Operating and installation instructions Differential pressure monitor

Similar documents
USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

SD1. Differential Controller. Operating and Installation Instructions F2 72.3

Manual Control Unit GFCD 16

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

Description TR D

Operating instructions. Speed monitor D / / 2014

User Manual. Item no.: Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel.: +49(0) Kunststofferzeugnisse D Teningen Fax: +49(0)

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

Compact universal controllers

Operating Manual Bedienungsanleitung. Digital Dispense Controller

Manual Control Unit GFC 32

I/O module (Expansion module)

Operating instructions Pressure sensor. PN50xx / / 2010

PSR DC/ESP4/2X1/1X2

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions

RТTH DUAL ROOM SWITCH

RS Stock No Instruction Manual RS Input Data Logging Thermometer

CDD4 Duct Carbon Dioxide Transmitter

Demonstration Case BENNING DB 1

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 120 W -... T-Logg 120 K -...

Product Information. DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design)

Operating instructions Electronic digital pressure sensor EPS25-XXXX-1001

KOBOLD PDA Series Digital Pressure Transmitter

INSTALLATION INSTRUCTIONS 07/2018

Valid for item nos.: (1-zone) (2-zone) (4-zone) (6-zone) HPS-C-Slot Hotrunner controllers Operating manual

Operating instructions Electronic pressure sensor PN7xxx

Operating instructions. Switching amplifier DN0210 DN / / 2015

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Operating instructions. Standstill monitor A / / 2011

Operating instructions Electronic pressure sensor. PN72xx PN73xx PN76xx / / 2016

Manual Simatek Control Unit GFC 32

CMC III Universal Sensor

RXTH DUAL ROOM SENSOR / SWITCH

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

M A C 3 Wind Speed Alarm & Controller

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

Operating instructions Optical distance sensor O1D / / 2012

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

KOBOLD Compact Electronics

PSR UC/ESAM4/3X1/1X2/B

Installation manual plugs and connectors with screw connection (16/32 A)

Operating instructions Programming and display unit PP / / 2010

Operating instructions Pressure sensor. PE30xx / / 2010

Supplementary operating instructions for your air curtain system Controller TMC 500

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

is then retained absolutely without interruption.

Operating instructions Pressure sensor. PN70xx / / 2012

OPERATING INSTRUCTION

Zone Pressure Touch Sensor - Standard Range

DS 96/48 PK. Digital indicator. Manual 42/33-90 EN Rev. 00 DIM

KOBOLD TDA Series Digital Temperature Transmitter

MINI MCR-SL-UI-REL(-SP)

2-Axis Counter BDD 622

Operating Instructions for Differential Pressure Sensor. Model: PMP

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Operating instructions Pressure sensor. PN70xx / / 2010

ES 4000 STANDARD. 1 General information Document Overview General description Introduction... 4

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

Operating Instructions for Digital Thermometers. Model: DTM

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

ETD-BL-1T-OFF-CC- 10S

Operating Instructions Differential Pressure Transducer PS27

Operating instructions AC010S Compact AS-i E-STOP safety module

Installation and Setting up Instructions for the Type 920 Auto Sequencer

Intrinsically safe batch controller Batching Master 110i

M2 OLED Temperature Monitor Instructions PN 1841

MAC3 Wind Speed Alarm & Controller. Installation Instructions

MINI MCR-SL-PT100-UI(-SP)(-NC)

Zone Pressure Touch (ZPT) Sensor - Standard Range

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

NETRONICS HS3500 CONTROLLER

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Electrical Actuators

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

Operating Instructions. For. Level Control Module. Model SSR 1000

Electrical devices may only be mounted and connected by electrically skilled persons.

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

DRUCK & TEMPERATUR LEITENBERGER GMBH

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Electrical Actuators

Operating Manual -ENGLISH- Page 1 KWG-ISO

Autoranging True RMS Multimeter User Manual

LCI User Manual mantracourt.com

Immersion Temperature Sensors

Type Quickstart

SP6R Level Controller Operation Manual

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812

Product and functional description

TSE. Functional Description. Order Code TSE HA /2010. Electrical Pressure Switch N D. p max up to 400 bar (5801 PSI)

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 100. T-Logg 100 E

Manometers 2PSI, 5PSI, 15PSI, 30PSI, 100PSI , , ,

Model No Universal Input Indicator Start-up Guide

Pressure-Converter UNICON -P Differential pressure - diminished pressure - overpressure - barometric pressure - flow rate Features

Portable low-pressure controller Model CPC2000

Transcription:

Operating and installation instructions Differential pressure monitor RM-DPC Micro SensorLine

Table of contents 1 Safety instructions...3 2 Equipment specification...3 3 Assembly...4 4 Step-by-step installation...4 5 Step-by-step settings...6 5.1 Function in delivery status...6 5.2 Display and setting elements...6 5.3 Setting parameters...8 5.4 Parameter list...9 6 Details on device function...10 6.1 Two-position controller (Parameters 01, 02, 03, 04, 05)...10 6.2 Differential pressure monitor (Parameters 01, 04, 05)...11 6.3 Timer function (Parameters 06, 07, 08)...12 6.4 Self-monitoring...12 7 Troubleshooting...12 8 Text messages on the display...13 8.1 Operating messages...13 8.2 Additional information...13 8.3 Alarm messages...13 9 Glossary...14 10 Technical specifications...15 Regulations VDE 0160 EN 60.439 Part 500 EN 60.204 Part 1 EEC 89 / 336 Legend Important note Important warning RDN 10000257 2 02.09.2008

1 Safety instructions When connected to the mains, the RM-DPC Micro differential pressure monitor is live and poses an electrical hazard. Device failure, serious or even fatal injuries may occur as a result of improper installation of the connected equipment. In addition to the general safety regulations for equipment in industrial electrical installations therefore, pay particular attention to the following points: - The device may only be installed by qualified experts, in accordance with the provisions of IEC 364, DIN VDE 0105 for electrical equipment. - All applicable laws, conditions, rules and regulations governing the setting up of electrical equipment must be observed in respect of the installation site. - Equipment with protection rating IP00 without covers may only be configured by authorised expert staff when disconnected and whilst observing the local safety and accident prevention regulations. The RM-DPC Micro may only be operated in the permitted operating area. Switch off the mains supply before replacing the differential pressure monitor or any components connected to it. Otherwise the equipment may be damaged. 2 Equipment specification The devices in the SensorLine RM-DPC Micro series are differential pressure controllers designed for use in robust, industrial environments. They are used for measuring, visualising and controlling nonaggressive, gaseous media in the excess pressure and insufficient pressure ranges. All necessary functions can be configured and displayed simply using a text display with two-key menu control. In operating mode, the text display shows the differential pressure in variable physical sizes. The status messages ON / SERVICE / ALARM are also indicated by LEDs. In addition to the controller functions for differential pressure, the software can also be used to allocate a two-position controller (Δp controller), a differential pressure monitor and a time function. The full scale output for the measured differential pressure can be set by the parameter 12 "dp range". The anlog output signal is automatically adjusted to the set full scale output. RDN 10000257 3 02.09.2008

3 Assembly 4 Step-by-step installation Connecting the supply voltage RDN 10000257 4 02.09.2008

More connections With a voltage supply of 24 V DC, the 4-20 ma signal or the 0-20 ma signal (terminals 8, 9) is not isolated from the input voltage. An isolating amplifier is required to connect display devices or to process the signal. Signal cables may not be run parallel to power cables. Tighten all cable glands in use to ensure that the cables are properly enclosed and that protection rating IP-66 is guaranteed. Cable glands that are not in use must be closed or replaced with blank plugs. Connection for differential pressure measurement lines Use hoses with an internal diameter of 4 mm and an external diameter of 6 mm. Connect the connection marked with 3 stripes (black screw cap) to the crude gas side and the other connection (blue screw cap) to the clean gas side of the filter. RDN 10000257 5 02.09.2008

5 Step-by-step settings 5.1 Function in delivery status The functions of a differential pressure dependent two-position controller and a differential pressure monitor are active on delivery. Two-position controller: If the increasing differential pressure exceeds the Δp max switch point (factory setting: 900 Pa), relay contact 15, 16 closes and contact 14, 15 opens (see point on page 5). If the decreasing differential pressure falls below the Δp min switch point (factory setting: 700 Pa), relay contact 15, 16 opens and contact 14, 15 closes. Differential pressure monitoring: If the increasing differential pressure exceeds the Δp max alarm switch point (factory setting: 1800 Pa), relay contact 21, 22 closes and contact 20, 21 opens (see point on page 5). If the differential pressure falls below the Δp max alarm switch point, relay contact 21, 22 opens and contact 20, 21 closes. If another function is required or you want to activate additional functions, then you must change the parameter settings of the RM-DPC Micro. For more on this refer to points + "Configuration keys" on page 7 and section 5.3 "Setting parameters". 5.2 Display and setting elements "ON" LED The "ON" LED is lit if supply voltage is present. "Service" LED This LED flashes if the set number of service hours has elapsed. This LED goes out when the service hours counter is reset to 0 hrs. In order to do this, Parameter 10 "Maintenance acknowledge?" must be configured to "Yes". RDN 10000257 6 02.09.2008

"Alarm" LED This LED flashes if one of the following alarms is triggered: Δp min alarm Differential pressure has fallen below the set Δp min alarm switch point (in the case of the Δp control device function) or has exceeded it (in the case of the Δp monitor device function). Δp max alarm (the set Δp max alarm switch point has been exceeded) + Configuration keys Selecting a parameter: Press and hold for more than 3 seconds. Then press briefly to scroll up, or to scroll down, until you see the required parameter in the display. Setting the parameter value: Once you have selected a parameter, press and hold for more than 3 seconds. Then press briefly to scroll up, or to scroll down, until you see the required parameter in the display. Then press and hold for more than 3 seconds to save the configured value. Then, if necessary, press briefly to scroll up, or to scroll down, and select additional parameters to configure or check. Returning to "Operation" mode: Press briefly. The program automatically returns to "Operation" mode if no button is pressed in over one minute. Cancelling the parameter setting: Press briefly. Then press again briefly to return to "Operation" mode. RDN 10000257 7 02.09.2008

5.3 Setting parameters For more on this refer to points + "Configuration keys" on page 7 RDN 10000257 8 02.09.2008

5.4 Parameter list Parameter Text on the display Explanation Factory setting Setting range 01 01 Contr. type Device function dp-control. dp-control, dp-monitor 02 02 dp min Δp min switch point 700 Pa 150 Pa... (dp max - 50 Pa) 1 03 03 dp max Δp max switch point 900 Pa 200 Pa... (dp max alarm - 50 Pa) 2 04 04 dp min alarm Δp min alarm switch point 0 3 03, 100 Pa... (dp max alarm - 50 Pa) 2 05 05 dp max alarm Δp max alarm switch point 1800 Pa 0 3, 500... dp range 4 06 06 Timer start Timer for relay output 5 0 3 0 3... 240 h 07 07 Timer unit Time unit of the timer min s, min 08 08 Timer period Time period of the timer 10 s 0 3... 500 (s / min) 6 09 09 Service hrs. Service hours alarm 7 0 3 0 3, 500 hrs... 25,000 hrs 10 10 Maintenance acknowledge? Resets the service hours counter No No, yes 11 11 dp source Internal / External sensor Internal Internal, external 12 12 dp range Full scale output 5000 Pa 8 1000 Pa... 5000 Pa 8 or 10000 Pa 9 or 1000 Pa... 10000 Pa 9 13 13 Current range 4-20 ma / 0-20 ma 4-20 ma 4-20 ma, 0-20 ma 14 14 dp attenuat. Alarm / Control delay 2 s 1 s... 30 s 15 15 dp unit Unit of the displayed differential pressure Pa Pa, mbar, hpa, inch H 2 O 16 16 Default set. Loads factory setting No No, yes 17 17 Language Display text language DE DE, EN, FR, ES 1 Maximum value of the setting range = configured Δp max switch point (see Parameter 03 "dp max") minus 50 Pa. 2 Maximum value of the setting range = configured Δp max switch point (see Parameter 05 "dp max alarm") minus 50 Pa. 3 0 = Function deactivated. 4 Configured measuring range of the sensor (see Parameter 12 "dp range") 5 See point on page 5 6 Depends on the setting of Parameter 07 "Timer unit". 7 The service hours counter runs when the differential pressure Δp is greater than 200 Pa and the parameter 09 "Service hrs." has not been configured to 0. 8 Applies to the RM-DPC 5000 Micro the full scale output can be configured in 500 Pa increments. 9 Applies to the RM-DPC 10000 Micro the full scale output is configurable in 500 Pa increments for the range 1000 Pa... 5000 Pa, and continuously configurable for the range 5000 Pa... 10000 Pa. RDN 10000257 9 02.09.2008

6 Details on device function 6.1 Two-position controller (Parameters 01, 02, 03, 04, 05) In order to implement a differential pressure dependent two-point controller with the switch points Δp min and Δp max, Parameter 01 "Contr. type" must be configured to "dp control.". (For more on this refer to points + "Configuration keys" on page 7 and section 5.3 "Setting parameters".) If the increasing differential pressure exceeds the configured Δp max switch point (Parameter 03), relay contact 15, 16 closes and contact 14, 15 opens (see diagram below). If the decreasing differential pressure falls below the configured Δp min switch point (Parameter 02), relay contact 15, 16 opens and contact 14, 15 closes. It is also possible to configure a Δp max alarm switch point (Parameter 05) for rising differential pressure, and a Δp min alarm switch point (Parameter 04) for falling differential pressure. If the differential pressure exceeds the Δp max alarm switch point, relay contact 21, 22 closes and contact 20, 21 opens (see diagram below). If the differential pressure falls below the Δp min alarm switch point, relay contact 18, 19 closes and contact 17, 18 opens. The setting Δp min alarm switch point (Parameter 04) = 0 deactivates the differential pressure monitoring function Δp min alarm. The setting Δp max alarm switch point (Parameter 05) = 0 deactivates the differential pressure monitoring function Δp max alarm. RDN 10000257 10 02.09.2008

6.2 Differential pressure monitor (Parameters 01, 04, 05) In order to implement a differential pressure monitor with the switch points Δp min alarm (for a Δp prealarm) and Δp max alarm, Parameter 01 "Contr. type" must be configured to "dp monitor". (For more on this refer to points + "Configuration keys" on page 7 and section 5.3 "Setting parameters".) Δp pre-alarm: If the increasing differential pressure exceeds the configured Δp min alarm switch point (Parameter 04), relay contact 18, 19 closes and contact 17, 18 opens (see diagram below). If the differential pressure falls below the Δp min alarm switch point, relay contact 18, 19 opens and contact 17, 18 closes. Δp max alarm: If the increasing differential pressure exceeds the configured Δp max alarm switch point (Parameter 05), relay contact 21, 22 closes and contact 20, 21 opens (see diagram below). At the same time, relay contact 18, 19 opens and contact 17, 18 closes. If the differential pressure falls below the Δp max alarm switch point, relay contact 21, 22 opens and contact 20, 21 closes. The setting Δp min alarm switch point (Parameter 04) = 0 deactivates the differential pressure monitoring function Δp min alarm. The setting Δp max alarm switch point (Parameter 05) = 0 deactivates the differential pressure monitoring function Δp max alarm. RDN 10000257 11 02.09.2008

6.3 Timer function (Parameters 06, 07, 08) In addition to the differential pressure dependent two-position control, the timer function also makes it possible to carry out time-controlled forced cleaning. The timer works independently of other device functions. After the time configured under "Timer start" (Parameter 06) elapses, relay contact 15, 16 closes and contact 14, 15 opens (see point on page 5). After the time configured under "Timer period" (Parameter 08) elapses with the configured "Timer unit" (Parameter 07), relay contact 15, 16 opens and contact 14, 15 closes. 6.4 Self-monitoring If all relay outputs are inactive (contacts 15, 16 / 18, 19 / 21, 22 are closed), then the RM-DPC Micro differential pressure monitor is either switched off or defective. 7 Troubleshooting Error Possible causes Recommended action The "ON" LED is not lit. No mains voltage Check power feed Device fuse is defective Replace fuse EMERGENCY STOP activated Check EMERGENCY STOP No differential pressure display Differential pressure measurement hoses are incorrectly attached. Reattach the hoses to the connecting piece of the RM-DPC Micro. Differential pressure display error Hose connection error Drain hoses. Clean joints between hose connections and the filter casing with compressed air (only towards the filter, never towards the sensor). Fit the hoses so there are no kinks. Check the hose connections in the device for water, kinks, etc. "Alarm" LED flashing Δp alarm Refer to the service instructions of the filter. "Service" LED flashing The configured number of service hours has elapsed. Perform filter maintenance. Then configure Parameter 10 to "Yes" (acknowledge the service message). RDN 10000257 12 02.09.2008

8 Text messages on the display 8.1 Operating messages Display RM-DPC Micro Software #.## Contr. active dp #### [Pa] Monitor active dp #### [Pa] Explanation Appears after the power is switched on and remains for approx. 1 second. The RM-DPC Micro can start up and perform a self-test during this time. Display on device function "dp control." #### currently measured differential pressure Display on device function "dp monitor" #### currently measured differential pressure 8.2 Additional information You can open the following additional information by pressing or in "Operation" mode, as long as there are no active alarm messages. Display Operating hrs ##### [h] Time to service ##### [h] Time to timer #### [min] Explanation Display of elapsed operating hours (#####) for 3 seconds. After 3 seconds, the display returns to the operating messages. Number of hours to next maintenance (#####), if the service hours counter has been activated. After 3 seconds, the display returns to the operating messages. Number of minutes to timer function (####), if the timer has been activated. 8.3 Alarm messages Display Explanation dp dp dp min alarm #### [Pa] dp max alarm #### [Pa] The Δp min alarm switch point has been exceeded. #### currently measured differential pressure The Δp max alarm switch point has been exceeded. #### currently measured differential pressure The Δp max alarm has priority over the Δp min alarm. The Δp max alarm and the Δp min alarm messages are not saved. They are automatically deleted when the differential pressure falls below the relevant switch points. RDN 10000257 13 02.09.2008

9 Glossary Term Bulkhead connectors Configuration Explanation Connections for attaching the differential pressure measurement hoses. Parameter settings Differential pressure monitor Device function that monitors two configurable Δp switch points. Differential pressure p Forced cleaning Difference between the pressure on the clean gas side and the pressure on the crude gas side of the filter. Forced cleaning cycle, independant of the current status of the control sequence. Service hours The filter maintenance interval in hours configured under Parameter 09 "Service hrs." Service hours counter Time function Timer Two-key menu control Two-position controller Δp controller Δp max alarm switch point Δp max switch point (also abbreviated as Δp max) Δp min alarm switch point Δp min switch point (also abbreviated as Δp min) Δp remote display Internal hour counter that must be reset to 0 hrs after each filter service (see Parameter 10) Relay contact 14, 15, 16 switches after the configured time elapses for the configured period of time. See time function The menu for parameter configuration can be operated with the two keys and. Controller with two switch points (here: Δp max and Δp min) Device function for implementing differential pressure dependent cleaning Differential pressure value, which when exceeded causes the message "dp max alarm" to appear and relay contact 20, 21, 22 to switch. Upper switch point of the two-position controller, which when reached causes relay contact 14, 15, 16 to switch thus starting differential pressure dependent cleaning. In the case of device function Δp controller: Differential pressure value, which when decreasing (falling differential pressure) causes the message "dp min alarm" to appear and relay contact 17, 18, 19 to switch. In the case of device function Δp monitor: Differential pressure value, which when exceeded (rising differential pressure) causes the message "dp min alarm" to appear and relay contact 17, 18, 19 to switch. Lower switch point of the two-position controller, which when reached causes relay contact 14, 15, 16 to switch thus stopping differential pressure dependent cleaning. Display that shows the differential pressure of the filter in a switch room. RDN 10000257 14 02.09.2008

10 Technical specifications RM-DPC 5000 Micro RM-DPC 10000 Micro ΔP measuring range Full scale output (FSO) Measuring sensor Accuracy (linearity and hysteresis) Full scale output configurable from 1000 Pa... 5000 Pa in 500 Pa increments For the range 1000 Pa... 5000 Pa the full scale output is configurable in 500 Pa increments For the range 5000 Pa... 10000 Pa the full scale output is continuously configurable. 5000 Pa 10000 Pa Piezoresistive, overpressure-proof up to 138 kpa ± 1 % FSO Supply voltages 230 V AC + / -10% 110 V... 120 V AC + / -10% 24 V DC +10% / -0% Signal input 4-20 ma to connect an external differential pressure sensor Signal outputs Relay outputs (change-over contact), potential-free max. contact load: 250 V AC, 10 A 50 V DC, 1,5 A / 30 V DC, 10 A (ohmic load) Output 4-20 ma / 0-20 ma 4-20 ma corresponding to 0... x Pa*; resistance 600 Ohm 0-20 ma corresponding to 0... x Pa*; resistance 600 Ohm The 4-20-mA signal or the 0-20-mA signal must be unearthed! With a voltage supply of 24 V DC, the signal is not isolated from the input voltage. An isolating amplifier is required to connect display devices or to process the signal. Output 2-10 V / 0-10 V 2-10 V corresponding to 0... x Pa* 0-10 V corresponding to 0... x Pa* The 2-10 V signal or the 0-10 V signal must be unearthed! With a voltage supply of 24 V DC, the signal is not isolated from the input voltage. An isolating amplifier is required to connect display devices or to process the signal. Fuses F1 T 0,4 A, 250 V, 5 x 20 mm F2 T 1 A, 250 V, 5 x 20 mm Temperature range - 20 C to + 60 C Protection rating Casing IP-66 / NEMA 4 Dimensions See section 3 "Assembly" Weight approx. 0.8 kg Installation height max. 3000 m above M.S.L. * set full scale output RDN 10000257 15 02.09.2008