Power Module PM230, IP20 / Push-through technology (PT) SINAMICS. SINAMICS G120P Power Module PM230, IP20 / Push-through technology (PT)

Similar documents
Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line filter SINAMICS. SINAMICS G130 Line filter. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

SIMOTION. SIMOTION SCOUT SIMOTION SCOUT TIA device proxy. Preface. Fundamental safety instructions 1. Overview 2. Create and configure device proxy.

Siemens Industrial s

Instruction manual. Output chokes 690V. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

Power Module PM330 SINAMICS. SINAMICS G120P Power Module PM330. Basic safety instructions 1. Introduction 2. Installing/Mounting 3

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SINAMICS G120. PM250 Power Module. Hardware Installation Manual 09/2012 SINAMICS. Answers for industry.

Getting Started SIMOTION SCOUT - sample project SIMOTION D435-2 SIMOTION

SINAMICS G120P. Power Module PM230 IP55/UL Type 12. Hardware Installation Manual 07/2010 SINAMICS. Answers for industry.

ST (6ES7132-6FD00-0BB1)

SIMOTION. SIMOTION SCOUT Updating SIMOTION Devices. Preface. Fundamental safety instructions 1. Overview 2. Updating 3. Restoring 4.

Getting Started SIMOTION SCOUT - sample project SIMOTION D435-2

SINAMICS G120. Power Module PM250. Hardware Installation Manual 07/2009 SINAMICS. Answers for industry.

Getting Started SINAMICS. S120 Getting Started. Preface. Fundamental safety instructions. SINAMICS S120 drive system 2. Overview 3

SINAMICS G120. Converter with Control Units CU230P-2 CU240B-2 CU240E-2. Safety information 1. Design of the frequency converter.

SINAMICS G120D converter with control units CU240D-2 and CU250D-2 SINAMICS

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

Device manual SINAMICS SINAMICS G120. Distributed inverter box Control cabinet for wall or floor mounting.

SINAMICS. SINAMICS G110M Distributed converter for SIMOGEAR geared motors. Fundamental safety instructions 1. Description 2.

Digital output module. DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC

SINAMICS G120D converter SINAMICS. SINAMICS G120D SINAMICS G120D converter. Fundamental safety instructions 1. Introduction.

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0)

Hardware Installation Manual Edition 11/2006. Power Module PM250 SINAMICS

SIMOTION. SIMOTION SCOUT Overview of service and diagnostics options. Preface 1. Fundamental safety instructions 2. Introduction 3

Medium-Voltage Drive SINAMICS SM150. Type 6SL3845. Tests carried out on drives This documentation pertains to SM150 wassergekühlt G20 F03 F72 F79 F76

SINAMICS S120 Combi SINAMICS. S120 SINAMICS S120 Combi. Preface. Fundamental safety instructions 1. System overview 2. Line-side power components

Converters with the CU240B-2 and. CU240E-2 Control Units SINAMICS. SINAMICS G120 Converters with the CU240B-2 and CU240E-2 Control Units

Power Module PM260 SINAMICS. SINAMICS G120 Power Module PM260. Introduction. Safety notes. Description 3. Installing/Mounting 4

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.

Siemens Drives & PLCs

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

Converter SINAMICS G150. Type 6SL37102G

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

G120P Variable Speed Drive Technical Manual

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

MINI-PS AC/10-15DC/8

CU240S CU240S DP CU240S DP-F CU240S PN CU240S PN-F

MDM 011-Z1 Regen Resistor

Use with 0 to 70 C ambient. temperature SIMATIC. Process Control System PCS 7 Use with 0 to 70 C ambient temperature. Preface 1. Product combination 2

SINAMICS G130. Cabinet design and EMC. Operating Instructions 03/2013 SINAMICS

SIMOTICS. Drive technology Replacing an encoder for SIMOTICS S-1FK7 G2, S-1FG1 and S-1FT7. Introduction. General safety instructions.

EMC-Compatible Installation of the Electric Cabinet

SIMATIC/SINAMICS. Getting started with SINAMICS V90 PN on S Motion Control. Fundamental safety instructions 1. Introduction

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview.

SINAMICS G120D SINAMICS CU250D-2. Power Modules: SINAMICS PM250D. Getting Started Guide 01/2013 SINAMICS. Answers for industry.

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

Digital output module. DQ 16x230VAC/2A ST Relay (6ES7522-5HH00-0AB0) SIMATIC

Description. SIMATIC Sensors. RF systems Wide-range power supply unit for SIMATIC RF systems. Operating Instructions 11/2007 J31069-D0169-U001-A4-7618

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties.

Operating instructions. Switching amplifier DN0210 DN / / 2015

Mechanical Installation Manual SINUMERIK. SINUMERIK 808D Mechanical Installation Manual. Preface. Safety instructions 1. Identification 2.

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Operating instructions Evaluation system for flow sensors VS / / 2013

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

Operating instructions. Speed monitor D / / 2014

PanelView Plus/VersaView CE Terminals and Display Modules

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Operating instructions. Standstill monitor A / / 2011

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide

MC 11 EB-2 Power supply cabinet with external bus, AC version

SIMATIC Ident RFID systems MDS D423 Compact Operating Instructions

Siemens Parts. SINAMICS S120M Distributed Drive. Technology SINAMICS. S120 SINAMICS S120M Distributed Drive Technology. Foreword

Installation Instructions

Readme SiVArc V14 SP1 Update 6

ST (6ES7522-5HF00-0AB0)

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

SINAMICS S120. Preface. Fundamental safety instructions 1. Overview 2. Startdrive commissioning tool 3. Fundamentals 4.

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E

Redundancy unit CP-A RU

Power supply CP-C 24/5.0

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

Power Electronics. Semiconductor relay / - contactor

Dell Networking S4810 Open Networking (ON) Getting Started Guide

STARTER Commissioning Manual SINAMICS. S120 STARTER Commissioning Manual. Preface. Fundamental safety instructions. Preparation for commissioning

SMVector Additional I/O Module Installation and Operation Manual

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

Analog Monitor Installation Manual

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

FAQ about Drives Technology

ST (6ES7522-1BH00-0AB0)

Installation Job Aid for Ethernet Routing Switch 3600 Series

ABB industrial drives. Safety instructions ACS880 multidrive cabinets and modules

QUINT-PS-3x AC/24DC/10

SINAMICS G120. SINAMICS G120C Inverter. Operating Instructions 01/2011 SINAMICS. Answers for industry.

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

Transcription:

Power Module PM230, IP20 / Push-through technology (PT) SINAMICS SINAMICS G120P Power Module PM230, IP20 / Push-through technology (PT) Hardware Installation Manual Fundamental safety instructions 1 Introduction 2 Installing/mounting 3 Connecting 4 Service and maintenance 5 Technical specifications 6 Accessories 7 A Appendix 06/2014 Edition 06/2014 A5E34331322B AA

Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: Trademarks WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. All names identified by are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY A5E34331322B AA P 04/2015 Subject to change Copyright Siemens AG 2013-2014. All rights reserved

Table of contents 1 Fundamental safety instructions... 7 1.1 General safety instructions... 7 1.2 Safety instructions for electromagnetic fields (EMF)... 10 1.3 Handling electrostatic sensitive devices (ESD)... 11 1.4 Industrial security... 12 1.5 Residual risks of power drive systems... 13 2 Introduction... 15 3 Installing/mounting... 17 3.1 Installation conditions... 17 3.2 Power losses and air cooling requirements... 18 3.3 Mounting the Power Modules... 20 3.3.1 Installing Power Modules... 20 3.3.2 Dimension drawings and drilling dimensions for IP20 Power Modules... 22 3.3.2.1 Build-in Power Modules - IP20... 22 3.3.3 Dimension drawings and drilling dimensions for PT Power Modules... 25 3.4 Control Unit installation... 27 3.5 Installing supplementary components... 27 4 Connecting... 29 4.1 Mains and Motor Connection... 32 4.1.1 Permissible line supplies... 32 4.1.2 Connection overview PM230... 36 4.1.3 Line connection... 37 4.1.4 Motor cable length... 38 4.1.5 Motor connection... 39 4.1.6 Connection terminals at the inverter... 39 4.2 EMC-compliant installation... 41 4.2.1 Avoiding electromagnetic influence (EMI)... 41 4.2.2 Installing the converter in compliance with EMC rules... 43 4.2.3 EMC-compliant cabinet design... 44 4.2.4 Cabling... 46 4.2.5 Equipotential bonding... 48 4.2.6 EMC-compliant wiring... 51 5 Service and maintenance... 53 5.1 Maintenance... 53 5.2 Replacing the cooling fan... 54 Hardware Installation Manual, 06/2014, A5E34331322B AA 5

Table of contents 6 Technical specifications... 57 6.1 General technical data (400 V inverters)... 58 6.2 Specific technical data... 62 6.3 Restrictions for special ambient conditions... 68 6.3.1 Current de-rating depending on the operating temperature... 68 6.3.2 Current and voltage derating dependent on the installation altitude... 69 6.3.3 Current and power limiting depending on the line voltage... 69 6.3.4 Current reduction depending on pulse frequency... 70 6.4 Permissible shock and vibration values... 70 6.5 Electromagnetic compatibility of the inverter... 71 6.5.1 Assigning the inverter to EMC categories... 73 6.5.2 EMC limit values in South Korea... 75 7 Accessories... 77 7.1 Mounting Frames... 77 7.2 Line filters... 79 A Appendix... 81 A.1 Manuals and technical support... 81 A.1.1 Manuals for your inverter... 81 A.1.2 Configuring support... 82 A.1.3 Product Support... 82 A.2 Standards... 83 A.3 Abbreviations... 84 Index... 85 6 Hardware Installation Manual, 06/2014, A5E34331322B AA

Fundamental safety instructions 1 1.1 General safety instructions DANGER Danger to life due to live parts and other energy sources Death or serious injury can result when live parts are touched. Only work on electrical devices when you are qualified for this job. Always observe the country-specific safety rules. Generally, six steps apply when establishing safety: 1. Prepare for shutdown and notify all those who will be affected by the procedure. 2. Disconnect the machine from the supply. Switch off the machine. Wait until the discharge time specified on the warning labels has elapsed. Check that it really is in a no-voltage condition, from phase conductor to phase conductor and phase conductor to protective conductor. Check whether the existing auxiliary supply circuits are de-energized. Ensure that the motors cannot move. 3. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems, or water. 4. Isolate or neutralize all hazardous energy sources by closing switches, grounding or short-circuiting or closing valves, for example. 5. Secure the energy sources against switching on again. 6. Ensure that the correct machine is completely interlocked. After you have completed the work, restore the operational readiness in the inverse sequence. WARNING Danger to life through a hazardous voltage when connecting an unsuitable power supply Touching live components can result in death or severe injury. Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV- (Protective Extra Low Voltage) output voltages for all connections and terminals of the electronics modules. Hardware Installation Manual, 06/2014, A5E34331322B AA 7

Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life when live parts are touched on damaged devices Improper handling of devices can cause damage. For damaged devices, hazardous voltages can be present at the enclosure or at exposed components; if touched, this can result in death or severe injury. Ensure compliance with the limit values specified in the technical data during transport, storage and operation. Do not use any damaged devices. WARNING Danger to life through electric shock due to unconnected cable shields Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected cable shields. As a minimum, connect cable shields and the conductors of power cables that are not used (e.g. brake cores) at one end at the grounded housing potential. WARNING Danger to life due to electric shock when not grounded For missing or incorrectly implemented protective conductor connection for devices with protection class I, high voltages can be present at open, exposed parts, which when touched, can result in death or severe injury. Ground the device in compliance with the applicable regulations. WARNING Danger to life due to electric shock when opening plug connections in operation When opening plug connections in operation, arcs can result in severe injury or death. Only open plug connections when the equipment is in a no-voltage state, unless it has been explicitly stated that they can be opened in operation. WARNING Danger to life due to fire spreading if housing is inadequate Fire and smoke development can cause severe personal injury or material damage. Install devices without a protective housing in a metal control cabinet (or protect the device by another equivalent measure) in such a way that contact with fire is prevented. Ensure that smoke can only escape via controlled and monitored paths. 8 Hardware Installation Manual, 06/2014, A5E34331322B AA

Fundamental safety instructions 1.1 General safety instructions WARNING Danger to life through unexpected movement of machines when using mobile wireless devices or mobile phones Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than approx. 2 m to the components may cause the devices to malfunction, influence the functional safety of machines therefore putting people at risk or causing material damage. Switch the wireless devices or mobile phones off in the immediate vicinity of the components. WARNING Danger to life due to the motor catching fire in the event of insulation overload There is higher stress on the motor insulation through a ground fault in an IT system. If the insulation fails, it is possible that death or severe injury can occur as a result of smoke and fire. Use a monitoring device that signals an insulation fault. Correct the fault as quickly as possible so the motor insulation is not overloaded. WARNING Danger to life due to fire if overheating occurs because of insufficient ventilation clearances Inadequate ventilation clearances can cause overheating of components with subsequent fire and smoke. This can cause severe injury or even death. This can also result in increased downtime and reduced service lives for devices/systems. Ensure compliance with the specified minimum clearance as ventilation clearance for the respective component. WARNING Danger of an accident occurring due to missing or illegible warning labels Missing or illegible warning labels can result in accidents involving death or serious injury. Check that the warning labels are complete based on the documentation. Attach any missing warning labels to the components, in the national language if necessary. Replace illegible warning labels. Hardware Installation Manual, 06/2014, A5E34331322B AA 9

Fundamental safety instructions 1.2 Safety instructions for electromagnetic fields (EMF) NOTICE Device damage caused by incorrect voltage/insulation tests Incorrect voltage/insulation tests can damage the device. Before carrying out a voltage/insulation check of the system/machine, disconnect the devices as all converters and motors have been subject to a high voltage test by the manufacturer, and therefore it is not necessary to perform an additional test within the system/machine. WARNING Danger to life when safety functions are inactive Safety functions that are inactive or that have not been adjusted accordingly can cause operational faults on machines that could lead to serious injury or death. Observe the information in the appropriate product documentation before commissioning. Carry out a safety inspection for functions relevant to safety on the entire system, including all safety-related components. Ensure that the safety functions used in your drives and automation tasks are adjusted and activated through appropriate parameterizing. Perform a function test. Only put your plant into live operation once you have guaranteed that the functions relevant to safety are running correctly. Note Important safety notices for Safety Integrated functions If you want to use Safety Integrated functions, you must observe the safety notices in the Safety Integrated manuals. 1.2 Safety instructions for electromagnetic fields (EMF) WARNING Danger to life from electromagnetic fields Electromagnetic fields (EMF) are generated by the operation of electrical power equipment such as transformers, converters or motors. People with pacemakers or implants are at a special risk in the immediate vicinity of these devices/systems. Ensure that the persons involved are the necessary distance away (minimum 2 m). 10 Hardware Installation Manual, 06/2014, A5E34331322B AA

Fundamental safety instructions 1.3 Handling electrostatic sensitive devices (ESD) 1.3 Handling electrostatic sensitive devices (ESD) Electrostatic sensitive devices (ESD) are individual components, integrated circuits, modules or devices that may be damaged by either electric fields or electrostatic discharge. NOTICE Damage through electric fields or electrostatic discharge Electric fields or electrostatic discharge can cause malfunctions through damaged individual components, integrated circuits, modules or devices. Only pack, store, transport and send electronic components, modules or devices in their original packaging or in other suitable materials, e.g conductive foam rubber of aluminum foil. Only touch components, modules and devices when you are grounded by one of the following methods: Wearing an ESD wrist strap Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring Only place electronic components, modules or devices on conductive surfaces (table with ESD surface, conductive ESD foam, ESD packaging, ESD transport container). Hardware Installation Manual, 06/2014, A5E34331322B AA 11

Fundamental safety instructions 1.4 Industrial security 1.4 Industrial security Note Industrial security Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates. For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. For more information about industrial security, visit Hotspot-Text (http://www.siemens.com/industrialsecurity). To stay informed about product updates as they occur, sign up for a product-specific newsletter. For more information, visit Hotspot-Text (http://support.automation.siemens.com). WARNING Danger as a result of unsafe operating states resulting from software manipulation Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe operating states to develop in your installation which can result in death, severe injuries and/or material damage. Keep the software up to date. You will find relevant information and newsletters at this address (http://support.automation.siemens.com). Incorporate the automation and drive components into a holistic, state-of-the-art industrial security concept for the installation or machine. You will find further information at this address (http://www.siemens.com/industrialsecurity). Make sure that you include all installed products into the holistic industrial security concept. 12 Hardware Installation Manual, 06/2014, A5E34331322B AA

Fundamental safety instructions 1.5 Residual risks of power drive systems 1.5 Residual risks of power drive systems The control and drive components of a drive system are approved for industrial and commercial use in industrial line supplies. Their use in public line supplies requires a different configuration and/or additional measures. These components may only be operated in closed housings or in higher-level control cabinets with protective covers that are closed, and when all of the protective devices are used. These components may only be handled by qualified and trained technical personnel who are knowledgeable and observe all of the safety instructions on the components and in the associated technical user documentation. When assessing the machine's risk in accordance with the respective local regulations (e.g., EC Machinery Directive), the machine manufacturer must take into account the following residual risks emanating from the control and drive components of a drive system: 1. Unintentional movements of driven machine components during commissioning, operation, maintenance, and repairs caused by, for example, Hardware and/or software errors in the sensors, control system, actuators, and cables and connections Response times of the control system and of the drive Operation and/or environmental conditions outside the specification Condensation/conductive contamination Parameterization, programming, cabling, and installation errors Use of wireless devices/mobile phones in the immediate vicinity of the control system External influences/damage 2. In the event of a fault, exceptionally high temperatures, including an open fire, as well as emissions of light, noise, particles, gases, etc. can occur inside and outside the inverter, e.g.: Component failure Software errors Operation and/or environmental conditions outside the specification External influences/damage Inverters of the Open Type/IP20 degree of protection must be installed in a metal control cabinet (or protected by another equivalent measure) such that contact with fire inside and outside the inverter is not possible. Hardware Installation Manual, 06/2014, A5E34331322B AA 13

Fundamental safety instructions 1.5 Residual risks of power drive systems 3. Hazardous shock voltages caused by, for example, Component failure Influence during electrostatic charging Induction of voltages in moving motors Operation and/or environmental conditions outside the specification Condensation/conductive contamination External influences/damage 4. Electrical, magnetic and electromagnetic fields generated in operation that can pose a risk to people with a pacemaker, implants or metal replacement joints, etc., if they are too close 5. Release of environmental pollutants or emissions as a result of improper operation of the system and/or failure to dispose of components safely and correctly Note The components must be protected against conductive contamination (e.g. by installing them in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12). Assuming that conductive contamination at the installation site can definitely be excluded, a lower degree of cabinet protection may be permitted. For more information about residual risks of the components in a drive system, see the relevant sections in the technical user documentation. 14 Hardware Installation Manual, 06/2014, A5E34331322B AA

Introduction 2 PM230 Power Module The PM230 Power Module is part of the modular family of SINAMICS G120 inverters. PM230 Power Modules have been specifically designed for pump and fan drives in HVAC applications. They are available with class A filter or no filter in a power range from 0.37 kw 75 kw and a line voltage range from 3 AC 380 V 480 V. The Power Modules can be used with the following Control Units including all communication variants with firmware version 4.4 or higher. CU230P-2 CU240B-2 CU240E-2 Operation with any other Control Units as listed above is not permitted. Note Failsafe functions are not supported by the PM230. Hardware Installation Manual, 06/2014, A5E34331322B AA 15

Introduction 16 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3 3.1 Installation conditions When installing the Power Modules carefully observe the conditions listed below in order to guarantee reliable, continuous and disturbance-free operation. The Power Module is designed for installation in a control cabinet. It provides protection against the ingress of solid foreign objects 12.5 mm. It does not provide any protection against the ingress of dust or liquids. For EMC-compliant installation, please observe Section Connecting (Page 29). WARNING To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in this manual. Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installation (e.g. EN 61800-5-1) as well as the relevant regulations regarding the correct use of tools and personal protective equipment (PPE). Hardware Installation Manual, 06/2014, A5E34331322B AA 17

Installing/mounting 3.2 Power losses and air cooling requirements 3.2 Power losses and air cooling requirements Cooling requirements Depending on the power loss of the individual components, the control cabinet will require a cooling airflow to prevent the components from overheating. Formula for calculating the cooling airflow: Power loss: Δ T Total of the power losses of the individual components. Permissible temperature rise in the electrical cabinet Measures in order to ensure that the components are adequately cooled 1. Add the power losses of the individual components. For the Power Module, apply the data in Section "Specific technical data (Page 62)". The power loss of the CU is less than 0.04 kw. Use the manufacturers data for components, for example reactors or filters 2. Calculate the air flow required, using the formula above. 3. Ensure that the control cabinet is appropriately ventilated and equipped with suitable air filters. 4. Ensure that the components have the specified clearances with respect to one another. 5. Ensure that the components are provided with adequate cooling air through the cooling openings. 6. Use the appropriate air barriers to prevent cooling air short circuits 18 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3.2 Power losses and air cooling requirements Figure 3-1 Air barriers for avoiding cooling air short circuits The power loss values specified in the technical data refer to the values specified for an output frequency of 50 Hz. Special features of Power Modules with push-through technology (PT Power Modules) When you use PT Power Modules, the majority of the power loss is dissipated through the heatsink located outside the control cabinet. Hardware Installation Manual, 06/2014, A5E34331322B AA 19

Installing/mounting 3.3 Mounting the Power Modules 3.3 Mounting the Power Modules 3.3.1 Installing Power Modules Mounting Power Modules with degree of protection IP20 Procedure Proceed as follows to correctly mount the Power Module: 1. Mount the Power Module in a control cabinet. 2. Maintain the minimum clearances to other components in the control cabinet specified below. 3. Install the Power Modules vertically with the line and motor connections facing downwards. It is not permissible to install them in any other position. 4. Position the Power Module in the control cabinet so that the cables for the motor and line supply are connected in accordance with the terminal layout. 5. Use the mounting devices specified below. 6. Comply with the torques of the mounting devices specified below. You have correctly mounted the Power Module. 20 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3.3 Mounting the Power Modules Mounting Power Modules using push-through technology We recommend that you use the optionally available mounting frame to mount the pushthrough unit in a control cabinet. This mounting frame includes the necessary seals and frame to ensure compliance with degree of protection IP54. If you do not use the optional mounting frames, then you must ensure that the required degree of protection is complied with using other appropriate measures. You must mount the inverter on unpainted metal surfaces in order to comply with EMC requirements. Procedure Proceed as follows to correctly mount the Power Module: 1. Prepare the cutout and the mounting holes for the Power Module and the mounting frame corresponding to the dimension drawings of the mounting frame. Also note that the PT Power modules must be vertically mounted with the line and motor connections facing downwards. 2. Position the mounting frame at the rear of the control cabinet and attach it to the control cabinet by tightening the corresponding screws by hand. 3. Attach the seal to the inner side of the control cabinet. 4. Mount the frequency inverter and initially tighten all of the mounting screws by hand. 5. Tighten the screws with a torque of 3.5 Nm. You have correctly mounted the Power Module. Mounting frame Hardware Installation Manual, 06/2014, A5E34331322B AA 21

Installing/mounting 3.3 Mounting the Power Modules 3.3.2 Dimension drawings and drilling dimensions for IP20 Power Modules 3.3.2.1 Build-in Power Modules - IP20 Drilling patterns, dimensions and clearances for PM230 Power Modules, IP20 Table 3-1 Dimensions of the PM230, without/with integrated filter Frame size Dimensions (mm) Drilling dimensions a (width) b (height) 1) c (depth) 2) d e f FSA 73 196 165 62,3 186 6 FSB 100 292 165 80 281 6 FSC 140 355 165 120 343 6 FSD 275 419/512 204 235 325/419 11 FSE 275 499/635 204 235 405/451 11 FSF 350 634/934 316 300 598/899 11 1) with shield connection kit: FSA: + 80 mm; FSB: + 78 mm; FSC: + 77 mm; FSD, FSE, FSF: + 123 mm 2) Total depth of the inverter: See below. 22 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3.3 Mounting the Power Modules Table 3-2 Mounting hardware and clearances to other devices for PM230 Frame size Hardware Tightening torque (Nm) Cooling air clearances (mm) Top Bottom Lateral Front FSA, FSB M4 screws 2,5 80 100 0 1) --- FSC M5 screws 3 80 100 0 1) --- FSD, FSE M6 screws 6 300 300 0 1) 100 FSF M8 screws 13 350 350 0 1) 100 1) mounting without lateral clearance is permissible. For tolerance reasons, we recommend a lateral clearance of approx. 1 mm. Total depth of the inverter Power Module PM230 FSA/FSB/FSC +CU240 +CU240 + BOP-2 +CU240 + IOP +CU230 +CU230 + BOP-2 +CU230 + IOP 205 mm 217 mm 227 mm 223 mm 235 mm 245 mm Power Module PM230 FSD/FSE +CU240 +CU240 + BOP-2 +CU240 + IOP +CU230 +CU230 + BOP-2 +CU230 + IOP 244 mm 256 mm 266 mm 262 mm 274 mm 284 mm Power Module PM230 FSF +CU240 +CU240 + BOP-2 +CU240 + IOP +CU230 +CU230 + BOP-2 +CU230 + IOP 356 mm 368 mm 378 mm 374 mm 386 mm 396 mm Hardware Installation Manual, 06/2014, A5E34331322B AA 23

Installing/mounting 3.3 Mounting the Power Modules Mounting the shielding plate Figure 3-2 Mounting the shielding plate, FSA FSC Figure 3-3 Mounting the shielding Plate, FSD... FSF 24 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3.3 Mounting the Power Modules 3.3.3 Dimension drawings and drilling dimensions for PT Power Modules Dimensions and drilling patterns for Power Modules with push-through technology Mounting cutout in the control cabinet for PM230 Power Modules; holes to attach the mounting frame FSA, FSB FSC Table 3-3 Dimensions for PM230 in push-through technology Frame size a (width) Dimensions (mm) b (height) 1) c (depth) 2) Drilling dimensions (mm) Cabinet cutout (mm) T1 T2 e d f g h FSA 126 238 171 118 54 103 106 27 88 198 FSB 154 345 171 118 54 147,5 134 34,5 116 304 FSC 200 411 171 118 54 123 174 30,5 156 365 1) With shield connection kit: FSA: +84 mm; FSB: +85 mm; FSC: +89 mm 3) Total depth of the inverter: See below. Table 3-4 Mounting hardware and clearances to other devices for PM230 in push-through technology Frame size Hardware Tightening torque (Nm) Cooling air clearances (mm) Top Bottom Lateral FSA, FSB, FSC M5 screws 3 80 100 0 1) 1) mounting without lateral clearance is permissible. For tolerance reasons, we recommend a lateral clearance of approx. 1 mm. Hardware Installation Manual, 06/2014, A5E34331322B AA 25

Installing/mounting 3.3 Mounting the Power Modules Total depth of the inverter Power Module PM230 FSA + CU240 + CU240 + BOP-2 + CU240 + IOP + CU230 + CU230 + BOP-2 + CU230 + IOP 211 mm, of which 158 mm in the cabinet 223 mm, of which 170 mm in the cabinet 233 mm, of which 180 mm in the cabinet 229 mm, of which 176 mm in the cabinet 241 mm, of which 188 mm in the cabinet 251 mm, of which 198 mm in the cabinet Mounting the shielding plate 26 Hardware Installation Manual, 06/2014, A5E34331322B AA

Installing/mounting 3.4 Control Unit installation 3.4 Control Unit installation The Control Unit is snapped onto the Power Module as shown in the figure. To disconnect the CU push the release button on top of the PM. The process of fitting the Control Unit onto the Power Module is the same technique independent of the type of Control Unit or Power Module. Fitting the Control Unit onto the Power Module 3.5 Installing supplementary components A line filter or n output reactor may be required depending on the particular application. Additional information about mounting these components is provided in the instructions supplied. Hardware Installation Manual, 06/2014, A5E34331322B AA 27

Connecting 4 Preconditions You can establish the line and motor connections once the inverter has been properly installed. In addition to the "Basic safety instructions (Page 7)", it is absolutely essential that you comply with the following notes. DANGER Danger to life through electric shock due to the residual charge of the DC link capacitors Because of the DC link capacitors, a hazardous voltage is present for up to 5 minutes after the power supply has been switched off. Contact with live parts can result in death or serious injury. Do not open the protective cover of the device until 5 minutes have elapsed. Before starting any work, check that the system is in a voltage-free state by measuring all terminals, also to ground. Ensure that the associated warning plate in the appropriate language is attached. WARNING Danger to life through interruption of the external protective conductor due to high leakage currents The drive components conduct a high leakage current via the protective conductor. Touching conductive parts when the protective conductor is interrupted can result in death or serious injury. Ensure that the external protective conductor satisfies at least one of the following conditions: It has been laid so that it is protected against mechanical damage. 1) If it is a single conductor, it has a cross-section of at least 10 mm² Cu. If it is a conductor of a multi-conductor cable, it has a cross-section of at least 2.5 mm² Cu. It has a second protective conductor in parallel with the same cross-section. It complies with the local regulations for equipment with increased leakage current. 1) Cables laid within control cabinets or closed machine housings are considered to be adequately protected against mechanical damage. Hardware Installation Manual, 06/2014, A5E34331322B AA 29

Connecting WARNING Danger to life for an excessively high line voltage If the line voltage is excessively high, this can destroy the inverter and there is a risk of electric shock. Ensure that the line voltage is in compliance with the inverter supply voltage. It is not permissible to connect higher line voltages! Note Operating displays for inverter operation If, when switching over a function from ON to OFF, an LED or other similar display is not lit or not active; this does not indicate that the device is switched-off or in a no-current condition. Note Circuit breakers/fuses Ensure that the appropriate circuit breakers or fuses with the specified LO output current are connected between the power supply and the drive. The technical data contain information about the circuit breaker and fuses (see Specifications). WARNING Danger to life due to fire or electric shock when using unsuitable residual current protection devices The inverter can cause a current to flow in the protective conductor. This current can cause the residual current device (RCD) or residual current monitoring (RCM) to incorrectly trip (nuisance trip). In the case of a fault (ground fault), the fault current can contain a DC component, which prevents the RCD/RCM from tripping, with the risk of subsequent fault or electric shock. Use the protection and monitoring devices recommended in the documentation. CAUTION Risk of injury due to hot surfaces During operation and for a short time after the inverter shuts down, the surface of the device can reach a high temperature. During this time, avoid any direct contact with the surface of the inverter. 30 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting Protection and monitoring equipment One of the following measures is suitable in order to ensure touch protection for the inverter: Disconnect the inverter from the line supply using a transformer Residual current device (RCD) or residual current monitoring (RCM) with the following properties and secondary conditions: You are using a super-resistant RCD/RCM, type B with a tripping current of 300 ma. e.g. a SIQUENCE circuit breaker from Siemens. Only one inverter is supplied from each RCD/RCM The motor cables are shielded and are not longer than 50 m. You can find additional information on the motor cables in Motor cable length (Page 38) Note Fuses and residual current devices and/or monitoring devices A residual current device (RCD) or residual current monitoring (RCM) does not replace the fuses listed in the Technical data. Hardware Installation Manual, 06/2014, A5E34331322B AA 31

Connecting 4.1 Mains and Motor Connection 4.1 Mains and Motor Connection Inverter terminal layout see Line and motor terminals (Page 39). For all connections, carefully observe the regulations relating to electromagnetic compatibility, also see EMC-compliant installation (Page 41). 4.1.1 Permissible line supplies The inverter is designed for the following power distribution systems according to IEC 60364-1 (2005). Above an installation altitude of 2000 m, the permissible line supplies are restricted. See also: Restrictions for special ambient conditions (Page 68). TN line system A TN line system transfers the PE protective conductor to the installed plant or system using a cable. Generally, in a TN line system the neutral point is grounded. There are versions of a TN line supply with a grounded line the conductor, e.g. with grounded L1. A TN line system can transfer the neutral conductor N and the PE protective conductor either separately or combined. Preconditions and restrictions when connecting an inverter to a TN line system Inverter with integrated or external line filter: Operation on TN line supply systems with grounded neutral point permissible. Operation on TN line supply systems with grounded line conductor not permissible. Inverter without line filter: Operation permissible on all TN line supplies. 32 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.1 Mains and Motor Connection Examples for Power Modules connected to a TN line supply Figure 4-1 TN line supply with separate transfer of N and PE and with a grounded neutral point Hardware Installation Manual, 06/2014, A5E34331322B AA 33

Connecting 4.1 Mains and Motor Connection TT system In a TT line system, the transformer grounding and the installation grounding are independent of one another. There are TT line supplies where the neutral conductor N is either transferred or not. Preconditions and restrictions when connecting an inverter to a TT line system Inverter with integrated or external line filter: Operation on TT line supply systems with grounded neutral point permissible. Operation on TT line systems without grounded neutral point not permissible. Inverter without line filter: Operation on TT line systems is permissible. Examples for Power Modules connected to a TT line supply Figure 4-2 TT line system where the neutral conductor N is transferred 34 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.1 Mains and Motor Connection IT system In an IT line system, all of the conductors are insulated with respect to the PE protective conductor or connected to the PE protective conductor through an impedance. There are IT line supplies where the neutral conductor N is either transferred or not. Preconditions and restrictions when connecting an inverter to an IT line system Inverter with integrated or external line filter: Operation on IT line systems is not permissible. Inverter without line filter: Operation on IT line systems is permissible. Examples for Power Modules connected to an IT line supply Figure 4-3 IT line supply where the neutral conductor N is transferred and with impedance with respect to the PE protective conductor Behavior of the inverter when a ground fault occurs In some instances, even for a ground fault, the inverter should still remain functional. In cases such as these, you must install an output reactor. This prevents an overcurrent trip or damage to the drive. Hardware Installation Manual, 06/2014, A5E34331322B AA 35

Connecting 4.1 Mains and Motor Connection 4.1.2 Connection overview PM230 Figure 4-4 Connecting the PM230 IP20 and push-through Power Module The line filter of Power Module PM230 fulfills Class A. For higher EMC requirements, you need an external Class B line filter. 36 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.1 Mains and Motor Connection 4.1.3 Line connection Special issues when connecting inverters, frame sizes FSA, FSB and FSC equipped with Profinet Control Units to the line supply If you are using a PROFINET Control Unit, then you must connect the line supply via two ferrite cores; e.g. "Würth 742-712 - 22" or equivalent versions. Special issues when connecting inverters, frame sizes FSB, FSC and FSD equipped with external filter B to the line supply If you are using a Class B EMC filter, then you must connect the filter for the Power Modules, frame sizes FSB, FSC and FSD, to the line supply via two ferrite cores. For frame sizes FSB and FSC ferrite cores, type "Würth 742-712 - 22" or equivalent are suitable. You require ferrite cores, type "Würth 742-701 - 91" or equivalent, for frame size FSD. The ferrite cores are required in addition to the EMC measures in order to attain EMC Category C2. Hardware Installation Manual, 06/2014, A5E34331322B AA 37

Connecting 4.1 Mains and Motor Connection 4.1.4 Motor cable length The following cable lengths are permissible for operation, and do not diminish the performance: Table 4-1 Permissible cable lengths taking into account the connection type and EMC category Connection type and permissible cable length Devices with integrated filter (Class A), the motor is connected using shielded cables Devices with integrated filter (Class A), the motor is connected using shielded cables Devices without integrated filter, but with an external Class B filter, the motor is connected using shielded cables Devices without filter or with integrated filter, the motor is connected using shielded cables Devices without filter or with integrated filter, the motor is connected using unshielded cables Devices without integrated filter, but with an external Class B filter, the motor is connected using shielded cables, in addition, an output reactor Permissible EMC category 25 m Second environment, Category C2 *) 50 m Second environment, Category C3 *) 50 m First environment, Category C1 *) 50 m Without taking into consideration the EMC category 100 m Without taking into consideration the EMC category 150 m Second environment, Category C2 *) *) EMC compliant connection required, see also EMC-compliant installation (Page 41) The permissible motor cable length also depends on the cable type and the selected pulse frequency (Page 70). 38 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.1 Mains and Motor Connection 4.1.5 Motor connection Star and delta connection Siemens motors have a diagram inside the terminal box showing both connection methods: Star connection (Y) Delta connection (Δ) The motor rating plate provides data about the correct connection. Connecting the motor Connect the protective conductor of the motor to the terminal of the inverter. Connect the motor cable to terminals U2, V2 and W2. Close the terminal covers of the inverter. There are no terminal covers for FSA FSC. Star connection / delta connection 4.1.6 Connection terminals at the inverter Connection terminals for the line supply and motor, FSA FSC The Power Modules are equipped with withdrawable connectors. You can withdraw the connector by pressing the red lever to release the interlock. The connectors are designed so that they cannot be accidentally interchanged. Cable cross-section/tightening torque: FSA 1.5 2.5 mm 2 / 0.5 Nm FSB 1.5 6 mm 2 / 0.6 Nm FSC 6 16 mm 2 / 1.5 Nm Hardware Installation Manual, 06/2014, A5E34331322B AA 39

Connecting 4.1 Mains and Motor Connection Connection terminals for the line supply and motor, FSD FSF Access to line and motor terminals The connecting terminals for the line and motor have covers to prevent them from being touched. To connect the cable, lift up the covers until they latch into place as shown in the diagram. Connecting the line and motor cables The line and motor cables are connected using cable lugs. Cable cross-section/tightening torque: FSD 16 35 mm 2 /6 Nm FSE 25 50 mm 2 / 6 Nm FSF 35 120 mm 2 / 13 Nm Establishing connections Procedure Proceed as follows to establish the connections 1. Ensure that the device is in a no-voltage condition 2. When available, remove the covers 3. Establish the connections 4. Reattach the covers before you connect the power You have established the connections. 40 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation 4.2 EMC-compliant installation Only the concurrent use of filtering, grounding and shielding ensure an installation in accordance with the EMC requirements. The next sections cover all of the most important rules for the installation of inverter and drive systems. 4.2.1 Avoiding electromagnetic influence (EMI) The inverters are designed for operation in industrial environments where high values of EMI are expected. Safe, reliable and disturbance-free operation is only guaranteed if the devices are installed by appropriately trained and qualified personnel. Control cabinet design Connect the metallic parts and components of the control cabinet to the frame of the cabinet through a good electrical connection. Side panels Rear panels Cover plate Base plates Use the largest possible contact area or many individual screw connections. Connect the PE busbar and EMC shielding bus to the control cabinet frame using a good electrical connection established through the largest possible surface area. Connect all metal enclosures of the devices installed in the control cabinet (such as the inverter and line filter) to the control cabinet frame through a good electrical connection established through the largest possible surface area. We recommend that these devices are mounted on a bare metal plate with good conducting properties. For screw connections onto painted or anodized surfaces, establish a good conductive contact using one of the following methods: Use special (serrated) contact washers that cut through the painted or anodized surface. Remove the insulating coating at the contact locations. Equip the following components with interference suppression elements: Coils of contactors Relays Solenoid valves Motor holding brakes Interference suppression elements include RC elements or varistors for AC-operated coils and freewheeling diodes for DC-operated coils. Connect the interference suppression element directly at the coil. Hardware Installation Manual, 06/2014, A5E34331322B AA 41

Connecting 4.2 EMC-compliant installation Cable routing and shielding Route all inverter power cables (line supply cables, connecting cables between the braking module and the associated braking resistance as well as the motor cables) separately away from signal and data cables. Maintain a minimum clearance of 25 cm. If cables can be separately routed, use metal partitions that have a good electrical connection to the mounting plate. Route the cables from the line supply to the line filter separately away from the following cables: Cables between the line filter and inverter Connecting cables between the braking module and associated braking resistor Motor cables Signal and data cables as well as filtered line supply cables may only cross non-filtered power cables at right angles. Keep all cables as short as possible. Always route signal lines, data cables, and the associated potential equalizing cables in parallel with the shortest possible clearance between them Use shielded motor cables. Route the shielded motor cable separately from the cables to the motor temperature sensors (PTC/KTY). Use shielded signal and data cables. Connect the shields to the grounded enclosure at both ends with a good electrical connection through the largest possible surface area Connect the cable shields as closely as possible to the point where the cable enters the control cabinet. Use EMC shielded busbars for power cables. Use the shield connection elements in the inverter for signal and data cables. Do not interrupt any cable shields by using intermediate terminals. Use the appropriate EMC terminals for cable shields. The EMC terminals connect the cable shield with the EMC shielded busbar or with the shield connection element through a large conductive surface. 42 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation 4.2.2 Installing the converter in compliance with EMC rules Rules for EMC-compliant cable routing Preconditions The inverter is mounted on a metal mounting plate. The mounting plate is unpainted and has good electrical conductivity. Use shielded cables for the following connections: Motor and motor temperature sensor Braking resistor (not available for all inverters) Fieldbus Inputs and outputs of the terminal strip Procedure To install the inverter cables in compliance with EMC rules, proceed as follows: 1. Expose the shields of the shielded cables. 2. Place the shields on the mounting plate or on the inverter shield plate using EMC clamps. Hardware Installation Manual, 06/2014, A5E34331322B AA 43

Connecting 4.2 EMC-compliant installation You have wired the inverter in an EMC-compliant fashion. EMC-compliant wiring shown using the example of a frame size A inverter 1 Unshielded line supply cable 2 EMC clamps (serrated rails) on the shield plate of the Power Module 3 Shielded cable to the braking resistor (not available for all inverters) 4 EMC clamp for the cable to the terminal strip on the shield plate of the CU 5 Shielded cable to the terminal strip 6 Shielded motor cable 4.2.3 EMC-compliant cabinet design The most cost-effective method of implementing interference suppression measures within the control cabinet is to ensure that interference sources and interference sinks are spatially separated. EMC zone concept within the control cabinet Split up the complete control cabinet into EMC zones. Electromagnetically decouple the zones from one another, either using large clearances (approximately 25 cm) or using a separate metal enclosure or sheet metal partition with a large surface area. Assign the various devices to zones in the control cabinet. Non-shielded cables can be used within a zone. It is not permissible to route cables of various zones in common cable harnesses or common cable ducts. If necessary, you must use filters and/or coupling modules at the interfaces of the zones. Use shielded cables for all communication and signal cables that exit the control cabinet. Connect the shields to the cabinet ground through a large surface area and low ohmic connection. Ensure that there are no potential differences between these zones, to avoid inadmissibly high equalization currents flowing through the cable shields. 44 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation Zone A: Line supply connection Limit values for conducted interference emission and interference immunity must not be exceeded. Zone B: Power electronics Sources of interference Zone C: Controller and sensors Interference sinks Zone D: Motor, braking resistor and corresponding cables Sources of interference Classification of the control cabinet or the drive system into EMC zones Control cabinet design All connections should be durable. Connect all the metallic parts of the control cabinet (doors, rear panels, side, top section and base plates) to the frame of the cabinet so that there is a good electrical connection. For screw connections at painted or anodized metal parts, either use special serrated washers, which penetrate the insulating surface or remove the insulating surface at the contact locations in order to establish a good contact between the metals. Connect the PE bar and the EMC shield bar to the control cabinet frame through a good electrical connection established through a large surface area. Connect all metal enclosures of the components installed in the cabinet with the control cabinet frame through a large surface area to ensure a good electrical connection. To achieve this, mount the components on a bare metal surface and mounting plate with good conductivity, which you then connect to the control cabinet frame through the largest possible surface area to establish a good connection, especially with the PE and EMC shield bars. Hardware Installation Manual, 06/2014, A5E34331322B AA 45

Connecting 4.2 EMC-compliant installation Radio interference suppression Connect interference suppressors to all contactors, relays, solenoid valves and motor holding brakes directly at the coil in order to dampen high-frequency radiation when these devices are switched off. Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors for DC-operated coils. 4.2.4 Cabling Cable routing inside the cabinet Route the power cables of the drive so that there is a minimum clearance of 25 cm to signal and data cables. Power cables are line, DC link and motor cables as well as connecting cables between the Braking Module and braking resistor. Alternatively, the separation can be realized using metal partitions connected to the mounting plate through a good electrical connection. Route power cables with low noise levels separately from power cables with high noise levels Power cables with low noise level: - line cables from the line to the line filter Power cables with high noise level: - cables between the line filter and inverter - DC link cables - cables between the Braking Module and braking resistor - motor cables Route the cables so that signal and data cables as well as power cables with low noise level only cross power cables with a high noise level at right angles. Keep the cables as short as possible. Route the cables as close as possible to grounded enclosure parts such as mounting plates or the cabinet frame. Route signal and data cables as well as the associated equipotential bonding cables parallel and as close to one another as possible. Route incoming and outgoing cables/conductors within a zone (where unshielded singleconductor cables are used), twisted or in parallel and as close to one another as possible. Ground any unused conductors of signal and data cables at both ends. Signal and data cables should enter the cabinet only at one point (e.g. from below). 46 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation Cables outside the control cabinet Route the power cables of the drive so that there is a minimum clearance of 25 cm to signal and data cables. Use shielded motor cables. Use shielded signal and data cables. Cable shields For shielded cables, only use cables with finely-stranded, braided shields. Connect the shield at the grounded enclosure as well as at the EMC shield bar. Connect the shields to the grounded enclosures through a large surface area at both ends of the cables to establish a low ohmic connection. Attach the shields to the appropriate EMC shield bars. Immediately after the cable enters the cabinet, connect the cable shields to the EMC shield bar through a larger surface area to establish a low ohmic conduction. If possible, always route the cable shields without any interruptions. Only use metallic or metallized connectors for the plug connections for shielded data cables (e.g. PROFIBUS connection). Hardware Installation Manual, 06/2014, A5E34331322B AA 47

Connecting 4.2 EMC-compliant installation 4.2.5 Equipotential bonding Grounding measures Proceed as follows to ground the drive system: For several cabinets, install a common PE bar for all cabinet elements Connect all of the drive system components to the PE conductor Connect the PE conductor to the PE bar of the control cabinet. Measures for high frequency equipotential bonding Proceed as follows, to ensure high-frequency equipotential bonding: Connect the metallic components in the control cabinet to the PE bar and the EMC bar through a larger surface area so that a good electrical connection is established. Either through a large surface area between the metal contact surfaces of the cabinet components with a minimum cross-section of several cm² for each contact location. Or, alternatively using short, finely stranded, braided copper wires with cross-sections 95 mm² / 000 (3/0) (-2) AWG. In plants and systems with several cabinet elements, screw the frames of the individual cabinet elements at several locations to one another using serrated washers to establish a good electrical connection. In plants and systems with very long rows of cabinets, which are installed in two groups back to back, connect the PE bars of the two cabinet groups at as many locations as possible. Therefore, connect the protective ground conductor and the cable shield to the motor and the inverter. Additional measures for high frequency equipotential bonding Route finely stranded or braided copper conductors in parallel to the motor cable with the shortest possible distance between them: in older systems with already existing unshielded cables for cables with poor high-frequency properties of the shield for poor grounding systems 48 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation Diagrams for grounding and high-frequency equipotential bonding measures The following diagram illustrates all grounding and high-frequency equipotential bonding measures using the example of a cabinet with a SINAMICS G120. Grounding measures 1 Conventional grounding without any special HF properties High-frequency equipotential bonding measures 2 3 4 5 Electrically conductive connection to the mounting panel through the largest possible surface HF equipotential bonding Connect the shield through a large contact surface and ground Connect the shield through an electrically conductive heavy-gauge threaded joint (gland) and ground Figure 4-5 Grounding and high-frequency equipotential bonding measures in the drive system and in the plant Hardware Installation Manual, 06/2014, A5E34331322B AA 49

Connecting 4.2 EMC-compliant installation The following diagram shows the additional measures for high-frequency equipotential bonding Figure 4-6 Additional measures for high frequency equipotential bonding of the drive system 50 Hardware Installation Manual, 06/2014, A5E34331322B AA

Connecting 4.2 EMC-compliant installation 4.2.6 EMC-compliant wiring EMC compliant wiring of the Power Module The terminal cover is not shown in the diagram, so that it is easier to see how the cable is connected. 1 Line connection cable (unshielded) for Power Modules with integrated line filter. If you use an external line filter, you will need a shielded cable between the line filter and the Power Module. 2 Strain relief 3 Line supply connection 4 Metal mounting plate (unpainted and with a good electrical conductivity) 5 Motor connection 6 Cable shield 7 Cable clamps for establishing the connection between the shield and the mounting plate through a large surface area 8 Motor connection cable (shielded) 9 Shield plate (option) Figure 4-7 EMC-compliant wiring of a Power Module frame size E as example Hardware Installation Manual, 06/2014, A5E34331322B AA 51

Connecting 4.2 EMC-compliant installation Figure 4-8 Shield connection - detail 52 Hardware Installation Manual, 06/2014, A5E34331322B AA

Service and maintenance 5 5.1 Maintenance Repair WARNING Repairs on equipment may only be carried out by Siemens Service, by repair centers authorized by Siemens or by authorized personnel who are thoroughly acquainted with all the warnings and operating procedures contained in this manual. Any defective parts or components must be replaced using parts contained in the relevant spare parts list. The purpose of maintenance is to preserve the specified condition of the Power Module. Dirt and contamination must be removed regularly and parts subject to wear replaced. The Power Module comprises mostly electronic components. Apart from the fan(s), the unit, therefore, contains hardly any components that are subject to wear or that require maintenance or servicing. The following points must generally be observed. Cleaning The unit must be cleaned using a brush, vacuum cleaner and dry compressed air (max. 1 bar) for areas that cannot be easily reached. Pollution must be regularly removed from the heat sinks of the PT devices. Depending on the degree of pollution, it may be necessary to remove the rear air deflection plate. Use a torque of 2 Nm when reconnecting. If you use water to clean the heat sink, the fan must be mounted, otherwise water could enter the plug connection. Ventilation The devices must be installed in a cabinet. It must be ensured that the ventilation slots of the cabinet are not blocked. The fan must be checked to ensure that it is functioning correctly. Hardware Installation Manual, 06/2014, A5E34331322B AA 53

Service and maintenance 5.2 Replacing the cooling fan Cables and screw terminals Cables and screw terminals must be checked regularly to ensure that they are secure, and if necessary, retightened. Retighten if necessary. The wiring must be checked for damage. Defective parts must be replaced immediately. Note The actual maintenance intervals depend on the installation and operating conditions. Siemens offers its customers support in the form of service contracts. For further information, contact your Siemens regional office or sales office. 5.2 Replacing the cooling fan Service life of the fan The average service life of the fan is 40,000 hours. In practice, however, the service life may deviate from this value. Especially a dusty environment can block up the fan. The fan must be replaced in good time to ensure that the inverter is ready for operation. DANGER Danger to life through electric shock due to the residual charge of the DC link capacitors Because of the DC link capacitors, a hazardous voltage is present for up to 5 minutes after the power supply has been switched off. Contact with live parts can result in death or serious injury. Do not open the protective cover of the device until 5 minutes have elapsed. Before starting any work, check that the system is in a voltage-free state by measuring all terminals, also to ground. Ensure that the associated warning plate in the appropriate language is attached. 54 Hardware Installation Manual, 06/2014, A5E34331322B AA

Service and maintenance 5.2 Replacing the cooling fan Fan replacement FSA FSC Procedure when replacing fan modules FSA FSC Proceed as follows to replace a fan module: 1. Switch the inverter off. 2. Withdraw the line and motor cable connectors and, if available, remove the braking resistor from the Power Module. 3. Remove the shield plate from the Power Module. 4. Remove the fan module from the Power Module as shown in the diagram. 5. Install the new fan module in the inverse sequence. You have replaced the fan module. Hardware Installation Manual, 06/2014, A5E34331322B AA 55

Service and maintenance 5.2 Replacing the cooling fan Fan replacement FSD FSF Procedure when replacing fans FSD FSF Proceed as follows to replace a fan: 1. Switch the inverter off. 2. Disconnect all the cables from the Power Module. 3. Remove the fan retaining board (12). 4. Release the fan cable connector(s) (3). 5. Remove the fan from the inverter (45). 6. Install the new fan in the reverse sequence. Figure 5-1 Fan removal for FSD and FSE Figure 5-2 Fan removal for FSF You have replaced the fan. 56 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6 Converters for Canadian installations (cul): FSA FSC In order that the system is cul-compliant, use cul-certified fuses type J or Siemens fuses of the 3NE1 type. Use only copper wire approved for 75 C. Install the converter with any external recommended suppressor with the following features: Surge-protective devices; device shall be a listed surge-protective device (Category code VZCA7) Rated voltage 3-ph. 480/277 VAC, 50/60 Hz Clamping voltage VPR = 2000 V, IN = 3 ka min, MCOV = 550 VAC, SCCR = 65 ka Suitable for type 1 or type 2 SPD application Clamping shall be provided between the phases and also between phase and ground Alternatively use the surge-protective device from Siemens AG, order no. 5SD7 424-1, to fulfil the cul requirements Converters for installation in the U.S. (UL): FSA FSF In order that the system is UL-compliant, use the fuses listed in section Specific technical data (Page 62). Use only copper wire approved for 75 C. Hardware Installation Manual, 06/2014, A5E34331322B AA 57

Technical specifications 6.1 General technical data (400 V inverters) 6.1 General technical data (400 V inverters) Feature Input data Line voltage Inrush current Input frequency Line impedance Specification 3 AC 380 V 480 V ± 10 % up to 2000 m installation altitude. For higher installation altitudes, see "Restrictions for special ambient conditions (Page 68)" < rated input current (see "Specific technical data (Page 62)") 50 Hz 60 Hz, ± 3 Hz Uk < 1 %, a line reactor is not permitted Short-circuit current rating (SCCR) 65 ka 1) Output data Output voltage 3-ph. AC 0 V line voltage * 0.95 Output current (see "Specific technical data (Page 62)") Output frequency Pulse frequency 0 Hz... 550 Hz (depending on the control mode) 4 khz (factory setting) Can be increased from 2 khz up to 16 khz in 2 khz steps. An increased pulse frequency results in a lower output current Pulse frequency for inverters, frame size FSF: Inverters, frame size FSF equipped with an external Class B filter, may only be operated up to a pulse frequency of 4 khz so that the guaranteed EMC properties are complied with. Power factor λ 0.9 for Uk = 1 % Ambient conditions Electromagnetic Compatibility (EMC) Based on IEC61800-3, devices with filter are suitable for environmental classes, Category C2: 2004. For details, please refer to Assigning the inverter to EMC categories (Page 73) Electromagnetic radiation It is not permissible that the inverter is installed close to sources of electromagnetic radiation Storage temperature -40 C +70 C Environmental requirements Protection according to environmental protection class 3C2, and protection against hazardous chemical substances, according to EN 60721-3-3 Pollution According to pollution degree 2 It is not permissible that the inverter is installed in environments with polluted air, for example dust and/or corrosive gases Moisture < 95% relative humidity, no condensation 58 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.1 General technical data (400 V inverters) Feature Shock and vibration Overvoltage category Specification Long-term storage in the transport packaging according to 1M2 to EN 60721-3-1: 1997 Transport in the transport packaging according to 2M3 to EN 60721-3-2: 1997 Vibration in operation according to 3M2 to EN 60721-3-3: 1995 The inverter insulation is designed for surge voltages according to EN 60664-1 (2008) according to the following categories. Overvoltage category III: Supply circuits Overvoltage category II: Non-supply circuits Rated surge voltage 3 AC 400 V: 4000 V Degree of protection Chassis units: IP20 to EN 60529 Operating temperature Installation altitude Functions Braking methods PT devices: IP55 acc. to EN 60529 0 C...40 C Low Overload 0 C...50 C High Overload For higher temperatures, refer to "Restrictions for special ambient conditions (Page 68)" Up to 1000 m, for higher installation altitudes, see "Restrictions for special ambient conditions (Page 68)" DC braking Compound braking 1) When fused using a Class J or 3NE1 fuse, rated voltage 600 V AC with the rated current of the specific inverter. Hardware Installation Manual, 06/2014, A5E34331322B AA 59

Technical specifications 6.1 General technical data (400 V inverters) Permissible converter overload The converters have different power ratings "High Overload" and "Low Overload" depending on the expected load. Figure 6-1 Duty cycles, "High Overload" and "Low Overload" Note Please note that the base load (100% power or current) for "Low Overload" is higher than the base load for "High Overload". The load cycles shown in the diagram are examples. We recommend the "SIZER" engineering software to select the inverter based on duty cycles. See Configuring support (Page 82). 60 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.1 General technical data (400 V inverters) Definitions LO base load input current 100% of the permissible input current for a load cycle according to Low Overload. LO base load output current 100% of the permissible output current for a load cycle according to Low Overload. LO base load power 100 % of the inverter power for 100 % LO base load output current. HO base load input current 100% of the permissible input current for a load cycle according to High Overload. HO base load output current 100% of the permissible output current for a load cycle according to High Overload. HO base load power 100 % of the inverter power for 100 % HO base load output current. If not specified otherwise, the power and current data always refer to a load cycle according to Low Overload. Hardware Installation Manual, 06/2014, A5E34331322B AA 61

Technical specifications 6.2 Specific technical data 6.2 Specific technical data Note The values for Low Overload (LO) are identical with those of the rated values. Table 6-1 PM230, IP20, Frame Sizes A, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE11-3UL1 1NE11-3AL1 0.37 kw 1.3 A 1.3 A 0.25 kw 0.9 A 0.9 A 3NE1 813-0 AJT2 / 3NE1 813-0 1NE11-7UL1 1NE11-7AL1 0.55 kw 1.8 A 1.7 A 0.37 kw 1.3 A 1.3 A 3NE1 813-0 AJT4 / 3NE1 813-0 1NE12-2UL1 1NE12-2AL1 0.75 kw 2.3 A 2.2 A 0.55 kw 1.8 A 1.7 A 3NE1 813-0 AJT4 / 3NE1 813-0 Power loss 0.04 kw 0.04 kw 0.05 kw Required cooling air flow 1.5 l/s 1.5 l/s 4.5 l/s Cross section of line and motor cables 1 2.5 mm 2 18 14 AWG 1 2.5 mm 2 18 14 AWG 1 2.5 mm 2 18 14 AWG Tightening torque for line and motor cables 0.5 Nm / 4 lbf in 0.5 Nm / 4 lbf in 0.5 Nm / 4 lbf in Weight without filter Weight with filter 1.4 kg 1.6 kg 1.4 kg 1.6 kg 1.4 kg 1.6 kg Table 6-2 PM230, IP20, Frame Sizes A, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE13-1UL1 1NE13-1AL10 1.1 kw 3.2 A 3.1 A 0.75 kw 2.3 A 2.2 A 3NE1 813-0 AJT6 / 3NE1 813-0 1NE14-1UL1 1NE14-1AL1 1.5 kw 4.2 A 4.1 A 1.1 kw 3.2 A 3.1 A 3NE1 813-0 AJT6 / 3NE1 813-0 -1NE15-8UL1-1NE15-8AL1 2.2 kw 6.1 A 5.9 A 1.5 kw 4.2 A 4.1 A 3NE1 813-0 AJT10 / 3NE1 813-0 Power loss 0.06 kw 0.07 kw 0.08 kw Required cooling air flow 4.5 l/s 4.5 l/s 4.5 l/s Cross section of line and motor cables 1 2.5 mm 2 18 14 AWG 1 2.5 mm 2 18 14 AWG 1.5 2.5 mm 2 16 14 AWG Tightening torque for line and motor cables 0.5 Nm / 4 lbf in 0.5 Nm / 4 lbf in 0.5 Nm / 4 lbf in Weight without filter Weight with filter 1.4 kg 1.6 kg 1.4 kg 1.6 kg 1,4 kg 1.6 kg 62 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.2 Specific technical data Table 6-3 PM230, IP20, Frame Sizes A, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL Power loss Required cooling air flow 6SL3210 6SL3210 1NE17-7UL1 1NE17-7AL1 3 kw 8.0 A 7.7 A 2.2 kw 6.1 A 5.9 A 3NE1 813-0 AJT10 / 3NE1 813-0 0.11 kw 4.5 l/s Cross section of line and motor cables 1.5 2.5 mm 2 Tightening torque for line and motor cables Weight without filter Weight with filter 16 14 AWG 0.5 Nm / 4 lbf in 1.4 kg 1.6 kg Table 6-4 PM230, PT, Frame Sizes A, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL Power loss Required cooling air flow 6SL3211 6SL3211 1NE17-7UL1 1NE17-7AL1 3 kw 8.0 A 7.7 A 2.2 kw 6.1 A 5.9 A 3NE1 813-0 AJT10 / 3NE1 813-0 0.11 kw 4.5 l/s Cross section of line and motor cables 1.5 2.5 mm 2 Tightening torque for line and motor cables Weight without filter Weight with filter 16 14 AWG 0.5 Nm / 4 lbf in 1.7 kg 1.9 kg Hardware Installation Manual, 06/2014, A5E34331322B AA 63

Technical specifications 6.2 Specific technical data Table 6-5 PM230, IP20, Frame Sizes B, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE21-0UL1 1NE21-0AL1 4 kw 10.5 A 10.2 A 3 kw 8.0 A 7.7 A 3NE1 813-0 AJT15 / 3NE1 813-0 1NE21-3UL1 1NE21-3AL1 5.5 kw 13.6 A 13.2 A 4 kw 10.5 A 10.2 A 3NE1 814-0 AJT20 / 3NE1 814-0 1NE21-8UL1 1NE21-8AL1 7.5 kw 18.6 A 18 A 5.5 kw 13.6 A 13.2 A 3NE1 815-0 AJT25 / 3NE1 815-0 Power loss 0.12 kw 0.15 kw 0.22 kw Required cooling air flow 9.2 l/s 9.2 l/s 9.2 l/s Cross section of line and motor cables 1.5 6 mm 2 16 10 AWG 1.5 6 mm 2 16 10 AWG 1.5 6 mm 2 16 10 AWG Tightening torque for line and motor cables 0.6 Nm / 5 lbf in 0.6 Nm / 5 lbf in 0.6 Nm / 5 lbf in Weight without filter Weight with filter 2.8 kg 3 kg 2.8 kg 3 kg 2.8 kg 3 kg Table 6-6 PM230, PT, Frame Sizes B, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL Power loss Required cooling air flow 6SL3211 6SL3211 1NE21-8UL1 1NE21-8AL1 7.5 kw 18.6 A 18 A 5.5 kw 13.6 A 13.2 A 3NE1 815-0 AJT25 / 3NE1 815-0 0.22 kw 9.2 l/s Cross section of line and motor cables 1.5 6 mm 2 Tightening torque for line and motor cables Weight without filter Weight with filter 16 10 AWG 0.6 Nm / 5 lbf in 3.4 kg 3.6 kg 64 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.2 Specific technical data Table 6-7 PM230, IP20, Frame Sizes C, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE22-6UL1 1NE22-6AL1 11 kw 26.9 A 26 A 7.5 kw 18.6 A 18 A 3NE1 803-0 AJT35 / 3NE1 803-0 1NE23-2UL1 1NE23-2AL1 15 kw 33.1 A 32 A 11 kw 26.9 A 26 A 3NE1 817-0 AJT45 / 3NE1 817-0 1NE23-8UL1 1NE23-8AL1 18.5 kw 39.2 A 38 A 15 kw 33.1 A 32 A 3NE1 817-0 AJT50 / 3NE1 817-0 Power loss 0.3 kw 0.35 kw 0.45 kw Required cooling air flow 18.5 l/s 18.5 l/s 18.5 l/s Cross section of line and motor cables 6 16 mm 2 10 6 AWG 6 16 mm 2 10 6 AWG 6 16 mm 2 10 6 AWG Tightening torque for line and motor cables 1.5 Nm / 13 lbf in 1.5 Nm / 13 lbf in 1.5 Nm / 13 lbf in Weight without filter Weight with filter 4.5 kg 5.1 kg 4.5 kg 5.1 kg 4.5 kg 5.1 kg Table 6-8 PM230, PT, Frame Sizes C, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL Power loss Required cooling air flow 6SL3211 6SL3211 1NE23-8UL1 1NE23-8AL1 18.5 kw 39.2 A 38 A 15 kw 33.1 A 32 A 3NE1 817-0 AJT50 / 3NE1 817-0 0.45 kw 18.5 l/s Cross section of line and motor cables 6 16 mm 2 Tightening torque for line and motor cables Weight without filter Weight with filter 10 6 AWG 1.5 Nm / 13 lbf in 5.4 kg 6 kg Hardware Installation Manual, 06/2014, A5E34331322B AA 65

Technical specifications 6.2 Specific technical data Table 6-9 PM230, IP20, Frame Sizes D, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE24-5UL0 1NE24-5AL0 22 kw 42 A 45 A 18.5 kw 36 A 38 A 3NE1818-0 3NE1818-0 1NE26-0UL0 1NE26-0AL0 30 kw 56 A 60 A 22 kw 42 A 45 A 3NE1820-0 3NE1820-0 Power loss 0.52 kw 0.68 kw Required cooling air flow 80 l/s 80 l/s Cross section of line and motor cables 16 35 mm 2 5 2 AWG 16 35 mm 2 5 2 AWG Tightening torque for line and motor cables 6 Nm / 53 lbf in 6 Nm / 53 lbf in Weight without filter Weight with filter 11 kg 14 kg 11 kg 14 kg Table 6-10 PM230, IP20, Frame Sizes E, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE27-5UL0 1NE27-5AL0 37 kw 70 A 75 A 30 kw 56 A 60 A 3NE1021-0 3NE1021-0 1NE28-8UL0 1NE28-8AL0 45 kw 84 A 90 A 37 kw 70 A 75 A 3NE1022-0 3NE1022-0 Power loss 0.99 kw 1.2 kw Required cooling air flow 80 l/s 80 l/s Cross section of line and motor cables 25 50 mm 2 3 1-1/0 AWG 25 50 mm 2 3 1-1/0 AWG Tightening torque for line and motor cables 6 Nm / 53 lbf in 6 Nm / 53 lbf in Weight without filter Weight with filter 15 kg 22 kg 15 kg 22 kg 66 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.2 Specific technical data Table 6-11 PM230, IP20, Frame Sizes F, 3 AC 380 V 480 V Order No. - without filter Order No. - with filter LO base load power LO base load input current LO base load output current HO base load power HO base load input current HO base load output current Fuse according to IEC Fuse according to UL 6SL3210 6SL3210 1NE31-1UL0 1NE31-1AL0 55 kw 102 A 110 A 45 kw 84 A 90 A 3NE1224-0 3NE1224-0 1NE31-5UL0 1NE31-5AL0 75 kw 135 A 145 A 55 kw 102 A 110 A 3NE1225-0 3NE1225-0 Power loss 1.4 kw 1.9 kw Required cooling air flow 150 l/s 150 l/s Cross section of line and motor cables 35 120 mm 2 2 4/0 AWG 35 120 mm 2 2 4/0 AWG Tightening torque for line and motor cables 13 Nm / 115 lbf in 13 Nm / 115 lbf in Weight without filter Weight with filter 33 kg 48 kg 33 kg 48 kg Hardware Installation Manual, 06/2014, A5E34331322B AA 67

Technical specifications 6.3 Restrictions for special ambient conditions 6.3 Restrictions for special ambient conditions 6.3.1 Current de-rating depending on the operating temperature Current de-rating depending on the ambient operating temperature NOTICE Restrictions for the permissible ambient operating temperature as a result of the Control Unit or operator panel For the permissible ambient operating temperature, also observe possible restrictions as a result of the Control Unit or an operator panel. 68 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.3 Restrictions for special ambient conditions 6.3.2 Current and voltage derating dependent on the installation altitude Current derating depending on the installation altitude Above 1000 m above sea level you must reduce the inverter output current corresponding to the adjacent curve as a result of the lower cooling power of the air. Permissible line supplies depending on the installation altitude Installation altitude up to 2000 m above sea level Connection to every supply system permitted for the inverter. Installation altitudes between 2000 m and 4000 m above sea level Connection to a TN system with grounded neutral point. TN systems with grounded line conductor are not permitted. The TN line system with grounded neutral point can also be supplied using an isolation transformer. The phase-to-phase voltage does not have to be reduced. Also observe restrictions related to the connection of components. 6.3.3 Current and power limiting depending on the line voltage Current and power limiting depending on the line voltage Hardware Installation Manual, 06/2014, A5E34331322B AA 69

Technical specifications 6.4 Permissible shock and vibration values 6.3.4 Current reduction depending on pulse frequency Table 6-12 Current reduction depending on the pulse frequency 1) LO base load Output base-load current at a pulse frequency of 2 khz 4 khz 6 khz 8 khz 10 khz 12 khz 14 khz 16 khz kw A A A A A A A A 0.37 -- 1.30 1.11 0.91 0.78 0.65 0.59 0.52 0.55 -- 1.70 1.45 1.19 1.02 0.85 0.77 0.68 0.75 -- 2.20 1.87 1.54 1.32 1.10 0.99 0.88 1.1 -- 3.10 2.64 2.17 1.86 1.55 1.40 1.24 1.5 -- 4.10 3.49 2.87 2.46 2.05 1.85 1.64 2.2 -- 5.90 5.02 4.13 3.54 2.95 2.66 2.36 3.0 -- 7.70 6.55 5.39 4.62 3.85 3.47 3.08 4.0 -- 10.20 8.67 7.14 6.12 5.10 4.59 4.08 5.5 -- 13.20 11.22 9.24 7.92 6.60 5.94 5.28 7.5 -- 18.00 15.30 12.60 10.80 9.00 8.10 7.20 11.0 -- 26.00 22.10 18.20 15.60 13.00 11.70 10.40 15.0 -- 32.00 27.20 22.40 19.20 16.00 14.40 12.80 18.5 -- 38.00 32.30 26.60 22.80 19.00 17.10 15.20 22 -- 45.00 38.25 31.50 27.00 22.50 20.25 18.00 30 -- 60.00 51.00 42.00 36.00 30.00 27.00 24.00 37 -- 75.00 63.75 52.50 45.00 37.50 33.75 30.00 45 -- 90.00 76.50 63.00 54.00 45.00 40.50 36.00 55 -- 110.0 93.50 77.00 66.00 55.00 49.50 44.00 75 -- 145.0 123.3 101.5 -- -- -- -- 1) The permissible motor cable length also depends on the cable type and the selected pulse frequency. 6.4 Permissible shock and vibration values Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3- 1: 1997 Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997 Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995 70 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.5 Electromagnetic compatibility of the inverter 6.5 Electromagnetic compatibility of the inverter The SINAMICS G120 drives have been tested in accordance with the EMC Product Standard EN 61800-3:2004. Details see declaration of conformity The electromagnetic compatibility refers to both the immunity and the emitted interference of a device. The following disturbance variables must be taken into consideration when evaluating the electromagnetic compatibility: Conducted low-frequency disturbance variables (harmonics) Conducted high-frequency disturbance variables Field-based, low-frequency disturbance variables Field-based, high-frequency disturbance variables The permitted limit values are defined in the EMC product standard EN 61800-3 in EMC categories C1 to C4. Below you will find some key definitions relating to this. Classification of EMC behavior The EMC environment and the EMC Categories are defined in the EMC product standard EN 61800-3 as follows: Environments: First environment (public systems) An environment that includes domestic premises and establishments that are connected directly to a public low-voltage line supply without the use of an intermediate transformer. Example: Houses, apartments, commercial premises, or offices in residential buildings. Second environment (industrial systems) An environment that includes all other establishments which are not connected directly to a public low-voltage line supply. Example: Industrial areas and technical areas of buildings that are supplied by an assigned transformer. Hardware Installation Manual, 06/2014, A5E34331322B AA 71

Technical specifications 6.5 Electromagnetic compatibility of the inverter Categories Category C4 Drive systems with a rated voltage 1000 V, with an LO output current 400 A, or for use in complex systems in the second environment Drive systems which correspond to category C4 may only be installed in the second environment. Category C3 Drive systems with a rated voltage < 1,000 V, which are intended for use in the second environment and not for use in the first environment. Drive systems which correspond to category C3 may only be installed in the second environment. Category C2 Drive systems with a rated voltage < 1,000 V, which are neither plug-in devices nor moveable devices and which, when used in the first environment, are only intended to be installed and commissioned by an expert. Drive systems which correspond to category C2 may only be used in the first environment if they are installed by an expert, with limit values for electromagnetic compatibility (Page 73) observed. Category C1 Drive systems with a rated voltage < 1000 V, which are intended for use in the first environment. Drive systems which correspond to category C1 can be installed in the first environment without restrictions. Note Expert An expert is a person or organization with the necessary experience for installing and/or commissioning drive systems (Power Drive Systems - PDS), including the associated EMC aspects. 72 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.5 Electromagnetic compatibility of the inverter 6.5.1 Assigning the inverter to EMC categories The inverters have been tested in accordance with the EMC product standard EN 61800-3. You can find precise information in the Declaration of Conformity on the Internet at: Declaration of Conformity (http://support.automation.siemens.com/ww/view/en/58275445) Requirements for electromagnetic compatibility To comply with the requirements of EN 61800-3, all drives must be installed in accordance with the manufacturer's instructions and EMC directives. See also: EMC installation guideline (http://support.automation.siemens.com/ww/view/en/60612658). The inverter must be permanently installed on the basis of the leakage currents (> 3.5 ma). In particular, installation must be carried out by an expert who has the necessary experience for installing and/or commissioning power drives, included the associated EMC aspects. Second environment - category C4 The unfiltered inverters correspond to category C4. EMC measures in the second environment, category C4, are carried out on the basis of an EMC plan on the system level. See also EMC-compliant installation (Page 41). Second environment - category C3 Immunity With respect to their immunity, the converters are suitable for the second environment. Emitted interference Using a converter with an integrated line filter ensures compliance with the limit values for category C3. If you are using unfiltered converters in an industrial plant, you must either use an external filter for the converter or install corresponding filters on the system level (conducted highfrequency disturbance variables). When installed professionally in accordance with EMC guidelines, the converters fulfill the requirements of the standard in relation to category C3 (field-based high-frequency disturbance variables). Hardware Installation Manual, 06/2014, A5E34331322B AA 73

Technical specifications 6.5 Electromagnetic compatibility of the inverter Second environment - category C2 Interference immunity With respect to their immunity, the inverters are suitable for the second environment. Interference emission In order for the inverters to comply with the limit values for category C2 relating to emitted interference, the following conditions must be fulfilled: The motor connection cable is shorter than 50 m The pulse frequency does not exceed 4 khz The current does not exceed the value of the LO input current (high-frequency conducted interference), see Specific technical data (Page 62) You are using a shielded motor connection cable with low capacitance (high-frequency, radiated faults) First environment - category C1 The converters do not correspond to category C1. EMC / Immunity The Power Modules have been tested in accordance with the immunity requirements of category C3 Second Environment and fulfill the requirements according 61800-38. Note The immunity requirements apply equally to both filtered and unfiltered Power Modules. Harmonic currents Typical harmonic current (% of rated input current) at UK 1 % 5. 7. 11. 13. 17. 19. 23. 25. 21 15 10 9 7 6 6 5 Note Installation of Power Modules in an environment of category C2 Power Modules, which are installed in an environment of category C2, require a connection approval for the low-voltage supply system. Contact your local supply system operator in this case. You can find the Configuration Manual "EMC installation guideline" here (http://support.automation.siemens.com/ww/view/en/60612658) 74 Hardware Installation Manual, 06/2014, A5E34331322B AA

Technical specifications 6.5 Electromagnetic compatibility of the inverter 6.5.2 EMC limit values in South Korea The EMC limit values to be complied with for South Korea correspond to the limit values of the EMC product standard for variable-speed electric drives EN 61800-3, Category C2 or limit value class A, Group 1 according to EN55011. By applying suitable supplementary measures, the limit values according to Category C2 or according to limit value class A, Group 1 are maintained. Further, additional measures may be required, for instance, using an additional radio interference suppression filter (EMC filter). The measures for EMCcompliant design of the system are described in detail in this manual respectively in the Installation Guideline EMC. Please note that the final statement on compliance with the standard is given by the respective label attached to the individual unit. Hardware Installation Manual, 06/2014, A5E34331322B AA 75

Technical specifications 6.5 Electromagnetic compatibility of the inverter 76 Hardware Installation Manual, 06/2014, A5E34331322B AA

Accessories 7 7.1 Mounting Frames Order numbers FSA: 6SL3260-6AA00-0DA0 FSB: 6SL3260-6AB00-0DA0 FSC: 6SL3260-6AC00-0DA0 The option package contains all necessary nuts and gaskets. Tightening torque for fixing mounting frame and converter for all frame sizes: 3 3.5 Nm. Dimensonal drawings Hardware Installation Manual, 06/2014, A5E34331322B AA 77

Accessories 7.1 Mounting Frames 78 Hardware Installation Manual, 06/2014, A5E34331322B AA

Accessories 7.2 Line filters 7.2 Line filters Dimensions for mounting the line filter Table 7-1 Technical data of the line filter (Class B) Order number 6SL3203-0BE17-7BA0 6SL3203-0BE21-8BA0 6SL3203-0BE23-8BA0 Power loss 13 W 22 W 49.4 W Line/load connection PE connection 2.5 mm 2 / 14 AWG 0.8 Nm / 7 lbf in 2.5 mm 2 / 14 AWG 2 Nm / 17.7 lbf in 6 mm 2 / 10 AWG 1.8 Nm / 15.9 lbf in 2.5 mm 2 / 14 AWG 2 Nm / 17.7 lbf in 16 mm 2 / 6 AWG 4.0 Nm / 35.4 lbf in 16 mm 2 / 6 AWG 3 Nm / 26.5 lbf in Degree of protection IP20 IP20 IP20 Weight 1.75 kg 4.0 kg 7.3 kg Hardware Installation Manual, 06/2014, A5E34331322B AA 79

Accessories 7.2 Line filters Table 7-2 Assignment table Line filter (Class B) Power Module 6SL3203-0BE17-7BA0 6SL3210-1NE11-3UL1 6SL3210-1NE11-7UL1 6SL3210-1NE12-2UL1 6SL3210-1NE13-1UL1 6SL3210-1NE14-1UL1 6SL3210-1NE15-8UL1 6SL321-1NE17-7UL1 6SL3203-0BE21-8BA0 6SL3210-1NE21-0UL1 6SL3210-1NE21-3UL1 6SL321-1NE21-8UL1 6SL3203-0BE23-8BA0 6SL3210-1NE22-6UL1 6SL3210-1NE23-2UL1 6SL321-1NE23-8UL1 Stands for 1 or 2: 1: Chassis device 2: Push-through device 80 Hardware Installation Manual, 06/2014, A5E34331322B AA

Appendix A A.1 Manuals and technical support A.1.1 Manuals for your inverter Table A- 1 Manuals for your converter Depth of the information Manual Contents Languages Download or order number + Getting Started Control Units CU230P-2; CU240B-2; CU240E-2 + Getting Started SINAMICS G120 Power Module ++ Operating Instructions Control Units CU230P-2 CU240B-2 / CU240E-2 +++ List Manual Control Units CU230P-2 CU240B-2 / CU240E-2 Installing the converter and commissioning. Installing the Power Module Installing and commissioning the converter, adapting fieldbus interfaces, description of the converter functions, data backup and series commissioning, service and maintenance Graphic function block diagrams. List of all parameters, alarms and faults. English, German, Italian, French, Spanish German, English Download manuals (http://support.automation.sie mens.com/ww/view/en/2233 9653/133300) SINAMICS Manual Collection Documentation on DVD, order number 6SL3097-4CA00-0YG0 +++ Hardware Installation Manual +++ Operating and installation instructions This manual For converter accessories, e.g. operator panel, reactors or filter. Hardware Installation Manual, 06/2014, A5E34331322B AA 81

Appendix A.1 Manuals and technical support A.1.2 Configuring support Table A- 2 Support when configuring and selecting the inverter Manual or tool Contents Available languages Catalog D 31 Online catalog (Industry Mall) SIZER Ordering data and technical information for the standard SINAMICS G inverters Ordering data and technical information for all SIEMENS products The overall configuration tool for SINAMICS, MICROMASTER and DYNAVERT T drives, motor starters, as well as SINUMERIK, SIMOTION controls and SIMATIC Technology English, German, Italian, French, Spanish English, German English, German, Italian, French Download or order number All about SINAMICS G120 (www.siemens.com/sinamics-g120) You obtain SIZER on a DVD (Order number: 6SL3070-0AA00-0AG0) and in the Internet: Download SIZER (http://support.automation.siemens.com/w W/view/en/10804987/130000) See also Engineering Manual Standard Drives (http://support.automation.siemens.com/ww/view/en/37728795) A.1.3 Product Support You can find additional information on the product and more in the Internet under: Product support (http://www.siemens.com/automation/service&support). In addition to our documentation, under this address we offer our complete knowledge base online: You can find the following information: Actual product information (Update), FAQ (frequently asked questions), downloads. The Newsletter contains the latest information on the products you use. The Knowledge Manager (Intelligent Search) helps you find the documents you need. Users and specialists from around the world share their experience and knowledge in the Forum. You can find your local representative for Automation & Drives via our contact database under "Contact & Partner". Information about local service, repair, spare parts and much more can be found under "Services". 82 Hardware Installation Manual, 06/2014, A5E34331322B AA

Appendix A.2 Standards A.2 Standards European Low Voltage Directive The SINAMICS G120 product series meets the requirements of the Low-Voltage Directive 2006/95/EU. The units are certified for compliance with the following standards: EN 61800-5-1 - Electrical power drive systems with adjustable speed European Machinery Directive The inverters are suitable for installation in machines. Compliance with the Machinery Directive requires a separate certificate of conformity. This must be provided by the plant construction company or the organization marketing the machine. European EMC Directive When installed according to the recommendations described in this manual, the SINAMICS G120 fulfils all requirements of the EMC Directive as defined by the EMC Product Standard for Power Drive Systems EN 61800-3. ISO 9001 Siemens I DT MC operates a quality management system which complies with the requirements of ISO 9001. UL508C Frame Sizes A-C: UL and CUL LISTED POWER CONVERSION EQUIPMENT, investigated according UL508C Frame Sizes D-F: TÜV SÜD (NRTL) certified Power Conversion Equipment, investigated according UL508C SEMI F47 Specification for Semiconductor Process Equipment Voltage Sag Immunity The Power Modules fulfill the requirements of the SEMI F47-0706 standard. Canadian Standards Association The Power Modules PM230, FSA FSC comply with the requirements of CSA 22.2 no. 14. Download certificates Certificates can be downloaded from the internet under the following link: Certificates (http://support.automation.siemens.com/ww/view/en/22339653/134200) Hardware Installation Manual, 06/2014, A5E34331322B AA 83

Appendix A.3 Abbreviations A.3 Abbreviations Abbreviation State AC Alternating current CE Communauté Européenne CU Control Unit DC Direct current DI Digital input DIP DIP switch DO Digital output ECD Equivalent circuit diagram EEC European Economic Community ELCB Earth leakage circuit breaker EMC Electromagnetic compatibility (EMC) EMI Electromagnetic interference FS Frame size... GSG Getting Started Guide HO High overload I/O Input/Output IGBT Insulated gate bipolar transistor LED Light emitting diode LO Low overload NC NC contact NEMA National Electrical Manufacturers Association NO NO contact OPI Operating instructions PELV Protective extra low voltage PM Power Module PPE Personnel protective equipment PT Push-through technology RCCB Residual-current operated circuit breaker RCD Residual current device RFI Radio frequency interference SELV Safety extra-low voltage VT Variable torque 84 Hardware Installation Manual, 06/2014, A5E34331322B AA

Index A Air barrier, 18 C Catalog, 82 Category C1, 72 Category C2, 72 Category C3, 72 Category C4, 72 Classification of EMC behavior, 71 Configuring support, 82 Cooling, 18 cul-compliant installation, 57, 57 Current reduction, 70 D Derating Installation altitude, 69 Dimensions, 25 Drilling patterns, 25 E Electrical installation, 29 EMC, 44 F First environment, 71 Fitting the CU, 27 G Getting Started, 81 H Hardware Installation Manual, 81 Harmonic currents, 74 Hotline, 82 I Industrial systems, 71 Industry Mall, 82 Installation altitude, 69 IP20 degree of protection, 17 IT system, 32 L Line supply type, 32 M Maintenance Cleaning, 53 Contamination, 53 Dirt, 53 Terminals, 54 Ventilation, 53 Manual Collection, 81 Manuals Converter accessories, 81 Download, 81 Overview, 81 Mounting, 20 N Neutral conductor, 32 O Operating instructions, 81 Overview Manuals, 81 P Parameter Manual, 81 Personal protective equipment, 17 Power distribution systems, 32 PPE, 17 Protective conductor, 32 Hardware Installation Manual, 06/2014, A5E34331322B AA 85

Index Public systems, 71 Pulse frequency, 70 Q Questions, 82 S Safety notes Electrical installation, 29 Second environment, 71 Service life of the fan, 54 SIZER, 82 Standards EN 61800-3, 71, 73 EN 61800-3, 71, 73 EN 61800-3:2004, 71 Star/delta connection, 39 Support, 82 T TN line system, 32 TT system, 32 U UL-compliant installation, 57, 57 86 Hardware Installation Manual, 06/2014, A5E34331322B AA