BACnet-over-Ethernet (BACnet TCP/IP) Gateways for Modbus RTU Devices

Similar documents
BACnet MS/TP Gateways for Mega Controls Modbus RTU Networking Devices

RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

BACnet Product Overview

TC-9102 Terminal Controller

BACnet Flow Controller for Fan Filter Units

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

System-10 BTU Meter BACnet Network Interface Installation Guide

Field selectable application type and room module series, via dip-switches on controller

Submittal Data Sheet intelligent Touch Manager DCM601A71

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

FCU-MULTI Modbus Fan Coil Unit Controller

Communicative controller for VAV systems

HRM-0800 Instruction Manual

FX Input/Output (I/O) Modules XM07 and XM14

clarity 3 Programmable Controller

Siemens BACnet Programmable TEC Unit Conditioner Controller

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

Siemens BACnet Programmable TEC Unit Vent Controller

Siemens BACnet Programmable TEC Constant Volume

BACnet Controller for General-purpose Building Applications

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

Heatronic Introduction. BAS Integration Manual. Table of Contents

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Multi-Point Gas Detection and Control System

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Multi-Point Gas Detection and Control System

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

BACnet. b3867 Terminal Controllers

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

EasyIO FC20 User Reference v1.3. EasyIO FC 20 DDC User Reference V1.3

Du line. Dupline Field- and Installationbus Dupline Ethernet Modbus/TCP Gateway Type G G Type Selection

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

MIC-2 MKII, Multi-instrument DATA SHEET

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

CONTROLS.COM. Bacnet and Modbus Modules. T3-22i. T3000 Building Automation System Overview. T3-8o. Ethernet MAIN NET1 RS485 SUBNET2 RS485.

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

Multi-Point Gas Detection and Control System

BACnet Terminal Box (VAV) Controller

FCU-4 FAN COIL CONTROLLER

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

HARDWARE GUIDE. Water Loop Controller C1000 Series. Specifications and Operational Guide

Andover ContinuumTM Infinet II

Remote I/O Product Specification

MIC-2 Multi-instrument DATA SHEET

ProtoConvert Modbus RTU / Modbus TCP/IP / BACnet MSTP / BACnet IP / SNMP - Telnet (Lighting Controller) PG

FCU-4 FAN COIL CONTROLLER

iologik E1200H Series

Extended Digital Controller

Andover ContinuumTM. b3850 Series Terminal Controllers

Remote I/O Product Specification

BAC-9000 Series VAV Controller Installation Guide

Submittal Data Sheet WAGO Node for itm

IntesisBox Modbus Server KNX

BAS Router BACnet Multi-Network Router

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

IMIO100 IMIO105. DDC controllers. Summary

Modular Room Control (MRC) Series Expansion Board

System-10 BTU Meter BACnet Network Interface Installation Guide

FX06 Field Controller

Modbus communication module for TCX2: AEX-MOD

mark150s mark150/485s DDC controllers Summary

MPI-DN, MPI-D MULTICHANNEL ELECTRONIC RECORDER for HART or RS-485/ MODBUS RTU SENSORS

---- IntesisBox KNX Modbus RTU Master and Modbus TCP Client

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

NovoCon S Digital/Hybrid - High Accuracy Actuator

iologik E1200 Series Ethernet remote I/O with 2-port Ethernet switch Introduction Remote I/O Daisy-Chained Ethernet I/O Connection

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

RTD-NET Installation Instructions

SHEET. BASgatewayLX Modbus to BACnet Gateway. BASgatewayLX

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

M1000 INTELLIGENT ZONE CONTROL SYSTEM

DATA SHEET LAN Server For Energy and Power meters AEM and APM with Modbus interface

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS)

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.

Features. :. Introduction. :. Leader 5000 Appearance. Ethernet-Based Block I/O System

LAUREL ELECTRONICS, INC.

S66 Series Electronic Fan Speed Control

Efficient. Innovative. Sustainable.

Andover ContinuumTM Infinet II

UC102 basic version with display and knob UC102BL version with display, knob and backlight UC102DK version without knob and display

DMT345 and DMT346 Dewpoint Transmitters

XT-9100 Technical Bulletin

NIEx9. Metasys. BAS network automation Supervisory controllers. Network Integration Engine

Flex Gateway Card. Installation and Operation Manual. For CPS 50kW/60kW 3-Phase String Inverters

iopac 8020 Series Rugged modular RTU controllers Overview Programmable RTU Controllers Ethernet bypass feature for seamless data transmission

oom Pressurization Con

Multi-Point Digital Gas Detection and Control System

BACnet. b3810 Series Local Controllers

D-100 FLOW DISPLAY BACnet Network Interface Installation Guide

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

Voltage Transducer UMT516 / MT516

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

Transcription:

Issue Date March 1, 2018 BMGE Series BACnet-over-Ethernet (BACnet TCP/IP) Gateways for Modbus RTU Devices General The BMGE Series BACnet-over-Ethernet (BACnet TCP/IP) gateways, which route communication traffic between BACnet network and Modbus RTU network, map registers in the Modbus RTU slave devices into standard BACnet objects, which are then accessible on a BACnet network via an Ethernet port. The gateways, pre-loaded with a Modbus program, become masters to the connected Modbus slave devices and communicate using the Modbus RTU protocol on a RS- 485 network. Each gateway is available with two RS-485 networks. Each network can support up to 32 Mega Controls NT10/NT50 Series, NTAF Series, NSM Series and NC24A and NC24T Modbus RTU devices. The gateway spontaneously detects the presence of slaves that go online in its NET 1 and NET 2 networks. However, these devices must not be mixed and must be of the same series or type in both network trunks. NT10 Series and NT50 Series are treated as the same type of devices and can be mixed in the same network trunks. Mounting It is strongly recommended to mount the gateway inside a metal cabinet for EMI shielding protection, with 2 or 4 screws or rack-mounted in a DIN rail. Ordering To order, specify the complete gateway model number. Specifications Gateway model number BMGE-1 Universal BACnet-over-Ethernet gateway for Mega Controls NT10/NT50 Series, NTAF Series, NSM Series, NC24A or NC24T Power requirements Voltage 22-28 V 50/60 Hz or 16-30 VDC Current Maximum 200 ma Technology CPU 32-bit ARM at 48M clock ROM 256 kb Flash RAM 64 kb SRAM EEPROM 2 kb Ethernet communication port Physical 10Base-T via RJ-45 phone jack Protocol Indicators Device MAC address Maximum number Service supported Objects supported Object names BACnet-over-Ethernet in compliance with ISO-8802-3 Red LED for data receiving and green LED for data transmitting Set via DIP switches 32 BMGE devices in one BACnet platform WhoIs, ReadProperty, ReadPropertyMultiple, WriteProperty Device, Analog Input, Analog, Analog Value, Binary Input, Binary, Input, Static NET 1 and NET 2 communication port Physical RS-485 with opto-coupler Isolation Baud rate Fixed at 19,200 bps Protocol Modbus RTU Indicators Red LED for data receiving and green LED for data transmitting Device address Always 1 for NET 1 and 2 for NET 2 Maximum number 32 slaves in one Modbus RTU network Ambient/storage temperature limits 0 to 55 o C / -30 to 50 o C, 10 to 90% RH Non-condensing Wiring class Class II for 24 VAC Power Supply Connectors Removable screw-type terminal connectors Power wires Wire size 1 mm 2 or 18 AWG solid copper recommended Ethernet communication wires Cat 5e cable (twisted pairs) NET 1 and NET 2 communication wires Balanced 100 to 120 Ω nominal Impedance twisted shielded pair (TSP) cable Shipping weight 0.25 kg (1 lb) Dimensions 110 x 155 x 60 mm (W x L x D) The performance specifications above are nominal and subject to tolerances and application variables of generally acceptable industry standards. The manufacturer shall not be liable for damages resulting from misapplication or misuse of its products. Copyright Mega Controls Limited www.megacontrols.com 1

Language and Gateway Instance ID Setup Procedure System Setting Objects There are 2 objects for system setup defined as: Object Name Object Value Unit Object Type Read/Write *** SYS SELECT 10123.AV1 *1 Analog Variable R/W *** SYS VALUE 10123.AV2 *1 Analog Variable R Priority Array Note: *1 System setting can be changed by writing value to *** SYS SELECT. Write property value to ***SYS SELECT Function Description 2012 Change all descriptions to CHINESE. New setting will take effect after entering a restart command 3003 followed by reloading descriptors at the BMGE Manager. 2014 Change all descriptions to ENGLISH. New setting will take effect after entering a restart command 3003 followed by reloading descriptors at the BMGE Manager. 3003 Restart 2004 To set device instance ID. This is a two-step operation: after writing 2004 to ***SYS SELECT, wait until *** SYS VALUE changes to 1, then write an integer n (where 0 n 12799) to ***SYS SELECT. Assuming the DIP switches MAC address is set as m, the device instance ID is n*100 + m. New setting will take effect after entering a restart command 3003 followed by a discovering new devices at the BACnet workstation. Notes: After all new entries have taken into effect, the new data will be saved to the EEPROM. Power restart will resume all data saved before power failure. Auto Detect of Supported Slave Devices Connected to Network Ports When BMGE is powered up first time and initialized, it will automatically detect the model numbers of slave devices connected to NET 1 and NET 2 ports, wait for response from these slave devices and implement communication based on the model numbers discovered. The slave device model numbers supported by the BMGE are those covered by the NT10/NT50 Series, NTAF Series, NSM Series, NC24 A and NC24T. Notes: Both the NET 1 and NET 2 ports must be connected to the slave devices of the same series or type. Each network trunk supports 32 slave devices, totaling 64 slave devices in one BMGE. NT10 Series and NT50 Series are treated as the same type of devices and can be mixed in the same network trunks. Gateway MAC Addressing The DIP switch is a binary switch. Each individual DIP switch represents a unique value, which forms the gateway MAC address when added together. To set the address, simply move the switches that add up to the gateway s desired address to the ON position. Example: If the gateway is to be address 7 on the network, set the switches numbered 1, 2 and 4 (equals 7) to the ON position. Note: Each gateway on the same BACnet network must have a unique DIP switch address. Figure 1: Network Configuration BMGE (Master) Slaves Slaves 2 BMGE Series BACnet-over-Ethernet Gateways Product Bulletin

Network, Cabling and Step-down Transformer Requirements To ensure network stability and reliable communications, it is imperative that the following network, cabling and step-down transformer requirements are adhered to: Item Description Network Trunk Cabling It is recommended to use networking cabling that matches the following specifications: Balanced 100 to 120 ohms nominal impedance, 22 or 24 AWG Twisted Shielded Pair (TSP) Cable Nominal capacitance of 52 pf/m or lower Nominal velocity of propagation of 66% or higher Terminating the shield to ground at one end only for each isolated segment will prevent ground loops in the shield and drain RF energy to ground. Grounding at the BACnet router or controller is preferred. 10Base-T Cabling Cat 5e cable with twisted pairs are recommended. Topology Ensure the Modbus RTU network cable is installed as a daisy chain from one device to the next. Maximum Nodes The maximum number of devices is 32 per Modbus RTU network and 64 per gateway. Terminator A terminator of 120-ohm impedance must be installed at each end of each Modbus RTU network. Ensure that this requirement is not overlooked in laying out the network architecture and when ordering product. Cable Shielding Use a shielded, twisted pair cable for communications. Never directly ground wire in more than one point on the shield. Doing so can induce large currents and result in communication problem. Repeater A repeater is not necessary unless the Modbus RTU network is extended beyond 1,000 m. Step-down Transformer A separate isolated double-wound transformer is recommended for supplying 24 VAC power to each gateway. If and when the same transformer is shared with other devices, observe the polarities of the power supply of all devices including the gateway. Termination Diagram Dimensions in mm IP Address Setting Open internet browser and enter the IP address of 192.168.10.32 in the address field. Confirm after the following data are displayed: BMGE Ethernet Device Chip: DM9051 (DAVICOM) MAC Address: xx: xx: xx: xx: xx: xx IP: 192.168.10.32 Gateway: 192.168.10.1 Mask: 255: 255: 255: 0 Notes: 1. BACnet operator workstation s IP address and BMGE s IP address must be in the same network segment or otherwise the BMGE will not be discovered by the browser. 2. When multiple BMGEs are connected to the same network and in service, the default IP address of each individual BMGE must be re-assigned online one by one and its new address must be unique in the network or otherwise there will be communication conflict. BMGE Series BACnet-over-Ethernet Gateways Product Bulletin 3

The monitoring status and control commands of the Modbus RTU devices can be displayed and operated via an internet browser by means of its intranet read/write properties. For example, the input/output status of a NT50-1 Modbus RTU networking thermostat will be displayed as: BMGE Ethernet Device Chip: MAC Address: DM9091 (DAVICOM) 00.:60:6e:90:51:00 IP: 0.0.0.0 192.168.10.6 Gateway: 0.0.0.0 192.168.10.1 MASK: 0.0.0.0 255.255.255.0 Slave Address: 01 Temperature Setpoint: 22.0 Operation Mode: Run Stop Control Mode: Fan Speed Command: Cool Auto Ambient Temperature: 24.0 Valve 1 Status: 100 Valve 2 Status: 00.0 Temperature Eng. Unit: Unoccupied Mode: Binary Input: Thermostat Keys: C Off Open Locked Unlocked Cooling Totalizator: 21.3 Heating Totalizator: 00.0 Submit Notes: 1. Enter the desired value to the text box of a corresponding object to perform the write operation. Press Submit to confirm new entry. 2. The value shown behind a text box is the object s current value, read only property. 3. Object of multiple selection type such as Run/Stop has read/write properties. Click Run or Stop to effect the desired action. Press Submit to confirm. 4. Object without the text box, such as ambient temperature, has the property of read only and its value cannot be changed. 5. The slave device s address can be set at the Slave Address object from 1 to 64, with 1 to 32 at Net 1 and 33 to 64 at Net 2. Press Submit to confirm new entry. Dynamic Created Objects The gateway spontaneously detects the presence of a NT10, NT50, NTAF, NSM, NC24A or NC24T slave that goes online in its NET 1 or NET 2 network and automatically creates a number of pre-defined objects associated with this slave s MAC address. When this slave goes offline, its objects will be automatically deleted. Notes: 1. When the device is connected to NET 1 port, its #xx range is 01 to 32. Example: MAC address = 01 and y = 1, object name and object will be displayed as #01NT.1-Temperature Setpoint and 10123.AO11 respectively. 2. When the device is connected to NET 2 port, its #xx range is 33 to 64. Example: MAC address = 01 and y = 2, object name and object will be displayed as #33NT.2-Temperature Setpoint and 10123.AO331 respectively. 4 BMGE Series BACnet-over-Ethernet Gateways Product Bulletin

For NT10 and NT50 Series Modbus RTU networking Room Thermostats Object Name Object Value Unit Type Read/Write Priority Array #xxnt.y - Temperature Setpoint 10123.AOxx1 (5-35) / (41-95) Analog #xxnt.y - Operating Mode 10123.BOxx1 Stop/Run Binary #xxnt.y - Control Mode 10123.MOxx1 Heat/Cool/ Fan Only/Auto #xxnt.y - Fan Speed Command 10123.MOxx2 High/Medium/ Low/Auto #xxnt.y - Ambient Temperature 10123.AIxx1 (5-35) / (41-95) Analog Input R #xxnt.y - Valve 1 Status 10123.AIxx2 (0-100) % Analog Input R #xxnt.y - Valve 2 Status 10123.AIxx3 (0-100) % Analog Input R #xxnt.y - Temperature Eng. Unit 10123.BIxx1 ºC/ºF Binary Input R #xxnt.y - Unoccupied Mode 10123.BIxx2 Off/On Binary Input R #xxnt.y - Binary Input 10123.BIxx3 Open/Closed Binary Input R #xxnt.y - Window Modeª 10123.MIxx1 Off/On/ Input R #xxnt.y - Fan Totalizator 10123.AVxx1 0-999999 hr Analog variable R/W #xxnt.y- Cooling Totalizator 10123.AVxx2 0-999999 hr Analog variable R/W #xxnt.y - Heating Totalizator 10123.AVxx3 0-999999 hr Analog variable R/W *** SYSTEM SELECT 10123.AV1 *1 Analog variable R/W *** SYSTEM SELECT 10123.AV2 *1 Analog variable R BMGE_MANAGER_10123 10123.DEV10123 Operational Device R ª This object is not applicable to and omitted in NT50 Series. Its value is displayed as Off/On in NT10 Series. For NTAF Series Modbus RTU Networking Room Thermostats Object Name Object Value Unit Type Read/Write Priority Array #xxnt.y - Temperature Setpoint 10123.AOxx1 (5-35) / (41-95) Analog #xxnt.y - Operating Mode 10123.BOxx1 Stop/Run Binary #xxnt.y - Control Mode 10123.MOxx1 Heat/Cool/ Fan Only/Auto #xxnt.y - Fan Speed Command 10123.MOxx2 H1/2/3/4/5/6/7/ Auto #xxnt.y - Ambient Temperature 10123.AIxx1 (5-35) / (41-95) Analog Input R #xxnt.y - Valve 1 Status 10123.AIxx2 (0-100) % Analog Input R #xxnt.y - Valve 2 Status 10123.AIxx3 (0-100) % Analog Input R #xxnt.y - Temperature Eng. Unit 10123.BIxx1 ºC/ºF Binary Input R #xxnt.y - Unoccupied Mode 10123.BIxx2 Off/On Binary Input R #xxnt.y - Binary Input 10123.BIxx3 Open/Closed Binary Input R #xxnt.y - Window Mode 10123.MIxx1 Off/On/ Input R #xxnt.y - Fan Totalizator 10123.AVxx1 0-999999 hr Analog variable R/W #xxnt.y- Cooling Totalizator 10123.AVxx2 0-999999 hr Analog variable R/W #xxnt.y - Heating Totalizator 10123.AVxx3 0-999999 hr Analog variable R/W *** SYSTEM SELECT 10123.AV1 *1 Analog variable R/W *** SYSTEM SELECT 10123.AV2 *1 Analog variable R BMGE_MANAGER_10123 10123.DEV10123 Operational Device R Mega Controls Limited Room 1521A, Star House 3 Salisbury Road, Tsimshatsui, Kowloon, Hong Kong Phone: +852 6281 1320 Fax: +852 3741 7084 E-mail: sales@megacontrols.com Website: www.megacontrols.com BMGE, 18-03(Mega) BMGE Series BACnet-over-Ethernet Gateways Product Bulletin 5

For NC24A Modbus RTU Networking Controllers Object Name Object Value Unit Type Read/ Priority Write Array #xxnc.y - Controller Setpoint 10123.AOxx1-99 to 999 Analog #xxnc.y - X1 Analog Input Value 10123.AIxx1-99 to 999 Analog Input R #xxnc.y - X2 Analog Input Value 10123.AIxx2-99 to 999 Analog Input R #xxnc.y - ECO Mode Status 10123.BIxx1 Off/On Binary Input R #xxnc.y - Day/Night Mode Status 10123.BIxx2 Day/Night Binary Input R #xxnc.y - Engineering Unit 10123.MIxx1 ºC/ºF/%/ Input R #xxnc.y - Application Number 10123.AVxx1 1 to 9 Analog Variable R #xxnc.y - Setpoint Differential 10123.AVxx2 (1 to 20 )/(1 to 99) Analog Variable R #xxnc.y - Control Bandwidth 10123.AVxx3-99 to 99 Analog Variable R #xxnc.y - Y1 Status 10123.AVxx4 0 to 100 % Analog Variable R #xxnc.y - Y2 Status 10123.AVxx5 0 to 100 % Analog Variable R #xxnc.y - Q1 Status 10123.AVxx6 0 to 100 % Analog Variable R #xxnc.y - Proportional Band 10123.AVxx7 (1 to 20)/(1 to 99) K Analog Variable R #xxnc.y - Integral Time 10123.AVxx8 0 to 30 min Analog Variable R *** SYSTEM SELECT 10123.AV1 *1 Analog Variable R/W *** SYSTEM SELECT 10123.AV2 *1 Analog Variable R BMGE_MANAGER_10123 10123.DEV10123 Operational Device R For NC24T Modbus RTU Networking Controllers Object Name Object Value Unit Type Read/ Priority Write Array #xxnc.y - Controller Setpoint 10123.AOxx1-99 to 999 Analog #xxnc.y - X1 Analog Input Value 10123.AIxx1-99 to 999 Analog Input R #xxnc.y - X2 Analog Input Value 10123.AIxx2-99 to 999 Analog Input R #xxnc.y - ECO Mode Status 10123.BIxx1 Off/On Binary Input R #xxnc.y - Day/Night Mode Status 10123.BIxx2 Day/Night Binary Input R #xxnc.y - Engineering Unit 10123.MIxx1 ºC/ºF/%/ Input R #xxnc.y - Application Number 10123.AVxx1 1 to 12 Analog Variable R #xxnc.y - Setpoint Differential 10123.AVxx2 (1 to 20 )/(1 to 99) Analog Variable R #xxnc.y - Control Bandwidth 10123.AVxx3-99 to 99 Analog Variable R #xxnc.y - Main Status 10123.AVxx4 0 to 100 % Analog Variable R #xxnc.y - Secondary Status 10123.AVxx5 0 to 100 % Analog Variable R #xxnc.y - Valve Stroke Time 10123.AVxx6 10 to 240 sec Analog Variable R #xxnc.y - Proportional Band 10123.AVxx7 (1 to 20)/(1 to 99) K Analog Variable R #xxnc.y - Integral Time 10123.AVxx8 0 to 30 min Analog Variable R *** SYSTEM SELECT 10123.AV1 *1 Analog Variable R/W *** SYSTEM SELECT 10123.AV2 *1 Analog Variable R BMGE_MANAGER_10123 10123.DEV10123 Operational Device R For NSM Series Modbus RTU Networking Setpoint Modules Object Name Object Value Unit Type Read/ Priority Write Array #xxns.y - Module Setpoint 10123.AOxx1-99 to 999 Analog #xxns.y - Operating Mode 10123.BOxx1 Stop/Run Binary #xxns.y - Analog Input Type 10123.AIxx1 0 or 1^ Analog Input R #xxns.y - Analog Input Value 10123.AIxx2-99 to 999 Analog Input R #xxns.y - Set Display Lower 10123.AVxx1-99 to 999 Analog Variable R/W #xxns.y - Set Display Upper 10123.AVxx2-99 to 999 Analog Variable R/W #xxns.y - Remote Set Lower 10123.AVxx3-99 to 999 Analog Variable R/W #xxns.y - Remote Set Upper 10123.AVxx4-99 to 999 % Analog Variable R/W *** SYSTEM SELECT 10123.AV1 *1 Analog Variable R/W *** SYSTEM SELECT 10123.AV2 *1 Analog Variable R BMGE_MANAGER_10123 10123.DEV10123 Operational Device R Notes: ^ 0 denotes 0-10 VDC input and 1 denotes temperature sensor input. 6 BMGE Series BACnet-over-Ethernet Gateways Product Bulletin