Source-Transfer Application Guide

Similar documents
Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Primary Injection Test Procedure

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

Docking Station Instructions

Configuration. S&C Scada-Mate Switching System Outdoor Distribution (14.4 kv through 34.5 kv)

PS/IO Circuit Board Retrofit

Wi-Fi and Security Administration

IntelliLink Setup Software

Setup. S&C 5800 Series Automatic Switch Controls With IntelliTeam Automatic Restoration System. Table of Contents. Instruction Sheet

Operating and Diagnostic Instructions for IntelliTeam SG Automatic Restoration System

Installation NOTICE. S&C IntelliCap Automatic Capacitor Control. Table of Contents. Instruction Sheet

Instructions for Operation of S&C Test Accessory Catalog Number TA-2669

Installation and Operation

Setup Instructions. S&C Universal Interface Module. Table of Contents. Instruction Sheet

Vista SD Portable Remote Control Pendant

Troubleshooting Instructions

Troubleshooting. S&C 6801M Automatic Switch Operators Reciprocating and Rotating Switch Operation. Table of Contents. Instruction Sheet 1045M-550

Operation. S&C 6800 Series Automatic Switch Controls with IntelliTeam SG Automatic Restoration System. Table of Contents. Instruction Sheet

Table of Contents Section Page Section Page Introduction Safety Information Installation Diagrams Installation

Operation. S&C IntelliRupter PulseCloser Fault Interrupter Outdoor Distribution (15.5 kv, 27 kv, and 38 kv) Table of Contents

Troubleshooting. S&C IntelliCap 2000 Automatic Capacitor Control. Table of Contents. Instruction Sheet

Troubleshooting. S&C IntelliCap Automatic Capacitor Control. Instruction Sheet Table of Contents

Quick-Start Programming

Troubleshooting. S&C IntelliCap Plus Automatic Capacitor Control. Table of Contents. Instruction Sheet

S&C 6801M Automatic Switch Operator

Troubleshooting. S&C 5800 Series Automatic Switch Control. Table of Contents. Instruction Sheet

DNP Points List and Implementation

DNP Points List and Implementation for Universal Controls

User s Guide. S&C IntelliTeam Designer. Table of Contents. Instruction Sheet

Setup. S&C IntelliCap 2000 Automatic Capacitor Control. Table of Contents. Instruction Sheet

Operation and Maintenance

Communications Card Operation

Specifications. S&C Micro-AT Source-Transfer Control. In Weatherproof Enclosure

Installation. Section Page Section Page NOTICE

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

IntelliTeam II Automatic Restoration System

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

DNP Points List and Implementation

Installation. Section Page Section Page NOTICE

DNP Points List and Implementation for the 6802 Vista Control

PG&E Points List for Universal Controls

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

PS8 - II. Professional Power Sequencer. User s Manual

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

Wi-Fi Administration and Operation

Specifications. S&C IntelliNode Interface Modules. Conditions of Sale

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

A0/A1 Controller Assembly Operation/Installation Manual READ AND FOLLOW ALL SAFETY INSTRUCTIONS

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 120 Volt

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

ZC Series Zone Monitoring Controllers

OPERATING PROCEDURES for the UPS-S2 Universal Power Supply Series 2

M250 (M LL) Safety

5504 Thermocouple Analog Input Module

POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 230 Volt

Installation Instructions

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

MFA-0801 & MFA-1201 D-M-E Smart Series Low Voltage Temperature Control System. User s Manual. D-M-E Company

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

User's Guide. MiniTec TM Series Model MN25 MultiMeter

M215-Z Safety Information (M LL-IG-ZC)

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

Resolver to Digital Expansion Board

Setup. Section Page Section Page NOTICE

Pressurized Line Leak Controller Module. For Veeder-Root TLS-350/350R Systems

Installation. S&C SpeedNet SDR Software Defined Radio. Table of Contents NOTICE. Instruction Sheet

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

M215 (M215-60) Safety

Conext CL-60 Inverter Firmware Upgrade Process

DCM Digital Control Modules

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

RGM180 Display Series

Micro-Ohmmeter Model 6292

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Installation Instructions

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

TDM-170 TIMER DISPLAY

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

Troubleshooting Guide

Series 8000 RF Signal Switch Solution

Series 8000 RF Signal Switch Solution

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

3-4 SAS/SATA II HDD Canister Entry version USER S MANUAL XC-34D1-SA10-0-R. Document number: MAN A

SATA II HDD Canister KISS DA 435 Quick Reference Guide

Economy Single Channel Output DC Power Supply

Specifications. S&C IntelliNode Interface Modules

5401 and 5402 Digital I/O Modules

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

Series 3700 Screw Terminal Assemblies Installation Instructions

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

S&C IntelliRupter PulseCloser Fault Interrupter Overhead Source-Transfer Application

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

ICM-25 INPUT CONTROL MODULE, 25 INPUTS RS-232(SERIAL) OUTPUT

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

Profibus DP Expansion Board

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

Transcription:

S&C Model 6802 Automatic Switch Control Source-Transfer Application Guide Table of Contents Section Page Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet.... 2 Warranty.... 2 Safety Information Understanding Safety-Alert Messages.... 3 Following Safety Instructions... 3 Replacement Instructions and Labels.... 3 Overview Site Information... 4 Overhead Source-Transfer Software... 5 April 8, 2013 S&C Electric Company Instruction Sheet 1045-568

Introduction Qualified Persons Read this Instruction Sheet Retain this Instruction Sheet Warranty Ç WARNING The equipment covered by this publication must be installed, operated, and maintained by qualified persons who are knowledgeable in the installation, operation, and maintenance of overhead electric power distribution equipment along with the associated hazards. A qualified person is one who is trained and competent in: The skills and techniques necessary to distinguish exposed live parts from non-live parts of electrical equipment. The skills and techniques necessary to determine the proper approach distances corresponding to the voltages to which the qualified person will be exposed. The proper use of the special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools for working on or near exposed energized parts of electrical equipment. These instructions are intended only for such qualified persons. They are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. Thoroughly and carefully read this instruction sheet before programming, operating, or maintaining your S&C Model 6802 Automatic Switch Control. Familiarize yourself with the safety information on page 3. The latest version of this instruction sheet is available online in PDF format at sandc.com/support/product-literature.asp This instruction sheet is a permanent part of your S&C Model 6802 Automatic Switch Control. Designate a location where you can easily retrieve and refer to this publication. The standard warranty contained in S&C s standard conditions of sale, as set forth in Price Sheet 150, applies to the S&C Model 6802 Automatic Switch Control and its associated options except that the first paragraph of said warranty is replaced by the following: (1) General: Seller warrants to immediate purchaser or end user for a period of 10 years from the date of shipment that the equipment delivered will be of the kind and quality specified in the contract description and will be free of defects of workmanship and material. Should any failure to conform to this warranty appear under proper and normal use within ten years after the date of shipment the seller agrees, upon prompt notification thereof and confirmation that the equipment has been stored, installed, operated, inspected, and maintained in accordance with recommendations of the seller and standard industry practice, to correct the nonconformity either by repairing any damaged or defective parts of the equipment or (at seller s option) by shipment of necessary replacement parts. This warranty does not apply to major components not of S&C manufacture, such as batteries and communication devices, as well as hardware, software, resolution of protocol-related matters, and notification of upgrades or fixes for those devices. However, S&C will assign to immediate purchaser or end user all manufacturers warranties that apply to such major components. 2 S&C Instruction Sheet 1045-568

Safety Information Understanding Safety-Alert Messages There are several types of safety-alert messages which may appear throughout this instruction sheet as well as on labels attached to the S&C Model 6802 Automatic Switch Control. Familiarize yourself with these types of messages and the importance of the various signal words, as explained below. Ç DANGER DANGER identifies the most serious and immediate hazards which will likely result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç WARNING WARNING identifies hazards or unsafe practices which can result in serious personal injury or death if instructions, including recommended precautions, are not followed. Ç CAUTION CAUTION identifies hazards or unsafe practices which can result in minor personal injury or product or property damage if instructions, including recommended precautions, are not followed. NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed. Following Safety Instructions If you do not understand any portion of this instruction sheet and need assistance, contact your nearest S&C Sales Office or S&C Authorized Distributor. Their telephone numbers are listed on S&C s website: sandc.com or call S&C Headquarters at (773) 338-1000; in Canada, call S&C Electric Canada Ltd. at (416) 249-9171. NOTICE Read this instruction sheet thoroughly and carefully before installing or operating your S&C Model 6802 Automatic Switch Control. Replacement Instructions and Labels If you need additional copies of this instruction sheet, contact your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd. It is important that any missing, damaged, or faded labels on the equipment be replaced immediately. Replacement labels are available by contacting your nearest S&C Sales Office, S&C Authorized Distributor, S&C Headquarters, or S&C Electric Canada Ltd. S&C Instruction Sheet 1045-568 3

Overview The S&C Model 6802 Automatic Switch Control can be easily configured for a sourcetransfer application that operates two S&C Scada-Mate or Scada-Mate CX Switches. Only one 6802 Switch Control is required for source-transfer when peer-to-peer communication with other switch controls is not required. IntelliTeam SG Automatic Restoration System software can be used for the 6802 Source-Transfer Application. IntelliTeam SG automatically handles multiple events, and can transfer multiple times back and forth to whichever source is available. Figure 1 shows the two FIC connectors on the bottom of the enclosure. Figure 1. Dual FIC connectors on the S&C Model 6802 Automatic Switch Control for sourcetransfer application. Site Information Before installation or configuration of the S&C Model 6802 Automatic Switch Control, review the Installation and Operating Instructions, and the Setting Phase and Ground Overcurrent Levels Instruction Sheet 1045-530, available at the S&C Website sandc.com Familiarize yourself with the features, procedures, warnings, settings, operation, and troubleshooting. The control can be configured in the shop prior to installation or after installation at the site. You need to collect basic information about the circuit and location where the equipment will be installed. Obtain the total clearing curves for the preferred- and alternate-source circuit breakers or other upstream fault-clearing devices, along with other relay settings, such as reclose times, number of trips, type of trips (instantaneous or delayed), and reset times. Determine if there are any capacity constraints on either source that should prevent transfer under certain loading conditions. Ensure that the voltage sensors on both switches face the substation side of the line. Obtain the sensor calibration sheets shipped with the switches. Record the switch serial numbers. Verify that you have the correct software for this switch control application. 4 S&C Instruction Sheet 1045-568

Overhead Source-Transfer Software Use these instructions with software SG6802DOInstaller-3.5.5 or a later revision. Step 1 Install SG6802DOInstaller-3.5.5 software on the computer that will be used to program the 6802 Controls. IntelliLink Software will be automatically installed. Step 2 Connect your computer to the switch control with a serial or USB cable. Always use battery power or a grounded, 3-wire extension cord for your computer and the ac powered switch control. Your serial or USB port may be damaged if the computer or switch control is not grounded. Step 3 Start IntelliLink with Start > Programs > S&C Electric > IntelliLink. IntelliLink will automatically connect to the 6802 Control and open the Operation screen. Step 4 On the Setup > General > Time screen, configure the parameters for Daylight Savings Time Automatic Switchover, Time and Date. On the Setup > General screen configure the Physical Location and Cabinet Heater settings. Ignore the Cabinet Heater setting if the control is not powered from a 120-Vac source, because the heater does not function with sensor power. Enter the serial number for each switch. Step 5 On the Setup > General > Sensor Configuration screen enable Visual Disconnect status for Scada-Mate installations. Scada-Mate CX Switches do not have a status contact for their optional visual disconnect. Enter the sensor calibration data provided for Switch 1 and Switch 2. Switch 1 is connected to the rear FIC near the mounting bracket, Switch 2 is connected to the front FIC near the enclosure door. Step 6 On the Setup > General > Site-Related screen enter the installation-dependent parameters for voltage. The Loss-of-Voltage Threshold setting can be increased as reliability and power quality dictate for a particular load. Please review the Setup Instructions. Instantaneous reclose of an upstream breaker or recloser must be considered when determining the LOV setting. A voltage loss less than 15 cycles may not be detected by a 6802 Control. To detect a 15-cycle voltage loss at the 6802 Control, do not set the Loss-of-Voltage Threshold any lower than 60 volts. For a phase-to-neutral connected transformer, the Phase Angle Offsets should be set to zero degrees. For phase-to-neutral transformers, the Phase Angle Offsets should be set to 30 or 330 degrees. Verify that the Real-Time Data is correct. The correct settings will result in current in the normal direction and a reasonable power factor. See the Setup Instructions for further details. Step 7 On the Setup > General > Fault Detection screen select phase and ground fault settings according to the time-current clearing curves of the upstream fault-clearing device. Instruction Sheet 1042-572 Setting Phase and Ground Overcurrent Levels can assist you in determining these settings. For most installations, the Phase Fault Detection Current Level should be set at 90% of the minimum trip setting of the upstream recloser or breaker, and the Fault Duration Time Threshold should be set according to the fastest clearing time for high-magnitude faults. Ground Fault protection should be set to coordinate with the time-current curve of the upstream fault-clearing device. The usual setting is 100% of minimum to trip. Inrush settings should consider the connected transformer and motor kva on the load side of the switch, and follow ANSI/IEEE guidelines. S&C Instruction Sheet 1045-568 5

Overhead Source-Transfer Software Step 8 Return to the Operation screen and click CHANGE to Enable Automatic Operation. On the Setup > General > Automatic Operations screen set Features Enabled to Sectionalizing + Phase Loss for both switches, or determine the most appropriate setting for your application, and enable the same feature set for both switches. Enter settings for all the other parameters. Refer to S&C Instruction Sheet 1045-530 Setup, or press F1 for detailed information on each parameter. Go to the Validate/Apply screen and click Apply. Step 9 Go to the Setup > Communications > DNP screen. If SCADA communication is used, enter the required parameters. Also enter a non-zero RTU address for the 6802 that matches the RTU address you enter in the next step. See Instruction Sheet 1045-530 for more information about communication settings. Step 10 Go to the Setup > Restoration > IntelliTEAM SG > Team 1 Setup screen. See Figure 2. Enter a Team ID and set Team Logic to IT-II. Adjust the Return to Normal Timer if you want to use that function. Figure 2. IntelliTeam SG Setup for Team 1. Step 11 Configure Rec 1 for Sw 1 and Rec 2 for Sw 2. Switch 1 is connected to the rear FIC next to the bracket mount, Switch 2 is connected to the front FIC near the enclosure door. Enter the same RTU Address for both Rec 1 and Rec 2; use the same RTU Address you entered in Step 10. Specify which switch is Normally Closed and which is Normally Open. For the Normally Closed switch set the Normal Switch Function to Src/Sub and the Return to Normal Mode to Close. For the Normally Open switch set the Normal Switch Function to Tie/Sub and set the Return to Normal Mode to Close. Close defines Return to Normal as a closed transition mode or make-beforebreak. At Return to Normal the normally closed switch will close and then the normally open switch will open the feeders are temporarily tied together, but there is no outage. 6 S&C Instruction Sheet 1045-568

Overhead Source-Transfer Software Adjust Maximum Capacity. Step 12 Step 13 Set the Team Setup to Stopped, if not already set to Stopped. Click OK. Then set it back to Running and click OK. Step 14 Wait for the control to go into the Ready mode by watching the LCD on the control. Step 15 Save a snapshot of the control data. The Save Snapshot command is in the File menu on the toolbar of the IntelliLink screen. For further assistance, contact your local S&C Sales Office. S&C Instruction Sheet 1045-568 7

Printed in U.S.A.