W8735A1013 EnviraCOM Serial Adapter

Similar documents
MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

MODBUS AND BACNET COMMUNICATION INSTRUCTIONS

R7284 Series. Electronic Oil Primary

H7625A, H7635A Humidity/Temperature Sensors

S7999D SOLA Operator Interface Display

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

MODBUS COMMUNICATION INSTRUCTIONS

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors

Athena Series RMC Hot Runner Controller Configuration and Operation Manual

Inc. SCC. for use OCI This allows or building managemen. SCC Inc.

IntesisBox. v.2.5. User Manual Issue Date: 12/2017 r1.9 EN. Modbus RTU (EIA-485) Interface for Fujitsu air conditioners.

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

SCC Inc. LMV5 Series. Installation Instructions. Document No. LV February 12, 2018

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

7800 SERIES S7810B Multi-Drop Switch Module

MODBUS COMMUNICATION INSTRUCTIONS

IntesisBox ModBus RTU Fujitsu Air Conditioning

RTD-W Installation Instructions

Modbus Module. Data sheet. Communication module for MULTICAL 403 and MULTICAL 603

Carbon Monoxide Sensor - ModBus

Modbus Register Map: InRow ACRD60x / ACRC60x

Manual FC 3500 DC Fan Control

LMV2 / LMV3... Modbus. User Documentation. Building Technologies Division

IntesisBox PA-AW-MBS-1 v.2.0

Wireless Receiver W/ USB Output BA/RCVxxx-USB Installation and Operating Instructions

PC PROGRAM INSTRUCTIONS FOR CREST and COPPERFIN MODELS

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

Venstar Thermostat Adapter

FX 2 Instruction Manual

TF243 Series Digital Thermostat Fan Coil Unit Control

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

IntesisBox PA-AC-MBS-1

4-step Chiller and Heat Pump Controller

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

Register Map: Ecoflair Indirect Air Economizer

RXTP ROOM TEMPERATURE

CTR21, CTR22, CTR23, and CTR24 Wall Modules

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016

MODBUS COMMUNICATION INSTRUCTIONS

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 3.30 and greater

BNI IOL Z036 BNI IOL Z036

Millennium Simplicity Elite Parameter Points and Quirks

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Modbus Interface Module

MM-A20 BMS Interface for Mitsubishi Electric Split Air-Conditioning

IntesisBox SMS - Mitsubishi Electric air conditioners

FX2-CHILLER. Digital Control. Operations Manual

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

CoolMaster Programmers Reference Manual (PRM)

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

GW-7228 J1939/Modbus RTU Slave Gateway

IntesisBox DK-RC-MBS-1 v.0.8

IntesisBox TO-RC-MBS-1

CDD Carbon Dioxide Transmitter

N20, N34 Series Non-Spring Return Direct Coupled Actuators

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

PROFIRE PF3100 Modbus Register Map PF

CDD4 Duct Carbon Dioxide Transmitter

M1000 INTELLIGENT ZONE CONTROL SYSTEM

ETM-2050/ETM-2051 Service Manual

Manual DTM Digital Pressure Transmitter

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

RTD-NET Installation Instructions

PC PROGRAM INSTRUCTIONS

MAXDTC-BT Family User Manual

A7800A1010 Tester for the 7800 SERIES System With Valve Proving Systems

ICN Mini Link/External. User s Guide. 1733N Model A Mini Link/EXT (Version 1) 1732N Model A ICN Interface Board (Version 1)

Wireless Remote Controller Kit

X47.CE Product Guide

S7999B, S7999C SOLA Local Operator Interface

Users Manual STP-103II. Thermal Printer Rev

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

Temperature controller Ducted systems

DESCRIPTION OF MODBUS CONNECTION

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

ETM-2040 Service Manual

RXTH DUAL ROOM SENSOR / SWITCH

JADE Economizer Module (MODEL W7220)

EXD-TEVI Economizer Controller for Tandem Compressors

Instruction Manual CTC-1

MXM-50. Modbus Interface for Mitsubishi Air-Conditioning. Installation and User Guide.

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Dip Switch settings.

Temperature controller Multi-zone ducted systems

OP10. Pre-programmed, configurable controller for simple applications

SPI Lasers UK Limited. Serial Command Reference for the PRISM Laser Platform

BNI IOL Z036 BNI IOL Z037. Smart Light User s Guide

IntesisBox DK-RC-MBS-1 v.0.2

Heatronic Introduction. BAS Integration Manual. Table of Contents

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

WavePRO Wireless Programmable T2500 Thermostat & R2500 Receiver OPERATING MANUAL. Model K

Digital Lighting Systems, Inc.

The PanasonicVRF Driver

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

BACnet MS/TP Interface User s Guide

Transcription:

W8735A1013 EnviraCOM Serial Adapter INSTALLATION INSTRUCTIONS TABLE OF CONTENTS INSTALLATION... 2 When installing this product... 2 Selecting Location... 2 Mounting W8735A1013 EnviraCOM Serial Adapter... 2 Wiring... 2 LED Description... 4 Glossary of Terms... 4 EnviraCOM Bus... 4 Message Format... 4 Message Checksum... 5 SELECTED MESSAGE CLASSES... 6 Node Identification 1 (10E0)... 6 Node Identification 2 (10E1)... 6 Device Status (3E70)... 7 DHW Cylinder Temperature (1260)... 7 DHW Cylinder Setpoint (10A0)... 7 DHW Setpoint Range (10A1)... 8 DHW Demand (30D0)... 8 Boiler Temperature (3200)... 8 Desired Boiler Setpoint (22D9)... 9 Central Heat Setpoint (22DB)... 9 Supply High Limit (1081)... 9 Heat/Cool Demand (3110)... 10 Boiler Heat/Cool Demand (3114)... 10 Displayed Temperature (12C0)...11 Outdoor Temperature (1290)...11 Outdoor Humidity (1280)...11 Alarm (3120)... 12 APPLICATION The W8735A1013 EnviraCOM Serial Adapter provides a host computer, gateway, or controller, with an RS-232 port, local access to an EnviraCOM HVAC System. The host provides the application to control the W8735A1013. The W8735A1013 EnviraCOM Serial Adapter is powered through the EnviraCOM connection and is optically isolated for universal compatibility. The W8735A1013 uses the EnviraCOM Table 1. W8735A1013 Description Model Application Terminals Comment W8735A1013 Local control of Envira- COM HVAC system using host computer, gateway or controller with RS- 232 serial port. Host provides application. 1, 2, 3 EnviraCOM DB9 RS-232 W8735A1013 used with host. Host provides application software and user interface. As an application software any terminal tool like Microsoft HyperTerminal can be used during initial evaluation. W8735A1013 provides means to move data from EnviraCOM Bus to RS-232 port. 69-2644-01

INSTALLATION When installing this product 1. Read these instructions carefully. Failure to follow these instructions can damage the product or cause a hazardous condition 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application. 3. Installer must be a trained, experienced service technician. 4. After completing installation, use these instructions to check out the product operation. CAUTION Electrical Hazard. Can cause electrical shock or equipment damage. Disconnect power before beginning installation. Selecting Location Locate the W8735A1013 near the host or near the HVAC system, as determined most suitable for the application. Wiring CAUTION Electrical Hazard. Equipment Mounting Damage Hazard. Mounting W8735A1013 inside HVAC can damage equipment. Mount W8735A1013 outside HVAC equipment. 1. Refer to Fig. 1 for wiring diagram. 2. Loosen terminal screws on W8735A1013 and connect system wires. See Fig. 2. 3. Securely tighten each terminal screw. 4. Connect serial cable to W8735A1013 DB9 RS-232 connector to the host RS-232 connector (see host installation instructions for details), using a serial cable (not provided with W8735A1013). NOTE: Maximum distance between W8735A1013 DB9 RS- 232 connector and the host RS-232 connector is 25 feet. 5. Restore power to HVAC systems and host. DB9 CONNECTOR Mounting W8735A1013 EnviraCOM Serial Adapter RS 232 CAUTION Electrical Hazard. Equipment Mounting Damage Hazard. Mounting W8735A1013 inside HVAC can damage equipment. Mount W8735A1013 outside HVAC equipment. Mounting the W8735A1013 is optional. When mounting is desired, use the sheet of two-sided adhesive tape (provided). 1 2 3 ENVIRACOM TM COMMUNICATION LED 1. Ensure the device is clean and dry and free of any oil or dirt. 2. Peel the protective lining from one side of the tape and press it to the back of the W8735A1013. 3. Remove the protective lining from the second surface of the tape and press the W8735A1013 to the mounting surface at the desired mounting location. ENVIRACOM TM NETWORK TERMINALS Fig. 1. Wiring W8735A1013 M20546 69-2644 01 2

SPARK IGNITER FLAME SENSE CIRCULATOR L1 L2 GND W8735A1013 TO BAS GND RS 232 INDUCER 24 VAC TRANSFORMER DAMPER ENVIRACOM DIAGNOSTIC 1 2 3 3 2 1 PRESSURE SWITCH LIMIT SWITCH MV PV PV/ MV GAS CONTROL SENSOR 1 SENSOR 2 M32685 Fig. 2. Connecting the W8735A1013 to an S936X EnviraCOM enabled Integrated Water Heater Control Table 2. Terminal Designations W8735A1013 Terminal Designations Function 1 To EnviraCOM network terminal 1 (data). 2 To EnviraCOM network terminal 2 (24 Vac). 3 To EnviraCOM network terminal 3 (24 Vac). Serial Connect W8735A1013 DB9 connector to host RS-232 serial port using serial cable (not provided with W8735A1013). 3 69-2644 01

Host Port Configuration The configuration of the host: Baud rate: 19200 bps. Parity: none. Data bits: 8. Stop bits: 1. Flow control: none. LED Description The green Light Emitting Diode (LED) on the front of W8735A1013 is used to show EnviraCOM Bus activity as follows: LED blinks rapidly LED blinks once Device is currently transmitting information on communications bus. Device received and acknowledged a message. Host Supports the application software. Devices such as a computer, gateway, controller are examples of a host. HVAC Heating, Ventilation and Air Conditioning. EnviraCOM Bus Communication over the EnviraCOM bus is managed by transmitting messages, one by one. There are three roles of EnviraCOM messages: Query, Report and Change Request. Query messages are used to retrieve information from devices. Devices respond to query messages by sending Report messages of the same message class. A Change Request message is used to request a change in settings of a device. Devices respond to Change Request messages with Report messages of the same message class to confirm the final settings. LED on constantly LED off constantly Device failure. Replace device. Wiring problem if device is not functioning correctly and there is no LED activity at least once a minute. Check wiring to communications bus terminals 1, 2 and 3. Message Format Messages sent or received from the W8735A1013 EnviraCOM Serial Adapter are coded in ASCII format (case sensitive) as follows with individual parts delimited by space characters (20 hex). All numbers are in hexadecimal format. The default message priority is medium. NOTE: Message Class along with Message Instance Number defines type of message. LED blinks continuously It is normal for LED to blink continuously during startup and discovery. Wiring problem if device is not functioning correctly and there is a continuous series of LED blinks. Check wiring to communications bus terminals 1, 2 and 3. Glossary of Terms RS-232 Long-established standard that describes the physical interface and protocol for relatively low-speed serial data communication between computers and related devices. Originally defined by industry trade group, the Electronic Industries Association (EIA), for teletype devices. MESSAGE PRIORITY H = HIGH M = MEDIUM L = LOW MESSAGE INSTANCE NUMBER DATA LENGTH (IN BYTES) CHECKSUM M 0418 00 Q 02 FF FF 5E MESSAGE CLASS DATA MESSAGE SERVICE Q = QUERY R = REPORT C = CHANGE REQUEST Fig. 3. Message format guide. In addition to EnviraCOM messages, the W8735A1013 sends status messages to the host application. Serial Only one event occurring at a time, contrasted with parallel, which means more than one event happening at a time. DB9 Standard 9-pin connector. DB9 used on W8735A1013 is a female configuration. EnviraCOM Three-wire communications protocol used in HVAC products. 69-2644 01 4

Message [Reset - Vxx.xx] [Idle] [Ack] [Nak] [Sent] Table 3. Status Messages. Description Sent during power-up where Vxx.xx denotes the version of adapter firmware, e.g. V01.11. Sent when EnviraCOM bus idle state is detected. Sent when received message contained a valid checksum and message has been queued for transmission to EnviraCOM bus. Sent when received message contained an invalid checksum. Sent when queued message has been successfully transmitted to EnviraCOM bus. NOTE: The host application will not send any new message before the previous one is transmitted to the EnviraCOM bus (i.e. prior receiving [Sent] status message). Each message sent to W8735A1013 EnviraCOM Serial Adapter is terminated with Carriage Return character (0D hex) and optionally followed by Line Feed character (0A hex). Each message received from W8735A1013 EnviraCOM Serial Adapter is terminated with following sequence of characters: Carriage Return (0D hex) + Line Feed (0A hex) + > (3E hex) Message Checksum Checksum is used as indicator of failure free communication between host application and W8735A1013 EnviraCOM Serial Adapter. Host application should check the checksum of received messages and only process messages with a correct checksum. W8735A1013 EnviraCOM Serial Adapter checks the checksum of messages received from the host application and sends the received messages to Envira- COM bus only if no corruption is detected. Checksum can be computed using Exclusive OR operation over all bytes of a message. Example: Received message: M 10E0 01 R 08 00 00 CE 45 D0 41 08 40 AB Message priority and service is converted to hexadecimal number based on Table 4 and 5. L Low M Medium H High Priority Service Q Report Query R Report C Change Request Table 4. Message Priority. 0(hex) 40(hex) 80(hex) Table 5. Service Priority. 0(hex) 40(hex) 80(hex) Value Value Checksum is computed as: 40 10 E0 01 40 08 00 00 CE 45 D0 41 08 40 = AB 5 69-2644 01

SELECTED MESSAGE CLASSES The following sections describe usage of most common message classes. Note that devices do not need to support all of the messages and sending of such messages will neither have an effect nor response will be received. WARNING Usage beyond provided examples is not supported by Honeywell. NOTE: Messages can be shorter than those shown in the following examples (truncated from the right). The callouts show samples of what bytes of information may be available to a device. Not all devices can transmitt all information. Node Identification 1 (10E0) Message is used to identify devices connected to EnviraCOM bus. Whenever any device sends a Query message to EnviraCOM bus, Report message from each connected device is transmitted over the EnviraCOM bus. Report message contains encoded OS Number. There are two formats of OS Number. Fig. 4 shows both formats as a response of two devices to Query message. OS NUMBER (NEW FORMAT): 1 CHARACTER = 1 BYTE DECODED OS NUMBER: S9360B1015C M 10E0 00 Q 00 B0 M 10E0 00 R 13 00 00 00 00 00 00 00 00 53 39 33 36 30 42 31 30 31 35 43 B8 11TH CHARACTER: 43(HEX) = C 10TH CHARACTER: 35(HEX) = 5 1ST CHARACTER: 53(HEX) = S M 10E0 01 R 08 00 00 CE 45 D0 41 08 40 AB OS NUMBER (LEGACY FORMAT): 1 CHARACTER = 6 BITS + 32 DECODED OS NUMBER: SD7000A 1ST CHARACTER = 1ST 6 BITS: 51 + 32 = 83 = S 2ND CHARACTER = 2ND 6 BITS: 36 + 32 = 68 = D 7TH CHARACTER = 7TH 6 BITS: 9 + 32 = 41 = A 8TH CHARACTER = 8TH 6 BITS: 0 + 32 = 32 = SPACE Fig. 4. Node Identification 1 (10E0). Optionally, devices can send Node Identification 2 and 3 reports right after their Node Identification 1 report, containing additional identification information. Node Identification 2 (10E1) Fig. 5 shows an example of report following Node Identification 1 report. M 10E1 00 R 09 33 41 01 28 00 00 6B 89 3A 7B FUNCTIONAL UNIT ID: ID OF THE FUNCTIONAL UNIT THAT BEST DESCRIBES THE DEVICE 33(HEX) = 51 = DOMESTIC HOT WATER (DHW) CONTROLLER 3A(HEX) = 58 = BOILER TEMPERATURE CONTROLLER MINOR SW REVISION NUMBER: 28(HEX) = 40 MAJOR SW REVISION NUMBER: 01(HEX) = 1 Fig. 5. Node Identification 2 (10E1). 69-2644 01 6

Device Status (3E70) Message is used to identify existence of control device in a system and its current state. Fig. 6 and 7 show responses to a Device Status query. M 3E70 00 Q 00 0E INSTANCE: 00(HEX) = ALL DEVICES 00(HEX) APPLIES TO ALL DEVICES THAT LISTEN TO THE MESSAGE CLASS 10(HEX) FAN CONTROLLER 11(HEX) GAS HEAT 42(HEX) COMPRESSOR COOLING F0(HEX) WATER HEATER M 3E70 F0 R 08 00 04 01 00 00 00 00 00 B3 FLAME CURRENT [na]: 0000(HEX) = 0nA CURRENT SEQUENCE STATE OF THE DEVICE: 01(HEX) = IDLE 00(HEX) = 0 = NOT USED THIS VALUE SHOULD BE USED BY ALL EQUIPMENT EXCEPT GAS VALVES. 01(HEX) = 1 = IDLE WAITING FOR A HEAT REQUEST 02(HEX) = 2 = WAIT PSW OPEN WAITING FOR PRESSURE SWITCH TO OPEN 03(HEX) = 3 = WAIT PSW CLOSE WAITING FOR PRESSURE SWITCH TO CLOSE 04(HEX) = 4 = PREPURGE FLUSHING COMBUSTION CHAMBER 05(HEX) = 5 = HIS WARMUP PREHEATING HOT SURFACE IGNITER 06(HEX) = 6 = IGN ACTV IGNITION ACTIVATION - START FUEL FLOW 07(HEX) = 7 = PROVE FLAME CHECKING FOR FLAME TO BE PRESENT WITHOUT IGNITION SOURCE 08(HEX) = 8 = RUNNING 09(HEX) = 9 = POSTPURGE FLUSHING COMBUSTION PRODUCTS FROM COMBUSTION CHAMBER 0A(HEX) = 10 = INTERPURGE SIMILAR TO POSTPURGE EXCEPT WILL RECYCLE BACK TO TRY ANOTHER IGNITION 0B(HEX) = 11 = PSW FAIL CLOSE PRESSURE SWITCH HAS FAILED IN THE CLOSED CONDITION 0C(HEX) = 12 = PSW FAIL OPEN PRESSURE SWITCH HAS FAILED IN THE OPEN CONDITION 0D(HEX) = 13 = SOFTLOCKOUT FAILURE DETECTED BUT WILL RETRY AFTER A LOCKOUT PERIOD 0E(HEX) = 14 = HARDLOCKOUT FAILURE DETECTED AND WILL NOT RETRY UNTIL A MANUAL RESET 0F(HEX) = 15 = LIMIT OPEN LIMIT SWITCH IS IN AN OPEN CONDITION 10(HEX) = 16 = FLAME OUT OF SEQ THE FLAME HAS BEEN DETECTED OUT OF SEQUENCE 11(HEX) = 17 = SELF TEST THE DEVICE IS IN A SELF TEST MODE 12(HEX) = 18 = WAIT VENT OPEN WAITING FOR VENT DAMPER TO OPEN (END SWITCH TO CLOSE) 13(HEX) = 19 = WAIT VENT CLOSE WAITING FOR VENT DAMPER TO CLOSE (END SWITCH TO OPEN) 14(HEX) = 20 = VENT FAIL CLOSE THE VENT DAMPER HAS FAILED IN THE CLOSED CONDITION (END SWITCH IS OPEN) 15(HEX) = 21 = VENT FAIL OPEN THE VENT DAMPER HAS FAILED IN THE OPEN CONDITION (END SWITCH IS CLOSED) CURRENT INSTANTANEOUS STATE OF THE DEVICE: 00(HEX) = OFF 00(HEX) = 0 = OFF C8(HEX) = 200 = FULL ON Fig. 6. Device Status (3E70). M 3E70 F0 R 08 C8 04 08 00 00 00 1B 30 59 FLAME CURRENT [na]: 1B30(HEX) = 6960nA CURRENT SEQUENCE STATE OF THE DEVICE: 08(HEX) = RUNNING CURRENT INSTANTANEOUS STATE OF THE DEVICE: C8(HEX) = FULL ON Fig. 7. Device Status (3E70). DHW Cylinder Temperature (1260) Message is used to retrieve the water temperature. Fig. 8 shows a response to a DHW Cylinder Temperature query. M 1260 F0 Q 00 C2 INSTANCE: F0(HEX) = WATER HEATER M 1260 F0 R 06 13 06 12 5C 15 B8 72 TEMPERATURE AT THE BOTTOM OF THE TANK [0.01 C]: 15B8(HEX) = 55.60 C (132.08 F) TEMPERATURE AT THE TOP OF THE TANK [0.01 C]: 125C(HEX) = 47.00 C (116.60 F) TEMPERATURE [0.01 C]: 1306(HEX) = 48.70 C (119.66 F) Fig. 8. DHW Cylinder Temperature (1260). DHW Cylinder Setpoint (10A0) M 10A0 F0 Q 00 00 M 10A0 F0 R 05 17 70 00 01 18 3B DHW SETPOINT DIFFERENTIAL [0.01 C]: 0118(HEX) = 2.80 C (5.04 F) DHW SETPOINT [0.01 C]: 1770(HEX) = 60.00 C (140.00 F) Change of the temperature setpoint is shown in Fig. 10. Fig. 9. DHW Cylinder Setpoint (10A0). 7 69-2644 01

M 10A0 F0 C 02 19 64 FF M 10A0 F0 R 05 19 64 00 01 18 21 DHW SETPOINT [0.01 C]: 1964(HEX) = 65.00 C (149.00 F) Fig. 10. DHW Temperature Setpoint (10A0). WARNING Changing of the temperature setpoint may not work when other interacting devices are connected to EnviraCOM bus. Can cause severe injury, death or property damage. DHW Setpoint Range (10A1) Message is used to retrieve or change the range of values allowed for temperature setpoint and setpoint differential. Fig. 11 shows a response to a DHW Setpoint Range query. M 10A1 F0 Q 00 01 M 10A1 F0 R 08 1A B8 05 00 05 6E 02 30 56 MINIMUM SETPOINT DIFFERENTIAL [0.01 C]: 0230(HEX) = 5.60 C (10.08 F) MAXIMUM SETPOINT DIFFERENTIAL [0.01 C]: 056E(HEX) = 13.90 C (25.02 F) MINIMUM SETPOINT [0.01 C]: 0500(HEX) = 12.80 C (55.04 F) MAXIMUM SETPOINT [0.01 C]: 1AB8(HEX) = 68.40 C (155.12 F) Fig. 11. DHW Setpoint Range (10A1). DHW Demand (30D0) Message is used to retrieve a demand for the domestic hot water equipment. Fig. 12 shows responses to a DHW Demand query message. M 30D0 F0 Q 00 50 DHW FORCED OFF. M 30D0 F0 R 02 FC 10 FE STATUS SUM OF FOLLOWING ITEMS: EQUIPMENT TYPE: 00(HEX) = ELECTRIC HEATING, 10(HEX) = GAS OR OIL HEATING ON/OFF: 00(HEX) = OFF, 01(HEX) = ON DEMAND: FC(HEX) = 252 = FORCE CHECK ON/OFF FIELD DHW DEMANDED TO RUN AT 100%. M 30D0 F0 R 02 C8 11 CB DEMAND: C8(HEX) = 200 = 100% DHW DEMANDED TO RUN AT 0%. M 30D0 F0 R 02 00 10 02 DEMAND: 00(HEX) = 0 = 0% Fig. 12. DHW Demand (30D0) Boiler Temperature (3200) Message is used to retrieve the temperature of water supplied by the boiler. Fig. 13 shows a response to a Boiler Temperature query. M 3200 3D Q 00 4F M 3200 3D R 04 18 6A 16 44 2B INSTANCE: 3D (HEX) = BOILER RETURN TEMPERATURE TO THE BOILER [0.01 C]: 1644(HEX) = 57.00 C (134.60 F) BOILER WATER TEMPERATURE [0.01 C]: 186A(HEX) = 62.50 C (144.50 F) Fig. 13. Boiler Temperature (3200) 69-2644 01 8

Desired Boiler Setpoint (22D9) Message is used to retrieve a desired setpoint of the boiler. Fig. 14 shows a response to a Desired Boiler Setpoint query. M 22D9 3D Q 00 86 M 22D9 3D R 02 19 64 B9 DESIRED BOILER SETPOINT [0.01 C]: 1964(HEX) = 65.00 C (149.00 F) Fig. 14. Desired Boiler Setpoint (22D9) Central Heat Setpoint (22DB) Message is used to retrieve or change the boiler setpoint for the central heating function of a boiler. Fig. 15 shows a response to a Central Heat Setpoint query. M 22DB 3D Q 00 84 M 22DB 3D R 04 13 1A 02 30 FB SETPOINT DIFFERENTIAL [0.01 C]: 0230(HEX) = 5.60 C (10.08 F) BOILER SETPOINT [0.01 C]: 131A(HEX) = 48.90 C (120.02 F) Fig. 15. Central Heat Setpoint (22DB) Fig. 16 shows a response to a Central Heat Setpoint change request. M 22DB 3D C 02 19 64 7B M 22DB 3D R 04 19 64 02 30 8F BOILER SETPOINT [0.01 C]: 1964(HEX) = 65.00 C (149.00 F) Fig. 16. Central Heat Setpoint (22DB) WARNING Changing of the boiler setpoint may not work when other interacting devices are connected to EnviraCOM bus. Supply High Limit (1081) Message is used to retrieve the supply high limit temperature setpoint, differential and the state of the limit. Fig. 17 shows a response to a Supply High Limit query. M 1081 3D Q 00 EC M 1081 3D R 05 20 1C 03 3E OO AB STATUS: 00(HEX) = NO HIGH LIMIT CONDITION, 01(HEX) = HIGH LIMIT CONDITION IS ACTIVE HIGH LIMIT DIFFERENTIAL [0.01 C]: 033E(HEX) = 8.30 C (14.94 F) SUPPLY HIGH LIMIT SETPOINT [0.01 C]: 201C(HEX) = 82.20 C (179.96 F) Fig. 17. Supply High Limit (1081) 9 69-2644 01

Heat/Cool Demand (3110) Message is used to retrieve a demand for the emergency heat, heating equipment. Fig. 18 shows responses to a Heat/Cool Demand query. M 3110 00 Q 00 61 EQUIPMENT (ONE STAGE) FORCED OFF: M 3110 00 R 04 01 FC 10 10 D8 SYSTEM STAGE1 SUM OF FOLLOWING ITEMS: EQUIPMENT TYPE: 10(HEX) = NATURAL GAS OR OIL HEATING IF MODE = 10(HEX) OR 30(HEX) STAGE1 ON/OFF: 00(HEX) = OFF, 01(HEX) = ON QUALIFICATION SUM OF FOLLOWING ITEMS: MODE: 10(HEX) = HEATING, 30(HEX) = EMERGENCY HEATING ON/OFF: 00(HEX) = ALL OF THE STAGES ARE OFF, 01(HEX) = AT LEAST ONE STAGE IS ON DEMAND: FC(HEX) = 252 = FORCE CHECK STAGE1 ON/OFF FIELD EQUIPMENT (ONE STAGE) DEMANDED TO RUN AT 100%: M 3110 00 R 04 01 C8 11 11 EC DEMAND: C8(HEX) = 200 = 100% EQUIPMENT (ONE STAGE) DEMANDED TO RUN AT 0%: M 3110 00 R 04 01 00 10 10 24 DEMAND: 00(HEX) = 0 = 0% Fig. 18. Heat/Cool Demand (3110) Boiler Heat/Cool Demand (3114) Message is used to retrieve a demand for the boiler. Fig. 19 shows responses to a Boiler Heat/Cool Demand query. M 3114 3D Q 00 58 INSTANCE: 3D(HEX) = BOILER BOILER (ONE STAGE) FORCED OFF: M 3114 3D R 04 01 FC 10 10 E1 SYSTEM STAGE1 SUM OF FOLLOWING ITEMS: EQUIPMENT TYPE: 10(HEX) = NATURAL GAS OR OIL HEATING IF MODE = 10(HEX) OR 30(HEX) STAGE1 ON/OFF: 00(HEX) = OFF, 01(HEX) = ON QUALIFICATION SUM OF FOLLOWING ITEMS: MODE: 10(HEX) = HEATING, 30(HEX) = EMERGENCY HEATING ON/OFF: 00(HEX) = ALL OF THE STAGES ARE OFF, 01(HEX) = AT LEAST ONE STAGE IS ON DEMAND: FC(HEX) = 252 = FORCE CHECK STAGE1 ON/OFF FIELD BOILER (ONE STAGE) DEMANDED TO RUN AT 100%: M 3114 3D R 04 01 C8 11 11 D5 DEMAND: C8(HEX) = 200 = 100% BOILER (ONE STAGE) DEMANDED TO RUN AT 0%: M 3114 3D R 04 01 00 10 10 1D DEMAND: 00(HEX) = 0 = 0% Fig. 19. Boiler Heat/Cool Demand (3114) 69-2644 01 10

Displayed Temperature (12C0) Message is used to retrieve a displayed ambient temperature. Fig. 20 shows responses to a Displayed Temperature query. M 12C0 00 Q 00 92 TEMPERATURE DISPLAYED IN DEGREES FAHRENHEIT: M 12C0 00 R 03 4D 00 FF 63 UNITS: 00(HEX) = F, 01(HEX) = 0.5 C DISPLAYED AMBIENT TEMPERATURE [ F]: 4D(HEX) = 77 F (25 C) TEMPERATURE DISPLAYED IN DEGREES CELSIUS: M 12C0 00 R 03 31 01 FF 1E DISPLAYED AMBIENT TEMPERATURE [0.5 C]: 31(HEX) = 24.5 C (76.1 F) Fig. 20. Displayed Temperature (12C0) Outdoor Temperature (1290) Message is used to retrieve an outdoor temperature. Fig. 21 shows a response to an Outdoor Temperature query. M 1290 00 Q 00 C2 M 1290 00 R 02 FB A0 DB OUTDOOR TEMPERATURE [0.01 C]: FBA0(HEX) = -11.20 C (11.84 F) Fig. 21. Outdoor Temperature (1290) Outdoor Humidity (1280) Message is used to retrieve an outdoor humidity. Fig. 22 shows a response to an Outdoor Humidity query. M 1280 00 Q 00 D2 M 1280 00 R 06 2C 0A 0A 7F FF 00 38 OUTDOOR DEW POINT TEMPERATURE [0.01 C]: OUTDOOR TEMPERATURE [0.01 C]: 0A0A(HEX) = 25.70 C (78.26 F) OUTDOOR HUMIDITY IN PERCENT RELATIVE HUMIDITY [%RH]: 2C(HEX) = 44%RH Fig. 22. Outdoor Humidity (1280) 11 69-2644 01

W8735A1013 EnviraCOM Serial Adapter Alarm (3120) Message is used to retrieve states of alarms. Fig. 23 shows responses to an Alarm query. M 3120 00 Q 00 51 NO ALARM REPORTED: M 3120 00 R 04 70 00 00 00 65 ALARM TYPE: 0000(HEX) = NO ALARM THE DEVICE HAS NO ALARMS MATURED ALARM REPORTED: M 3120 00 R 08 F8 00 38 F0 33 00 00 00 1A INSTANCE: IDENTIFYING INSTANCE OF THE DEVICE F0(HEX) = WATER HEATER ALARM TYPE: 0000(HEX) = 0 = NO ALARM THE DEVICE HAS NO ALARMS 0002(HEX) = 2 = LPS OPEN PRESSURE SWITCH FAILED TO OPEN 0004(HEX) = 4 = FLAME CURRENT FLAME CURRENT CAUTION LEVEL WHILE RUNNING 0006(HEX) = 6 = SLO FLAME SEQ SOFT LOCKOUT FLAME SENSED OUT OF NORMAL SEQUENCE 0017(HEX) = 23 = FLAME IN PREPURGE FLAME SENSED DURING PREPURGE 0018(HEX) = 24 = FLAME IN POSTPURGE FLAME SENSED DURING POSTPURGE 001A(HEX) = 26 = HIGH LIMIT HIGH LIMIT SWITCH OPEN 001D(HEX) = 29 = LPS CLOSE PRESSURE SWITCH FAILED TO CLOSE 001F(HEX) = 31 = DHW UPPER THE DHW UPPER TEMPERATURE SENSOR IS OUT OF SPECIFICATION 0020(HEX) = 32 = DHW LOWER THE DHW LOWER TEMPERATURE SENSOR IS OUT OF SPECIFICATION 0037(HEX) = 55 = DAMPER SW CLOSE ATMOSPHERIC DAMPER END SWITCH FAILED TO CLOSE (STUCK OPEN) 0038(HEX) = 56 = DAMPER SW OPEN ATMOSPHERIC DAMPER END SWITCH FAILED TO OPEN (STUCK CLOSED) 0039(HEX) = 57 = ROD SHORT FLAME ROD SHORTED TO GROUND 003A(HEX) = 58 = ZERO CROSSING AC LINE FREQUENCY ERROR SIGNAL IS TOO NOISY OR FREQUENCY IS OUT OF RANGE 003B(HEX) = 59 = AC LINE AC LINE VOLTAGE TOO HIGH OR TOO LOW 003C(HEX) = 60 = STAT PHASE THERMOSTAT INPUT PHASE WRONG 003D(HEX) = 61 = POWER SUPPLY POWER SUPPLY OUTPUT UNSTABLE 003E(HEX) = 62 = SLO RETRY SOFT LOCKOUT MAXIMUM NUMBER OF RETRIES EXCEEDED 003F(HEX) = 63 = SLO RECYCLE SOFT LOCKOUT MAXIMUM NUMBER OF RECYCLES EXCEEDED 0040(HEX) = 64 = SLO ELECTRONICS SOFT LOCKOUT ELECTRONICS FAILURE 0041(HEX) = 65 = WATER HIGH TEMP OVER TEMPERATURE ERROR. SENSORS MEASURED TEMPERATURE IN EXCESS OF ECO LIMIT FAULT STATE, 7TH BIT: 1 ON, 0 OFF F8(HEX) AND 80(HEX) = 80(HEX) ALARM IS ON CLEARED ALARM REPORTED: M 3120 00 R 08 78 00 37 F0 33 00 00 00 95 ALARM TYPE: 0037(HEX) = 55 = DAMPER SW CLOSE DAMPER END SWITCH FAILED TO CLOSE (STUCK OPEN) FAULT STATE, 7TH BIT: 78(HEX) AND 80(HEX) = 00(HEX) ALARM IS OFF Fig. 23. Alarm (3120) Automation and Control Solutions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com U.S. Registered Trademark 2011 Honeywell International Inc. 69-2644 01 M.S. 06-11 Printed in U.S.A.