxx controllers.

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Semi flush-mounted room temperature controllers with LCD

PXM20-E. Operator unit BACnet auf Ethernet/IP DESIGO PX

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

Extension module for BACnet over Ethernet / IP and graphic Web functions

ERF910. RF Repeater. Synco living

Fast running actuators for air dampers

Room controller. For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode)

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

Airflow Pressure Sensor

Automation station, compact series

Non-communicating room controllers

TM-2100 Series Room Command Module

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

RDF301 RDF CE1N3171en 02 Jun 2010 Building Technologies

AEW Pulse Adapter. Building Technologies

Automation stations compact model

Network node WTT56.. A6V _en--_c Building Technologies

QVE3000.0xx QVE3100.0xx. Flow sensor. for liquids in DN10 25 pipes

TM-2100 Series Room Command Module

Room automation station

Temperature controller Ducted systems

LON Module for Variable Speed Drive

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

Electromotoric actuators

Communication over Modbus protocol Connection with multiple controllers Application upgrade by using an SD 1) card or a USB stick

Air damper actuators

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Product and Application Description

SEH62.1. Digital Time Switch

Heating Circuit Controller

Temperature Controller

Air Damper Actuators Modbus RTU

Air Damper Actuators Modbus RTU

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

Room automation stations

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

M-bus RF gateway. Meters and Energy Cost Allocation WTT563-0C0000

Push Button Interface UP 220D31

UCU Room Display. Operation Modes. Features. Applications DATASHEET

Mobile Data Collector

EY-RU : Room operating unit, ecounit

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Immersion Temperature Sensors

EY-RU : Room operating unit, ecounit

Electromotoric actuator

Transcription:

1 642 Desigo RX Room unit with PPS2 interface for use with: QAX33.1 devices of the ranges Desigo RXC, RXB, RXL, and RXA (PPS2) Desigo PX Automation stations 1) devices with a PPS2 interface Room temperature measurement Room temperature setpoint adjuster Rocker switch for control mode selection ( / Auto) and manual control of the fan in fan-coil systems (up to 3 speeds) PPS2 interface to controller Socket for commissioning and service tool or service terminal Use The room unit is used in rooms controlled by an individual room control system, to measure the room temperature and for operation of a room controller. The QAX33.1 is typically used in conjunction with a fan-coil system (for fan control). It can also be used in conjunction with a Desigo PXC automation station 1). The room unit incorporates a socket for a commissioning and service tool or service terminal. This tool socket provides access via the PPS2 interface or via a bus system (e.g. LONWORKS bus) to the connected individual room controller. 1) If room units QAX32.1, QAX33.1, QAX34.1 or QAX84.1 are used in conjunction with a PXC automation station, the room unit will show the request of the user and not the effective state. CA2N1642en_03 2015-12-23 Building Technologies

Ordering When ordering, please specify the quantity, product name and type code. Example: 30 Room units QAX33.1 Equipment combinations The room unit is suitable for use in conjunction with all controllers which incorporate a PPS2 room unit interface (e.g. Desigo RX, Desigo PX). Mechanical design The room unit is designed for surface mounting (with knock-outs for cable entry from the top or bottom) or for mounting on a recessed conduit box with the cables connected from the rear. The unit comprises a housing and base unit, connected by releasable snap-fittings. The base unit accommodates the screw terminals which have an integrated terminal strip. The housing accommodates a printed circuit board, room temperature sensor element, setpoint adjuster, rocker switch for mode selection and fan speed selection, plug-in connectors and a socket for the commissioning and service tool or service terminal. Both the housing and base are made of plastic. Base unit 80082 80084 Housing Socket for the commissioning and service tool or service terminal Operator controls and indication 80168A Dial for stepless adjustment of the setpoint LEDs to indicate control mode and fan speed Rocker switch for mode selection and fan speed Rocker switch for selection of mode and fan speeds The controller control mode can be selected on the basis of occupancy, using the rocker switch on the room unit. The same switch can also be used for manual selection of up to three fan speeds. Pressing once in the direction of the left arrow switches one stage to the left, and pressing once in the direction of the right arrow switches one stage to the right. The current control mode or the manually selected fan speed is indicated by LED. 2/6

Position Fan control 1) Control mode 1) Auto Fan controlled automatically by controller Fan controlled automatically by controller Manual, fan speed 1 Manual, fan speed 2 Manual, fan speed 3 The controller operates at the setback setpoints (at night, or when room is unoccupied or occupied intermittently) Comfort mode (room occupied) 1) For details of these functions, refer to the application description for the relevant controller range. Address plugs 01884 Address plugs inside the housing They allow setting the address in cases where several room units are connected to one controller. The room units are delivered with address 1. Disposal The device is classified as waste electronic equipment in terms of the European Directive 2012/19/EU (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. Engineering notes The device receives its power from the connected controller via the PPS2 interface (extra low voltage). Only one room unit may be connected to a RX room controller. A maximum of 5 room units may be connected to a PXC automation station (they are identified by different settings of their address plugs) A twisted-pair cable is required for the connection to the controller. Desigo RX uses four-core cables, Desigo PX uses two-core cables (see the respective installation guides). Screening is not required. Mounting The room unit is suitable for wall-mounting and for mounting on a recessed conduit box. Do not mount in recesses, shelves, behind curtains or doors, or above or near heat sources. Avoid exposure to direct sunlight or draughts. The electrical wiring conduit must be sealed where it joins the room unit, to prevent the occurrence of draughts in the conduit which could affect the sensor. The specified ambient conditions must be complied with. Mounting instructions are printed on the room unit packaging. A mounting kit is included with the unit. 3/6

Installation notes STOP Note! Local installation regulations must be observed. The room unit is not protected against connection to AC 230 V. Commissioning notes Response on start-up After an interrupt of the PPS2 interface the communication will only be re-established when the connected controller polls the PPS2 addresses. The duration of the corresponding cycle is: RXA: 10 sec; RXB, RXL and RXC: 3 min; PX: 30 sec. The following routine occurs in the room unit when the power supply is connected (via the PPS2 interface) or after a reset via the controller: Step Function Description 1 LED test The LEDs are operated in sequence for 1 s each 2 Device ready After a delay of 1 s the device will be ready for PPS2 communication. The actual control mode is displayed after a further delay of 5 s. Technical data Supply voltage Operating voltage range DC 12...15 V (SELV) DC 12 15 V class 2 (US) The room unit receives its power from the connected controller, via the PPS2 interface Power consumption (from controller) Max. 0.10 VA Function data Temperature sensor Measuring element NTC resistor Measuring range 0... 40 C Response time 8 min Accuracy (5... 30 C) ± 0.5 K Accuracy (25 C) ± 0.25 K Setpoint correction Correction range (determined by controller) max. ± 12 K (default ± 3 K) Accuracy over full correction range 10 % Indication (control mode) 2 LEDs, yellow Interfaces Type of interface between controller and room unit PPS2 (point-to-point interface, Version 2) Baud rate 4.8 kbit/s Cable connections Connection terminals (screw terminals) Stranded or solid conductors 0.8... 2.5 mm 2 Single cable length controller Room unit See Installation guidelines: Desigo RXC: CA110334, Desigo RXB & RXL: CM110381 Desigo RXA: CA2Z3884 Desigo PX: CA110396 Cable type 2-core or 4-core, twisted pairs, unscreened Connecting cable for service tool Off-the-shelf, max. 3 m Protection data Housing protection IP 30 to EN 60529 Protection class III to EN 60730-1 4/6

Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temperature 0... 50 C 25... 70 C Humidity < 85 %rh < 95 %rh Mechanical conditions Class 3M2 Class 2M2 Standards, directives and approvals Product standard EN 60730-1 Automatic electrical controls for household and similar use Electromagnetic compatibility (Applications) For use in residential, commerce, lightindustrial and industrial environments EU conformity (CE) CA2T1741xx *) UL certification (US) UL916, http://ul.com/database RCM-conformity (EMC) A5W00005055 *) EAC conformity Eurasia conformity Environmental compatibility Product environmental declaration (contains A6V10736277_en--_a *) data on RoHS compliance, materials composition, packaging, environmental benefit, disposal) Dimensions See Dimensions Color Housing front, dial NCS S 0502-G, RAL 9003 signal white Housing, base unit, rocker switch RAL 7035 light grey Weight Excluding packaging 0.12 kg *) The documents can be downloaded from http://siemens.com/bt/download. Connection terminals The tool socket on the room unit provides access to the connected individual room controller via the commissioning and service tool or the service terminal. The bus cable (Terminals 3 and 4) is therefore looped to the tool socket (Pins 1 and 2). The bus cable is not affected by the room unit. For connection of a service terminal, the PPS2 interface (Terminals 1 and 2) is also connected to the tool socket. Terminal layout 8 7 6 5 4 3 2 1 C C+ CP CP+ 80085 PPS2 interface, supply voltage CP+ 1 Device supply, Data PPS2 (pos.) CP 2 Device supply, Data PPS2 (neg.) Bus connection (looped to tool socket) C+ 3 With LONWORKS bus (Desigo RXC): CLA C 4 With LONWORKS bus (Desigo RXC): CLB 5... 8 Not used Tool socket Standard type RJ45 tool socket. 1 2 3 4 5 6 7 8 1. With LONWORKS bus (Desigo RXC): CLA 2. With LONWORKS bus (Desigo RXC): CLB 3. Not used 4. Not used 5. Not used 6. Not used 7. CP+ Data PPS2 8. CP Data PPS2 3206Z01 5/6

Connection diagram (Example: RXC) The following example shows the room unit connected to a Desigo RXC room controller: PPS2 R1 7 8 1 2 Tool 4 3 2 1 C C+ CP CP+ PPS2 CP+ CP CLA CLB N1 B A LonWorks Bus 1741A03 = Twisted pair R1 N1 A B Room unit QAX33.1 Room controller RXC... Connection for RXT10 commissioning and service tool Connection for service terminal with PPS2 interface Dimensions All dimensions in mm 4,2 80087 9,5 56 60 100 90 32 36 56 60 Published by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Siemens Switzerland Ltd 2000 Delivery and technical specifications subject to change 6/6