ATS Automatic transfer switches Advanced version

Similar documents
Automatic Control Unit Configurator

AUTOMATIC TRANSFER SWITCH CONTROLLERS ATL SERIES

100% electricity. Automatic transfer switch controllers ATL series

Automation control units

Digital multimeters DMG

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

RM35TF V AC

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

Energy Management Modular DC Energy analyzer Type VIM-E and VIM-X

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

Zelio Control-modular measurement and control relays 1

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

Nemo SX - Multifunction control module

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

EMS CX 3 - State and control module for Latching relays and Contactors

EMS CX 3 - State and control module for Latching relays and Contactors

Programmable Relay ZEN V2 Units

Zelio Control Measurement Relays Multifunction 3-phase supply control relays RM17T 00

RM35LM33MW liquid level control relay RM35-L V AC/DC

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

COUNTIS ATv2/ATiv2 GB

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

RM17UB3. Price* : USD

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

3 Pole Contactors with AC operating coils

ENGINE, GENERATOR AND ATS CONTROLLERS. Engine Protection Controllers p18-1

ict contactors EN 61095, IEC 1095 Interference

ADXL Series SIMPLE, EFFICIENT AND SAFE MOTOR CONTROL

IDE Load break switches for machine control Remotely trippable switch from 32 to 160 A

Motor protection relays

ISOMETER isoev425/isoev425hc with coupling device AGH420

Monitoring Relays. SIRIUS 3UG Monitoring Relays for Stand-Alone Installation. Line monitoring. 8/62 Siemens IC Overview

MIC-2 MKII, Multi-instrument DATA SHEET

Page measurement up to 15th order Front optical USB and Wi-Fi communication port for PC, smartphone and tablet connection

NPW800R RETROFITTING. Power and Volatge Protection Relay

DEEP SEA ELECTRONICS PLC

Logic Controller Millenium Evo

CPS kVA TRIFASE EN50171

Mini Energy Web Server

ISOMETER isoev425 with coupling device AGH420

Model Number Structure

TeSys IEC Contactors and Overload Relays

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

EMS CX 3 - Signalling Auxiliary Contact (CA + SD)

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

METERING INSTRUMENTS AND CURRENT TRANSFORMERS

Safe monitoring relays

Technical data. Safety parameters: see page 333. DC maximum residual ripple: 10% Supply voltage tolerance: DC consumption: Control circuit

29 $ Manual Motor Starters FREESHIPPING. MOTOR CONTROLS 25. Features: MMS-32H Frame. MMS-63H Frame.

Postfach 2327, Offenburg * Helmholtzstr. 13, Offenburg. Technical Data. Model protecto ER

TeSys contactors From 115 to 2750 A

RM4TR31 three-phase network control relay RM4-T - range V

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Automatic transfer switch

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

Select a Micro800 Controller

93 SERIES. Timed socket for 34 series 93.68/93.69

Monitoring Relays MRU, MRI, MRM

QUINT-PS/ 1AC/24DC/ 5

DGC-2000 DIGITAL GENSET CONTROLLER

XBP24-E Base 24 I/O Ethernet PRELIMINARY. General characteristics Part number

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet

Logic Controller Millenium Evo

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

Page Backlight graphic display, 128x80 pixels. Optic interface port for programming, data download and diagnostics

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter

SR3B261FU modular smart relay Zelio Logic - 26 I O V AC - clock - display

SR3B261FU modular smart relay Zelio Logic - 26 I O V AC - clock - display

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

DATA SHEET Compact Genset Controller, CGC 200

RM35LM33MW liquid level control relay RM35-L V AC/DC

Earth-fault Relay SPAJ 110 C. Product Guide

SR2B121B compact smart relay Zelio Logic - 12 I O - 24 V AC - clock - display

RM4TA32 three-phase network control relay RM4-T - range V

Energy Management Energy Transducer Type ET112

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

COMPALARM AP. INSTRUCTION MANUAL IM620-U v0.41. Alarm Annunciator. General. Particulars. COMPALARM AP Instruction Manual IM620-U v0.

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Monitoring Relays. 3UG Monitoring Relays for Electrical and Additional Measurements. Line monitoring 7/61. Overview

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

MIC-2 Multi-instrument DATA SHEET

SENTRON ATC Automatic Transfer Control Device

Simple solutions for control technology

DSE2548 LED expansion module INTRODUCTION

AUTOMATIC POWER FACTOR CONTROLLERS AND THYRISTOR MODULES 23

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

PHOENIX CONTACT - 01/2007

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

NF760 Batch Controller

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

Transcription:

87045 LIMOGES Cedex Phone :+33 05 55 06 87 87 Fax :+33 05 55 06 88 88 ATS CONTENTS PAGES 1. USE 1 2. RANGE 1 3. DIMENSIONS 1 4. ELECTRICAL AND MECHANICAL CHARACTERISTICS 2 5. CONFORMITY 4 6. EQUIPMENTS AND ACCESSORIES 5 7. SYNOPTICS 9 8. SOURCE PRIORITIES 13 9. OPEN OR CLOSED TRANSITION 13 1. USE ATS automation transfer switches can control power supply inversion between two sources, manage generator start/stop, control single phase, two-phase and three-phase networks, control phase-phase and phase-neutral voltages. 4 226 83 overall dimensions (mm) 2. RANGE Reference Management 4 226 82 2 breakers advanced managing 4 226 83 3 breakers advanced managing 3. DIMENSIONS 4 226 82 overall dimensions (mm) 4 226 83 panel cutout (mm) 4 226 82 panel cutout (mm) 1/14

4. ELECTRICAL AND MECHANICAL CHARACTERISTICS AC power supply DC power supply Line 1 and Line 2 voltage inputs 4 226 82 4 226 83 100-240 V AC 101-240 V AC Rated voltage Ue 110-250 V DC 111-250 V DC Frequency 45-66 Hz 45-66 Hz Power consumption/ dissipation 3.8 W 9.5 VA 100 V AC: 10 VA, 5.3 W 240 V AC: 12.5VA, 5.5W Battery rated voltage 12 or 24 V DC 12-48 V DC Maximum current consumption Maximum power consumption/ dissipation Maximum rated voltage Ue Measuring range 230mA at 12 V DC 120mA at 24 V DC 2.9W 4.8W 480 V AC L-L (277 V AC L-N) 50-576 V AC L-L (333 V AC L-N) 400mA at 12 V DC 220mA at 24 V DC 100mA at 48 V DC 600 V AC L-L (346 V AC L-N) 50 720V L-L (415VAC L-N) Frequency range 45 66 Hz 45 66 Hz 360 440 Hz Measuring method True RMS True RMS Measuring input impedance > 0.5MΩ L - N > 0.55MΩ L - N > 1,0MΩ L - L > 1,10MΩ L - L Single-phase, two-phase, three-phase with or without Wiring mode three-phase with or without neutral or balanced threephase neutral or balanced threephase system system Measuring accuracy ±0.25% f.s. ±1digit ±0.25% f.s. ±1digit AC Supply Insulation voltage Line 1 and Line 2 voltage inputs insultation voltage Ambient operating conditions Connections Housing Modbus onboard port default configuration Rated insulation voltage Ui 250 V AC 250 V AC Uimp 7.3 kv 7.3 kv 3 kv 3 kv Rated insulation voltage Ui 480 V AC 600 V AC Uimp 7.3 kv 9.8 kv 3.8 kv 5.2 kv Operating temperature -30 C +70 C -30 C +70 C Storage temperature -30 C +80 C -30 C +80 C Measurement category III III Terminal type Plug-in / removable Plug-in / removable Cable cross section (min max) 0.2 2.5 mm2 (24 12 AWG) 0.2 2.5 mm2 (24 12 AWG) Tightening torque 0.56 Nm (5 lbin) 0.56 Nm (5 lbin) Degree of protection IP40 on front; IP65 on front; IP20 terminals IP20 terminals Weight 680 g 1000 g Node address - 1 Speed - 19200 Data format - 8 bit - EVEN Stop bits - 1 Protoocol - RTU 4 226 82 Inputs and outputs Digital inputs Input type Negative Current input 8mA Input Low Voltage 2.2V Input High Voltage 3.4V Input delay 50ms 4 226 83 Inputs and outputs Digital inputs Input type Negative Current input 8mA Input Low Voltage 2.2V Input High Voltage 3.4V Input delay 50ms OUT1 - OUT3 Contact type AC1-8A 250 V AC Rated current AC15-1.5A 250 V AC Max rated voltage Mechanical endurance Electrical endurance Max current at common contact Rated insulation voltage U i 250 V AC Uimp 7.3 kv 3 kv Contact type Rated current Max rated voltage Mechanical endurance Electrical endurance Rated insulation voltage Outputs OUT2 - OUT4 3 x 1 NO 3 x 1 NO 300 V AC 300 V AC 12 A 12 A OUT7 - OUT9 - OUT10 1 changeover AC1-8A 250 V AC DC1-8A 30 V DC AC15-1.5A 250 V AC 300 V AC U i 250 V AC Uimp 7.3 kv 3 kv 4.1 MONITORED PARAMETERS AC1-8A 250 V AC AC15-1.5A 250 V AC U i 250 V AC Uimp 7.3 kv 3 kv Contact type Rated current Max rated voltage Mechanical endurance Electrical endurance Max current at common contact Insulation type OUT1 - OUT2 2 x 1 NO AC1-8A 250 V AC DC1-8A 30 V DC AC15-1.5A 250 V AC 300 V AC - Single between OUT1 and OUT2 Double among the others Outputs OUT3 1 changeover AC1-8A 250 V AC DC1-8A 30 V DC AC15-1.5A 250 V AC 300 V AC - - Rated insulation voltage U i 250 V AC U imp 4.8 kv U imp 7.3 kv (single insulation) (double insulation) 1.5 kv 3 kv (single insulation) (double insulation) U i 250 V AC Uimp 7.3 kv 3 kv OUT4 - OUT5 OUT6 - OUT7 Contact type 2 x 1 NO + common contact AC1-8A 250 V AC 2 x 1 NO + common contact AC1-8A 250 V AC Rated current DC1-8A 30 V DC AC15-1.5A 250 V AC DC1-8A 30 V DC AC15-1.5A 250 V AC Max rated voltage Mechanical endurance Electrical endurance Max current at common contact 300 V AC 10 A 300 V AC 10 A Insulation type Single between OUT4 and OUT5 Single between OUT6 and OUT7 Double among the others Double among the others Rated insulation voltage U i 250 V AC U i 250 V AC U imp 4.8 kv U imp 7.3 kv U imp 4.8 kv U imp 7.3 kv (single insulation) (double insulation) (single insulation) (double insulation) 1.5 kv 3 kv 1.5 kv 3 kv (single insulation) (double insulation) (single insulation) (double insulation) Value Parameter Limits Voltage Value Delay Threshold MIN MAX MIN MAX MIN MAX Line presence without recovery line available - delay with recovery line available - Phase failure Asymmetry Frequency Threshold Limit Limit - MAX MIN MAX Delay Delay Delay - MAX MIN MAX 2/14

4.1 MONITORED PARAMETERS (NEXT) 4.3 DISPLAY To enhance and to simplify configuration and navigation, advanced ATSs have a graphic LCD display: Main menu Example of variation of the main line voltage within the minimum and maximum thresholds and relative hysteresis, with indication of the presence / absence delay times. The example considers the secondary line voltage absent with its circuit breaker open, hence the changeover times are not shown. The BREAKER STATUS bar represents the required status of the main line switch, while the LOGIC STATUS bar represents actual logic status of line controller. Px.y identify values to set for ATS (see instruction manual for details) and they correspond to the ones listed into table above on line Voltage. 4.2 PLC MODE FOR 4 226 83 For 4 226 83 advanced 3 ways driver, it s possible to use Legrand Automatic Control Unit Configurator (see chap. 6.4) to set a ladder program to create a PLC internal logic inside the ATS. In this way, user can create any function necessary to manage any kind of application. In application program logic, all the variables managed internally by the ATS can be entered, such as inputs, threshold limits, remote variables, controller states, etc... With timers menu it s possible to add timings to application. The processing results of the different branches of the ladder logic are stored in internal variables, which may later be used to control the outputs, or as support memories to built a more complex logic or to control the alarms defined by the user. With Legrand Automatic Control Unit Configurator, the operation of the logic created with the ladder program may be real time checked and modified. Through navigation buttons it s possible to reach any configuration or visualization menu, as, for example, plant synoptic: Plant synoptic for 4 226 83 Languages Advanced ATSs are available with different language packs onboard. For 4 226 82: - English (default) - French - Spanish - Russian - Polish For 4 226 83: - English (default) - French - Spanish - Russian - Polish - Portuguese - Italian - German Other language packs are available on Legrand e-catalogue for free download. To upload language pack into ATS, use Legrand Automatic Control Unit Configurator software. 3/14

4.4 CONTROL PANEL 4 226 82 5. CONFORMITY IEC 60 947-6-1 5.1 MARKING Led Colour Status ON Status OFF Status BLINK 1 Green AUTO Mode active - - 2 Red - - Alarm active 3,4 Green Voltage on Line within limits - - Mismatch between 5,6 Yellow Breaker - Breaker feedback OPEN/CLOSE status status and set one 4 226 82 Rear connections 4 226 83 Button Behaviour A OFF mode B AUTO mode C MANUAL mode Navigation and D main menu access 4 226 83 Rear connections Led Colour Status ON Status OFF Status BLINK 1 Red - - Alarm active 2,4 Yellow Mismatch between Breaker - Breaker feedback OPEN/CLOSE status status and set one 3,5 Green Voltage on Line within limits - - 6 Yellow OFF Mode active - - 7 Yellow MANUAL Mode active - - 8 Yellow AUTO Mode active - - 9 Yellow TEST Mode active - - Button Behaviour A Navigation B Confirm and main menu C Breakers manual command D OFF mode and RESET E MANUAL mode F AUTO mode G TEST mode H Breakers manual selection 4/14

6. EQUIPMENTS AND ACCESSORIES 6.1 Auxiliary power supply Auxiliary Dual power supply: it automatically selects the most appropriate source between two single-phase AC power supply lines (based on the presence of voltage within the minimum and maximum preset limits) ref. 4 226 86 Line 1 and Line 2 voltage inputs Maximum rated voltage Ue Operating range Frequency range Measuring method Measuring input impedance Power consumption/dissipation Connection methods 4 226 86 110 230 V AC 80 300 V AC 45 66 Hz True RMS > 8MΩ L-N 7 VA - 2.4 W Power supplied by the system with phase-to-neutral 300V AC Measuring accuracy ±1% 2 x 2 NO (presence Line 1 and Line 2) Contact type 1 x 2 CO (relay exchange line) Max voltage switching 300 V AV Rated voltage 250 V AC Relay outputs Ambient operating conditions Mechanical endurance Electrical endurance Rated current 6.2 Expansion accessories Rated insulation voltage U i 250 V AC U imp 4.8 kv 2.21 kv Operating temperature -30 C +70 C Storage temperature -30 C +80 C Measurement category III 4A 250VAC AC1-1,5A 250V AC AC15 Plug-in accessories 4 opto-isolated static outputs ref. 4 226 90 2 relay outputs ref. 4 226 91 2 opto-isolated digital inputs and 2 relay outputs ref. 4 226 92 The modules connection can be done simply by plugging them into the expansion slot of the base device which will automatically recognise them. The module parameters setup will be done directly from the main device menu. Connection procedure 1. Remove any dangerous voltage. 2. Remove terminal covers and terminal block. 3. Remove the expansion slot cover where the module will be plugged in. 4. Insert the module into the plug: Technical data SSR output Output ratings (at 60 C) Output connection Number of terminals 4 Insulation Ambient operating conditions Relay outputs Connection Insulation Ambient operating conditions Digital inputs Relay outputs 4 226 90 Solid state relays 40 V DC / 30 V AC 55 ma max Plug in/removable terminals Conductor cross section (min/max) 0.2-1.5 mm 2 (28-14 AWG) Tightening torque 0.18 Nm 7.3 kv 4 kv Operating temperature -20 C +60 C Storage temperature -30 C +80 C Degree of protection IP20 4 226 91 Number of outputs 2 1 changeover Rated operating voltage 250 V AC AC1 5A 250VAC - AC15 1.5A 250V AC, Rated current 5A 28 V DC Mechanical endurance Electrical endurance Plug in/removable terminals Conductor cross section (min/max) 0.2-2.5 mm 2 (28-12 AWG) Tightening torque 0.5 Nm Operating temperature -20 C +60 C Storage temperature -30 C +80 C Degree of protection IP20 7.3 kv (between DMG and outputs) 2.5 kv (between relay outs) 4 kv (between DMG and outputs) 1.5 kv (between relay outs) 4 226 92 Number of inputs 2 Negative Input current 7 ma Input delay 50ms Max frequency (COUNTER cfg) 2 khz Max frequency (STATUS cfg) 50 Hz Terminals voltage 5 V DC isolated Number of outputs 2 1 NO Rated operating voltage 250 V AC AC1 5A 250VAC - AC15 0.75A 250V AC, Rated current 2A 30 V DC Mechanical endurance Electrical endurance Terminals voltage 5 V DC isolated Plug in/removable terminals Connection Conductor cross section (min/max) 0.2-2.5 mm 2 (24-12 AWG) Tightening torque 0.5 Nm Inputs insulation 4 kv 2 kv Outputs insulation Ambient operating conditions Operating temperature -20 C +60 C Storage temperature -30 C +80 C Degree of protection IP20 6.5 kv (contact to low voltage circuits) 4 kv (contact to contact) 3.6 kv (contact to low voltage circuits) 2.25 kv (contact to contact) Module dimensions 5. Replace the terminal block and terminal covers. 6. Power up the system (the main device will automatically recognise the expansion unit): 5/14

Terminals and connections 4 226 90 6.3 Communication accessories Plug-in accessories Opto-isolated RS485 interface ref. 4 226 89 The module connection can be done simply by plugging it into the expansion slot of the base device which will automatically recognise it. The module parameters setup will be done directly from the main device menu. Connection procedure 4 226 91 1. Remove any dangerous voltage. 2. Remove terminal covers and terminal block. 3. Remove the expansion slot cover where the module will be plugged in. 4. Insert the module into the plug: 4 226 92 Inputs 5. Replace the terminal block and terminal covers. 6. Power up the system (the main device will automatically recognise the expansion unit): Technical data Outputs Port connection Insulation Ambient operating conditions 4 226 89 Plug in/removable terminals Number of terminals 4 Conductor cross section (min/max) 0.2-1.5 mm 2 (28-14 AWG) Tightening torque 0.18 Nm 7.3 kv 4 kv Operating temperature -20 C +60 C Storage temperature -30 C +80 C Degree of protection IP20 Module dimensions 6/14

Terminals and connections Link status LED Status IR presence WiFi status Data traffic Red steady No - - Orange blink Yes Connected, Stand-by - Orange steady Yes Connected, Ready - Green steady Yes Connected, Active No Green blink Yes Connected, Active Yes Front side accessories USB front connector for programming the automation control units or downloading the event log via PC. Galvanic insulation for safety connections guaranteed by IR communication port toward device. ref. 4 226 87 WiFi front connector for programming the automation control units or downloading the event log via PC, smartphone or tablet. Galvanic insulation for safety connections guaranteed by IR communication port toward device. ref. 4 226 88 Module description Dongle menu To enter the dongle menu it is necessary to perform the start-up procedure described below: Insert the dongle into the IR port of the device with which you want to communicate. Switch on dongle on by pressing the button for 2 s. Wait until the Link status LED becomes orange flashing. Press 3 times consecutively and fast the dongle button. The base device display will show the Dongle menu. To navigate the menu dongle use the arrow keys on the basic, following the directions of the bar on the last line of the page. Select the desired command and confirm it. For each command from D1 to D4 a second confirmation is requested before performing the selected operation: Charging the battery Before using the device fully charge the battery, leaving it connected to a USB power source until the battery LED will glow green: Colour Battery charge status Red < 10% Orange >10%, < 90% Green > 90% Power on Press and hold the button for 2 seconds to activate WiFi dongle. D1: it allows to download the setup menu from the device to the dongle. The data is saved in non-volatile memory of the dongle. If during the data transfer any error occurs (ex: dongle not perfectly connected to the device), then after the download the display will show error message CHECKSUM ERROR RETRY COMMAND'. In this situation the setup data is not saved. Retry D1 command. D2: it allows to transfer the data stored in the dongle (with previous command D1) to a different device. D3: it allows to download all the data of the device (setup, page info, events...) and save it in the non-volatile memory of dongle. If during the data transfer any error occurs (ex: dongle not perfectly inserted in the device IR port) then after the download the display will show error message CHECKSUM ERROR RETRY COMMAND'. In this situation the setup data is not saved. Retry D3 command. D4: it allows to transfer the data stored in the dongle with the command D3 to a different device. D5: it shows information about data currently stored in the internal memory of the dongle Power off Press and hold for 3 seconds the button to turn off permanently dongle. The dongle automatically turns off after 30 seconds if it is not placed in front to an active IR port. 7/14

Technical data 6.4 Software and mobile App Supply USB Supply voltage Supply current Power consumption/dissipation 4 226 88 5 V DC (taken from USB) 400 ma max 2 W B Programming software (Automatic Control Unit Configurator) available for download via E-catalogue; App (Automatic Control Unit Configurator) for smartphone & tablet available on Apple Store and Google Play. Li-Ion Battery Ambient operating conditions IP Rated voltage Capacity Life before recharge Recharging type Charging current 3.7 V 700 ma > 5 hours Connection to USB host 350 ma max Operating temperature 0 C +50 C Storage temperature -20 C +60 C Degree of protection IP20 Address 1.2.3.4 Port 2000 Module dimensions 8/14

7. SYNOPTICS Many configurations can be done with advanced ATS drivers. Here below some schematics. 4 226 82 4 226 83 For every possible setup, a range of example synoptic is available on Legrand e-catalogue. Besides synoptic, parameters configuration files for every product is available on e-catalogue. Synoptics and configuration files are for free download. 7.1 UNDERVOLTAGE RELEASE MANAGED BY 4 226 82 9/14

7.2 DIRECT COMMAND WITH FEEDBACK FOR DPX 3 160 AND DPX 3 250 WITH 4 226 82 7.3 DIRECT COMMAND WITH FEEDBACK FOR DPX 3 630 WITH 4 226 82 10/14

7.4 FAST CLOSING OPERATION COMMAND WITH FEEDBACK FOR DPX 3 1600 WITH 4 226 82 7.5 DMX 3 WITH FEEDBACK WITH 4 226 82 11/14

7.6 COMMANDS FOR CTX 3 WITH 4 226 82 7.7 MANAGEMENT WITH FEEDBACK FOR 4 226 83 12/14

8. SOURCE PRIORITIES DEFAULT 9. OPEN OR CLOSED TRANSITION Transfer switch equipment can be categorized into two general groups: Open-transition transfer devices: open the connected source before closing the new source, causing a total power interruption for a short period of time; Closed-transition transfer devices: operate like an open-transition transfer switch when a source has failed, but will parallel the two sources for 100 milliseconds or less and then disconnect when both sources are available, so a total interruption of power is avoided. 4226 83 ATS driver can manage both open and closed transitions, while 4 226 82 can manage only open one. Open-transition transfer switches Open-transition transfer switches provide a break before-make switching action. They are specifically designed to transfer power between main line and recovery line. The connection to one source is opened before the connection to the second source is closed (a black-out period must occur on loads during transition). Mechanical interlocks that positively prevent interconnection of sources in automatic and manual modes are commonly used. Open-transition transfer switches are the most commonly used type of transfer switch and are used in all types of applications. By design, they neither require nor allow recovery line paralleling with the main line, in order to have simpler and safer management. 13/14

Closed-transition transfer switches Closed-transition transfer switches provide a make-before-break switching action and utilize a momentary paralleling of both sources, avoiding black out situations on loads. While fast closed-transition transfer devices switch from sources without a total interruption, there is generally a disturbance in power supplied to the loads due to the sudden load change on the source. This is particularly true when transferring a load from the main line to the recovery one. In general, in order to prevent disruptive transients, fast closed-transition transfer switches must be transferred sequentially, and each switch load should be limited to less than 25 percent of the standby rating of the recovery line. Due to short timings, this kind of transition is useful in applications with fast motors (as in case of air circuit breakers or DPX 3 1600 with fast closing motor version). So, for closed transitions, a mechanical interlock cannot be compatible. 14/14