Control Interface 369369 Rev. B 1 06.02.11 Description Integrates GRAFIK 5000TM, GRAFIK 6000, GRAFIK 7000TM, Softswitch128, and LCP128 systems with a touchscreen or other digital equipment that supports TCP/IP communication over Ethernet. Provides monitoring commands that allow a touchscreen to query lighting systems to: Determine which scene is selected. Keep track of buttons pressed. Provides control commands that allow a touchscreen or PC to operate lighting systems to: Select or sequence lighting scenes. Raise or Lower one or more zones. Activate panic mode (lights go to full on). Simulate button actions Disable or Enable timeclock(s)
Specifications 369369 Rev. B 2 06.02.11 Power IEC PELV/NEC Class 2 Operating Voltage: 12 V 125 ma 24 V 65 ma Uses OMX RS232 Command Set Monitoring: Scene selection and scene status updates. Control: Scene selection, scene lockout, sequencing, zone lockout, zone raise/lower. System Communications and Capacity IEC PELV/NEC Class 2 wiring connects Interface to Processor Panel. Standard CAT5 cable, 328 ft (100 m) maximum, connects Interface to PC or other Ethernet source. Supports MDI/MDIX auto-crossover (no crossover cable needed). Multiple may be used in a single system. Environment 32 to 104 F (0 to 40 C). Relative humidity less than 90% non-condensing. Dip 1 2 3 4 9 10 11 12 17 18 19 20 25 26 27 28 5 13 21 29 6 14 1 2 3 4 5 6 22 1 2 3 4 5 6 30 7 15 23 31 8 16 24 7 8 32 ing Up Down (On) (Off) Not used
369369 Rev. B 3 06.02.11 Dimensions 2.47 in (62.7 mm) Mounting Holes 3.75 in (95.3 mm) 4.26 in (108.2 mm) 5.26 in (133.6 mm) 1.06 in (26.9 mm) Mounting 1. Mount the control interface directly on a wall, as shown in the Mounting Diagram, using screws (not included). When mounting, provide sufficient space for connecting cables. The unit can also be placed in the LUT-19AV-1U AV rack using the screws provided with the unit. The LUT-19AV-1U will hold up to four units. If conduit is desired for wiring, the LUT-5x10-ENC can be used to mount one unit. 2. Strip 4 in (10 mm) of insulation from wires. Each data link terminal will accept up to two 18 AWG (1.0 mm 2 ) wires. 3. Connect wiring as shown in the Wiring Diagram (next page). LED 1 lights continuously (Power) and LED 7 blinks rapidly (Data Link RX) when the IEC PELV/NEC Class 2 Data Link is installed correctly. Mounting Diagram Control Interface Wall Mounting Hole Detail Dimensions: in (mm) 0.25 (6.4) #6 or #8 (M3 or M4) screw recommended (not included) Wire Strip Length 4 in (10 mm) 0.18 (4.6) 0.34 (8.6) 0.18 (4.6) LUT-5x10-ENC LUT-19AV-1U
Ethernet Link Wiring 369369 Rev. B 4 06.02.11 Standard CAT5 cable connects Interface to PC, router, or other Ethernet source. No crossover cable needed. Must be 328 ft (100 m) or less. Ethernet network and cable provided by others. IEC PELV/NEC Class 2 Wiring Daisy-chain the Interface to the IEC PELV/NEC Class 2 Wallstation Link that connects to the Processor Panel. Make daisy-chain connections to the IEC PELV/NEC Class 2 Data Link terminals on the front of Interface. Do not use T-taps. Run all wires in and out of terminal block. Each terminal accepts up to two 18 AWG (1.0 mm 2 ) wires. LED 1 lights when the IEC PELV/NEC Class 2 Data link is installed correctly. Consult Processor Panel Specification Submittal for more details. Ethernet link/ activity CAT5 Cable: maximum 328 ft (100 m) Ethernet speed To PC or AV Equipment. For Ethernet Link, use CAT5 cable provided to connect to auxiliary equipment. The Ethernet Link LED will light continuously when link is present and will flash when there is link activity. Additional Ethernet network equipment and cables provided by others. 7 RJ45 jack: Ethernet Link (to PC or A/V equipment) Data Link (to Control Units, processors, and wallstations) DIP Switches 12 or 24 V to outlet (with optional transformer). Do not wire terminal 2 on Data Link when using optional transformer. To power separately from the Data Link, order the following Lutron transformer model numbers: 120 V : T120-15DC-9-BL 240 V : TE240-15DC-9-BL 240 V (UK): TU240-15DC-9-BL LED 1: Power LED 2: Ethernet link LED 3, 4, 5: Unused LED 6: Data link TX LED 7: Data link RX
IEC PELV/NEC Class 2 Terminal Connections 369369 Rev. B 5 06.02.11 Two 12 AWG (2.5 mm 2 ) conductors for common (terminal 1) and 24 V (terminal 2). These will not fit in terminals. Connect as shown. Ensure that the terminal 2 connection is wired when not using optional transformer. One shielded, twisted pair 18 AWG (1.0 mm 2 ) for data link (terminals 3 and 4). Connect Drain/Shield as shown. Do not connect to Ground (Earth) or Wallstation/Control Interfaces. Connect the bare drain wires and cut off the outside shield. Data Link: (1) shielded, twisted pair 18 AWG (1.0 mm 2 ) 4: MUX 3: MUX Use Lutron Cable GRX-CBL-46L 4 3 2 1 D: Drain/Shield (2) 12 AWG (2.5 mm 2 ) Note: Do not connect Drain/Shield to Ground (Earth) or Wallstation/Control Interfaces. Connect the bare drain wires and cut off the outside shield. IEC PELV/NEC Class 2 Power wiring: 1: Common 2: 24 V Power (2) 18 AWG (1.0 mm 2 ) pigtails, 6 in (152 mm) maximum length (2) 12 AWG (2.5 mm 2 ) Note: 12 AWG (2.5 mm 2 ) conductors for Common (terminal 1) and 24 V Power (terminal 2) will not fit in terminals; use 18 AWG (1.0 mm 2 ) pigtails (< 6 in/152 mm).