Next Generation DCP Optimization using MV VSDs

Similar documents
Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

where we are, where we could be, how we can get there. 12/14/2011

DEDICATED HEAT RECOVERY UNIT (DHRC)

Data Center Energy Savings By the numbers

Optimizing Chilled Water Plant Performance. David Herman, PE, LEED AP Principal EnerG Associates, LLC

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Air-Cooled Chillers. R134a. Performance Matters

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

Trailblazer AGZ-E air-cooled scroll chillers

Large Tonnage Chillers. Kingsley Hu Technical Support Engineer

that may have a direct effect on your bottom line. The question

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Global Optimisation of Chiller Sequencing and Load Balancing Using Shuffled Complex Evolution

Air-Cooled Series R Chiller

District Cooling Marches on in Dubai The Emirates Towers Case Study

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

PROCESS COOLING STUDY WORKSHEET

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Chiller Replacement and System Strategy. Colin Berry Account Manager

Ecotel Free Cool 5-15kW

IN-DEPTH UNDERSTANDING OF HVAC EQUIPMENT & SYSTEM SPECIFICATIONS AND PERFORMANCE 11 & 12 JULY 2016 WISMA IEM

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

IBM Symposium Data Center Cooling. EC Systems for HVAC architecture and Direct air Cabinet Cooling

Trane Series S CenTraVac Chillers with AdaptiSpeed Technology tons

Welcome Association of Energy Engineers to the Microsoft Technology Center

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

Case study on Green Data Center. Reliance Jio Infocomm Limited

Pathfinder AWV air-cooled screw chillers

Optimiz Chilled January 25, 2013

18 th National Award for Excellence in Energy Management. July 27, 2017

MSYS 4480 AC Systems Winter 2015

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

Retro-Commissioning Report

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Magnitude magnetic bearing centrifugal chillers

Saving Energy with Free Cooling and How Well It Works

Existing Building Energy Saving

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

Variable Speed IPLV.36 kw/tr

Chilled Water Distribution Design Considerations in Super Tall Buildings. Dusan Mrdalj, Associate, ChapmanBDSP

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

IT Air Conditioning Units

Committed to Energy Efficiency

APC InRow Cooler Prototype Initial Report - Test Setup Verification. H. Coles, S. Greenberg Contributing: J. Bean (APC) November 18, 2011

LIFE CYCLE COST ANALYSIS, CRITERIA AND DATA SHEETS DOCUMENT NUMBER: APPLICATION: ELEMENTARY, MIDDLE AND HIGH SCHOOL

Efficiency of Data Center cooling

MPC Air-Cooled Chillers MPC-FC Free-Cooling Chillers

CASE STUDIES. Brevard Community College: Florida Power & Light. Cape Canaveral Air Force Station: NORESCO

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

Water cooled chiller plant (all-variable)

MOLLIER DIAGRAM CAN BE IMPROVED!

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

glide glider kw R134a air cooled liquid chillers AND free cooling chillers FREE COOLING SHELL A C CLASS E C Energy Class RCGROUP SpA

Precision Cooling. Precision Cooling Advantages

Specification and Design Catalog. Waterside Economizer

Data Center Temperature Design Tutorial. Ian Seaton Chatsworth Products

Indirect Adiabatic and Evaporative Data Centre Cooling

Oil Free Magnetic Bearing Chillers. Lloyd Davis ESTech Energy Ltd

Indirect Adiabatic and Evaporative Data Center Cooling

Aquaflair. BREC/F and BCEC/F kw

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

Series S CenTraVac Chillers Leading efficiency and proven reliability BEYOND EFFICIENCY. BEYOND RELIABILITY. BEYOND SUSTAINABILITY. LET S GO BEYOND.

Saving Water and Operating Costs at NREL s HPC Data Center

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

Chiller Plant Optimization: A Case Study

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

How Green can you go?

District Cooling Workshop

DATA CENTER LIQUID COOLING

LANL High Performance Computing Facilities Operations. Rick Rivera and Farhad Banisadr. Facility Data Center Management

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen,

Achieving Operational Excellence

Stratadyne Group Inc.

MLC Air-Cooled Chillers MLC-FC Free-Cooling Chillers MLC-AD Adiabatic Chillers

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

Comprehensive Energy Management & Utility Master Plan

2018 Business Cooling Equipment Rebate Application

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

Green IT Project: The Business Case

MODELS VSD 270, 292, 351, 385, 419, 424, 503, 608, 658, AND 704 MODELS LVD 270, 292, 351, 385, 419, 424, 503, 608, 658, 704, AND 900

Dykin Engineering Part & Services Sdn. Bhd.

E e n rgy g y St S ud u y y Pr P og o r g ams December 2011

CenterPoint Energy Retro-Commissioning Program Application

Commercial Retro-Commissioning Program Manual for 2016 SECTION 1

What is the Carrier ChillerVu series counterflow application?

Impact of Air Containment Systems

VARIABLE REFRIGERANT FLOW SYSTEMS HITACHI SMARTFLEX VRF GEN II FLEXIBILITY, PERFORMANCE AND CONTROL

Climate Technologies Investor Update

MEASURE MONITOR UNDERSTAND

Transcription:

Next Generation DCP Optimization using MV VSDs Vivek Apte Regional Product Director Johnson Controls - Middle East Cell : +971506243059 IDEA 2016- Dubai 1

Central Plant Optimization Energy and operating Costs Electricity costs are rising at rates greater than inflation Owners are seeking a total cost of ownership solution Total Chiller Plant Energy Use Chillers 64% Pumps 22% Towers 11% Other 3% 2

Background Why are talking VSD Chillers In a District Cooling Plant, Chillers, by far, have the Largest Energy Demand. Chillers Spend more than 99% of Operating hours at Offdesign Conditions. Simultaneous occurrence of 100% Load and Design Outdoor Conditions is very unlikely. Compressor Running at Lower Speeds, whenever possible, Consumes Less Power and Can Potentially save upto 30% of Annual Energy Consumption.

ECWT ( F) Annual Hours General Weather Pattern in the Gulf 1200 1000 Less than 1% of chiller run hours are at design conditions! 800 600 400 200 0 4 115-119 313 81 110-114 510 105-109 633 871 1067 952 861 923 949 873 99% Dry-bulb Temperature Bins ( F) 602 100-104 95-99 90-94 85-89 80-84 75-79 70-74 65-69 60-64 55-59 107 50-54 14 45-49 95 90 85 80 75 70 65

Centrifugal Chillers at Design Conditions Constant Speed Variable Speed Loaded Chiller : PRVs Open Motor at Design Speed Loaded Chiller : PRVs Open Motor at Design Speed

Centrifugal Chillers at Off-Design Conditions Constant Speed Variable Speed PRV close as load decreases Motor speed remains constant at full Optimizes compressor efficiency Motor speed slows down Optimizes PRV position Consumes less energy

Centrifugal Chillers at Off-Design Conditions With the use of VSD, Can we do away with the Inlet Vanes? No, Certainly not. Refri FLow ~ Speed Lift ~ Speed 2 Power ~ Speed 3 A balance between the speed reduction and vane throttling is needed for Surge-Free Operation at Low Load conditions.

Centrifugal Chillers at Off-Design Conditions Chilled Water Temp. Temp. Setpoint Evap / Cond Pressure PRV Position Actual Motor Speed Refri FLow ~ Speed Lift ~ Speed 2 Power ~ Speed 3 Optimum Motor Speed Optimum PRV Position

Additional Benefits of a VSD Improved and Constant PF of 0.98 Eliminates PF correction Capacitors Reduces Current for Same Power Eliminates Inrush Current (<100% FLA) Enhances motor life Reduces Emergency Power Generator Size. Reduced driveline wear Reduced Sound Level at Lower Loads. At night time, when you need low noise operation. Eliminates ill-effects of exaggerated design parameters. Higher Condenser Water Temp Fouling Factors

VSD Chiller : District Cooling Application Can I apply this Breakthrough Technology to District Cooling? But.I have so many chillers, which are sequenced and hence run close to full load most of the time

VSD Chiller : District Cooling Application We are very familiar with VSD application where the speed is Modulated to maintain static pressure at varying flow-rate. Air Handling Units in Variable Air Volume systems Secondary Chilled Water Pumping

VSD Chiller : District Cooling Application Centrifugal Chiller Compressor are also subject to situations, where the static pressure is reduced while the flow rate needs to be maintained Imagine.Reduced Cond pressure due to lower Wet Bulb conditions and constant refrigerant flow rate due to constant cooling load.

kw / TR Impacts of Cooling Water Temp & Load on COP 0.750 Constant Speed 0.700 0.650 0.600 92F 90F 85F 80F 75F 70F 0.550 0.500 0.450 0.400 0.350 100 90 80 70 60 % Chiller Load 13 Chiller Best Efficiency is at near full load conditions.

kw / TR Impacts of Cooling Water Temp & Load on COP 0.750 Variable Speed 0.700 0.650 0.600 92F 90F 85F 80F 75F 70F 0.550 0.500 0.450 0.400 0.350 100 90 80 70 60 % Chiller Load 14 Constant Speed Chiller Best Efficiency is at near-full load condition.

kw / TR Impacts of Cooling Water Temp & Load on COP 0.750 Constant v/s Variable Speed 0.700 0.650 0.600 0.550 0.500 0.450 92F 90F 85F 80F 75F 70F 92F 90F 85F 80F 75F 70F 0.400 0.350 100 90 80 70 60 % Chiller Load 15 VSD saves power even at Full load and more so at lower loads

Impacts of Cooling Water Temp & Load on COP VSD saves power even at Full load and more so at lower loads

Medium Voltage Variable Speed Drives Misconceptions & Fact Check MV Variable Speed Drives are expensive, with un-attractive payback MV-VSD costs and size, both have reduced with improved technology and its time to evaluate the payback District Cooling Plants always operate at Full Load Conditions DCP s seldom see full Delta T. As such, chillers are loaded between 60% and 80% Use for Thermal Storage means the chillers will always be operating at full design load. Chillers must be evaluated for Full Load Efficiency at Design Conditions Again, limited by the low Delta T. Also, Thermal Storage Tank is always charged at off peak conditions and hence at low WB temp it will benefit most with VSD technology. Real World conditions will always see reduced ECWT s and lower loads. Off design performance of Chillers is critical. 17

Medium Voltage Variable Speed Drives Misconceptions & Fact Check MV Variable Speed Drives are expensive, with un-attractive payback District Cooling Plants always operate at Full Load Conditions Use for Thermal Storage means the chillers will always be operating at full design load. Chillers must be evaluated for Full Load Efficiency at Design Conditions MV-VSD costs and size, both have reduced with improved technology and its time to evaluate the payback DCP s seldom see full Delta T. As such, chillers are loaded between 60% and 80% Again, limited by the low Delta T. Also, Thermal Storage Tank is always charged at off peak conditions and hence at low WB temp it will benefit most with VSD technology. Real World conditions will always see reduced ECWT s and lower loads. Off design performance of Chillers is critical. 18

Impacts of Cooling Water Temp & Load on COP

Medium Voltage Variable Speed Drives Misconceptions & Fact Check MV Variable Speed Drives are expensive, with un-attractive payback District Cooling Plants always operate at Full Load Conditions Use for Thermal Storage means the chillers will always be operating at full design load. Chillers must be evaluated for Full Load Efficiency at Design Conditions MV-VSD costs and size, both have reduced with improved technology and its time to evaluate the payback DCP s seldom see full Delta T. As such, chillers are loaded between 60% and 80% Again, limited by the low Delta T. Also, Thermal Storage Tank is always charged at off peak conditions and hence at low WB temp it will benefit most with VSD technology. Real World conditions will always see reduced ECWT s and lower loads. Off design performance of Chillers is critical. 20

Impacts of Cooling Water Temp & Load on COP

Medium Voltage Variable Speed Drives Misconceptions & Fact Check MV Variable Speed Drives are expensive, with un-attractive payback District Cooling Plants always operate at Full Load Conditions Use for Thermal Storage means the chillers will always be operating at full design load. Chillers must be evaluated for Full Load Efficiency at Design Conditions MV-VSD costs and size, both have reduced with improved technology and its time to evaluate the payback DCP s seldom see full Delta T. As such, chillers are loaded between 60% and 80% Again, limited by the low Delta T. Also, Thermal Storage Tank is always charged at off peak conditions and hence at low WB temp it will benefit most with VSD technology. Real World conditions will always see reduced ECWT s and lower loads. Off design performance of Chillers is critical. 22

Medium Voltage Variable Speed Drives Misconceptions & Fact Check MV Variable Speed Drives are expensive, with un-attractive payback District Cooling Plants always operate at Full Load Conditions Use for Thermal Storage means the chillers will always be operating at full design load. Chillers must be evaluated for Full Load Efficiency at Design Conditions MV-VSD costs and size, both have reduced with improved technology and its time to evaluate the payback DCP s seldom see full Delta T. As such, chillers are loaded between 60% and 80% Again, limited by the low Delta T. Also, Thermal Storage Tank is always charged at off peak conditions and hence at low WB temp it will benefit most with VSD technology. Real World conditions will always see reduced ECWT s and lower loads. Off design performance of Chillers is critical. 23

Annual Water and Electricity Cost Comparison for a 20,000 TR Plant with following Options Case Study Annual Utilities Cost 20,000 TR Plant OPTION 1 Normal Full Load Efficiency 4 x 5,000 TR series pair @ Full Load 0.658 ikw/tr OPTION 2 Option 1 + VSD 4 x 5,000 TR series pair @ Full Load 0.691 ikw/tr OPTION 3 High Full Load Efficiency 4 x 5,000 TR series pair @ Full Load 0.627 ikw/tr Joh 24 nso

Summary of Case Study Option1 Option2 Option3 0.653 kw/tr 0.691 kw/tr 0.627 kw/tr Description Constant Speed Variable Speed Constant Speed Normal Efficiency Standard Efficiency High Efficiency Normal Pressure Drop Option 1 + VSD Low Presure Drop Annual Cost of Utilities (AED '000) as of Nov2016 Chillers 21,950 19,900 21,770 Primary Chilled Water Pump 2,110 2,110 1,770 Condenser Water Pump 6,382 6,382 5,827 Total Energy Cost 30,442 28,392 29,367 Total Water Consumption 8,137 8,034 8,128 Total Cost of Utilities 38,579 36,426 37,495 Budgetary Initial Cost (AED '000) Price of Chiller 19,925 19,925 23,900 Price of Solid State Starter 2,540 2,540 Price of Variable Speed Drive 8,257 Total Initial Cost 22,465 28,182 26,440 Additional Cost of VSD (Compared to Option3) 1,742 Saving in Annual Cost of Utilities (Compared to Option3) 1,069 Simple Pay back period in years 1.63 Costs common among Options (Secondary Pump and Cooling Tower) not considered for comparison 25

Medium Voltage Variable Speed Drives Selection Suggestions MV VSDs have an internal transformer irrespective of incoming voltage and output voltage. Eliminate external transformer. Select output voltage to allow compact one piece drive. MV VSD Application Suggestions Incoming Voltage New Projects Specified Motor Voltage VSD In Voltage VSD Out Voltage Motor Size Remarks 11000 3300 11000 3300 Upto 2250 HP Eliminate External Step Down Xmer 11000 11000 11000 3300 Upto 2250 HP 11000 3300 11000 4000 2500 HP 11000 11000 11000 4000 2500 HP Retrofit Project with VSD compatible motor 11000 3300 3300 3300 Upto 2500HP Using existing step down Xmer 11000 3300 11000 3300 Upto 2500HP Remove existing Xmer to save losses 11000 11000 11000 11000 Upto 2500HP Retrofit Project with VSD incompatible motor (motor needs replacement) Treat as if a new proejct For Use of Next Gen Compact VSDs 26

Now that we have VSDs How do we sequence the plant so as to operate chillers at their the Best Efficiency (COP)?

Sequencing for Best Year-round COP The answer to the Big Questions is simple and straight forward for Constant Speed Drive Chillers. For best COP, the Chillers should be made to operate at near full load, as far as possible. So, Sequence in a way that we run just enough quantity of Chillers to meet the Demand Load. This is extended to pumps as well along with the chillers and thus we run lesser water quantity in the primary loop and run fewer pumps And.this is the traditional Load Based Sequencing

Building Load Traditional Load based Sequencing Consider: 10,000 TR Chiller Plant Qty (5) 2000 TR chillers piped in parallel Dedicated auxiliaries* Typical Load Line Year round operation - 24H/7D Facility Load (%) Chiller Systems Operating Chiller Load Range (%) 100 5 100-80% 80 4 100-75% 60 3 100-65% 40 2 100-50% 20 1 100-10% 10000 9000 8000 7000 6000 5000 4000 3000 2000 1000 0 CH1 CH2 CH3 CH4 CH5 29

Building Load Energy Based Sequencing Consider: Energy Based Sequencing 10,000 TR Chiller Plant Qty (5) 2000 TR chillers piped in parallel Dedicated auxiliaries* Typical Load Line Year round operation - 24H/7D 10000 9000 8000 7000 6000 5000 4000 3000 2000 CH1 CH2 CH3 CH4 CH5 Facility Load (%) Chiller Systems Operating Chiller Load Range (%) 1000 0 100 5 100-81% 80 5 75-65% 60 5 60-43% 40 3-4 43-35% 20 1-2 50-35% 30

Energy Based Sequencing Load Based Sequencing Energy Based Sequencing 10000 10000 9000 9000 8000 8000 7000 6000 5000 4000 3000 CH1 CH2 CH3 CH4 CH5 7000 6000 5000 4000 3000 CH1 CH2 CH3 CH4 CH5 2000 2000 1000 1000 0 Multiple Chiller plant piped in parallel Sequence based on return water temperature Split the load equally among fewest number of chillers to satisfy the load 0 Multiple Chiller plant piped in parallel Keep chillers on line and in part load operation for as long as possible as cooling load decreases Turn on and off chiller systems based on energy consumption 31

KWH Energy Based Sequencing 31,000,000 10,000 TR plant 27,000,000 23,000,000 18% Savings 27% Savings 49.7 Million Ton Hours 19,000,000 At $0.10/KWH 15,000,000 Annual Savings $600,000 11,000,000 7,000,000 Constant Speed Chiller Plant (.565 KW/TR IPLV) VSD Load sequenced Chiller Plant (.510 KW/TR IPLV) VSD Energy Sequenced Chiller Plant (.452 KW/TR IPLV) 32 Energy Based Sequencing Enhances the Savings of VSD chillers

Energy Based Sequencing Fantastic!...We saved so much in Chiller Energy.. but, What about the pumps? Shall we end up running more pumps than required. Yes, you will. But, when you combine it with Variable Primary Flow (VPF), you will actually save power.

KWH Bringing together the potential of Variable Speed Chillers & Variable Primary Flow pumping 31,000,000 10,000 TR plant 27,000,000 23,000,000 18% Savings 27% Savings 19,000,000 15,000,000 11,000,000 With VPF, the savings can be further enhanced to in excess of 30%. 7,000,000 Constant Speed Chiller Plant (.565 KW/TR IPLV) VSD Load sequenced Chiller Plant (.510 KW/TR IPLV) VSD Energy Sequenced Chiller Plant (.452 KW/TR IPLV) 34

Bringing together the potential of Variable Speed Chillers & Variable Primary Flow pumping..and we all have been using it for so many years already. The best technologies are inspired by Nature.