KNX/EIB Flush-mounted universal dimming actuator 210 W. 1 Safety instructions. 2 Device components. Order-No. : Operating instructions

Similar documents
1 Safety instructions. 2 Device components. 3 Function. Control unit, 1-10 V 3-gang. Order-No. : Operating instructions

The LED display (1) turns green when the load is switched on.

1 Safety instructions. 2 Device components. 3 Function. DALI Tronic transformer 105 W. Order-No. : Operating instructions

1-channel shutter actuator 6A UP Installation Instructions

KNX/EIB Push button sensor 3 Plus F Safety instructions. 2 Device components. 3 Function

KNX/EIB KNX Blind actuator. 1 Safety instructions. 2 Device components. Blind actuator 4-gang 24 V DC Order-No. :

picture 1: Device components

1 Safety instructions. 2 Device components. 3 Function. Control unit 1-10 V, 3-gang. Art.-No.: 2193 REG. Operationsmanual

1 Safety instructions. 2 Intended use. 3 Product characteristics. 4 Operation. LB management. Universal rotary dimmer LED

Bus coupler 3 Bus coupler 3 external sensor Order No

Universal dim actuator 1gang RMD Universal dim actuator 2gang RMD Universal dim actuator 4gang RMD

Electrical devices may only be mounted and connected by electrically skilled persons.

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

Operating Instructions. DALI-Gateway

Figure 1: Device components

picture 1: Device components

Product and functional description

Product and functional description

Mounting and Operating Instructions

Product and functional description

Water-protected surface-mounted push-button bus coupler Order No , , ,

1 Safety instructions. 2 Device components. 3 Function. DALI transformer W. Art.-No.: D SNT 105. Operationsmanual

Product and functional description

Operating Instructions

1 Safety instructions. 2 Device components. KNX Touch/Glass sensor comfort

Four-channel Venetian blind actuator 230 V Installation Instructions

Installation Instructions

Structure of the device. Push-button sensor module. Ref.-no.: 4008 TSM Safety instructions

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

KNX DALI Gateway Plus - User Manual

Operating Instructions. Power-DALI-Potentiometer

UNIVERSAL DIMMER DIM02SA/500U

UNIVERSAL DIMMER DIM02SA/500U

UNIVERSAL DIMMER DIM04SA/500U

COMPACT LED DRIVERS. PrimeLine DALI dimmable & Selectable Current (Dip Switch) PrimeLine DALI DIMMABLE & SELECTABLE CURRENT (DIP SWITCH)

Product documentation. KNX Blind- a.heating-act.fm w.3 Inputs Art.-No. MEG

Product documentation. KNX Blind Act.FM w.3 Inputs Art.-No. MTN

LINEAR LED DRIVERS. PrimeLine DALI dimmable. PrimeLine DALI DIMMABLE , , , , ,

COMPACT LED CONVERTERS 48 V

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

CC COMPACT DIP SWITCH

COMPACT LED DRIVERS. ComfortLine Residential. ComfortLine RESIDENTIAL , , ,

Operating voltage Maximum

Product documentation

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , , , , , ,

Product documentation

LinkRay LED Drivers EasyLine With Selectable Current , Typical Applications

Siemens Spares. RL 513D23 Switching actuator (relay), 3 x 6A. Technical Product Information

Product documentation

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

COMPACT LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

COMPACT LED DRIVERS. EasyLine Selectable Current (Output Terminal) EasyLine SELECTABLE CURRENT (OUTPUT TERMINAL) , , ,

LINEAR LED DRIVERS. EasyLine Simple Fix. EasyLine SIMPLE FIX , , , , ,

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

OT EASY 60 II. LED control unit Operating instructions

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

KNX/EIB Product documentation. Page 1 of 23. Order-No xx Order-No xx Order-No xx Order-No xx

Operating instructions. Switching amplifier DN0210 DN / / 2015

4 CHANNEL UNIVERSAL DIMMING ACTUATOR

Operating instructions. Standstill monitor A / / 2011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

1 Safety instructions. 2 Device components. Gira Control 9 Client 2. Gira Control 9 Client 2 Order no.: Operating instructions

Datasheet RCUXXYY EAE KNX Room Control Unit RCUXXYY DT R1.0. General Description. EAE Technology Page 1/10

KNX/EIB Product documentation. Issue:

Operating instructions. Speed monitor D / / 2014

AQStation Dimmer. Manual. LAN/Wi-Fi-based-control. Typ: AQS Dimmer black Order-No.: Typ: AQS Dimmer white Order-No.:

LINEAR LED DRIVERS. ComfortLine Industry Selectable Current (LEDset) ComfortLine INDUSTRY SELECTABLE CURRENT (LEDset) ,

DALI Professional Controller-4. Control unit Operating instructions

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Product manual. Mylos KNX 350w Dimmer 2CSYK1205C/S

Technische Daten: instabus EIB supply instabus line: YY 6 x 0.6 mm; red: bus (+) / black: bus (-)

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011

1 Safety instructions. 2 Device components. 3 Function. Smart Control IP. Art. No. SC 1000 IP. Operating instructions

LED Driver Constant voltage. Udriver LCU 100/96W 12/24V IP67 EXC EXCITE outdoor IP67 series

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

Product documentation

PSR UC/ESAM4/3X1/1X2/B

Product and functional description

LED Driver Constant voltage. Udriver LCU 180W 12/24V IP67 EXC EXCITE outdoor IP67 series

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Blind actuator 4-gang 230 V AC Order-No

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

LINEAR LED DRIVERS. ComfortLine NFC. ComfortLine NFC , , ,

Original operating instructions Safety relay with relay outputs G1501S / / 2016

A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 Controls:

Product and functional description

LED power supplies Constant voltage. Uconverter LCU 180W 12/24V IP67 TOP Outdoor IP67 series

Lighting control for commercial buildings

DEK-REL- 5/I/1. Extract from the online catalog. Order No.:

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

4-gang and 8-gang switch actuator 16A C-load SE

1 Safety instructions. 2 Device components. Smart Panel. Art.-No.: SP 9 KNX. Operating instructions

Product and Applications Description. Application programs. instabus EIB Technical Product Information. February 2012

Transcription:

Order-No. : 1058 00 Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage to the device and result in fire and other hazards. Danger of electric shock on the KNX installation. Do not connect any external voltage to the inputs. Doing so may damage the device(s), and the SELV potential on the KNX bus line will no longer be available. Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load is not electrically isolated from the mains even when the device is switched off. Danger of electric shock. Before working on the device or before exchanging light bulbs, disconnect mains voltage and switch off circuit breakers. Do not connect any lights with integrated dimmers. Device can be damaged. Do not connect any electronic lamps, e.g. switchable or dimmable compact fluorescent lamps or LED lamps. Device can be damaged. Fire hazard. For operation with inductive transformers, each transformer must be fused on the primary side in accordance with the manufacturer's instructions. Only safety transformers according to EN 61558-2-6 may be used. These instructions are an integral part of the product, and must remain with the end customer. 2 Device components Figure 1: Flush-mounted dimmer actuator (1) Control cable (2) Programming button and LED (3) Connection of mains and power cables Connection assignment, power cables BK, black: connection conductor L BN, brown: dimming output 32576312 10499261 I00 06.01.2012 1/6

Connection assignment of control cable RD, red: KNX+ BK, black: KNX GN, green: input 1 YE, yellow: input 2 WH, white: COM input 1 BN, brown: COM input 2 Figure 2: Connection assignment of control cable 3 Function System information This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding. The function of this device depends upon the software. Detailed information on loadable software and attainable functionality as well as the software itself can be obtained from the manufacturer s product database. Planning, installation and commissioning of the device are carried out with the aid of KNX-certified software. The latest versions of product database and the technical descriptions are available on our website. Intended use - Switching and dimming of incandescent lamps, 230 V halogen lamps and LV halogen lamps with inductive transformers or Tronic transformers - Installation in appliance box to DIN 49073 Product characteristics - Automatic selection of the dimming principle suitable for the load - Protected against no-load, short-circuit and overheating - - Feedback of the switching position and the dimming value Parameterisable switch-on and dimming behaviour - Timed dimmer: switch-on delay, switch-off delay, staircase lighting timer - Light scene operation - Two binary inputs for potential-free contacts, usable as extension inputs for local operation - Supply via bus, no additional power supply necessary - Mains failure longer than approx. 0.7 seconds leads to switch-off of the dimmer actuator. i Ripple-control pulses from the electric power company may be visible in the form of flickering. This does not represent any defect in the device. 32576312 10499261 I00 06.01.2012 2/6

4 Information for electrically skilled persons 4.1 Fitting and electrical connection DANGER! Electrical shock when live parts are touched. Electrical shocks can be fatal. Before working on the device, disconnect the power supply and cover up live parts in the working environment. Connecting and mounting the device DANGER! When connecting the bus/extensions and mains voltage wires in a shared appliance box, the KNX bus line may come into contact with the mains voltage. This endangers the safety of the entire KNX installation. People at remote devices may also receive an electric shock. Do not place bus/extensions and mains voltage terminals in a shared connection compartment. Use an appliance box with a fixed partition wall (Figure 3) or separate boxes. Figure 3: Installation in appliance box (4) Appliance box (5) Partition (6) Potential-free contacts, e.g. for window contact or installation pushbuttons 32576312 10499261 I00 06.01.2012 3/6

Figure 4: Spacing between mains cable and control cable Minimum spacing between the mains voltage and bus/extension wires: 4 mm (Figure 4). Do not exceed permissible total load including transformer power dissipation. Operate inductive transformers with at least 85% nominal load. Mixed loads with inductive transformers: ohmic load max. 50%. Trouble-free operation is only ensured with electronic transformers manufactured by us or with dimmable inductive transformers. CAUTION! Danger of destruction from mixed loads. The dimmer and load may be destroyed. Do not connect capacitive loads, e.g. electronic transformers, and inductive loads, e.g. inductive transformers, together on the same dimmer output. o Connect the load (Figure 5). Use the supplied sprung screwless terminals. Flexible cable ends must be tin-plated. o Connect the device to KNX. o If necessary, connect potential-free contacts to the inputs (Figure 2). o Install the device in the appliance box. Figure 5: Connection 32576312 10499261 I00 06.01.2012 4/6

Function of Inputs 1 and 2 in the as-delivered state Input NO contact Output 1 Press briefly Light on 100% 1 Press for a long time Dimming brighter 2 Press briefly Light off 2 Press for a long time Dimming darker 4.2 Commissioning Load the address and the application software o Switch on the bus voltage o Assign physical addresses and load application software into the device. o Note the physical address on the device label. 5 Appendix 5.1 Technical data Rated voltage AC 230 V ~ Mains frequency 50 / 60 Hz Ambient conditions Ambient temperature -5... +45 C Storage/transport temperature -25... +70 C Contact type Connected load Incandescent lamps HV halogen lamps Inductive transformers Tronic transformers Mixed loads Ohmic-inductive ohmic-capacitive capacitive-inductive Control cable and inputs Control cable (preterminated) Input type Total length of extension unit cable Poll voltage, extension inputs ε, MOSFET 50... 210 VA 50... 210 VA not permitted YY6x0.6 Potential-free max. 5 m approx. 5 V Dimensions Ø H 53 28 mm Connection mode Screwless terminal (enclosed) Single stranded 1.0... 2.5 mm² KNX KNX medium TP 1 Commissioning mode S-mode Rated voltage KNX DC 21... 32 V SELV Power consumption KNX typical 150 mw Connection mode KNX Connection terminal on control cable 5.2 Troubleshooting Light has switched off Cause 1: short-circuit in output circuit. Disconnect device from mains; switch off associated circuit breakers. Eliminate short-circuit. Switch mains voltage on again. 32576312 10499261 I00 06.01.2012 5/6

Switch device off and then on again. i When a short-circuit occurs the affected output switches off. Automatic restart when shortcircuit is eliminated within 100 ms (inductive load) or 7 seconds (capacitive or ohmic load). After that lasting switch-off. i When a short-circuit occurs during the calibration process, the load calibrates itself again after the short-circuit is eliminated. Cause 2: load failure. Check load, replace light bulb. For inductive transformers, check primary fuse and replace if necessary. Cause 3: Output is disabled. Cancel disabling. Cause 4: bus voltage failure. Check bus voltage. Cause 5: mains voltage failure. Check mains voltage. Cause 6: overheating protection has tripped due to overload or too high ambient temperature. Disconnect device from mains; switch off associated circuit breakers. Let device cool down for at least 15 minutes. Check installation situation, ensure cooling, e.g. provide distance from surrounding devices. Reduce the connected load. Luminaires flicker or buzz, proper dimming not possible, device buzzes Cause: wrong dimming principle set Installation or commissioning error. Disconnect device and luminaire, switch off circuit breaker. Check installation and correct. Luminaires flicker irregularly Cause: ripple-control pulses from the electric utility or distribution network operator. Use audio frequency suppressors. 5.3 Warranty The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center. Gira Giersiepen GmbH & Co. KG Elektro-Installations- Systeme Industriegebiet Mermbach Dahlienstraße 42477 Radevormwald Postfach 12 20 42461 Radevormwald Deutschland Tel +49(0)21 95-602-0 Fax +49(0)21 95-602-191 www.gira.de info@gira.de 32576312 10499261 I00 06.01.2012 6/6