POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 230 Volt

Similar documents
POWER AVAILABILITY 2U POD USER MANUAL. Power Output Distribution 120 Volt

Liebert MicroPOD 230V

GXT 2U Configuration Program

MONITORING INTELLIRACK USER MANUAL

SERIES 610 LOAD BUS SYNC

Liebert IntelliSlot Relay Card

Liebert Load Bus Sync Extender/Adapter for Dual Bus UPS

Liebert THE NEW SHAPE OF NETWORK POWER PROTECTION. UPStation GXT 2U. An On-Line UPS With Proven Reliability,

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Liebert Maintenance Bypass Cabinet

THE NEW SHAPE OF NETWORK POWER PROTECTION

POWER AVAILABILITY POWERSURE PSP USER MANUAL VA 120V

HP UPS R/T3000 ERM. Overview. Precautions. Installation Instructions

Chloride CROSS Rack 16 A, 32 A and 63 A

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

Liebert XDA Air Flow Enhancer. User Manual

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA. GE Critical Power

300 Series 330/320 Surge Protective Device Installation, Operation and Maintenance Manual

Liebert STS2/PDU, Static Transfer Switch 2/Power Distribution Unit. A Streamlined Package For Power Distribution And Source Switching

XBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE

Liebert Precision Power Center

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual

MODEL 805 USER MANUAL

Network Camera. Quick Guide DC-B1203X. Powered by

SmartAisle Intelligent, Integrated Infrastructure Using Row-based Building Blocks. Solutions For Business-Critical Continuity

Installation of the POTS splitter card requires the following steps: Determining the cables you need. Installing the POTS splitter chassis

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

INSTRUCTION MANUAL DISTRIBUTION UNIT. Please read this manual thoroughly before use, and keep it handy for future reference.

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

actilib Library 2U Quick Start Guide

Omnitron Systems Technology, Inc. 1. iconverter. 19-Module Managed Power Chassis User s Manual

TRC-190 User s Manual

D-Pack 6 Classic ORDERCODE 50315

DC-D4213RX DC-D4213WRX

User Manual AIMB-C200. Economical Embedded Chassis for Mini-ITX Motherboard

Thank you for your purchase of the Supa-Charger! Features Include:

Party Dimmer IEC ORDERCODE 50324

Eaton 9PX PowerPass Distribution Modules and Transformers 9PXTFMR5, 9PXPPDM2, 9PXTFMR11, and 9PXPPDM1 User's Guide

Version /11/2015. User Manual. PowerLine AV HD Gigabit Passthrough Kit DHP-P601AV

1 Channel Strobe Controller ORDERCODE 40226

VFI RTG PDU 6-10K. Installation and user manual. Service and support: Call your local service representative

Installation RA5112-C-16A-C20. Basic Rack Power Distribution Unit

VOICE-ACTIVATED INTERCOM SYSTEM

SmartRow Intelligent, Integrated Infrastructure in a Self-Contained Line-Up. Solutions For Business-Critical Continuity

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

JanusRAID SA-6692J Hardware User Manual

Liebert LM Series. Continuous Protection For Your Business. Surge Protection For Business-Critical Continuity

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

UPS READY POWER DISTRIBUTION ASSEMBLY

Network Camera. Quick Guide DC-T3243HRX. Powered by

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

EATON Transformer Module

ANI SWH. PDU: Per Outlet Control and Total Current Monitoring INSTRUCTION MANUAL

EPS Power Supply

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

WARNINGS AND PRECAUTIONS... 3 PACKING LIST... 5 FRONT PANEL... 5 REAR PANEL... 6 MENU SETTINGS... 7 EXAMPLE SETUP SPECIFICATIONS...

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

MBE Mounts and Adapters

Pulsar EXtreme 2000/3000 VA

Outdoor Housing PIH-5063/5064/5067 INSTRUCTION MANUAL

MIC-3001/8. 3U/4U CompactPCI. Enclosure for Rackmounting

PS 289 DUAL CHANNEL POWER SUPPLY USER MANUAL

LVN5200A-R2, rev. 1, Hardware Installation Guide

Liebert APM UPS The Industry s Highest Energy Efficiency In A Row-Based, On-line UPS. AC Power For Business-Critical Continuity

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Installation. MGE Galaxy 3500 and Smart-UPS VT. Maintenance Bypass, Distribution and Transformer Cabinet

Large Police Light 100W ORDERCODE 80361

icore Kiosk system Installation Guide

ANI MTH. PDU: Total Current Monitoring INSTRUCTION MANUAL

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

PS8 - II. Professional Power Sequencer. User s Manual

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Network Camera. Quick Guide DC-S1283WRX. Powered by

Liebert. GXT3 5kVA-10kVA Compact UPS Systems For High Power Network Rack Applications

Installation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL

Liebert PSI5. Installer/User Guide

Broadband Automatic Disconnect Switch. User Manual

Promopar ORDERCODE 30120

Ethernet Test Access Panel (ETAP) User Manual

Higher Availability: Self-diagnostics. Automatically tests unit electronics and batteries. Designed to simplify maintenance and troubleshooting.

Model 7705 Control Module

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

DC-V3213XJ-4.3mm DC-V3213XJ-2.5mm

INSTRUCTION MANUAL. * Design and Specifications are subject to change without notice. ver. 1.0 PRINTED IN KOREA

IGLOO IGLOO EASY INSTRUCTION MANUAL

Model 2380 Rack-Mount Kit

SUBWOOFER SYSTEM YST-MSW10

DVI KVM. Extra Long Range Extender Over One CAT5. User Manual EXT-DVIKVM-ELR. Release A8

QIT600F1 USER'S GUIDE

LED Par 64 Short DMX ORDERCODE 42431

User s Guide. POWERVAR Single Phase Power Conditioners

Operation Manual. Concorde 600 Power Supply. *This instrument is intended for laboratory use only.

TRC-190 User s Manual

Antenna Distributor ORDERCODE D1444

Owner s Manual. MOON Series 320 S. Power Supply

SATA II HDD Canister KISS DA 435 Quick Reference Guide

Startup Guide C01

Transcription:

POWER AVAILABILITY 2U POD USER MANUAL Power Output Distribution 230 Volt

TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................................... 1 GLOSSARY OF SYMBOLS.................................................. 2 INTRODUCTION AND SYSTEM DESCRIPTION..................................... 3 System Description....................................................... 3 INSTALLATION ON GXT 2U............................................ 4 RACK MOUNT INSTALLATION............................................... 6 INDICATOR LAMPS....................................................... 7 MAINS Indicator Lamp..................................................... 7 Indicator Lamp....................................................... 7 OPERATION............................................................ 8 Transfer to Maintenance Bypass............................................ 8 Transfer to.......................................................... 8 SPECIFICATIONS........................................................ 9 TROUBLESHOOTING..................................................... 10 FIGURES Figure 1 mode of operation...................................................... 3 Figure 2 MAINS/maintenance bypass mode........................................... 3 Figure 3 2U POD connections........................................................ 3 Figure 4 Attaching POD securing brackets to rear of................................ 4 Figure 5 Attaching POD to securing brackets.......................................... 4 Figure 6 2U POD with rack mounting brackets......................................... 6 Figure 7 Indicator lamps on 2U POD.................................................. 7 i

! IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and operation of the 2U POD. This product is designed for commercial / industrial use only, with Liebert systems. It is not intended for use with life support and other designated critical devices. Do not exceed POD or rating labels. Read all safety and operating instructions before operating the 2U POD and the connected system. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. Turn the off and unplug the 2U POD before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. The and 2U POD are designed for data processing equipment. Do not plug laser printers or appliances, such as hair dryers, heaters, vacuum cleaners, or electric drills, into the output sockets.! WARNING DO NOT ATTEMPT TO SERVICE THIS PRODUCT YOURSELF. OPENING OR REMOVING THE COVER MAY EXPOSE YOU TO DANGEROUS VOLTAGES, EVEN WHEN THE AC CORD IS DISCONNECTED FROM THE ELECTRICAL SOCKET. REFER ALL SERVICING TO QUALIFIED SERVICE PERSONNEL. The and the 2U POD are equipped with earthed plugs (plug types vary depending on model). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the designated socket, contact a qualified electrician or your local dealer or Liebert representative for assistance. Route power supply cords so they are not walked on or pinched in anyway.!!!! WARNING DO NOT MODIFY THE CABLES IN ANY WAY. THE POD SOCKETS SHOULD MATCH THE SOCKETS. CONSULT YOUR DEALER IF THE AC CORDS DO NOT MATCH THE MAINS SOCKET. THE 2U POD MUST BE EARTHED AT ALL TIMES WHILE IN USE. TURN OFF THE BEFORE UNPLUGGING IT. CAUTION Risk of electric shock, do not remove cover, no user serviceable parts inside. Refer servicing to qualified service personnel. CAUTION This device receives power from multiple sources. Before servicing this device, remove all connections. Before servicing the, follow Maintenance of instructions in the user manual for your. CAUTION For use in a controlled environment. Refer to manual specifications for environmental conditions. WARNING WHEN THE 2U POD IS IN MAINS POSITION (MAINTENANCE BYPASS MODE) THE POWER TO THE CONNECTED LOAD IS NOT FILTERED OR CONDITIONED BY THE. THE LIEBERT CONNECTED EQUIPMENT GUARANTEE IS NOT VALID WHILE IN THIS MODE OF OPERATION. 1

GLOSSARY OF SYMBOLS Indicates AC Input. Indicates AC Output. i Consult the manual for additional information. MAINS MAINS lamp indicates local power is available and the load may be transferred to bypass the. lamp indicates power is available and the load may be transferred to the to provide computer-grade power to the load. 2

INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the Liebert 2U POD. The Liebert 2U POD provides maintenance bypass capability as well as power output distribution. The Liebert 2U POD can be used on s in the rack mount or tower configuration. The Liebert 2U POD provides an isolated path of power for your system for preventive maintenance or service. System Description The 2U POD has two modes of operation: ( available) and MAINS (maintenance bypass). In mode, the power is routed through the system delivering conditioned power to the load, as shown in Figure 1. Figure 1 mode of operation Mains POD Connected loads In MAINS mode, the power is routed around (bypassing) the system (see Figure 2). Mains power is supplied directly to the load through the 2U POD. Figure 2! CAUTION Battery back-up and conditioned power are NOT available during the MAINS mode of operation. MAINS/maintenance bypass mode Mains POD Connected loads The may be turned off and removed without affecting the load. See Figure 3. Figure 3 2U POD connections INPUT Rotary switch MAINS INPUT Connect to load socket on and power Connect to mains wall socket. Use rear of. Cable supplied. indicator lamps. original mains input cord. AVAILABLE MAINTENANCE BYPASS AVAILABLE 10A A 10A MAINS CIRCUIT BREAKER 16A 250V-/T B 10A CAUTION IF MAINS LAMP IS ILLUMINATED CONNECT LINE CORD HERE MAINTENANCE BYPASS POSITION MAY BE SELECTED. SWITCH TO POSITION ONLY WHEN LAMP IS ILLUMINATED. A+B MAX. 16A MAINS Connect loads. Connect input cord here. Cable supplied. Connect loads. 3

INSTALLATION ON GXT 2U NOTE This manual provides instructions for the 2U POD only. Refer to your manual for operation and installation instructions. 1. Unpack the 2U POD carefully, noting the packing method. Retain the box and packing material for possible future shipments. 2. Visually inspect the 2U POD for freight damage. Report damage to the carrier and your local dealer or Liebert representative. 3. Verify that the 2U POD input cord, input cord, and socket for the are the same type of configuration. 4. If you already have a installed, turn off all connected loads and unplug them from the. Turn off the and disconnect the input cord. 5. Attach the two POD securing brackets (this is optional for GXT 2U ) to the rear of the (see Figure 4). You will need a long M3 Phillips head screwdriver for this procedure (the torque is 0.79 Nm, or 7 in-lb). The POD brackets have a hole to allow the screwdriver to reach the screw. Figure 4 Attaching POD securing brackets to rear of 4

6. Next attach the POD to the securing brackets (see Figure 5). The POD can be installed to face one of three different directions utilizing the same mounting procedures. Figure 5 Attaching POD to securing brackets 7. Make sure the 2U POD rotary switch is in the MAINS position. Use the mains input cord originally used with the. Plug the mains input cord from the mains input socket to the mains wall socket. WARNING: The 2U POD is now electrically live. The MAINS lamp (orange) should now be illuminated. 8. Using the cord provided, connect the input power socket to the POD socket labeled CONNECT LINE CORD HERE. WARNING: The system is now electrically live. 9. Using the cord provided, connect the POD socket labeled to one of the output sockets on the rear of the. 10. Plug in all loads to the output distribution sockets, evenly distributing them on the 2U POD. The 2U POD now powers your equipment in the MAINS mode. 11. Turn ON the loads and ensure all are up and operating according to specification. 12. Start the according to its specific user manual. 13. Verify that the lamp (green) on the 2U POD is illuminated. If so, transfer the rotary switch from MAINS to. The load is now being supplied with conditioned power through the. 14. Before any operation or procedure, always verify that both the lamp (green) and the MAINS lamp (orange) are illuminated before changing the status of the rotary switch. 5

RACK MOUNT INSTALLATION 1. Rack mount installation of the 2U POD is possible with the use of the rack mounting brackets (shipped with the POD). See Figure 6. 2. The rack mount brackets allow you to rack mount the POD in a 19" enclosure (23" to 19" rack adapters would have to purchased separately if you are using our 23" Foundation or equivalent cabinet). 3. The POD can be mounted to face one of four directions depending on your application, and utilizing the rack mount brackets provided. 4. Determine the desired position and direction for the POD, face it in that direction, then attach the brackets to the POD with the screws provided. 5. Consult your rack/enclosure manufacturer s recommendations for specific rack mounting hardware that will be required. 6. The holes on the rack mount bracket are notched for easy installation. Tighten the POD securely to the rails and then follow the startup directions for the POD in the previous section, Installation on GXT 2U. Figure 6 2U POD with rack mounting brackets AVAILABLE MAINTENANCE BYPASS AVAILABLE 10A A 10A MAINS CIRCUIT BREAKER 16A 250V-/T B 10A CAUTION IF MAINS LAMP IS ILLUMINATED MAINTENANCE BYPASS POSITION MAY BE SELECTED. CONNECT LINE CORD HERE SWITCH TO POSITION ONLY WHEN LAMP IS ILLUMINATED. A+B MAX. 16A MAINS Rack mounting brackets 6

MAINS Indicator Lamp INDICATOR LAMPS This orange lamp is illuminated when mains power is present (see Figure 7). It signals that you may transfer the loads to maintenance bypass (MAINS mode) operation via the rotary switch. During a mains power outage, this lamp will be off and the will supply battery back-up power to the connected loads. Indicator Lamp This green lamp is illuminated when there is output power available from the (see Figure 7). It signals that it is safe to transfer the connected loads from mains power back to output power. Figure 7 Indicator lamps on 2U POD Green lamp: Output power available from Orange lamp: MAINS power present AVAILABLE MAINTENANCE BYPASS AVAILABLE MAINS CIRCUIT BREAKER 16A 250V-/T CONNECT LINE CORD HERE Rotary switch 7

Transfer to Maintenance Bypass OPERATION To transfer to maintenance bypass (mains) from, use the following steps: 1. Ensure the MAINS lamp (orange) is illuminated. If the lamp is not illuminated, refer to Troubleshooting section. 2. Transfer the rotary switch from to MAINS, provided the MAINS lamp is illuminated on the 2U POD. 3. Turn the off. 4. Disconnect the two cables connecting the to the 2U POD. 5. You may now service the. Transfer to To transfer to from maintenance bypass (mains), use the following steps: 1. Reconnect the to the 2U POD. Start the according to the instructions in the user manual. 2. Verify that lamp (green) on the 2U POD is illuminated. If so, transfer the rotary bypass switch from MAINS to. If the lamp does not illuminate, refer to Troubleshooting section. 3. Conditioned power is now being supplied through the. 8

SPECIFICATIONS Transfer Time (to and from maintenance bypass) Operating Ambient Temperature Storage Ambient Temperature < 6 milliseconds 0 C to +40 C (32 F to 104 F) -20 C to +60 C (-4 F to 140 F) Dimensions W x D x H: mm (in.) 88 x 77 x 394 (3.5 x 3.0 x 15.5) Weight: kg (lbs) 4.5 (10) Humidity Agency/Standards Electrical Rating 0 to 95% non-condensing CE, EN 60950, ISTA Procedure 1A See Model Label on MicroPOD This 2U POD is intended for use with a meeting all the following requirements: input cord is compatible with the rating and type of socket on the 2U POD labeled CONNECT LINE CORD HERE. output socket is compatible with the 2U POD input power connector labeled. Available mains socket is compatible with the 2U POD input power connector labeled MAINS. The user must provide a suitable mains power cord with the appropriate country connector. This will usually be the original power cord which has been removed from the mains input. 9

TROUBLESHOOTING Problem Cause Solution MAINS lamp (orange) not illuminated. Available lamp (green) not illuminated. 2U POD will not start some / all connected loads. 2U POD circuit protectors trip after resetting. Mains not present. 2U POD input cord not connected to mains. output power not present. input and/or output cord not connected to 2U POD. 2U POD output circuit breaker has tripped. Overcurrent on 2U POD socket. Call qualified service personnel to restore power to socket. Refer to 2U POD installation instructions in this manual: Installation on GXT 2U and Rack Mount Installation. Turn on. Refer to user manual. Refer to 2U POD installation instructions in this manual: Installation on GXT 2U and Rack Mount Installation. Reset 2U POD circuit protectors. Recalculate load requirements, distribute load among other 2U POD sockets. 10

POWER AVAILABILITY 2U POD The Company Behind the Products With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics: Environmental systems close-control air conditioning from 1 to 60 tons Power conditioning and with power ranges from 300 VA to more than 1000 kva Integrated systems that provide both environmental and power protection in a single, flexible package Monitoring and control from systems of any size or location, on-site or remote Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. 2002 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. SLI-23153 (5/02) USER MANUAL Technical Support United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Single-Phase 800-222-5877 Outside the United States 614-841-6755 3-Phase 800-543-2378 Environmental Control 800-543-2778 Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 FAX: +39 049 5841 257 Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 FAX: +852 2 831 0114 Web Site www.liebert.com E-mail tech@liebert.com