Power System Protection with Relay Co-Ordination

Similar documents
GUJARAT TECHNOLOGICAL UNIVERSITY

POWER FLOW ANALYSIS AND PROTECTION COORDINATION OF REAL TIME SYSTEM

RELAY CO-ORDINATION IN A 11KV SUBSTATION USING ETAP

ELG4125: System Protection

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

System Protection and Control Subcommittee

4. CIRCUIT BREAKERS. Functional Emergency Switching

SARDAR RAJA COLLEGE OF ENGINEERING ALANGULAM : PROTECTION AND SWITCHGEAR

OPTIMAL COORDINATION OF OVERCURRENT RELAYS IN AN INTERCONNECTED POWER SYSTEM

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

Applying branch circuit breakers and supplementary protectors in North America

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

Application Notes on Generator Protection Schemes

Applying branch circuit breakers and supplementary protectors in North America

Date of Publication: THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING GSM TECHNIQUE

Loop Automation. Technical Manual for the ADVC Controller Range

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

IMP/ 001 / 014 Policy for the Protection of Distribution Networks

Busbar protection REB 670

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

ESS20 Electronic Circuit Breaker

MiCOM P122C Time-Overcurrent Protection

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

Solid State Remote Power Controller E /627

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

REYROLLE 2RMLG. Operating Recommendations

EE 868: Digital Techniques for Power System Protection. Laboratory Assignment #2 (Feb. 8 (12pm)) Overcurrent Relay Coordination

Automation of Distribution Grid with FLISR using ZigBee Communication

Common Departures Interconnecting Facilities Requirements

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Switchgear FEATURE. Basler Electric Company

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

MRI1-IU - Voltage controlled time overcurrent relay

MiCOM P521. Fast Feeder Differential Protection

Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011

SECTION DISCONNECT SWITCHES

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

MiCOM P521. Fast feeder differential protection

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

Bus Protection Application Challenges

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

Supplemental Information

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

VIP 40/45 VIP 400/410

Purpose of High Voltage Circuit Switchers

2 F undamentals of Protection Practice

MV Network Switchgear, Protection and Control

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

OVERCURRENT / GROUND FAULT PROTECTION RELAY MPRB GF. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

IMPACT OF DISTRIBUTED GENERATION ON DISTRIBUTION NETWORK PROTECTION

Safe Isolation of Main Circuits with Switch-Disconnectors N or with Molded Case Switches NS

Amsterdam 27 September 2017 David MacDonald

1. Coordination of series-rated devices is permitted where indicated on Drawings.

PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE

Bulletin 1489 Circuit Breakers. Selection Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

Products Portfolio. Pole mounted Vacuum Recloser

Sentron 3VT circuit breakers Simply Smart: First choice for power distribution

Circuit Breaker Operation & its load calculations

ELECTRIC LINEMAN PROTECTION USING USER CHANGEABLE PASSWORD BASED CIRCUIT BREAKER 1

ADVANCED. Protection Co-ordination. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

Solid-State Switching Devices

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Ground Fault Current Protection Devices Prevent Costly Production Shutdowns

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Lessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc.

Short-Circuit Calculation Methods

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

Ground Fault Protection on Solidly Grounded Low Voltage Electrical Systems APPLICATION GUIDE. application GUIDE

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System

Emergency Stop Devices (MD Annex I ) Background

Power systems 5: Protection

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

1. Project Description

USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION

Deploying Digital Substations: Experience with a Digital Substation Pilot in North America. Harsh Vardhan, R Ramlachan GE Grid Solutions, USA

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR SYMBOLS. 2010, The McGraw-Hill Companies, Inc.

AUGUST 2001 APPLICATION AND COMMISSIONING MANUAL MIT161 RELAY EASUN REYROLLE LIMITED

satech TSB-14 MAIN FEATURES

INTEGRATION OF RECLOSERS INTO SCADA SYSTEMS

4. Fundamental Research, Educational, or Technological Advancement Barriers and Methodologies Used to Address Them

Relion 605 series. Self-powered feeder protection REJ603 Application Manual

Substation Automation Products. Line differential protection RED670 Relion 670 series

Intrinsically safe batch controller Batching Master 110i

Mitigating Arc Flash Hazards

MPSC Microprocessor-based protection and metering devices for low voltage power circuit breakers. ABB Power Distribution

REACTIVE ENERGY REGULATORS

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

RELT Reduced Energy Let Thru 2018

No actual trip output occurs if the upper paddle is removed first.

Earth-fault Relay SPAJ 110 C. Product Guide

CP30F Series Circuit Protector for Improving Safety and Wiring Workability

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

EMS-LECTURE 2: WORKING OF EMS

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL OVER CURRENT & EARTH FAULT PROTECTION RELAY TYPE MJT 315

Transcription:

Power System Protection with Relay Co-Ordination Mehulkumar D. Devdhariya 1, Vibhuti R. Adroja 2, Kajal M. Rafaliya 3, Prof. Manan M. Desai 4 1,2,3 Students, B.E. in Electrical Engineering, 4 Assistant Professor Dr. Subhash Technical Campus, Junagadh, Gujarat, India Abstract: Relay co-ordination plays an important role in the protection of power system. For proper protection, proper coordination of relays with appropriate relay settings is to be done. Relay settings are done in such a way that proper coordination is achieved along various series network. Relay co-ordination can be done by selecting proper plug setting and time multiplication setting of the relay, considering maximum fault current at the relay location. After selecting the plug setting and time multiplier setting, the co-ordination can be checked graphically. When plotting co-ordination curves, certain time intervals must be maintained between the curves of various protective devices in order to ensure the correct sequential operation of the devices when co-coordinating inverse time over current relays. For a given fault current, the operating time of IDMT relay is jointly determined by its plug and time multiplier settings. Thus this type of relay is most suitable for proper coordination. Operating characteristics of this relay are usually given in the form of a curve with operating current of plug setting multiplier along the X axis and operating time along Y axis. Keywords: Optimal coordination of relay, Primary and Back-up relay, Time setting multiplier, Plug setting multiplier, Relay setting, Over current relay, IDMT relay. 1. Introduction: Protection system for power system has been developed to minimize the damage and to make sure supply in safe condition, continuously and economically. Relay is one of the most important components in protection system. There is several kind of relay that each kind has own characteristic. A relay is device that makes a measurement or receives a signal that causes it to operate and to effect the operation of other equipment. It responds abnormal conditions in faulty section of the system with the minimum interruption of supply. The advantages of isolating a system fault as quickly as possible include safety for personnel and public, minimizing damage to Power plant and minimizing effects on system stability. 2. Problem Statement: Power system for must have a reliable and efficient protection scheme. Once fault occurred on the system, it must be isolated as quickly as possible. This action could minimize the effects on system stability and damage to plant. Referring to figure 1.1, when a fault occurred on the system, one of the relay should be operated. However, sometimes the relay that should be operated due to the fault does not work properly delay in operation or does not function at all. It might be due to the problems from the setting of the relay. Therefore, relay should be set properly to make it will function accordingly. So, related to the problem, the study will be focused to the setting and coordination of the relays that used in distribution system. 3. Primary and Back-up Protection: For attaining higher reliability, quick action and improvements in operating flexibility of the protection schemes, separate elements of a power system, in addition to main or primary protection, are provided with a back-up and auxiliary protection. First in line of defense is main protection which ensures quick action and selective clearing of faults within the boundary of the circuit section or the element it protects. Main protection is essentially provided as a rule. Back up protection gives back up to the main protection, when the main protection fails to operate or is cut out for repairs etc. Failure of the main protection may be due to any of the following reasons: A) D.C supply to the tripping circuit fails B) Current or voltage supply to the relay fails C) Tripping mechanism of the circuit breaker fails D) Circuit breaker fails to operate E) Main protective relay fails Back up protection may be provided either on the same circuit breakers which will be opened by the main protection or may use different circuit breakers. Usually, more than the faulty section is isolated when the back-up protection operates. Very often the main protection of a circuit acts as back up protection for the adjacent circuit. Back up protection is provided where main protection of the adjacent circuit fails to back up the given circuit. For simplification, back up protection can have a lower sensitivity factor and be operative over a limited back up zone i.e. be operative for only part of the protected circuit. Methods of back up protection can be classified as follows: IJEDR1702017 International Journal of Engineering Development and Research (www.ijedr.org) 101

A) Relay Back-up B) Breaker Back-up C) Remote Back-up D) Centrally Co-ordinated Back-up Back-up protection by Time Grading principle: Fig. 1: Primary and Back-up Protection by Time Grading Principle In this, current is measured at various points along the current path, for e.g., at source, intermediate locations, consumers end. The tripping time at these locations are graded in such a way that the circuit breaker nearest to the faulty section operates first, giving primary protection. The circuit breaker at the previous section operates only as a back-up. In Fig.3 the tripping time at sections C, B and A are graded such that for a fault beyond C, breaker at C operates as a primary protection. Relays at A and B also may start operating but they are provided with enough time lags so that breaker at B operates only if breaker at C does not. Thus, for a fault beyond C, breaker at C will operate after 0.1 second. If it fails to operate, the breaker at B will operate after 0.6 second (Back-up for C) and if the breaker at B also fails to operate, breaker a A will operate after 1 second (Back-up for B and C. 4. Test System: The step by step analysis is described in the subsequent segments. Fig. 2 : Single line diagram IJEDR1702017 International Journal of Engineering Development and Research (www.ijedr.org) 102

Relay Characteristics: Fig. 3: Various characteristics of IDMT relay Fig. 3 shows various inverse characteristics of induction disc relays. Characteristics are of four types: A) Standard or Normal Inverse B) Very Inverse C) Extremely Inverse D) Long Inverse For Normal inverse over current characteristics, the operation time is inversely proportional to the applied current. Very inverse over current characteristics are particularly suitable if there is a substantial reduction of fault current. The characteristics of this relay are such that its operating time is approximately doubled for a reduction in current from 7 to 4 times the relay current setting. This permits the use of the same time multiplier setting for several relays in series. 5. Calculations : Calculation of relay operating time: In order to calculate the actual relay operating A) Time / PSM Curve B) Plug Setting C) Time Setting D) Fault Current E) Current Transformer Ratio The procedure for calculating the actual relay operating time is as follows:- A) Convert the fault current into the relay coil current by using the current transformer ratio. B) Express the relay current as a multiple of current setting, i.e. calculate the PSM. C) From the Time/PSM curve of the relay, with the calculated PSM the corresponding time of operation can be obtained. D) Determine the actual time of operation by multiplying the above time of the relay by time-setting multiplier in use. IJEDR1702017 International Journal of Engineering Development and Research (www.ijedr.org) 103

Formulae for calculations: Relay current at fault condition, I R = I f CT Ratio Plug setting multiplier, fault current in relay coil PSM = Pick upcurrent Pick up current = Rated secondary current of C.T x Current setting Operating time, T = In general, T = 0.14 1 0.02 I r k TMS (I/I >) -1 TMS Ir = PSM, Where, T = Operating time in sec TMS = Time Multiplier Setting k,α, β = Curve constants I = Fault Current, I > = set current Table : Table of constants for various curves By using this calculation equation and table, we can calculate PSM, TSM, pick up current, actual operating time as shown in below. Table of calculation: C.T. RATIO P.S. (%) Fault Current TSM (ka) 300/5 200 5.870 0.25 250/5 150 5.0 0.20 60/5 125 4.80 0.15 60/5 100 4.75 0.10 30/5 50 4.42 0.05 PSM PICK UP IR ACTUAL OPERATING TIME 0.587 10 0.097 0.146 0.66 7.5 0.1 0.132 0.68 6.25 0.4 0.102 0.95 5 0.39 0.095 1.768 2.5 0.736 0.0884 IJEDR1702017 International Journal of Engineering Development and Research (www.ijedr.org) 104

6. Conclusion: Main objective of protective relay co-ordination in an interconnected power system is to achieve proper selectivity and speed without sacrificing sensitivity and fast fault clearance time. For optimal relay co-ordination the current setting of relays are known prior and then find the time multiplier setting (TMS) of the relays. Current setting and time multiplier setting of all relays are considered as optimization parameters. By appropriate relay coordination we can achieve proper fault identification and fault clearance sequence. A coordination study provides data useful for selection of instrument transformers, protective relay characteristics and settings, fuse ratings, and other information pertinent to provision of optimum protection and selectivity in coordinating these devices. Coordination is a systematic application of current actuated devices in a power system, which in response to a fault or overload will remove only a minimum amount of equipment from service. The objective of relay co-ordination is to minimize the equipment damage. REFERENCES : Research papers : [1] Divya S. Nair; Reshma S., Optimal Co- ordination of Protective Relays, International Conference on Power, Energy and Control (ICPEC), 2013, IEEE. [2] Manohar Singh; B. K. Panigrahi and A. R. Abhyankar, Combined Optimal Distance To Overcurrent Relay Coordination, International Conference on Power Electronics, Drives and Energy Systems (PEDES), 2012, IEEE. [3] Amir Enayati; Thomas H. Ortmeyer, A Novel Approach to Provide Relay Coordination in Distribution Power Systems with Multiple Reclosers, North -American Power Symposium (NAPS), 2015, IEEE. [4] Manohar Singh; B. K. Panigrahim, Minimization of Operating Time Gap Between Primary Relays at Near and Far Ends in Overcurrent Relay Coordination, North American Power Symposium (NAPS), 2014, IEEE. [5] Minu Yadav; Chetanya Gupta; Saurabh V. Kumar; Ikram Hasan, Optimal Coordination of Directional Overcurrent Relay: A Review, International Journal of Emerging Technology and Advanced Engineering (IJETAE), Volume 4, Issue 5, May 2014. Reference Books : [1] Switchgear And Protection S. S. Rao, Khanna publication. [2] Fundamentals Of Power System Protection Y. G. Parithankar & S. R. Bhide, Second edition, PHI. [3] Power System Protection and Switchgear Badri Ram & D. M. Vishwakarma, Second Edition. IJEDR1702017 International Journal of Engineering Development and Research (www.ijedr.org) 105