Switching Power Supply DIN-Rail Mount Power Supply With Capacity Up to 240 W for General or Industrial Applications Wide power range: 15 to 240 W 15 W and PFC Models with Universal voltage of 100 to 230 VAC 120/240 Selectable on Non-PFC Models 30, 50, 100 and 240 W Meets EN61000-3-2 (limits for harmonic current emissions) with PFC on 240 W T-type models with undervoltage detection function are available: 15-, 30-, and 50-W: Undervoltage detection indicator 100- and 240-W: Undervoltage detection indicator and output Conforms to UL, CSA, VDE, and CE Safety Standards 3-year warranty Ordering Information SWITCHING POWER SUPPLIES Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC Standard 100 -- 240 VAC 15 W 5 V 2.5 A -01505 12 V 1.2 A -01512 24 V 0.6 A -01524 120/240 0 VAC selectable ec e 30 W 12 V 2.5 A -03012 24 V 1.3 A -03024 50 W 24 V 2.1 A -05024 100 W 24 V 4.2 A -10024 240 W 24 V 10 A -24024 Undervoltage detectionec indicator 100 -- 240 VAC 15 W 5V 2.5 A -01505T Undervoltage detection indicator and output t With PFC 12 V 1.2 A -01512T 24 V 0.6 A -01524T 120/240 0 VAC selectable ec e 30 W 12 V 2.5 A -03012T 24 V 1.3 A -03024T 50 W 24 V 2.1 A -05024T 100 W 24 V 4.2 A -10024T 240 W 24 V 10 A -24024T 100 -- 240 VAC 240 W 24 V 10 A -P24024
MODEL NUMBER LEGEND - 1 2 3 4 1. Power Factor Correction None: No P: Yes 2. Power Ratings 015: 5 W 030: 30 W 050: 50 W 100: 100 W 240: 240 W 3. Output Voltage 05: 5 V 12: 12 V 24: 24 V 4. Additional Functions None: Standard type T: With undervoltage detection indicator (15-/30-/50-W) With undervoltage detection indicator and output (100-/240-W) ACCESSORIES (SOLD SEPARATELY) Description Length Width Part number DIN-rail (See Dimensions section for details.) 0.5 m (1.64 ft) 7.3 mm (0.29 in) PFP-50N Specifications Item PFC No 1 m (3.28 ft) 7.3 mm (0.29 in) PFP-100N 1 m (3.28 ft) 16 mm (0.63 in) PFP-100N2 Power rating 15 W 30 W 50 W 100 W 240 W 240 W Efficiency (typical) Life expectancy Input Voltage 100 to 240 VAC (85 to 264 VAC) 66% to 84% (depends on the model) 8 yrs. min. (with standard installation at 40 C at the rated input with a 50% load) 120 VAC (85 to 132 VAC) or 240 VAC (170 to 264 VAC) selectable 120 VAC (85 to 132 VAC) or 240 VAC (170 to 253 VAC) selectable Yes 100 to 230 VAC (85 to 253 VAC) Frequency 47 to 450 Hz 47 to 63 Hz Current 100-V input 0.45 A max. 0.9 A max. 1.3 A max. 2.5 A max. 5.5 A max. 4Amax. (See Note 1.) 200-V input (230-V input) 0.25 A max. 0.6 A max. 0.8 A max. 1.5 A max. 3.5 A max. (3.2 A max.) 2Amax. (1.4 A max.) Power factor --- 0.95 min. Leakage cur- 100-V input 0.5 ma max. rent (See Note 1.) 200-V input 1mAmax. Inrush current 100-V input 15 A max. 25 A max. (see Note 1.) 200-V input 30 A max. 50 A max. Noise filter Yes Output (See Note 2.) Voltage adjustment range Ripple (See Note 1.) ±10% (adjustable with variable resistor (V.ADJ)) 2% (p-p) max. Input variation influence 0.5 % max. (at 85 to 132 VAC/170 to 264 VAC input, 100% load) 0.5%max.(at85to 132 VAC/170 to 253 VAC input, 100% load) Load variation influence 1.5% max. (with rated input, 10 to 100% load) Temperature variation 0.05%/ C max. (with rated I/O at an ambient temperature range between 0 C to50 C) influence Rise time Hold time (See Note 1.) 100 ms max. (up to 90% of output voltage at rated input and output) 20 ms min. (This table continues on the next page.) Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC). 2. The output specification is defined at the power supply output terminals. 200 ms max. 300 ms max. 1000 ms max.
Specifications Table -- continued from previous page Item PFC No Yes Power rating 15 W 30 W 50 W 100 W 240 W 240 W Additional function Overload protection Overvoltage protection Undervoltage detection indicator (DC LOW indicator) Undervoltage detection output (DC LOW output) 105% to 160% of rated load current (typical), inverted L drop type, automatic reset No, except the -T (shut-off type with an input resetting method) The -T models only (color: red) --- - 10024T model only - 24024T model only Parallel operation Impossible Possible (2 units max.) Characteristics Ambient temperature Operating See the derating curve in the Engineering Data section Storage --25 C to65 C (--13 F to 149 F) Ambient humidity Operating 25% to 85% Dielectric strength Insulation resistance Vibration resistance Shock resistance Output indicator Electromagnetic interference (See Note 1.) Limits for harmonic current emission Storage 25% to 90% 3,000 VAC at 50/60 Hz for 1 min. (between all inputs and outputs) 2,000 VAC at 50/60 Hz for 1 min. (between all inputs and GR terminal) 1,000 VAC at 50/60 Hz for 1 min. (between all outputs and GR terminal) 100 MΩ min. at 500 VDC (between all outputs and all inputs/gr terminal) Malfunction: 10 to 55 Hz, 0.375-mm single amplitude for 2 hrs each in X, Y, and Z directions Malfunction: 294 m/s 2 (approx. 30G), 3 times each in ±X, ±Y, and ±Z directions Yes (green) Conforms to FCC class B Conforms to FCC class A --- Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 2 hrs eachinx,y, and Z directions --- Conforms to EN61000-3-2, IEC1000-3-2 EMC Emission Enclosure: EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A Immunity ESD: EN61000-4-2: 4 kv contact discharge (level 2) 8 kv air discharge (level 3) Immunity RF-interference: ENV50140: 10 V/m (10 k to 1 GHz) (level 3) Immunity Conducted Disturbance: ENV50141: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: EN61000-4-4: 2 kv power-line (level 3) 2 kv I/O signal-line (level 4) EMC standards Conforms to EN50081-2 and EN50082-2 Conforms to EN50081-2 and EN50082-2 (See Note 3.) Approved standards UL 508, CSA C22.2 No.14, UL1012, CSA E.B1402C VDE0160, VDE0805, EN60950 (IEC 950) Conforms to VDE0106/P100 and CE Weight 260 g max. 380 g max. 480 g max. 600 g max. 1800 g max. 2200 g max. Note: 1. Defined with a 100% load and the rated input voltage (100 or 200 VAC). 2. The output specification is defined at the power supply output terminals. 3. To ensure the Emission Enclosure rating, a ferrite ring core should be used on all cables.
Engineering Data DERATING CURVE Note: The derating curve depends on the mounting position of the Power Supply. 15-/30-/50-/100-W Models Installation B Installation A Load (%) Ambient temperature ( C) 240-W Model Single-Unit Operation Parallel-Unit Operation Load (%) P24024: 100-V input (see note) Load (%) Top Ambient temperature ( C) Ambient temperature ( C) Note: 100-V input: 85 to 132 VAC Note: Provide a clearance of at least 10 mm between Units when installing them in horizontal series. Installing them in vertical series is not allowed. Follow the standard mounting directions. Mounting Position (A) Standard (Vertical) Installation Top (B) Horizontal Installation Note: Not permitted for 240-W models. Top
INRUSH CURRENT, RISE TIME, HOLD TIME Input ON Input OFF AC input voltage Inrush current on input application AC input current 90% 96.5% Output voltage Rise time: 100 to 1000 ms max. depending on the model. Hold time 20 ms min. OVERLOAD PROTECTION The Power Supply is provided with an overload protection function that protects the load and the power supply from possible damage by overcurrent. When the output current rises above a set value (105% of the rated output current), the protection function is triggered, decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared. OVERVOLTAGE PROTECTION (-T MODELS ONLY) The Power Supply is provided with an overvoltage protection function that protects the load and the Power Supply from possible damage by overvoltage. When the output voltage rises above a set value, the protection function is triggered, shutting off the output voltage. If this occurs, reset the Power Supply by turning it off for 1 minute min. and then turning it on again. Rated voltage Output voltage (V) Output voltage (V) Approx. 20% 10% Rated output voltage --10% Variable range Overvoltage protection operating Output current (%) Note: To avoid damage to (or deterioration of) the circuitry, do not short-circuit the output terminals of the or use the with excessive output current for a long time.
Nomenclature -015-030/ -050-100 1 1 8 1 5 7 6 5 7 6 5 7 6 2 3 2 3 4 2 3 4-24024 8 1 5 7 6 2 3 4 9 1. DC output terminals -- Connect the load lines to these terminals. 2. Input terminals -- Connect the input lines to these terminals. 3. Ground terminal (GR) -- Connect a ground line to this terminal. 4. Input voltage selector terminals -- Selects a 100 V or 200 V input voltage. 5. Output indicator (DC ON) -- Lights while a Direct Current (DC) output is ON. 6. Output voltage adjuster (V.ADJ) -- It is possible to increase or decrease the output voltage. 7. Undervoltage detection indicator (DC LOW) ---T only. 8. Undervoltage detection output (DC LOW) -- 100- and 240-W -100T models only. 9. Parallel/single operation selector -- Set to PARALLEL for parallel operation.
Operation MODELS WITH UNDERVOLTAGE DETECTION INDICATOR AND OUTPUT FUNCTION (-T ONLY) If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the -T (DCLOW indicator) will be lit. In the case of the -10024T/24024T, a voltage drop alarm will be output via the relay available in the models (DC LOW output). Note: This function detects the voltage at the output terminal of the Power Supply. To check the precise output voltage, measure the voltage at the load terminal. Indicator Voltage Operation of 10024T/ 24024T s output (DC LOW output) (See Note 2.) Green: DC ON If the voltage at the output terminal is more than 90% of the rated voltage, the green indicator will be lit. Red: DC LOW Green: DC ON If the voltage at the output terminal is 75% to 90%, Red: DC LOW (see note 1) the red indicator will be lit. Green: Red: DC ON DC LOW If the voltage at the output terminal is 0 V, both the green and red indicators will not be lit. Note: 1. The more the voltage at the output terminal drops, the darker both the green and red indicators will be. 2. The relay contacts have a capacity of 0.1 A at 24 VDC. BLOCK DIAGRAMS -015 (15 W) Fuse (3 A) AC (L) Noise filter AC (N) GR Inrush current Rectifier protection circuit Drive control circuit Rectifier Detector Undervoltage detection indicator DC OUTPUT -- V Overload Photocoupler Overvoltage (see note) Overvoltage protection circuitry (see note) Note: The overvoltage protection circuitry and undervoltage detection indicator are available in the -015T only.
-030 (30 W) -050 (50 W) Fuse (3 A) AC (L) Noise filter AC (N) 100 or 200 V (selectable) (See Note 2.) GR Inrush current protection circuit Drive control circuit Rectifier Rectifier Detector Undervoltage detection indicator DC OUTPUT -- V Photocoupler (See Note 1.) Overload Overvoltage Overvoltage protection circuitry (See Note 1.) Note: 1. The overvoltage protection circuitry and undervoltage detection indicator are available in the -0T only. 2. Use the short bar to short-circuit terminals 4 and 5 to select 100 to 120 VAC and remove the short bar to select 200 to 240 VAC. -100 (100 W) -24024 (240 W) Fuse (5 A) AC (L) Noise filter AC (N) 100 or 200 V (selectable) (See Note 2.) GR Inrush current protection circuit Drive control circuit Rectifier Rectifying and smoothing circuit Detector DC OUTPUT -- V DC LOW Overload Photocoupler Overvoltage Overvoltage protection circuitry (see note) Undervoltage detection indicator/output (See Note 1.) Note: 1. The overvoltage protection circuitry and undervoltage detection indicator are available in the -T only. 2. Use the short bar to short-circuit terminals 4 and 5 to select 100 to 120 VAC and remove the short bar to select 200 to 240 VAC (100 W), 200 to 230 W (240 W). -P24024 (240 W) Fuse (8 A) AC (L) AC (N) Noise filter Inrush current protection circuit Rectifier Harmonic current emission control Smoothing Rectifying and smoothing circuit DC OUTPUT -- V Drive control circuit Overload Detector GR
SELECTION OF 100 TO 120 OR 200 TO 240 VAC VOLTAGE Select a 120 V or 240 V input by shorting or opening the Input Voltage Selector Terminals, as shown in the following diagram (All models except for 15-W and 240-W models with PFC). 100 to 120 V Input GENERATING OUTPUT VOLTAGE (±) An output of ± can be generated by using two Power Supplies as shown below, because the Power Supply produces a floating output. When connecting the Power Supplies in series with an operation amplifier, connect diodes to the output terminals as shown by the dotted lines in the figure. No diodes are required with 100-W/240-W models. Use the short bar to short-circuit terminals 4 and 5. 200 to 240 V Input PARALLEL OPERATION 100-W/240-W models can be operated in parallel. Remove the short bar. 100- and 240-W Models SERIES OPERATION Load 100-W/240-W model can be operated in series. 100-W/240-W Model Note: When operating the 240-W model in parallel operation, set the switch to PARALLEL. Refer to the derating curve for the rated current under this operation. 15-, 30-, and 50-W Models 15-, 30-, 50-W Models Load Parallel Operation Precautions The length and thickness of each wire connected to the load must be the same so that there is no difference in voltage drop value between the load and the output terminals of each Power Supply. Adjust the output voltage of each Power Supply so that there will be no difference in output voltage between each Power Supply. If the 240-W Power Supply is used in single operation under the parallel operation setting, the overcurrent protection will be actuated at an output of 90% to 95% (in current), and will not allow a 100% output.
Dimensions Unit: mm (inch) SWITCHING POWER SUPPLIES -015 45 (1.77) 9.8 8.3 7.5 75 (2.95) 58.1 45 35 4.6 (sliding 7 max.) M3.5 with square washer 91 5 96 (3.78) Mounting Holes Two, M4 or 4.5-dia. mounting holes 60 35-030 -050 90 (3.54) 80 9.8 8.3 Four, 4.5 dia. 7.5 58.1 60 45 35.3 75 (2.95) 4 M3.5 with square washer (sliding 7 max.) M3.5 terminal screw Short bar 91 5 96 (3.78) Mounting Holes Four, M4 or 4.5-dia. mounting holes 60 (2.36) 80 (3.15)
-100 145 (5.71) 9.8 8.3 135 Four, 4.5 dia. 7.5 75 (2.95) 58.1 60 45 35.2 4 (sliding 7 max.) M3.5 with square washer M3.5 terminal screw Short bar 91 96 (3.78) 5 Mounting Holes Four, M4 or 4.5-dia. mounting holes 60 (2.36) 135 (5.31) -24024 280 (11.02) 270 (10.63) 9.8 (0.39) 8.3 (0.33) Four, 4.5 dia. 7.8 (0.31) 27.5 (1.08) 112.8 (4.44) 130 (5.12) 100 (3.94) 35 (1.38) 4 (sliding 8 max.) M3.5 with square washer M3.5 terminal screw Short bar 115 (4.53) 130 (5.12) 4.2 (0.17) Mounting Holes 270 (10.63) 115 (4.53) Four, M4 or 4.5-dia. mounting holes
Unit: mm (inch) DIN-RAIL MOUNTING TRACK PFP-100N/PFP-50N PFP-100N2 4.5 7.3±0.15 35 27 4.5 12, 25 x 4.5 oblong 35±0.3 27 24 16 29.2 15 25 25 25 25 10 1,000 (500) (See Note.) 10 15 (5) (See Note.) 1 15 25 25 25 25 15 10 10 1,000 1 1.5 Note: The values shown in parentheses are for the PFP-50N. Precautions MOUNTING To improve and maintain the reliability of the Power Supply over a long period of time, consider the heat dissipation that takes place. The Power Supply is designed to radiate heat by means of natural air-flow. Mount the Power Supply so that air flow takes place around the Power Supply. When mounting two or more Power Supplies side-by-side, allow at least 20 mm (0.79 in.) spacing between them, as shown in the following illustration. Omron recommends forced-air cooling. To DIN-Rail Mount the Power Supply To mount the Power Supply on a DIN rail, hook portion (A) of the Power Supply to the rail and press the Power Supply toward direction (B). To Remove To remove the Power Supply, pull down portion (C) with a flat-blade screwdriver and pull out the Power Supply. (C) Rail stopper 30 mm min. (A) (B) 20 mm min. Air
NOTE: DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters to inches divide by 25.4. OMRON ELECTRONICS, INC. One East Commerce Drive Schaumburg, IL 60173 1-800-55-OMRON OMRON CANADA, INC. 885 Milner Avenue Scarborough, Ontario M1B 5V8 416-286-6465 Cat. No. GC PS4 3/98 Specifications subject to change without notice. Printed in U.S.A.