Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Similar documents
UL 489 or UL 1077 in control panels and equipment a quick guide

Industrial Control Panels Tested product combinations to meet NEC Article 409 and UL 508A Standard

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

UL 508 A standard-compliant design of industrial control panel

Equipment Short-Circuit Current Rating and Available Fault Current

Applying branch circuit breakers and supplementary protectors in North America

Short Circuit Current Ratings and AC Drives

Applying branch circuit breakers and supplementary protectors in North America

Spacing Requirements for Power Distribution and Terminal Blocks

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

UL508Afor Panel Builders Getting Started

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

FAZ Supplementary Protectors, FAZ Miniature Circuit Breakers, P2 Disconnect Switches Overview

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

Application Techniques CENTERLINE 2100 Motor Control Centers

Supplement to Instruction Manual

Learning Module 9: Miniature Circuit Breakers and Supplementary Protectors. 101 Basic Series

UL 489 DIN rail branch circuit breakers

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

Electrical Service Change-Tn Neenah

Document C0. Use for:

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

White Paper Surge Protective Devices in Automatic Transfer Switches

Miniature Circuit Breakers and Supplementary Protectors. Contents

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Circuit Protection Methods

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL


MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

Title Power Supply Units for Signalling Equipment - DC (Regulated & Filtered) Units. Reference Number SPS 30 - (RIC Standard: SC SP)

1. Coordination of series-rated devices is permitted where indicated on Drawings.

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Standards Update Notice (SUN) Issued: August 11, 2017

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

Electrical Plan Review

PowerFlex 400 AC Drive Guide Specification

1510 MOTOR CONTROLLERS

Entry Level Assessment Blueprint Electrical Occupations

WHITE PAPER. Overload or Short Circuit Protection? How to protect your design against both dangers. E-T-A Circuit Breakers USA. E-T-A Circuit Breakers

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

WMS SUPPLEMENTARY PROTECTORS

Supplement to Instruction Manual

920 Remote Control (RC) Switches

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

2014 NEC Code Changes. Code changes based on the 2014 NEC

Secondary Surge Arrester Instruction Manual Page 1 of 5

60103 Circuit Breaker

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

30-Cycle Rated Switchboards - Selectivity Tradeoffs

SECTION DISCONNECT SWITCHES

Medium Voltage Metal-Enclosed Power Capacitor Banks

STANDARD SUBMITTAL PACKAGE

ASCO 920 Remote Control (RC) Switches

UL 489 DIN Rail Miniature Circuit Breakers

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

Medium Voltage Metal-Enclosed Harmonic Filter Systems

UL 489 DIN Rail Miniature Circuit Breakers

Product Guide. UL 1077 DIN Rail Supplementary Protectors

PRODUCT BROCHURE. Deploying effective power protection in data centers

NEMA Standards Publication AB Establishing Levels of Selective Coordination for Low Voltage Circuit Breakers

Mitigating Arc Flash Hazards

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

GE Digital Energy. Power Quality

1.3. Miniature Circuit Breakers and Supplementary Protectors. Contents. WMZS Circuit Breaker. UL 1077 DIN Rail Supplementary Protectors

Solar Combiner Enclosure

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Standards Update Notice (SUN) Issued: April 25, 2017

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

ECNR/ECSR Class RK5 Dual-Element Time-Delay Fuses. Catalog Number ECNR (1-600A) 250Vac or Less Catalog Number ECSR (1-600A) 600Vac or Less

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

UL 489 Cable-In / Cable-Out Branch Circuit Breaker

Advantage Series Switch-Rated IEC Pin & Sleeve. Highest Performing IEC Pin & Sleeve Connections for the Most Demanding Environments

Powering innovation. Powering efficiency. Powering home

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011

PanelFAST. Setting a new standard for immediate product availability with Square D Ready to Install (RTI) Panelboards

1.2. Miniature Circuit Breakers and Supplementary Protectors. Contents. WMZ Circuit Breaker. UL 489 DIN Rail Miniature Circuit Breakers

ABB Industrial Systems Inc. Standard Drives. ACH500-06E Effective 6/1/95

Close Protection from Moeller. miniature branch circuit breakers miniature supplementary protectors

Solid-State Switching Devices

Superseding REVISED SHEET NO. 34D-8 REVISED SHEET NO. 34D-8 Effective May 27, 2010 Effective December 3, 2011

Install Motor Controller User Manual

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

E-Series General Specifications

Agilent 34401A 6½ 桁マルチメータ ユーザーガイド

FTA750 LIMITED SERVICE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

Transcription:

Understanding SCCR What is SCCR? When it comes to industrial machinery, it s critical to ensure that electrical panels are designed and built with the proper SCCR to maintain the system, eliminate downtime and increase worker safety. The goal of this paper is to explain why it is important, and how to find the calculations needed. SCCR stands for Short-Circuit Current Rating, which is defined in the 2017 NEC (National Electric Code), Article 100 as: The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria. In simpler terms, SCCR is the maximum short-circuit current an electrical component can safely withstand without causing a shock or fire hazard. In general, the SCCR rating for an electrical panel is based on understanding each electrical components SCCR rating in that panel. SCCR has become an increasingly important topic, regarding to the installation of industrial machinery and electrical panels at customer facilities. Why Is SCCR Important? Because the SCCR represents the highest short-circuit fault current that equipment such as industrial control panels can safely withstand, exceeding the SCCR may cause catastrophic and violent equipment and component failure. 2017 NEC ARTICLE 670 INDUSTRIAL CONTROL PANELS 409.22 Short Circuit Current Rating. (A) Installation. An industrial control panel shall not be installed where the available short-circuit exceeds its short-circuit rating as marked in accordance with 409.110(4) Therefore, it s necessary to identify (calculate) the maximum short-circuit current that can be present where the industrial control panel or other equipment is installed. The available short-circuit current must be less than the marked SCCR of the industrial control panel to comply with the NEC. It s important to understand short-circuit current ratings for industrial control panels. Industrial control panel is a general term that describes an assembly of two or more components that are enclosed. The assembly can be power, control or both, but doesn t include the controlled equipment. In UL 508A, the UL Standard for Safety for Industrial Control Panels and the National Electrical Code (NEC ) the standard requires industrial control panels that contain power circuit components (supply main line power to loads such as motors, heating, lighting, appliances or receptacles) to be marked with an SCCR, previously referred to as a withstand rating. Page 1 of 6 THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

As referenced in UL 508A and the NEC, industrial control panels that contain only control circuit components do not have to be marked with an SCCR. If the industrial control panel contains a power circuit branch-circuit overcurrent protective device supplying the control circuit, then the SCCR must be marked based on the interruption rating of the overcurrent protective device. Power Circuit vs. Control Circuit Prior to the release of the latest edition of UL 508A, Supplement SB dated December 20, 2013, SCCR applied only to the power circuit of a control panel. The power circuit supplies electricity to the workers that do the heavy lifting, powering large motors, for example. This is typically somewhere between 240VAC ~ 600VAC, 3 phase power. The control circuit is lower power, as low as 5 volts. As the name implies, it controls the operation of the power circuit, but is isolated from it. This is important so as to isolate the user from the high voltages and currents of the power circuit. Think of the control circuit as the brains and the power circuit as the brawn of a control panel. Figure 1: Power and Control Circuits L1 L2 L3 F1 F1 F1 L1 F3 L1 F3 1 3 5 S0 2 4 6 1 3 5 S1 S1 F2 F2 F2 2 4 6 F2 F2 U V W L2 L2 (a) (b) (c) (a) Power Circuit; (b) Control Circuit (Momentary Contact); (c) Control Circuit (Maintained Contact) Page 2 of 6

Calculating Short-Circuit Current Rating (SCCR) Today, the majority of electrical components have the SCCR marked on the component itself by the manufacturer or a combination rating on the UL website. If the SCCR is not available, a default value can be assigned by referencing Table SB4.1 in the UL 508A standard. Taking these values and the time needed to completely understand the circuit design being used, you realize that basically the component with the smallest SCCR in certain circuits determines the electrical panel SCCR rating. Step 1. Identify all the components in the power circuit. These include, but may not be limited to: Disconnect switches Circuit breakers Fuse holders Overload relays Motor controllers (contactors) Terminal blocks or power distribution blocks Step 2. Determine the SCCR value for all components in the power circuit. SCCR is usually marked on the component, combination ratings are available on the UL website, or with the manufacturer s instructions. If not available from the manufacturer, the SCCR value can be determined by using UL Table SB4.1 (see Appendix). Figure 2: Feeder and Branch Circuits FEEDER CIRCUIT BRANCH 1 BRANCH 2 Page 3 of 6

Step 3. Determine the SCCR for each branch circuit. The lowest component SCCR is the equivalent branch circuit SCCR Step 4. Determine the SCCR for the feeder circuit. Step 5. Take in to account feeder circuit Over Current Protection Devices. Step 6. Determine the lowest value for any component or branch circuit, this is the SCCR for the control panel. Figure 3: Example SCCR Disconnect Branch 1 = 100kA Branch 2 = 50kA 60A Fuse Terminal Block I P = 10kA @ 100kA 100kA Branch 3 = 5kA 20A Miniature Circuit Breaker 480V Primary 5kVA 120V Secondary 25A Fuse 30A Fuse Power Transformer Control Circuit 15A Molded Case Circuit Breaker 65kA 18A Contactor Overload Relay 10kA Motor Controller 5kA Power Supply Smart Programmable Relay Push Button Surge Protection Device 12A Contactor Overload Relay SB4.1 5kA 10HP Motor M SCCR for panel = 5kA Indicator 5HP Motor Page 4 of 6

Why SCCR is Important for Installation Since the release of the 2005 NEC, industrial machinery electrical panels are required to be marked with an SCCR rating. Prior to this, panel manufacturers only had to supply the interrupting rating of the panel overcurrent protective device, or the amperage at which the main disconnect to the panel would trip. This means that since the 2005 NEC release, industrial machinery electrical panel manufacturers had to start not only calculating SCCR ratings for their panels, but also understand the available short-circuit current that is supplied at the customer facility where installation of the panel will be. If the available short-circuit current supplied to the panel is higher than the SCCR rating marked on the rating label of the panel, installation of the panel is prohibited by NEC, 670.5. This requires industrial machinery electrical panel installers to verify the available fault current at their customer facilities. 2017 NEC ARTICLE 670 INDUSTRIAL MACHINERY 670.5 Short Circuit Current Rating (1) Industrial machinery shall not be installed where the available short-circuit current exceeds its short-circuit rating as marked in accordance with 670.3(A) (4). SCCR Compliance To summarize, three things are important to remember when complying with SCCR ratings. The SCCR for the control panel is determined the lowest SCCR value for any component or branch circuit. The available fault current must be determined at the customer facility where the electrical panel will be installed. This determination can be done by the manufacturer or the installation contractor. The SCCR rating of the electrical panel must be equal to or greater than the available fault current determined. Disclaimer: The content provided in this white paper is intended solely for general information purposes and is provided with the understanding that the authors and publishers are not herein engaged in rendering engineering or other professional advice or services. The practice of engineering is driven by site-specific circumstances unique to each project. Consequently, any use of this information should be done only in consultation with a qualified and licensed professional who can take into account all relevant factors and desired outcomes. The information in this white paper was posted with reasonable care and attention. However, it is possible that some information in these white papers is incomplete, incorrect, or inapplicable to particular circumstances or conditions. We do not accept liability for direct or indirect losses resulting from using, relying or acting upon information in this white paper. Page 5 of 6

Appendix Table SB4.1 Assumed Maximum Short Circuit Rating for Unmarked Components Component Short Circuit Current Rating, ka Bus Bars 10 Circuit Breaker (including GFCI type) 5 Current Meters a Current Shunt 10 Fuse Holder 10 Industrial Control Equipment: a. Auxiliary Devices (Overload Relay) 5 b. Switches (other than mercury tube type) 5 c. Mercury Tube Switches 5 Rated over 60 amperes or over 250 volts 3.5 Rated 250 volts or less, 60 amperes or less, and over 2 kva Rated 250 volts or less and 2 kva or less 1 Motor controller (including combination motor controllers, float and pressure-operated motor controllers, power conversion equipment, and solid-state motor controllers) rated in horsepower (kw)d a. 0 50 (0 37.3) 5c b. 51 200 (38 149) 10c c. 201 400 (150 298) 18c d. 401 600 (299 447) 30c e. 601 900 (448 671) 42c f. 901 1600 (672 1193) 85c Meter socket base 10 Miniature or miscellaneous fuse 10b Receptacle (GFCI type) 2 Receptacle (other than GFCI type) 10 Supplementary protector 0.2 Switch Unit 2 Terminal block or power distribution block 10 Multi-point interconnection power cable assembly 5 a. A short circuit current rating is not required when meter connected via a current transformer or current shunt. A directly connected current meter shall have a marked short circuit current rating. b. The use of a miniature fuse is limited to 125-volt circuits. c. Standard fault current rating for motor controller rated within specified horsepower range. d. Highest rated horsepower of motor controller. Source: UL Standard for Safety for Industrial Control Panels, UL 508A, Second Edition, December 20, 2013 Page 6 of 6 THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing