Installation Manual. BN interface. Model name: BMS-IFBN640TLUL. English

Similar documents
Installation Manual INTELLIGENT SERVER. Model name: BMS-LSV6UL

INTELLIGENT SERVER. Model: BMS-LSV6E

DIGITAL INPUT/OUTPUT RELAY INTERFACE BMS-IFDD01E

DYNA-KIT. Owner s Manual. COMMUNICATION ADAPTER Model name: TCB-DK01SS-E. 1 English

TOUCH SCREEN CONTROLLER for Air Conditioning Control System

BACnet System SERVICE MANUAL. Intelligent Server. BACnet Server Software BMS-LSV6UL BMS-STBN09UL. FILE No. A Revised Nov (2) Model name:

Installation Manual RB-RWS20-E. Lite-Vision plus Remote Controller. Model name: English

ERV Control Interface Installation / Operation manual. TCB-IFVN1UL ERV Control Interface ENGLISH

RBC-AMS55E-ES RBC-AMS55E-EN

INSTALLATION MANUAL For authorized service personnel only.

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

Nokeval. FD100 series. User Manual

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

Mid-span 802.3af PoE Injector. Installation Guide KPOE-100

Mitsubishi Electric Air-conditioner Network System

KPW-T2P25. PoE Splitter. Industrial IEEE 802.3at High Power. User s Manual -1- DOC

PAR-WT50R-E PAR-WR51R-E

KFC-200. Installation Guide

USB Data Transfer Cable CA3-USBCB-01 Installation Guide

Lantech. IPES /100TX with 4 PoE Injectors 24~48VDC Industrial Switch. User Manual


4-port 10/100TX + 1 or 2-port 100FX Industrial Switch. User Manual

XTM1250SA DIN rail three phase four wire LCD display energy meter

Industrial 5-Port Fast Ethernet Switches with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541 PoE Model: KSD-541-P. Installation Guide

TOP - 1. Instruction Manual. Version 1.0 Produced in Jan. 2004

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

INSTALLATION MANUAL Wired Remote Control

PM Series Power Meter

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

KSD-800 Series. Installation Guide. Industrial 8-Port Fast Ethernet Switches with Fiber Connectivity DOC A -1-

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

SERVICE MANUAL WEB BASED CONTROLLER


See instructions to download and install the latest version of LinkBoxLON and the user's manual at

PRO-75 SERIES. User manual

Installation manual for for Schleifenbauer DPM3

EX-RC1 Remote I/O Adapter

BASIC PA AMPLIFIER A-1031 A-1061 A-1121 OPERATING INSTRUCTIONS TABLE OF CONTENTS

Preparing to Install the VG248

Power supply unit Model: PAC-SC51KUA

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

IEC-0101FT Industrial 10/100TX to 100M-FX Slim Type Converter User Manual

PRO-1250D CT MID DIN rail three phase four wire energy meter.

High Power over Ethernet Midspans PD Port Model PD Port Model

Expansion Module HZS 541-1S

LNP series. 5-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 1*10/100Tx, 12~36VDC Input.

10/100/1000T to Mini-GBIC Industrial Switch Converter 10/100/1000T to 1000SX/LX Industrial Switch Converter. AMG9011G-H (-40 to 75C) User Manual

Quick Start Guide. Indoor Stand-Alone Access Point. SunSpot AC1200 and SunSpot N300.

EC Series. Safety Guide

PoE Powered 10/100BASE-TX to 100BASE-FX Media Converters. KC-351 Series. Installation Guide

ALLPLEX Access Easy Master Controller APC-AEMC-SVR. Quick Installation Guide

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Industrial 5-Port Fast Ethernet Switches. with SFP Slot and optional 4 PoE PSE Ports. Basic Model: KSD-541. PoE Model: KSD-541-HP. Installation Guide

JANOME DESKTOP ROBOT JR2000N Series. Operation Manual. <Setup> For Qualified Installer ONLY

INSTALLATION MANUAL. Gateway option box EKLONPG EKBNPG

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

PoE Powered Gigabit Ethernet Media Converters 1000BASE-T TO 1000BASE-SX/LX. KGC-352 Series. Installation Guide

OWNER S MANUAL SINGLE CAT5E/6 3D EXTENDER B-320-1CAT-HDIR

6 10/100/1000TX + 2G Fiber Industrial Ethernet Switch User Manual

S66 Series Electronic Fan Speed Control

USER GUIDE. AXIS T8120 Midspan 15 W 1-port ENGLISH

Touch-controller_IM_03943A_1_Co_EN.indd 오후 3:06:00

0311 A OI GTW-LC SERVICE MANUAL. GT System Lift control adaptor GTW-LC INSTALLATION & OPERATION MANUAL

Industrial 3-Port Fast Ethernet Media Converter Switches

MODEL: R2K-1 SEN TRONIC AG. R2K Series

INSTALLATION INSTRUCTIONS

EX-RC1 Remote I/O Adapter

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

CONTENTS PRODUCT FEATURES... EG-2 SAFETY PRECAUTIONS... EG-2 PARTS DESCRIPTION... EG-3 INSTALLATION AND ADJUSTMENT... EG-4 SPECIFICATIONS...

CoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

CoolPlug CooLinkHub HVAC Bridge. Quick Installation Guide

1:1 Model Connection Interface

MF BASE-T to 1000BASE-X INDUSTRIAL MEDIA CONVERTER WITH SFP SUPPORT INSTALLATION GUIDE

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5

4P S. Wireless LAN Connecting Adapter <BRP069A42> Installation Manual

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT

EX-RC1 Remote I/O Adapter

H3C S1016/1024 Ethernet Switch User Manual

dedicated KVM switch and rackmount screen technology User Manual CV-1201D DVI-D KVM Designed and manufactured by Austin Hughes

Installing and Configuring Rialto Analytic Appliances

4P Wireless LAN Connecting Adapter <BRP069B41> <BRP069B42> <BRP069B43> <BRP069B44> <BRP069B45> Installation Manual

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

8 10/100/1000T Industrial Switch. User Manual MS655208(X)

Hypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :

5504 Thermocouple Analog Input Module

rcc.1081 Installation Instructions

Lantech. IPGS-0005T /100/1000T PoE at T Industrial Unmanaged Switch. User Manual

5 10/100TX w/ 4 PoE Injector Industrial Switch. User Manual

DIO-1616LN-FIT. Features. Specifications. Ethernet Remote I/O F&eIT N Series Isolated Digital Input/Output Unit DIO-1616LN-FIT 1. Ver.1.

COLOR USB CAMERA. W-01U2 (Preliminary Specs SUBJECT TO CHANGE) For more details, see NEW ITEM.

OWNER S MANUAL SINGLE CAT5E/6 3D EXTENDER B-200-1CAT-HDIR. Receiver

LNP-0602 series. 6-port Industrial PoE+ Unmanaged Ethernet Switches 4*10/100Tx (30W/Port) + 2*100Fx. User Manual

Installation Job Aid for VSP 4850GTS

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

4P R. Wireless LAN Connecting Adapter <BRP069A81> Installation Manual

Transcription:

BN interface Model name: BMS-IFBN640TLUL English

Contents Precautions for safety.................................................... 3 Introduction............................................................. 4 1 Installation........................................................... 6 2 Power and signal line connections....................................... 8 3 Settings............................................................. 10 3-1. Switch setting................................................. 10 3-2. LED.......................................................... 11 4 Factory default settings............................................... 11 5 Test run............................................................. 12 5-1. BACnet communication settings.................................. 12 5-2. Setting up equipment data in the indoor unit........................ 12 5-3. Cause of problem occurring during setup.......................... 13 6 Turning off the BN interface............................................ 13 2 -EN

Precautions for safety The following instructions must be observed. Carefully read these "Precautions for Safety" before installation, and perform installation work safely. These precautions contain important information regarding safety. After installation work, carry out an operation trial to confirm that there are no problems, and explain to the customer how to operate and maintain the system. Ask the customer to keep this. Expressions Warning Caution Graphic symbols Text set off in this manner indicates that failure to adhere to the directions in the warning could result in serious bodily harm (*1) or loss of life if the product is handled improperly. Text set off in this manner indicates that failure to adhere to the directions in the caution could result in serious bodily injury (*2) or damage (*3) to property if the product is handled improperly. *1: Serious bodily harm indicates loss of eyesight, injury, burns, electric shock, bone fracture, poisoning, and other injuries which leave aftereffect and require hospitalization or long-term treatment as an outpatient. *2: Bodily injury indicates injury, burns, electric shock, and other injuries which do not require hospitalization or long-term treatment as an outpatient. *3: Damage to property indicates damage extending to buildings, household effects, domestic livestock, and pets. Prohibited Compulsory " " indicates prohibited items. The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol. " " indicates compulsory (mandatory) items. The actual contents of the obligation are indicated by a picture or text placed inside or next to the graphic symbol. Warning Installation and reinstallation should be performed by your dealer or a qualified electrician Attempting to carry out installation work on your own, and doing so incorrectly, may result in electric shock or fire. Electrical work must be performed by a qualified electrician in accordance with this. The work must satisfy all local, national and international regulations Inappropriate work may result in electric shock or fire. Be sure to turn off the power before starting work Failure to do so may result in electric shock. Use only the power adapter supplied with this unit A power adapter other than that supplied with this unit may provide a different voltage and have different polarity (+) ( ), which could lead to fire, explosion or generation of heat. Do not modify the unit Doing so may result in excessive heat or fire. 3- EN

BN interface Introduction Overview The BN interface refers to equipment used for controlling Building Management Systems (Procured locally) and air conditioners (TCC-LINK compatible models) through communications via a network to enable centralized control. Included Items Component Q'ty Remarks BN interface equipment 1 Power adapter 1 BN interface power supply (model name: UI318-0526) Pin terminal 2 TCC-LINK caulked connectors Mounting bracket (DIN rail) 1 Use screws to secure the unit in locations without DIN rails (walls, etc.) Screws (M4 x 12) 2 For securing the DIN rails Rubber feet 4 For levelling the unit Screws (M3 x 8) 4 For securing the rubber feet to the unit 1 This manual Tie-wrap 1 Specifications Power supply Rated voltage Power consumption 120 VAC 60 Hz 3 W Operating temperature range Storage temperature range Dimensions 32 to 104 F (0 C to 40 C), 10% to 80% RH (no condensation) 14 to 140 F ( 10 C to +60 C), 10% to 90% RH (no condensation) 5.51" (W) x 3.54" (H) x 1.77" (D) inch (140 (W) x 90 (H) x 45 (D) mm) Mass BN interface 0.57 lb (260 g) Power adapter 0.31 lb (140 g) External View (BN interface equipment) Unit: inch (mm) About 0.47" (12) ~0.51" (13) 4 -EN

(Power adapter) Unit: inch (mm) Component Names Name 5V DCIN USB Ethernet (LAN) Shutdown button L1 L2 Function Connect the power adapter (For service) Connect to the Building Management System Shutdown or switch to air-conditioning search mode BACnet communication status indicator BACnet communication status indicator, setting error indicator 5- EN

1 Installation REQUIREMENT Do not install the unit in any of the following places. Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain (outdoors, under eaves, etc.) BN Interface Installation and Orientation Install and orient the interface using the DIN rail to mount the unit or wall mount or surface mount it as shown below. Use the supplied mounting bracket to wall mount or surface mount the interface. (1) DIN rail mount Install the interface on DIN rails mounted on a switchboard or elsewhere. Front view Back view (2) Wall mount Use screws to attach the supplied DIN rails to a wall and install the interface on the DIN rail. Supplied DIN rail Wall mount A Wall mount B Wall mount C (3) Surface mount Use screws to secure the supplied rubber legs to the interface before surface mounting it. Supplied rubber leg Supplied rubber leg mounting screw 6 -EN

Installation Space and Maintenance Space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation. The other sides can be adjacent to surrounding objects. 7- EN

2 Power and signal line connections Cables Use the following cable for signal line connections. (Procured locally) No. Line Description Type Ethernet is a registered trademark of Xerox Co., Ltd. Cable Connections Connect the cables to the specified connectors. Length of stripped TCC-LINK communication cable 2-core shielded wires 1 For TCC-LINK Wire size 1.25 mm 2, 3200 ft (1000 m) max. total length Length 2.00 mm 2, 6500 ft (2000 m) max. including air conditioner wiring length LAN cable (higher than Category 5, UTP) 2 For Ethernet Type The appropriate use of straight cable/cross cable should be done depending on your system used Length 320 ft (100 m) max. 1.96" (50) 0.39" (10) Connect the supplied pin terminal to the TCC-LINK communication cable as necessary. Air conditioner The TCC-LINK communication cable must be earthed on the air conditioner. Do not connect the shield wire to the connector. It should be open and insulated. Connection of TCC- LINK Communication Cables Connect the supplied power adapter Connect the LAN cable CAUTION The TCC-LINK communication cable have no polarity. * Secure the TCC-LINK communication cable and power cable to the switchboard etc. using the supplied cable tie to ensure that no excess load is placed on the power cable connection and TCC-LINK communication cable connection. 8 -EN

Example of System Wiring Connections BN interface Building Management System Power adapter Power Supply TCC-LINK main bus Outdoor unit Outdoor unit Indoor unit Remote controller Indoor unit Remote controller 9- EN

3 Settings 3-1. Switch setting SW300 SW301 SW302 SW100 SW700 Not used Test switch Set all bits to "OFF". Test button Not used during normal operation. TCC-LINK terminator resistor setting switch Set the TCC-LINK terminator resistor on the air conditioner side. Set SW100 to "OFF". Shutdown function / air-conditioning search mode function button Use this button to stop BACnet process and network process of the BN interface or to start up in the air-conditioning search mode. Note that button operation changes depending on how long it is depressed. Time duration button is depressed Less than 4 seconds Operation Stop BACnet process and network process of the BN interface. 4 seconds or more Starts air-conditioning in the air-conditioning search mode. Use the air-conditioning search mode to set up equipment data in the indoor unit. 10 -EN

3-2. LED LED LED color Use POWER Red Power indicator TCC-LINK Orange TCC-LINK communication status indicator ERROR Red TCC-LINK communication error indicator CPU Green Communication status indicator in the BN interface L1 Green BACnet communication status indicator L2 Red BACnet communication status indicator, setting error indicator 4 Factory default settings No. Item Factory default setting 1 IP address IP address 192.168.1.100 Subnet mask 255.255.255.0 2 UDP port 47808 (0xBAC0) 3 Device object instance number 100 4 Address setting switch 1 5 Test switch All OFF 6 TCC-LINK terminator resistor select switch OFF 11- EN

5 Test run To perform test run of the BN interface, BACnet communication settings and the equipment data of the connected indoor units are required. 5-1. BACnet communication settings Set the IP address of the BN interface and the device object instance number of the BACnet communications. These setting can set from Setting File Creation Software for North America. For details, contact your dealer. 5-2. Setting up equipment data in the indoor unit Obtain the equipment data of the indoor unit that is controlled by the BN interface from the indoor unit via the TCC-LINK communication cable. Preparing to set up equipment data in the indoor unit Central Control address must be set in the indoor unit you want to control. For information on how to set the address, refer to the installation manual of each indoor unit. Turn on all indoor and outdoor units. Set up as follows, waiting 10 minutes after turning on all the units. Setup work Turn on the BN interface. When 10 minutes has elapsed since turning on the BN interface, hold down the shutdown button for 4 seconds or longer. L1 LED goes on. When the BN interface has started up normally, start reading the equipment data of the interface unit. During this operation L1 LED will be on while L2 LED will be blinking on the BN interface. When reading of equipment data in the indoor unit ends normally, the BN interface will automatically start preparing for BACnet communication. L1 LED on the BN interface is blinking. When the preparations for BACnet communications end normally, L1 LED and L2 LED of the BN interface will start blinking. If an error occurs during reading of equipment data from the indoor unit or when preparing for BACnet communications, L1 LED and L2 LED of the BN interface will go on. Determining the cause of such an error will require the use of engineering tools. For details, contact your dealer. 12 -EN

5-3. Cause of problem occurring during setup Cause of problem Cause Action The indoor unit cannot be found. The central control address set in the indoor units are not unique. The indoor and outdoor units have not been turned on. The indoor and outdoor units are being initialized and it is not possible to communicate with them. TCC-LINK LED does not blink at all The TCC-LINK cables have been incorrectly connected. The centralized control address has not been set in the indoor units. The same centralized control address has been set in a number of indoor units. Make sure that indoor and outdoor units are turned on. Make sure that indoor and outdoor units are turned on. Make sure they have been on for at least 10 minutes. Connect the cables correctly. Make sure that the centralized control address has been set in the indoor units. Make sure that the centralized control address has been correctly set in the indoor units. 6 Turning off the BN interface Press the shutdown button, then wait 5 minutes before turning it off. CAUTION As the air-conditioning search mode will be engaged if the shutdown button is pressed for 4 seconds or longer, do not hold down the button. 13- EN

DEA6719101