This Datasheet for the IC69C11 Communications Coprocessor, C, RTU, SNP, and SNPx Protocols http://www.cimtecautomation.com/parts/p-144-ic69cmm11.aspx Provides the wiring diagrams and installation guidelines for this GE Series 90-30 module. For further information, please contact Cimtec Technical Support at 1-866-599-650 sales@cimtecautomation.com
1 1 Communications odules IC69C11 Communications Coprocessor odule (C) (IC69C11) datasheet Features Single-Slot odule SNP/SNP-X Protocol (master, slave) CC Protocol (master, slave, peer) RTU odbus Protocol (slave only) Supports connection to S-DOS or Windows programming and configuration software package (monitor only) 12 hz, 80C186 icroprocessor Two RS-422/RS-485 or RS-232 Serial Ports CC, RTU and SNP/SNP-X Available on Either or oth Ports Simultaneous Communications on oth Ports (up to 9.6 Kbps, or 19.2 Kbps individually) High Performance Access to PLC emory Three Status LEDs Reset pushbutton Soft Switch Configuration (no switches or jumpers) No attery Required Functions The Communications Coprocessor odule (C) is a member of a family of communication modules, and provides both communications control (CC), remote terminal (RTU), and general IC69 communications (SNP) functionality. CC, RTU and SNP are available on either or both serial ports in any of nine possible configurations: CC/CC, CC/RTU, RTU/CC, RTU/RTU, SNP/SNP, SNP/CC, CC/SNP, SNP/RTU, and RTU/SNP. The C provides both the RS-232 and RS-485 Interfaces and communicates with the PLC CPU over the backplane. any Cs can be placed in a single IC69 PLC system as illustrated by Figure 2. Communications Coprocessor odule (C) OK COUNICATIONS COPROCESSOR C 11 ODULE OK ON = OK, ACTIVE LINK = COUNICATING PUSH TO RESTART APPLICATION COPATILE COPATILE ODULE FUNCTION COUNICATIONS COPROCESSOR & 2 RS 232 & 2 PIN 1 2 3 4 5 8 20 PIN 9 10 11 12 13 21 22 23 24 25 SIGNAL SHIELD TD RD RTS CTS DCD DTR SIGNAL SD (A) RTS (A) CTS (A) TER PIN 11 RD (A) SD () RTS () CTS () TER PIN 25 RD () CONFIGURA TION DEPENDENT ODULE IC69C11 LAEL 44A2658 124R01 a44823 Figure 1. Communications Coprocessor odule S-DOS and Windows are registered trademarks of icrosoft Corporation. Series 90-0 Programmable Controller Data Sheet anual 1-1
2 CC: Functions provided by the C module in the CC mode of operation are: read/write of register, input and output tables (PLC memory types %R, %I and %Q); bit set/clearof inputs and outputs (%I and %Q); read of scratch pad; Q sequence commands for fast reads; and the ability to modify the diagnostic status word. In the master and peer CC configurations, the C module initiates communications with remote devices through application ladder program communications requests (COREQs). RTU: The RTU mode of operation is a query/response protocol used for communicating between the C and a host computer. The host computer is the master device and transmits the query to the RTU slave which responds to the master. In RTU mode, only slave configuration is available. In the RTU slave protocol, the following functions are provided: read input and output tables (%I and %Q), read analog input (%AI), read register table (%R), read scratchpad, read exception status, force a single or multiple output(s) (%Q), preset a single or multiple register(s) (%R), report the device type, and perform loopback maintenance. Communications odules Communications Coprocessor odule (C) SNP/SNP-X: SNP is the native protocol of all IC69 PLCs. SNP is a master-slave protocol, where the slave device responds to requests from the master. An SNP slave device is built into every IC69 PLC. Each serial port on the C can be configured to provide SNP master or slave capability. The SNP protocol on the C module provides read and write access to PLC memory (types %R, %I, %Q, %AI, %AQ, %T, %, %P, %L, and %G), full Series 90 Datagram support, and many status and control functions. An Autodial feature is also provided to control a modem attached to an SNP master port. The SNP-X extensions to SNP provide easy-to-use, high performance read and write access to PLC memory (types %R, %I, %Q, %AI, %AQ, %T, %, and %G). SNP-X is especially useful for simple, high-speed data acquisition and control in multidrop configurations. As an SNP master, the C module initiates communications with remote devices through application ladder programs communication requests (COREQS). An SNP master port on a C module can communicate with the SNP slave port built into any IC69 PLC, or with other SNP slave devices. As an SNP slave, the C module provides additional communications port(s) for connection to remote operator interface units or other SNP communications devices. The S-DOS or Windows based software package may be connected to an SNP slave port on a C module for data monitoring only. Programming and configuration of IC69 PLCs are not possible through the C SNP ports. 1-2 Series 90-0 Programmable Controller Data Sheet anual
Communications odules Communications Coprocessor odule (C) 3 Systems Configuration Figure 2 illustrates typical C interface installations in a IC69 PLC system. PARALLEL a45299 IC69 PLC (RACK 0) P S C C C G P T C U PROGRAER ONE ETER IC69 PLC (RACK 1) (GENERIC) PC (GENERIC) PC R C ASTER CC DEVICE PEER CC DEVICE IC69 PLC (RACK 6) (GENERIC) PC R C NOTE ALL RACKS UST E AT SAE POTENTIAL (8 RACKS AXIU). ASTER RTU DEVICE SNP SLAVE DEVICES ONE ETER C C P U IC693 PLC IC69 PLC (RACK ) IC692 PLC P S C P U T C IC69 PLC P S R I/O TERINATOR (LAST RACK) LEGEND CPU SELECTED CPU ODEL R US RECEIVER ODEL, E11 T US TRANSITTER ODEL, E13 GC GENIUS US CONTROLLER, E31 C COUNICATIONS COPROCESSOR ODULE PS POWER SUPPLY, PWR10/11/24/48 Figure 2. Typical PLC System Configuration Series 90-0 Programmable Controller Data Sheet anual 1-3
4 odule Physical Description The C module is a single-slot module that plugs into either the IC69 PLC or I/O rack. Figure 3 shows the maintenance controls and indicators located on the C module. a44825 Communications odules Communications Coprocessor odule (C) User aintenance Items The C module has the following user-accessible elements: Three LEDs located at the top of the module. Restart Pushbutton: located immediately beneath the LEDs. Two Serial Ports: two 25-pin female connectors provide RS-232 and RS-422/RS-485 communication. Installation C 11 ODULE OK ON = OK, ACTIVE LINK = COUNICATING PUSH TO RESTART APPLICATION Installation should not be attempted without referring to the Installation anual. (See Related Publications listed on page 6.) ake sure rack power is OFF before attempting to install module. Install module in the rack (see Figure 2). Turn ON power. The C is configurable only using the S-DOS or Windows programming software package. COPATILE Status Indication C 11 1-4 COPATILE ODULE FUNCTION COUNICATIONS COPROCESSOR & 2 RS 232 PIN SIGNAL 1 2 3 4 5 8 20 & 2 PIN SIGNAL 9 10 11 12 13 21 22 23 24 25 SHIELD TD RD RTS CTS DCD DTR SD (A) RTS (A) CTS (A) TER PIN 11 RD (A) SD () RTS () CTS () TER PIN 25 RD () CONFIGURA TION DEPENDENT ODULE IC69C11 LAEL 44A2658 124R01 Figure 3. C odule - User Details Three Status LEDs are available as shown in Figure 3. The top LED indicates the condition of the module. The bottom two LEDs indicate activity at the serial ports: Port 1 LED indicates activity on port 1; Port 2 LED indicates activity on port 2. The module should power up and blink the top LED. When the diagnostics have completed successfully, the top LED stays on. Pushbutton Control One pushbutton is provided. Push to reinitialize communications at both serial ports. Serial Ports oth ports are RS-232 and RS-422/RS-485 compatible. oth ports acting simultaneously can each provide up to 9.6 Kbps of full duplex data communications, or up to 19.2 Kbps individually. Series 90-0 Programmable Controller Data Sheet anual
Communications odules Communications Coprocessor odule (C) 5 Port 1 (3PL) and Port 2 (4PL): Table 2. Port 1 or 2: RS-422/RS-485 Connectors 3PL and 4PL contain signals for both RS-232 and RS-422/RS-485 types of communication circuits. The pin assignment for the RS-232 signals are per the RS-232 specification with an exception that pins not normally used for RS-232 are used for RS-422/RS-485 signals. Refer to Tables 1 and 2. Pin Table 1. Port 1 or 2: RS-232 Function Signal Name I/O 1 Shield - - 2 Transmitted Data TD Output 3 Received Data RD Input 4 Request To Send RTS Output 5 Clear To Send CTS Input Signal Ground 0V - 8 Data Carrier Detect DCD Input 20 Data Terminal Ready DTR Output Pin Function Signal Name I/O 9 Send Data (A) SD (A) Output 10 Request To Send (A) RTS (A) Output 11 Clear To Send (A) CTS (A) Input 12 Termination for pin 11 - - 13 Receive Data (A) RD (A) Input 21 Send Data () SD () Output 22 Request To Send () RTS () Output 23 Clear To Send () CTS () Input 24 Termination for pin 25 - - 25 Receive Data () RD () Input Configuration There are no user DIP switches or jumpers on this board for configuration. However, the board must be configured before operation using the S-DOS or Windows software package. Refer to the Related Publications listed on page 6. Series 90-0 Programmable Controller Data Sheet anual 1-5
6 Communications odules Communications Coprocessor odule (C) Table 3. Related Publications Reference Title 1 Programming Software User s anual 2 Programmable Controller Reference anual 3 Programmable Controller Installation anual 4 PLC Serial Communications User s anual 5 Using the Windows Programmer (GFK-1295) Table 4. odule Specifications Serial Ports Current Required from +5V backplane bus RS-232 and RS-422/RS-485 compatible 0. amps VE System designed to support the VE standard C.1 Refer to GFK-086, or later for product standards and general specifications. For installations requiring compliance to more stringent requirements (for example, European Union), refer to Installation requirements for Conformance to Standards. Table 5. Ordering Information Description Communications Coprocessor odule (C) Catalog Number IC69C11 Note: For Conformal Coat option, or Low Temperature Testing option please consult the factory for price and availability. 1-6 Series 90-0 Programmable Controller Data Sheet anual