SC100 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Similar documents
INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

Wireless Transducer MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

Digi-Gage Control Systems.

Echotouch, EchoSpan & EchoSwitch Ultrasonic Liquid

LC-5 Level Controller & Flow Monitor

Catalog Index Page Description C A Briggs Company -

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

TPE 1464 Series Pressure Transducer

Zone Pressure Touch (ZPT) Sensor - Standard Range

LC-1 Level Controller & Flow Monitor

ALTERNATING RELAYS & CONTROLLERS ARM Series

Zone Pressure Touch Sensor - Standard Range

SCC Inc. TS-D Series. Technical Instructions. Document No. TS-3000 March 10, Deaerator, Surge and/or Condensate Control Panel.

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

KOBOLD PDA Series Digital Pressure Transmitter

Large DIspLay process Meters

Level Plus. Product Accessories. Magnetostrictive Liquid-Level Sensors with Temposonics Technology

Ordering Information - Level Measurement

PC-3000x PC-3000xC PUMP CONTROLLER. User Manual 844-4PRIMEX ( ) WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER

Sidewinder Pumps Inc. AC Timer/Controller

Trident and Trident X2 Digital Process and Temperature Panel Meter

Time Mark Corporation Model 42A Pump Controller User s Guide

analytical bulk flow distance FLOW level pressure temperature industrial communication

LC-3 Flow Monitor & Pump Run Verification

Level Plus. Product Accessories. Magnetostrictive Liquid-Level Sensors with Temposonics Technology

Differential Liquid/Gas Pressure Transmitter

dual-line 6-dIGIt process MeteR

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology. Accessories Catalog

SP6R-LSC CONTROLLER. User Manual. DUPLEX LIFT STATION CONTROL BAR GRAPH 4-20 ma INPUT AUTOMATIC ALTERNATION MOTOR STATUS LEDs

INSTRUCTIONS FOR MODEL 1000 DIGITAL PROCESS INDICATOR AND ALARM

Level Plus. Magnetostrictive Liquid Level Transmitters with Temposonics Technology. Accessories for liquid level transmitters Catalog

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

LAUREL. Laureate Digital Panel Meter for Process and Ratiometric Signals ELECTRONICS, INC. Features. Description

DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features Instruction Manual

DEVAR Inc. 706 BOSTWICK AVE. BRIDGEPORT, CT Tel: Fax:

SS2200 Remote Controller

Pump Station Controller. Quick Start

AccuTank ULTRASONIC LEVEL MONITORING SYSTEM

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

APPLICATIONS FEATURES UL LISTINGS YOUR PRIME CHOICE FOR MUNICIPAL WATER CONTROL SOLUTIONS

Resolution 1 F (1 C) single point; degrees C or Calibration single or dual point Calibration F

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PC-200-LLC-GM INSTALLATION INSTRUCTIONS. Revision A1 Rapid City, SD, USA, 10/2009 II_PC-XXX-LLC-GM_A1

CDD Carbon Dioxide Transmitter

KOBOLD TDA Series Digital Temperature Transmitter

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

TELEDYNE HASTINGS INSTRUMENTS

AS Keypad User Manual

SWING Ultrasonic Level & Flow Controller

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

SP6R Level Controller Operation Manual

DM28 - Economical Digital Process and Strain Gauge Panel Meters

Installation and Maintenance Instructions for GC55 Differential Pressure Transducer Version 1.0 5/11

EMS467 Monitoring System. Installation and Operations Manual Section 40

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

DIMENSION/WEIGHT kpa. 0 to 20 m / 0 to 60 ft 0 to 2 bar / 0 to 29 psi. 0 to 50 m / 0 to 160 ft 0 to 5 bar / 0 to 72.5 psi

Process displays For current and voltage

Remote Level Display with Explosion Proof Enclosure

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Digital Indicator Solutions

Digital Level Sensor. Consistent accuracy, unparalleled reliability. Answers for energy.

Interface Manual Chemical Injection System

PRESSURE MONITOR DATASHEET D053 - PRESSURE MONITOR WITH ONE HIGH / LOW ALARM OUTPUT.

1.6. Counters, Panel Meters, Tachometers and Timers. Contents Description Fusion Integrated Machine Control Standards and Certifications...

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

NT PRESSURE TRANSDUCER MODELS 4100, 4210, 4130, 4230

MODEL SIB-V245 / V453

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS

H3CA-8H-AC/100/110/120

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc.

HIGH-VOLTAGE DC METER

Operating Instructions. For. Level Control Module. Model SSR 1000

METERING/DISPLAY MANUAL

PD6210 / PD6310. PROVU Dual-Line 6-Digit Batch Controllers BATCH CONTROL. PRECISION DIGITAL CORPORATION SERIES

ULTRASONIC LEVEL CONTROLLER DISPLAY

Model 675 DREXELBROOK. Shark Cage Submersible Level Transmitter DATA SHEET. Description. Features. Applications.

Product description for ED1600 generic Sigfox Module

PDS100 Programmable Dispensing System SAFETY INSTRUCTIONS

300 SERIES 300 SERIES. Indicators to measure and control your daily operations.

Process Indicator Controller (Digital) (Product code 3.1 to 3.15)

Proportional Control Unit (PCU)

icon Series Controls

Simplified information where and how you want it.

CDD4 Duct Carbon Dioxide Transmitter

PST...-R ELECTRONIC PRESSURE SWITCHES

Deaerator and Surge Tank Control

Level Plus. Magnetostrictive Liquid-Level Transmitters with Temposonics Technology. Liquid-Level Transmitter Accessories Catalog

PD765 TRIDENT. Trident Series Process & Temperature Meters.

+GF+ SIGNET ph/orp Transmitter Instructions

Introduction. Upon completion of Basics of PLCs you should be able to: Identify the major components of a PLC and describe their functions

Echotouch, EchoSpan & EchoSwitch Ultrasonic Liquid

Installation and Maintenance Instructions for GC31 Ultra-Compact Digital Pressure Sensor

High Voltage DC Meter

Product Data. Model 675 Shark Cage Submersible Level Transmitter ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS

Transcription:

SC100 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 1 Revision Date: 4-2-18

APPLICATIONS STATION CONTROLLER SC100 Simplex or Duplex Liquid Level Control Pump Down (Empty a Tank) or Pump Up (Fill a Tank) STANDARD FEATURES 4 Digit, 7 Segment LED Level Display with Selectable Decimal Point Position All Setup Parameters Values may be viewed or changed from the front of the unit Level Input Source: Analog Level Input (4-20 ma from Pressure Transducer) Level Input Zero and Span Calibration Parameters for Field Calibration Provides +24 VDC Power for Analog Level Input Two Pump Call Relay Outputs with Status Indication High and Low Level Alarm Relay Outputs with Status Indication 10 Second Power Up Delay (the first pump call is delayed by 10 seconds after a power interruption) Adjustable Lag Pump Delay for Pump Call Output Automatic Pump Alternation or Fixed Sequence: 1-2 or 2-1 Level Simulation (Automatically ends after 60 seconds) Level Input Signal Conditioning Parameter (May be used to dampen out fluctuations in the Level Input Signal) Stores all Setup Parameter values in EEPROM (Does not require a backup battery) SPECIFICATIONS Supply Power: 120 VAC ±10%, 7.8 VA max Enclosure Dimensions: 6.10 x 7.70 x 2.78 ( H x W x D ) Enclosure Material: Aluminum Faceplate Color: White with Blue Lettering Agency Approval: UL 508, CAN/CSA UL FILE #: E101681 Ambient Operating Temperature: -20 C to +65 C ( -4 F to +149 F ) Storage Temperature: -45 C to +85 C ( -49 F to +185 F ) 4 Digit, 7 Segment LED Display Range: 0-2310 (Selectable Decimal Point Position) Indicators: Red LED Relay Outputs: 10 A Resistive @ 120 VAC 3.6 A Inductive @ 120 VAC Analog Level Input: 4-20 ma, 147 Ω Load, Transient Protected Power for Analog Level Input: 24 VDC, Overload and Transient Protected ORDERING INFORMATION Part Number: SC100 1

OPERATOR INTERFACE FUNCTIONS Press to Return to Level Display Press to Enter the Level Simulation Mode Press to Toggle Between Menu Scroll and Value Change Modes Press to Scroll Up the Menu, or to Increase Parameter Value Press to Scroll Down the Menu, or to Decrease Parameter Value Note: To Prevent the Accidental Changing of a Parameter Value, there is a 4 second Delay Before a Parameter Value will Change. (The PB-D or PB-U Push-Button must be Held Down for the Entire 4 second Delay.) How to View a Setup Parameter Value 1. Press push-button PB-M until the Menu Scroll Mode indicator comes on. 2. Press push-button PB-D or PB-U as needed to arrive at the Parameter you wish to view. 3. Press push-button PB-M until the Value Change Mode indicator comes on. 4. The current value of the Parameter may then be viewed on the display. How to Change a Setup Parameter Value 1. Press push-button PB-M until the Menu Scroll Mode indicator comes on. 2. Press push-button PB-D or PB-U as needed to arrive at the Parameter you wish to change. 3. Press push-button PB-M until the Value Change Mode indicator comes on. 4. The current value of the Parameter may then be viewed on the display. 5. Press and hold for 4 seconds, either push-button PB-D or PB-U, to change the Parameter to the desired new value. 6. Press push-button PB-M or PB-L to exit the Value Change Mode. How to Simulate Levels 1. Press push-button PB-S. Note: The Simulation starts from the actual level displayed prior to entering the Level Simulation mode. 2. Press push-button PB-D or PB-U as needed to change the simulated level. 3. To end the level simulation press push-button PB-L. Note: If you do not exit the Level Simulation mode, normal operation will resume automatically 60 seconds after the last time the PB-U, PB-D, or PB-S push-buttons were pressed. 2

MENU - SYSTEM SETUP Parameter Default Value Current Value Setting Definitions LoAL 2.0 Low Level Alarm Range: 0.1-231.0 PoFF 3.0 Pump 0ff Level Range: 0.2-231.0 1 Pon 6.0 1st Pump 0n Level Range: 0.2-231.0 2 Pon 7.0 2nd Pump 0n Level Range: 0.2-231.0 HI AL 10.0 High Level Alarm Range: 0.5-231.0 Note: Decimal Point Position for above Parameters is set by Parameter P - 21. LAGd 5 sec. Lag Delay Range: 1-100 seconds ZEro 0.0 SPAn 11.5 P - 13 2 P - 19 1 P - 20 0 P - 21 1 P - 22 240 Level Input Calibration - Zero Notes: 1. 4.0mA is Typically Applied to the Process Input while Setting the Zero. 2. Parameter ZEro Shows the Level Input, while allowing the Up & Down Push-buttons to Change the Internal Number used to Zero the Displayed Value. 3. Decimal Point Position is set by Parameter P - 21. See Page: 4. Level Input Calibration - Span Range: 0.9-231.0 Notes: 1. 20mA is Typically Applied to the Process Input while Setting the Span. 2. Parameter SPAn Shows the Level Input, while allowing the Up & Down Push-buttons to Change the Internal Number used to Calculate the Displayed Value. 3. Decimal Point Position is set by Parameter P - 21. See Page: 4. Number of Pumps Present 1 = 1 Pump 2 = 2 Pumps Pump Up or Down Mode 1 = Pump Down - Empty a Tank 2 = Pump Up - Fill a Tank Note: When Parameter P - 19 is Changed New Default Pump On and Off Level Parameter Values will be loaded. Forced Lead Pump Position 0 = Normal Alternation 1 = Pump as 1 Lead 2 = Pump as 2 Lead Level Display Decimal Point Position 0 = No Decimal Point 1 = XXX.X 2 = XX.XX 3 = X.XXX Level Input - Signal Conditioning Control Range: 1-254 10 = Very Slow 100 = Slow 240 = Normal 250 = Fast o P r - Operating Program Revision Number High Level Alarm Upon a High Level Alarm, the indicator will come on, the relay will de-energize and the contacts will close. The High Level Alarm relay contacts will be closed when there is no power on the controller. Low Level Alarm Upon a Low Level Alarm, the indicator will come on, the relay will energize and the contacts will close. The Low Level Alarm relay contacts will be open when there is no power on the controller. A Low Level Alarm is delayed for 10 seconds after power is applied. 3

LEVEL INPUT (4-20mA Input) CALIBRATION PROCEDURE Notes: 1. Do not attempt to change the Span or Zero calibration using Parameters ZEro and SPAn without first applying the appropriate 4-20mA signal to the Analog Level Input during each step of the calibration procedure. 2. The rate of change of the displayed Level may be customized using Parameter P - 22. LEVEL INPUT ZERO - Parameter ZERo This Parameter is used to make the Level Display read zero with a Level Input of 4.0mA. Calibration Procedure: 1. Apply a 4.0mA signal to the Analog Level Input. (Alternate Procedure - Pull the pressure transducer out of the water, or disconnect the bubbler tube.) 2. Scroll in the menu to Parameter ZERo and press push-button PB-M to view the Level. 3. Press and hold down the UP or DOWN push-buttons as need to make the display read zero. Note: It is slow to change at first. 4. Perform the procedure below to calibrate the Span. LEVEL INPUT SPAN - Parameter SPAn This Parameter is used to establish what the Level Display should show with a Level Input of 20mA. Calibration Procedure: 1. Apply a 20mA signal to the Analog Level Input. (Alternate Procedure Subject the Transducer to a known condition (for example under 6.0 feet of water). 2. Scroll in the menu to Parameter SPAn and press push-button PB-M to view the Level. 3. Press and hold down the UP or DOWN push-buttons as need to make the display read the span of the Pressure Transducer. Note: It is slow to change at first. (Alternate Procedure Use the Up / Down push-buttons to make the display read the same as the current level of liquid in the wet well (for example 6.0 feet of water). LEVEL INPUT SPAN in Feet Of Water Versus TRANSDUCER CALIBRATION in PSI Transducer Calibration 5.0psi 10psi 15psi 30psi 60psi 100psi Level Input Span - - - - 139 feet 231 feet P - 21 = 0 11.5 feet 23.1 feet 34.6 feet 69.3 feet 139.0 feet 231.0 feet P - 21 = 1 11.50 feet 23.10 feet - - - - P - 21 = 2 Notes: 1. Parameter P - 21 is used to set the decimal point position. 2. To find the Span Setting for other transducers use the following equation: Pressure (psi) x 2.309 = Level (feet of water) 4

CONNECTION DIAGRAM 5

CONTROL SCHEMATIC EXAMPLE - Duplex with 24V Float Backup 6

OPERATOR INTERFACE 7

ENCLOSURE MECHANICAL LAYOUT Left Side Right Side Rear View 8

PANEL CUTOUT 9