HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems

Similar documents
Power distribution solutions for the ProLiant DL580 G2 server

Powering HP BladeSystem c7000 Enclosures

The HP BladeSystem p-class 1U power enclosure: hot-plug, redundant power for a server blade enclosure

HP Power Capping and HP Dynamic Power Capping for ProLiant servers

HP Uninterruptible Power Supplies Overview

Z8 G4 Site Prep Guide Table of contents

HP Proliant DL360 G6 Carrier-Grade Server Read Before Install

Dynamic Power Capping TCO and Best Practices White Paper

Server Technology Inc.

SCSI Cable Installation Instructions

Replacing the Battery HP t5730 and t5735 Thin Clients

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

Compaq Ultra-Dense Server Deployment in Telecommunications (Telco) Racks

Powering Change in the Data Center. A White Paper from the Experts in Business-Critical Continuity TM

QuickSpecs. HP Parallel 3 Phase Uninterruptible Power Systems. Overview

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

HPE BladeSystem c3000 Enclosure Quick Setup Instructions

HP Modular Cooling System: water cooling technology for high-density server installations

HP ProLiant DL165 G7 Server

HP Rackmountable 3 Phase Uninterruptible Power Systems Overview

Newest generation of HP ProLiant DL380 takes #1 position overall on Oracle E-Business Suite Small Model Benchmark

QuickSpecs. HP 1x4 USB/PS2 KVM Switch. HP 1x4 USB/PS2 KVM Switch. Models HP 1x4 USB/PS2 KVM Switch

QuickSpecs. HP Remote Monitoring Power Distribution Units. Overview

Intel Hyper-Threading technology

QuickSpecs. HP Basic Power Distribution Units (bpdu) Overview

Retired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)

At a Glance. HP Dynamic Smart Cooling. Overview. DSC Base Station

TECHNOLOGY BRIEF. Compaq 8-Way Multiprocessing Architecture EXECUTIVE OVERVIEW CONTENTS

QuickSpecs. Models HP SC11Xe Host Bus Adapter B21. HP SC11Xe Host Bus Adapter. Overview

Server Technology, Inc.

HP SAS benchmark performance tests

HP ProLiant BL35p Server Blade

QuickSpecs. Models SATA RAID Controller HP 6-Port SATA RAID Controller B21. HP 6-Port SATA RAID Controller. Overview.

HP ProLiant MicroServer

QuickSpecs HP BladeSystem Breaker Panel

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

3331 Quantifying the value proposition of blade systems

QuickSpecs. What's New New 146GB Pluggable Ultra320 SCSI 15,000 rpm Universal Hard Drive. HP SCSI Ultra320 Hard Drive Option Kits (Servers) Overview

Systems and Technology Group. IBM Technology and Solutions Jan Janick IBM Vice President Modular Systems and Storage Development

HP ProLiant DL580 G5. HP ProLiant BL680c G5. IBM p570 POWER6. Fujitsu Siemens PRIMERGY RX600 S4. Egenera BladeFrame PB400003R.

Looking for a simple and intuitive solution that allows you to access and manage servers across your entire network?

Looking for a simple and intuitive solution that allows you to access and manage servers across your entire network?

HP PDU Best Practices

The Virtualized Server Environment

Sun StorageTek. 1U Rackmount Media Tray Reference Guide. Sun Doc Part Number: Second edition: December 2007

QuickSpecs. Models 64-Bit/133-MHz Dual Channel Ultra320 SCSI host bus adapter B bit/133-MHz Dual Channel Ultra320 SCSI host bus adapter

HP ProLiant SL160z G6 Server

QuickSpecs. HPE Basic Power Distribution Units (PDU) Overview

QuickSpecs. HPE Rackmountable 3 Phase Uninterruptible Power Systems. Overview. (UPS R8000/3 and R12000/3)

HP ProLiant delivers #1 overall TPC-C price/performance result with the ML350 G6

QuickSpecs. HPE Standard Power Supplies. Overview. HPE Standard Power Supplies

HPE ProLiant DL360 Gen P 16GB-R P408i-a 8SFF 500W PS Performance Server (P06453-B21)

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

Find the right platform for your server needs

QuickSpecs. HPE Flexible Slot Power Supplies. Overview

Calculating Total Power Requirements for Data Centers

Aruba JL311A Cable Guard Installation Instructions

QuickSpecs HP Rack 5642

Overview of HP tiered solutions program for Microsoft Exchange Server 2010

QuickSpecs. HPE Apollo 6000 Power Shelf. Overview

QuickSpecs. HPE Standard Series G2 Basic Power Distribution Units (PDU) Overview. Basic, reliable power distribution for your HPE IT solutions

QuickSpecs. Models. Overview

QuickSpecs. HPE Metered and Switched Power Distribution Units (PDU) Overview

AC4G-D User s Manual

QuickSpecs. Models. Overview

PoE ( Power over Ethernet) Devices

HP recommended configuration for Microsoft Exchange Server 2010 and HP ProLiant SL4540 Gen8 Servers (3 node)

HP StorageWorks Enterprise Virtual Array 4400 to 6400/8400 upgrade assessment

R/T2000 G2 HP R/T 2200 UPS INTL HP R/T 2200 UPS JPN/TWN

HPE Intelligent Power Distribution Unit Installation Instructions

QuickSpecs. Models 64-Bit/133-MHz Dual Channel Ultra320 SCSI host bus adapter B bit/133-MHz Dual Channel Ultra320 SCSI host bus adapter

HPE Integrity MC990 X Server Getting Started Guide

HPE Direct-Connect External SAS Storage for HPE BladeSystem Solutions Deployment Guide

HP BladeSystem c-class enclosures

QuickSpecs. HP Performance Optimized Datacenter (POD) 20ce. Overview. Retired

QuickSpecs. Models HP T1500 UPS JPN/TWN. HP UPS T1000 G2, T1500 G2 Models. Overview. Retired

Retired. ProLiant iscsi Acceleration Software Pack for Embedded Multifunction Server Adapters Overview

QuickSpecs. Compaq Rack Accessories

Installation and Getting Started Guide. HP ProCurve 600/610 External Power Supplies. PoE. Power over Ethernet Devices

HPE Altoline QSFP28 x86 ONIE AC Front-to-Back Switch HPE Altoline QSFP28 x86 ONIE AC Back-to-Front Switch

T1000 G2 and T1500 G2 1. Battery Compartment 1. Battery Compartment 2. LED display 2. LED display HP T1500 UPS INTL HP T1500 UPS JPN/TWN

HP ProCurve Network Access Controller 800

HP Cluster Platform Server and Workstation Overview

INCREASING DENSITY AND SIMPLIFYING SETUP WITH INTEL PROCESSOR-POWERED DELL POWEREDGE FX2 ARCHITECTURE

HP EVA P6000 Storage performance

Models PDC/O5000 9i W2K Cluster Kit B24

HP ProCurve Power over Ethernet (PoE/PoE+)

QuickSpecs. HP StorageWorks 60 Modular Smart Array. Overview

HP ProLiant ML370 G4 Storage Server

* * Agilent Power Distribution Unit (PDU) Installation Guide

QuickSpecs. Models HP 30-Notebook Managed Charging Cart

E-Series Site Preparation Guide

QuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview

HPE ProLiant DL580 Gen10 Server

QuickSpecs. Models. HP StorageWorks Modular Smart Array 30 Multi-Initiator (MSA30 MI) Enclosure. Overview

HP 3PAR OS Messages and Operators Guide

Wall-Mounting your HP TouchSmart. User Guide

Rack-mountable 14 drive enclosure with single bus, single power supply. Tower 14-bay drive enclosure, single bus, single power supply, LCD monitor

Fully integrated and tested with most ProLiant servers and management software. See list of servers with each adapter specifications.

QuickSpecs. Models. Features and benefits Additional information. HP 620 Redundant/External Power Supply Overview

Transcription:

HP Power Calculator Utility: a tool for estimating power requirements for HP ProLiant rack-mounted systems technology brief Abstract... 2 Introduction... 2 Key parameters... 2 Input line voltage... 2 Device VA rating... 3 Device input power... 3 BTUs required for cooling... 3 Input/inrush current... 3 Leakage current... 3 Determining power needs... 3 HP Power Calculators... 5 Developing the calculators... 5 Using the calculators... 5 Example rack calculation... 7 Conclusion... 9 Do use the calculator for:... 9 Do not use the calculator for:... 9 For more information... 10 Call to action... 10

Abstract With power requirements of computing equipment continuing to increase and the cost of energy forever rising, IT organizations need to obtain accurate estimates of power and cooling requirements when designing and expanding data centers. The use of equipment nameplate ratings can yield inflated numbers that can result in overspending for power infrastructure components and a less efficient data center design. HP developed the Power Calculator utility to enable IT planners to better estimate the power needs of HP ProLiant systems. This paper identifies factors affecting power needs, explains how the Power Calculator works, and provides an example of how it is used. Introduction As integration technology evolves and system density increases, the amount of power once required for several racks of computing equipment is now consumed by systems housed in a single rack. A key benefit of high-density systems is the efficient use of valuable floor space. Advances in processor architectures and speeds have resulted in performance-per-watt gains with a reduction in cost-pertransaction. Table 1 indicates an approximate 3x performance-per-watt increase over a four-year period. Table 1. Cost per tpm comparison HP ProLiant System Date of system availability TPC-C [1] Cabinet Power $ price/tpm [2] DL580 6/900 4S Intel Xeon 10/15/01 39.1K 5.8 kw $7.95 DL585 G1 DC AMD Opteron 11/28/05 236.034 K 10.8 kw $2.02 NOTES: [1] Transaction Processing Performance Council benchmark of online transaction processing (OLTP) [2] tpm = transactions per minute Nevertheless, new applications and virtualization techniques require more processing and I/O capacity, and power consumption per rack will continue to increase. Effective sizing of a computing infrastructure while managing IT costs requires realistic estimates of current and future power and cooling requirements. Determining the power consumption of individual racks can yield an estimate for the total consumption for a data center. It can also provide a starting point for determining power distribution requirements and cooling needs at the rack level. To determine power distribution, power redundancy, and battery backup requirements, the major active components within a rack must be analyzed for their needs based on operating parameters. Considerations such as system serviceability and scalability should also be taken into account during planning. Key parameters Determining total power needs for a data center requires consideration of the key parameters described in the following paragraphs. Input line voltage Input voltage may be low-line or high-line voltage, and it is determined by what is available at the data facility. Low-line voltage [100 120 volts alternating current (VAC)] is commonly delivered to standard AC wall outlets in North America, while high-line voltage (200 240 VAC) is commonly used in other parts of the world but is also increasingly common in data centers in North America. Most HP server equipment is designed to operate in the 100- to 240-VAC range. Electrical equipment requiring high power consumption usually operates more efficiently at 200 240 VAC. Using a higher voltage lowers current drain and creates less heat, thus reducing the 2

demand (kilowatt hours) on cooling systems while increasing equipment reliability. Some systems that can use either low-line or high-line power actually require high-line voltage to meet maximum performance specifications. Facilities may also distribute AC power as single- or three-phase. Threephase high-line power (such as 3-phase 208 VAC in the U.S.) is more efficient and recommended for systems requiring 3 kilowatts or greater. Device VA rating The total amount of power a device requires from the facility AC feed is known as apparent power and is measured in volt-amperes (VA). Knowing the total amount of VA for all active components in a system helps IT designers determine the type and quantities of power distribution unit (PDU) and uninterruptible power supply (UPS) needed for a given rack configuration. Device input power The amount of power a device turns into work and dissipates as heat is known as real (or true) power and is measured in watts (W). Since any heat created by electrical equipment must be extracted, knowing the total amount of watts created by systems in a data center helps determine the cooling capacity needed by the facility. BTUs required for cooling The British Thermal Unit (BTU) is the standard for measuring the capacity of cooling systems. The amount of power (watts) consumed by equipment determines the number of BTUs/hr required for component cooling, based on this formula: For example: BTUs/hr = watts x 3.41. 399 watts x 3.41 = 1360 BTUs/hr. Air conditioning equipment is typically rated in terms of tons of cooling, an old measurement based on the cooling ability of tons of ice (1 ton of cooling = 12000 BTUs/hr). Input/inrush current Input current is the amount of amperes a system draws during normal operation. However, when AC voltage is first applied (power cord plugged in and/or a circuit breaker is switched on), power supplies of electrical components can momentarily draw several times more current than they will draw while operating. This inrush current is cumulative across devices within a common power circuit, and it must be considered when building a rack. Power supplies in HP servers include circuitry that minimizes inrush current. Staggering activation of segmented circuits can further reduce the effects of inrush current. Leakage current Leakage current (typically measured in milliamps) is residual current that originates in power supply filters and flows from chassis ground to the phase and neutral power conductors. Leakage current is cumulative across components within a power distribution circuit and can become a hazard if proper grounding procedures are not used. Determining power needs Equipment power needs have commonly been determined in one of two ways: Nameplate ratings Actual power measurements 3

Nameplate ratings on power supplies typically represent the maximum amount of output power the supplies are capable of providing. Name plate ratings are typically based on the power needs of fully loaded servers configured for maximum processing and storage capability and running at 100 percent utilization. Since servers rarely are configured to their maximum and run at 100 percent utilization, estimating rack requirements using nameplate ratings would likely result in inflated power requirement numbers. Figure 1 illustrates how the use of nameplate ratings can distort rack installation planning. Using the power supply nameplate rating of 700 watts as a guide, only 14 DL360 G5 servers could be installed in a rack designed to handle 10 kw of power. Significant rack space would be unused. However, depending on processor and peripheral configuration and system utilization, DL360 G5 servers may use substantially less power. A DL360 G5 using the latest low-wattage Intel processors and utilized at 75 percent may require only 400 watts, so more servers can be installed in the same 10 kw rack. Figure 1. Loading of a 10 kw rack Rack loading using nameplate ratings DL360 G5 14 servers @ 700 W ea. = 9800 watts Rack loading using actual measurements DL360 G5 25 servers @ 400 W ea. = 10,000 watts The most accurate power consumption predictions are those obtained by pre-configuring and measuring actual systems under load. This method of obtaining data is usually impractical for customers in a planning mode since it would require purchasing, setting up, configuring, and running of each component to acquire the measurements. HP has taken the initiative of performing a number of tests on server products under various configurations to determine actual power requirements. 4

HP Power Calculators The HP Power Calculator utility reduces the research and guess-work for determining power requirements of systems based on ProLiant servers. Each calculator provides precise data that planners can use to accurately predict power and cooling requirements for single systems and, consequently, for racks of systems. NOTE: HP Power Calculator is intended to be a conservative estimator of power. No two software programs will consume exactly the same amount of power. Even programs that report the same CPU utilization will have different power consumption characteristics, based on the exact mix and sequence of instructions being executed. The programs used as the measurement reference for the HP Power Calculator were intended to consume as much or more power than actual user applications. Developing the calculators HP develops a unique Power Calculator for a specific ProLiant server using data collected from server tests. Each test starts with a system fully-configured with the maximum number of processors, memory, hard drives, expansion cards, and power supplies. Proprietary software is used to exercise the processors and all peripherals while voltage and current measurements are taken. Tests are repeated for all levels of processor support at all speeds, with different memory amounts and hard drive sizes. Revised or updated servers are retested during development cycles to ensure calculator integrity. Using the calculators Online HP Power Calculators for HP ProLiant DL, ML, and PL servers are available at this URL: http://h30099.www3.hp.com/configurator/powercalcs.asp Online Power Sizer utilities for HP ProLiant BladeSystem (BL) p-class and c-class servers are available at this URL: HP BladeSystem Power Sizer NOTE: For planning hybrid installations involving varied and dissimilar equipment, the HP Site Preparation Utility is also available at this URL: http://h30099.www3.hp.com/configurator/calc/site%20preparation %20Utility.XLS. The time required to download the program will depend on the Internet connection. 5

Figure 2 shows a partial screen of the Power Calculator for the HP ProLiant DL360 G5. The upper half of the screen provides an overview of the server model. The lower half of the screen provides the data fields for configuring the server as desired. Users can configure such parameters as level of input voltage; number, type, and speed of processors; amount of memory; number and size of hard drives; and types of expansion boards, all of which affect power consumption. The resulting operating parameters of that configuration will be displayed in real time. Figure 2. HP Power Calculator for HP ProLiant DL380 G5 (partial screen shown) Each Power Calculator also provides a slider control allowing users to set the utilization level for the server from 0 (minimum or idle) to 100 percent (maximum usage). Resulting power consumption data is updated in real time. NOTE: The slider control does not replicate CPU usage as measured by the operating system. Instead, it approximates overall system utilization, which is a more meaningful figure. 6

Example rack calculation The HP Power Calculator utility provides accurate operating parameters that planners can use to predetermine the worst-case power requirements of a populated rack. In the following example, the HP ProLiant DL380 G5 server is the key component type to be installed in a standard 42U rack. The HP ProLiant DL380 G5 server supports one or two Intel Xeon 5000, 5100, or 5300 series processors, up to 32 gigabytes (GB) of memory, up to eight hot-plug hard drives, four PCI expansion cards, and one (plus one for redundancy) power supply. For this calculation, each server in the rack will be configured with two Intel Xeon 5150 processors, 2 GB of memory, one PCI Express (PCI-e) card, four 72-GB hard drives, and 1 + 1 power supplies for redundancy (Figure 3). Figure 3. Power calculation for single HP DL380 G5 server With the system utilization slider control set at 75 percent, the system input requirement for operating at 208 VAC will be 372 watts. The apparent power (VA) required will be 399 VA, and the system will draw approxiamately1.9 amperes of current. 7

While a standard 42U rack can physically accommodate 21 ProLiant DL380 G5 servers, it is advisable to allow space for server expansion, power distribution components such as PDUs and UPSs, keyboard/video/mouse (KVM) equipment, or networking components. Figure 4 shows a rack configuration of 16 servers with redundant power. Based on individual unit needs determined using the Power Calculator, the rack configuration would require the following: 6384 VA total apparent power (16 x 399 VA) that the power distribution components must handle 30.4 amperes total current (16 x 1.9 A) drawn by the 16 servers In a system with redundant power (Figure 4), the power supplies (PS A and PS B) of each server are typically connected through PDUs to separate power buses. With both power buses active, each power supply will evenly share the server load. Should one power bus fail, the power supplies on the active bus will handle 100 percent of the server load. The associated PDU will need to distribute the full 30.4 amps (16 x 1.9 A) required by all the servers. It is a common but unwise practice to plug additional components into a PDU that has available outlets even if measurements made under normal conditions indicate that the PDU loading is well under the rated capacity. To ensure full redundancy, a PDU should never handle more than 50 percent of its rated capacity in normal operation. For redundant PDUs with segmented circuits, circuit loading for each segment should be held at less than 50 percent of the circuit breaker rating. In the configuration shown in Figure 4, the 40-amp PDUs provide some headroom for additional equipment to be installed. Figure 4. 42U rack configuration of HP ProLiant DL380 G5 servers with redundant power Physical Configuration Functional Block Diagram DL380 G5 servers 1 thru 8 40A PDU PS A PS B 40A PDU DL380 G5 servers 1 thru 8 31A DL380 G5 servers 9 thru 16 16 A DL380 G5 servers 9 thru 16 16 A Bus A (208 VAC) Bus B (208 VAC) Normal operation Redundant operation (Bus A failure) The cooling requirement for the rack configuration shown in Figure 4 would be 19776 BTUs/hr (1236 x 16). Actual cooling requirements can be affected by additional factors including air flow within the rack and rack placement within the data center. If the configuration in Figure 4 were to require battery backup support due to a power failure, the UPSs would need to provide 6384 VA for the servers. The HP UPS and PDU sizing tool provides UPS and PDU model suggestions based on user input. The sizing tool is available at the following URL: http://www.upssizer.com/ 8

Conclusion The HP Power Calculator is a valuable utility for planning systems based on HP ProLiant products. The calculator provides meaningful estimates of power for use in sizing an infrastructure. It is important to note, however, that actual power consumption of an installed system running certain applications may vary. To use the Power Calculator effectively, IT organizations must observe the following caveats: Do use the calculator for: Estimating requirements only for HP systems Determining maximum equipment power and cooling needs at the unit (chassis) and rack levels Do not use the calculator for: Estimating requirements of systems from other vendors Direct comparisons with other vendors products Precise predictions of the power consumption of a single instance of a server running a particular application. Actual power consumption can be less than the power and cooling needs indicated by the Power Calculator. Estimating power consumption of individual components (memory, hard drives, cards, etc.) NOTICE The HP Power Calculator is provided as is without any warranty of any kind. The entire risk arising out of the use of the Power Calculator remains with the customer. In no event shall HP be liable for any direct, consequential, incidental, special, punitive, or other damages whatsoever (including without limitation, damages for loss of business profits, business interruption or loss of business information) even if HP has been advised of the possibility of such damages. Refer to the HP Power Calculator program license terms for more information. 9

For more information For additional information, refer to the resources listed below. Resource HP Power Calculator Catalog HP UPS and PDU Sizer HP rack and power products HP Site Preparation Utility Hyperlink http://h30099.www3.hp.com/configurator/powercalcs.asp or www.hp.com/go/bladesystem/powercalculator http://www.upssizer.com/ http://h18004.www1.hp.com/products/servers/platforms/rackan dpower.html http://h30099.www3.hp.com/configurator/calc/site%20preparation %20Utility.XLS Call to action Send comments about this paper to TechCom@HP.com. 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Intel and Xeon are trademarks or registered trademarks of Intel Corporation or its subsidiaries in the United States and other countries. TC070307TB, March 2007 0