ST: TP14D/2 TEST SHEET COMBINED LV CT & METER CABINET INSTALLATIONS OFF-LOAD TESTING

Similar documents
INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

Company Directive STANDARD TECHNIQUE: TP14J. Management of Metering CT & VT Test Certificates

MIC-2 MKII, Multi-instrument DATA SHEET

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

Engineering Recommendation G87 Issue

REYROLLE 2RMLG. Operating Recommendations

MMLB 01/MMLB 02 Multi-finger Test Plug/ Single-finger Test Plug Technical Data MMLB_EN_TD_A

Company Directive STANDARD TECHNIQUE: TP18A/1. Application of Connection Control Panels for Soft Intertrip and/or Voltage Constraint Schemes

NPIH800 NPIH800R. First Handling Guide Earth overcurrent relay

LF3-400 Three Phase Frequency Converter, Operation and Maintenance.

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

Single-Core PVC 6491X

LINEAR LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

COMPACT LED CONVERTERS 48 V

POCKET MULTIMETER Model No: MM18

COMPACT LED DRIVERS. ComfortLine Residential. ComfortLine RESIDENTIAL , , ,

MIC-2 Multi-instrument DATA SHEET

Version 5 Controls for natural ventilation. WUF 110 / 121 / 150 Actuator interfaces

LinkRay LED Drivers EasyLine With Selectable Current , Typical Applications

G8 - Contracts for Difference Metering

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , , , , ,

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

RIK-5A Flexible Current Tranformer User's Manual

CC COMPACT DIP SWITCH

NO: PH-185 PRODUCT: E3JK Photoelectric Sensors DATE: May 2014 TYPE: Discontinuation Notice

2 Check that Public Safety has been considered (e.g. cabinet secured and locked, trip hazards removed where applicable).

Please use the Q & A utility to ask us any questions concerning the material being presented.

Panduit Basic Rack PDU

Title System Substation Commissioning Tests. Reference Number PCP 07 - (RIC Standard: EP SP)

Basic Setup for the Current Probes Input Option

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH)

LINEAR LED DRIVERS. ComfortLine Industry Selectable Current (LEDset) ComfortLine INDUSTRY SELECTABLE CURRENT (LEDset) ,

LINEAR LED DRIVERS. ComfortLine NFC. ComfortLine NFC , , ,

B.T.C. Iberica Instrumentation Cable

B.T.C. Iberica Instrumentation Cable

What s New in Version 5.00 Compared to Version 4.52

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions

6 Check that the earth system is complete, undamaged and bonded to earth points ( including capacitor and control).

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

96x48. gal/h. Digital panel meter 4½-digit DV4. Without setpoints. Sensor supply

MiCOM Agile P99x. Grid Solutions. Testing & Commissioning. Test Block, Multi-finger Test Plug and Single-finger Test Plug. Design Flexibility

Part No. Z , IA Jul OPERATION MANUAL. High Voltage Digitalmeter A

BUTT SET MODEL TT-200

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

ReCon T Energy Logger

B.T.C. Iberica Instrumentation Cable

Extension module for lighting control

BOX TRANSDUCER SMALL SIZED AC TRANSDUCER 90 SERIES

Energy Meter and. Current Transducer. Assembly Manual

IEC An introduction. 28 March 2012 By Craig McKee Technical Manager

Air damper actuators

MMLG 01, 02, 03, 04 MMLB01

Part No. Z , IA Nov OPERATION MANUAL. High Voltage Digitalmeter A

BMX DDM Mixed Relay Input/Output module

ETHOS Auto Ranging Digital Multimeter

CONTA-ELECTRONICS. CONTA-PROTECT overvoltage protection

COMPACT LED DRIVERS. EasyLine Selectable Current (Output Terminal) EasyLine SELECTABLE CURRENT (OUTPUT TERMINAL) , , ,

Superseding SHEET NO. 34C-51 REVISED SHEET NO. 34C-51 Effective May 27, 2010 Effective December 3, 2011

Masterpact NW Restricted Earth Fault Protection

SWA Cable BS5467 Steel Wire Armoured PVC

EC07 EC63. Compatible actuators: ERL2 ESD2. How to order EC 07 B. Series. B Installation. method

B.T.C. Iberica Instrumentation Cable

UL TEST REPORT AND PROCEDURE

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

Panduit Basic Rack PDU with Local Meter

I n s t a l l a t i o n M a n u a l. T E D P r o. ( T P C O n l y ) A B C. Rev 1.1

CONTROL PANEL WIRING SPECIFICATIONS

MODEL: 43AL1. Digital Panel Meters 43 Series

Power supply 142. Couplers 143. Data interfaces 144. Accessories 145

NEMO HD MULTI-FUNC METER BASE (MF96001)

Part No. Z , IA Mar OPERATION MANUAL. High Voltage Digitalmeter A

LINEAR LED DRIVERS. PrimeLine DALI dimmable. PrimeLine DALI DIMMABLE , , , , ,

Product Performance Specification Mini Coaxial Connector

Installation Instructions

UL TEST REPORT AND PROCEDURE

EDS LONDON 33KV DISTRIBUTION NETWORK DESIGN AND CUSTOMER SUPPLIES

ELECTRICIANS REGULATIONS EXAMINATION 21 November 2015 QUESTION AND ANSWER BOOKLET

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

Installation manual for for Schleifenbauer DPM3

LED power supplies Constant voltage. Uconverter LCU 180W 12/24V IP67 TOP Outdoor IP67 series

USER INSTRUCTIONS FOR LEAK CURRENT LOCATOR ELMA 4000 EL.NO EL.NO EL.NO Garver Ytteborgsvei Oslo Tlf.:

ECP NORTROLL CABLETROLL 2350 FPI INSTALLATION AND COMMISSIONING PROCEDURE

SURGE SUPPRESSOR INSTALLATION INSTRUCTIONS. Includes TDS-AR Alarm Relay and TDS-SC Surge Counter. ISSUE: 3 April

Lab 4: Introduction to ELVIS II+ Introduction to ELVIS II+

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Technical Data Sheet Medium Current Power Surge Filters

OPTIMISED LUMINAIRE PROTECTION

Outdoor 200w Driver SL-L2282B002US

Common Departures Interconnecting Facilities Requirements

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

Best Prac ce Guide 8 (Issue 2) Selection and use of plug-in socket-outlet test devices

Protection against electric shock

PERMANENT DOCUMENT. Annex AU to Routine Test Requirements for manufacturers (as per Article 9 of the Agreement)

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

LED Driver Constant voltage. Udriver LCU 100/96W 12/24V IP67 EXC EXCITE outdoor IP67 series

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

Model 7705 Control Module

LPI SST Surge Filters

Contents. BMS icom Manual

Transcription:

COMBINED LV CT & METER CABINET INSTALLATIONS Summary This Test Sheet shall be employed during the off-load testing of Combined LV CT & Meter Cabinet Installations in accordance with Standard Technique TP14D/2. This Test Sheet shall be read in conjunction with the associated Guidance Note. The section numbers in this Test Sheet relate to the section numbers in the associated Guidance Note. This document has been written around the product manufactured by Lucy Electric Ltd. This document replaces the version dated October 2016. Authors: Graham Brewster Date: May 2017 V4 - May 2017 Page 1 of 6

EVIDENCE OF COMPLIANCE WITH BALANCING & SETTLEMENT CODE: CODE OF PRACTICE 4 CoP 4 Description 5.5.2 Test That CTs are of the correct ratio Section 4.7 Relevant Section On This Test Sheet 5.5.2 Test That CTs are of the correct polarity Sections 4.4 & 4.6 5.5.2 Test That VTs are of the correct ratio Section 5.6 (No VT) 5.5.2 Test That VTs are of the correct polarity Section 5.6 (No VT) 5.5.2 Test That the relationships between voltages and currents are correct Section 4.5 & 5.2 5.5.2 Test That the phase rotation is standard Sections 5.5 & 5.6 5.5.4 Record Site name Section 4.2 5.5.4 Record Site address Section 4.2 5.5.4 Record Metering system identifier (MPAN) Section 4.2 5.5.4 Record Date of commissioning Section 4.2 5.5.4 Record Name and organisation of person responsible for commissioning Section 4.2 5.5.4 Record Current transformer details Section 4.4 5.5.4 Record Voltage transformer details Not Applicable 5.5.4 Record Results of inspections, tests & observations Entire Test Sheet 4.2 GENERAL DETAILS Import MPAN Export MPAN (Where Applicable) (Where Applicable) Customer s Name Customer s Address WPD Enquiry Number (Where Applicable) Date Of Off-Load Testing Off-Load Tested By Name Company V4 - May 2017 Page 2 of 6

4.3 COMBINED LV CT & METER CABINET DETAILS Manufacturer Lucy Electric Rating 200A 400A 600A Serial Number Phase L1 L2 L3 Cut-Out (J) Fuse Rating A A A Voltage Fuse Rating A A A Meter Fuse Rating A A A 4.4 CT DETAILS Phase L1 L2 L3 Manufacturer Serial Number Ratios Available Ratio Connected Rating (VA) Class Face P1 Points Towards Incoming Service Cable [ ] [ ] [ ] 4.5 WIRING CHECKS Phase L1 L2 L3 N Colour Of Voltage Wiring BROWN [ ] BLACK [ ] GREY [ ] BLUE [ ] Colour Of CT Secondary Wiring BROWN [ ] BLACK [ ] GREY [ ] Colour of Test Terminal Block Wiring BROWN BLACK GREY BLUE T1 [ ] T2 [ ] T3 [ ] T10 [ ] T4 [ ] T5 [ ] T6 [ ] T11 [ ] T7 [ ] T8 [ ] T9 [ ] T12 [ ] T13 [ ] V4 - May 2017 Page 3 of 6

4.6 CT POLARITY CHECKS L1 L2 L3 CT Polarity Correct [ ] [ ] [ ] 4.7 CT RATIO CHECKS Primary Injection Current L1 A [A] CT Secondary Current L1 (Wire D11) A [B] Calculated CT Ratio L1 [A] 5 [B] / 5 A Ratio On CT Label L1 / 5 A L1 CT Ratio Correct [ ] Primary Injection Current L2 A [C] CT Secondary Current L2 (Wire D31) A [D] Calculated CT Ratio L2 [C] 5 [D] / 5 A Ratio On CT Label L2 / 5 A L2 CT Ratio Correct [ ] Primary Injection Current L3 A [E] CT Secondary Current L3 (Wire D51) A [F] Calculated CT Ratio L3 [E] 5 [F] / 5 A Ratio On CT Label L3 / 5 A L3 CT Ratio Correct [ ] 5.2 DC RESISTANCE CHECKS L1 L2 L3 DC Resistance of CT secondary circuit (Terminals T2-T3) Ω (Terminals T5-T6) Ω (Terminals T8-T9) Ω V4 - May 2017 Page 4 of 6

L1 L2 L3 Voltage & Meter Fuses connected in correct phase and in phase conductor only [ ] [ ] [ ] 5.3 INSULATION RESISTANCE CHECKS L1 L2 L3 Insulation Resistance of Busbars & Voltage Connections (ph-ph tests only when meter not fitted) Insulation Resistance To Earth of CT Secondary Circuit L1-E MΩ L2-E MΩ L3-E MΩ L1-L2 MΩ L2-L3 MΩ L3-L1 MΩ MΩ CT Secondary Circuit Earthed [ ] [ ] [ ] 5.5 INCOMING SUPPLY CHECKS AT J FUSE POSITION Polarity Correct [ ] Phase Rotation Correct [ ] L1 - L2 V L1 - N V L1 - E # V L1 - L3 V L2 - N V L2 - E # V L2 - L3 V L3 - N V L3 - E # V # TN-S (SNE) Systems Only WPD Earth Terminal TN-C-S (PME) TN-S (SNE) NONE (TT) L1 - E L2 - E L3 - E Earth Loop Impedance of Incoming Service Cable Ω Ω Ω V4 - May 2017 Page 5 of 6

5.6 CHECKS AT TEST TERMINAL BLOCK Polarity Correct [ ] Phase Rotation Correct [ ] L1 - N Voltage (Terminals T10-T13) V L2 - N Voltage (Terminals T11-T13) V L3 - N Voltage (Terminals T12-T13) V L1 - L2 Voltage (Terminals T10-T11) V L1 - L3 Voltage (Terminals T10-T12) V L2 - L3 Voltage (Terminals T11-T12) V V4 - May 2017 Page 6 of 6